150m (175m)

Longest Piping Length


from ODU ~ IDU (Equivalent)

OUTDOOR UNITS
15m
Height Difference
between IDU ~ IDU

300m
Total Piping Length

M U LT I V S
50m
Height Difference
between ODU ~ IDU

Highlight How does it work?

Available in Heat Pump and Combination of Cooling, Heating


Heat Recovery Models and Hot Water Solution

Energy
Reliability Convenience
savings

Indoor Unit
- Air cooled VRF Heat pump & Heat Recovery
- 9.0 ~ 33.6kW (Cooling capacity based)
- Both 1Ø, 220 ~ 240V, 50Hz and 3Ø, 380 ~ 415V, 50Hz Energy saving
by heat recovery unit
- Side discharge outdoor unit MULTI V S
HYDRO KIT
Heat Recovery
- Includes the industry’s first single phase Heat Recovery system
- Includes the industry’s first R32 side discharge ※ Heat Pump and Recovery are separated models.
E N E R G Y S AV I N G S
Smart Load Control Applied Inverter Twin Rotary & Inverter Scroll Compressor
E N E R G Y S AV I N G S

Enhanced comfort and up to 23% energy savings with MULTI V load control Adapted high efficient compressor according to capacity

MULTI V S changes indoor discharge air temperature continuously according to load, to save energy.
Inverter Twin Rotary Compressor Efficiency Comparison Inverter scroll compressor
(12.1kW ~ 15.5kW) (22.4kW ~ 33.6kW)

Efficiency
SLC (Smart Load Control) operation
Startup Operation Real Time Operation ... Scroll Compressor
Rotary Compressor

Startup After 20 minutes

Startup Operation
12.1 19.6 28 kW
(Cooling capacity)
Basic Operation Smart Load Control ※ Based on internal test data

Indoor
Discharge Air Inverter Twin Rotary Inverter scroll compressor
Temperature
Concentrated Winding Motor Best-in-class Compressor Speed

Operation Range (Hz)


150
120
Oil path area is improved by over 50% by increasing the extra stator - Rapid response capability
Power cavity. Due to this, caloric value of motor is reduced, improving the - Compact core design (Concentrated motor) 20
Input cooling function of stator coil. - Down to 15Hz : Part load efficiency improvement 15
Conventional

Until 20 minutes after startup operation Twin Rotary Rotor 6 Bypass Valve
Upper and lower part rotor offset imbalance in shaft rotor rotation. Vibration and Compressor reliability is maximized with 6 Bypass Valve
noise is reduced. Max torque load decreased by 45% compared to single rotor. - Prevent compressor damage due to excessively compressed
refrigerant more efficiently than 4 Bypass valve

Max 10% Energy saving


Surface Coating Direct Oil Injection
Surface coating of outstanding abrasion resistance property on vane and - Eliminate suction refrigerant gas heat loss through direct oil injection into
※ Indoor air discharge temperature crank shaft. compression chamber (Efficiency increases)

OUTDOOR UNITS
- Energy efficiency increased by 3-step Smart Load Control during startup phase
- Discharge air temperature adjusted according to outdoor and indoor temperature
- Increased reliability with regulated oil supply
- Comfort level in cooling / heating operations ensured
Scroll Profile
- The enhanced reliability with regulated oil supply
- Efficiency increases by expanding 96% Bypass area and 17% improved volume
ratio by non-uniform scroll thickness
Real Time Operation
Basic Operation Smart Load Control

3°C 10°C

M U LT I V S
Refrigerant Refrigerant
20°C 20°C Optimal Heat Exchanger
Maximize efficiency according to different heat exchanger path by cooling and heating
3°C 3°C
Refrigerant Refrigerant Variable Heat Exchanger Circuit intelligently selects the optimal path. With this smart path selection technology, an average of 6%
increase in the efficiency of both operations has been achieved.
35°C 35°C

Fixed refrigerant temperature Fixed refrigerant temperature

Max 13% Energy saving

※ How to set up : By dip switch in outdoor unit (Referred to Product Data Book) Factory default setting is Off. Fixed heat
-O utdoor temperature condition : EER 100% / 75% / 50% / 25% = 35℃ (DB) / 30℃ (DB) / 25℃ (DB) / 20℃ (DB)
- Indoor temperature condition : 27°C (DB) / 19°C (WB)
exchanger circuit
※D  ual sensing (Temperature & humidity) smart load control is possible with Remote controller Cooling Heating
PTEMTB100 (White) / PREMTBB10 (Black)

Efficiency performance Efficiency up due to Fin shape


Efficiency Improved heat exchanger efficiency of up to 28%
Conventional Wide Louver Plus Fin

Heating
Cooling 100% Cooling 128%

Cooling
Heating 100% Heating 123%

Previous Design (Fixed) Number of circuit

066 067
RELIABILITY
Reliable Refrigerant Components Corrosion Resistance Black Fin
RELIABILITY

LG technology allows for superior performance and component durability Strong durability against high salinity and heavily polluted air

Black Fin ensures continued operation of MULTI V S in highly corrosive environments such as salt laden atmosphere in coastal
Refrigerant towns or severe air pollution in industrial cities. This improvement in durability prolongs the product’s lifespan and lowers both the
❶ Cyclonic oil separator Refrigerant
+Oil
operational and maintenance costs.
- Highly reliable and efficient oil separation by
centrifuge using cyclonic methods Cyclone
Centrifuges Corrosion Resistance Proven by Certified Tests Enhanced Coating Layers
- High collection efficiency as well as outstanding
Oil
resistance to high temperature and pressure Oil Separator
LG Corrosion Resistance solution passed ISO 21207 accelerated corrosion The black coating with enhanced epoxy resin is applied for strong
test conducted by an independent test organization and the result has been protection from various corrosive external conditions such as salt
certified by prestigious global certification organization, TUV. contamination and air pollution. Moreover, the hydrophilic film keeps
❷ Large Volume Accumulator
water from accumulating on the heat exchanger’s fin, minimizing
- Improved reliability by adopting the large volume accumulator moisture buildup and eventually making it even more corrosion
(38% volume up compared to conventional) Accumulator resistant.
- Prevents the liquid refrigerant entering the compressor suction Certified protection
-M  aximize efficiency by optimal amount of refrigerant
- Protects compressor breakdown to increase product lifetime

40% 20%
❸ BLDC Fan Motor

Efficiency (%)
100
BLDC
Motor
- The BLDC Fan motor is more efficient than a conventional
Hydrophilic Coating (Water flow)

50
AC motor, offering an additional 40% energy savings AC The Hydrophilic coating minimizes
at low speeds and 20% at high speeds Motor
moisture buildup on the fin.
MULTI V S improved reliability 500 1,000
Motor Speed (RPM)
Complex Resin (Corrosion resistant)
with advanced technology : The Black coating provides strong
- Oil separator
❹ Double Sub-cool Interchanger ※ Verification of corrosion resistance performance protection from corrosion.
- Test Method B of ISO 21207
- Accumulator - Reliability is enhanced by minimizing pressure drop due to high Aluminum fin
- ASTM B117 / ISO 9227 (10,000 hours)
- Sub-cooling
efficiency spiral structure and 2 times larger size
 Long pipe is possible (up to* 175m) and high elevation (up to* 50m)
Reduction of indoor refrigerant noise level
* Based on equivalent pipe length Double Sub-cool Interchanger

Sufficient Piping Length

IMPROVED USER CONVENIENCE


Increased piping length allows for flexible design and installation
Smart Control MULTI V S inverter technology and sub cooling control circuit technology allows greater piping length and outstanding elevation
differences. A cooling system can be implemented more flexibly in a shop, office and even high-rise building, reducing the designer’s work
time and providing more efficient design.
Pressure control applied for smart, quick and precise response to user's temperature request

Temperature + Pressure Control Quick Operating Response Piping Capabilities 4 Way Piping
Senses and controls pressure directly using pressure sensor for faster Desired temperature can be reached up to 14% faster in cooling - Free design and installation by 4 way piping.
and more precise response to load variation. mode with pressure control, allowing more accurate control of indoor
environment for maximized comfort. 300m
Total piping length
※ Specifications may vary for each model.

50m
ODU ~ IDU
Outlet Temp (°C) Height
27 150m difference
(175m)
Longest 15m
pipe length IDU ~ IDU
12 14% (Equivalent) Height
Quicker difference

High Pressure Low Pressure


Sensor Sensor
14%

2min Time

Pressure +Temperature Control


Temperature Control

068 069
T E C H N I C A L D AT A
Low Noise Operation Nomenclature ARUN040GSS0
IMPROVED USER CONVENIENCE
Symbols
[Unit : mm] A 165 620 Piping Direction
ARU N 100 L S S 0 A Datum Iine
Piping
Direction
Serial number

390
360
Decreased noise during operation with low noise functionality Model Type
S : Standard
4 holes for Anchor Bolts (M10)
L : Compact
At night low noise mode, the noise level can reduce up to 14% in comparison with normal operation mode. C A
Air Discharge Type 330 (34) 26 950
C
S : Side Discharge (7) 81 26 97 82 244
Capacity
Electrical Ratings
5 5
L : 3Ø, 380-415V, 50Hz
Load Max G : 1Ø, 220-240V, 50Hz 5 5
58 58dB(A) Total Cooling Capacity in Horse Power(HP) unit

834
660
EX) 8HP → '080', 10HP → '100'

627
3

141 466
476
Sound Level Combination of Inverter Type and Cooling Only
58 Night 50 ※ Normal mode noise level (28kw) : or Heat Pump

24
B B

83
Mode Start Mode End 58dB(A) N : Inverter and H/P, V : Inverter and C/O
56 Step 1 50dB(A) ※ Night 3 step noise level (28kw) : 1
51
2
148
4
56dB(A),53dB(A), 50dB(A) MULTI V System Outdoor Unit using R410A 64
53 Step 2 416 B
※ Sound pressure tested by following 40
50 Step 3 Day Night conditions : 1m distance / 1.5m height

111
291
276
8:00 12:00 16:00 20:00 0:00 4:00 8:00 12:00 16:00
Time
Outdoor Units Function
5-1.D. Ø20 holes for drain connection 91
Category Functions MULTI V S 250 696
A
Variable Path of Outdoor Unit
-
HEX

Fan Technology and RPM Control Key Refrigerant


HiPORTM (High Pressure Oil
Return)
-

Components Humidity Sensor ARUB060GSS4 only


Corrosion Resistance Black Fin ○
External static pressure control enables outdoor unit to offer more flexibility in installations.
Oil Sensor -
New axial fan offers higher air volume, increased static pressure, decreased noise and enhanced efficiency. 3D View
Dual Sensing ARUB060GSS4 only
Low Noise Operation ○
Fan Technology Fan RPM control
Hgih Static Mode of Outdoor ARUN080LSS0

OUTDOOR UNITS

The new axial fan has a mogul trailing edge, narrow hub blade and Due to the new shroud and ROM control, the air flows straight away Unit Fan 620
Piping
[Unit : mm] Direction
reverse hub, this provides a high efficiency, low noise, wide fan, as well as from the fan even in high-rise buildings. Partial Defrosting -

14
improving the air flow rate. Auto Dust Removal of Outdoor

390
360
Special Function Unit -
(Fan reverse rotation) C
Reverse Fan RPM control A
Mogul hub + + (Fan Max RPM Up)
Indoor Cooling Comfort Mode
○ 4 holes for Anchor Bolts (M10)
trailing edge Based Outdoor Temperature
Smart Load Control (SLC) C
A 950
(Changing indoor discharge air ○ 330 26
526mm Fan Shroud temperature according to load) 90
C

Narrow Outdoor Unit Control Refer to


ARUB060GSS4 only
Humidity

M U LT I V S
hub blade
(1Ø) 4 / 5HP (1Ø) 5 / 6HP Defrost / Deicing ○
(3Ø) 4 / 5 / 6 / 8HP
5

1380
High Pressure Switch ○
Super cannon fan increases the air volume in 50 CMM and the noise level Phase Protection ○ 2
is decreased by 4dB(A).

606
Basic Function Restart Delay (3-minutes) ○

80
80
Grooved Self Diagnosis ○ 52
25
suction surface 26

52
Soft Start ○ B 1 6 96 B 96
7

Test Run Function - 695


Tip vortex • Straight air flow 416
250
suppressor - New shroud adopted AC Ez (Simple Controller) PQCSZ250S0 91
40 164
Super Canon Fan - Performs high static pressure
AC Ez Touch PACEZA000

111
291
276
(3Ø) 10 / 12HP
AC Smart IV PACS4B000
5-1.D. Ø
Central Controller AC Smart 5 PACS5A000 20 holes for drain connection

ACP (Advanced Control Platform) 75


PACP4B000 A
IV
ACP (Advanced Control Platform)
Upgraded Fault Detection and Diagnosis 5
PACP5A000

60
44
42
AC Manager 5 PACM5A000 91

ACP5 (w U60FT) ○ 4
BNU (Building
3
Easy and convenient maintenance with self-diagnosis Network Unit) ACP BACnet PQNFB17C0

606

536
557
IO Module (ODU Dry Contact) PVDSMN000
The inclusion of FDD elements - Auto start-up, auto refrigerant check, black box

85
PDI (Power Standard PPWRDB000
functionality, simultaneous evaluation, and auto refrigerant collection, provides the Distribution 24

52
B 25 8
optimal solution for user reliability and ease of maintenance. Indicator) Premium PQNUD1S40 3D View 81

Piping connection port


Cool / Heat
- Auto commissioning mode FDD Selector
PRDSBM
94

- Auto refrigerant collection MICOM LGMV PRCTIL0 Note No. Part Name Description
Cycle Monitoring
1. Unit should be installed in compliance with the 1 Air Outlet -
- Auto evaluation of refrigerant amount and charging Device Mobile LGMV PLGMVW100 installation manual in the product box. 2 Power and communication cable Hole -
- Able to access LGMV (LG Monitoring View) by smartphone 2. Unit should be grounded in accordance with Welding
3 Gas Pipe Connection
○ the local regulation or applicable national joint
- Black box function (Logical operation) codes. 4 Liquid Pipe Connection
Welding
Refrigerant Charging Kit joint
- Piping & wiring error check-up Not applied to 3. All electrical components and materials to be 5 Handle -
ARUB060GSS4 supplied from the site must comply with the
- FDD (Fault Detection and Diagnosis) Additional kit 6 Pipe routing hole (front) -
Low Ambient Kit - local regulations or international codes. 7 Pipe routing hole (side) -
4. Electrical characteristics chapter should be 8 Pipe routing hole (back) -
Variable Water Flow Valve Control considered for electrical work and design.
-
Kit Especially the power cable and circuit breaker
should be selected in accordance with that.
※ ○ : Applied, - : Not Applied
070 071
M U LT I V S H E AT P U M P
Heat Pump ARUN040GSS0
T E C H N I C A L D AT A

Cooling 45°C Heating 20°C


43°C 18°C
40°C 15°C

Outdoor Temperature (°C WB)

Range for warming up operation


Outdoor Temperature (°C DB)

Range for continuous operation


Range for continuous operation
35°C
10°C

Range for pull down operation


30°C
5°C
25°C

20°C 0°C

15°C -5°C

10°C LG participates in the ECP programme


-10°C for EUROVENT VRF program.
5°C Check ongoing validity of certification
-15°C : www.eurovent-certification.com
0°C
-20°C
-5°C
-10°C -25°C
10°C 14°C 15°C 20°C 25°C 27°C 30°C 10°C 15°C 20°C 25°C 27°C 30°C

Indoor Temperature (°C WB) Indoor Temperature (°C DB) HP 4


Model Name ARUN040GSS0
Heat Recovery Cooling (Rated) kW 12.1
Capacity
Heating (Rated) kW 12.5
Cooling 50°C
Heating Cooling (Rated) kW 4.03
48°C Input
45°C 20°C Heating (Rated) kW 3.10
18°C
40°C
15°C
EER 3.00

Range for warming up operation


Range for continuous operation

Range for pull down operation

continuous operation
35°C SEER 5.63

Outdoor Temperature (°C WB)


Outdoor Temperature (°C DB)

10°C
30°C COP Rated Capacity 4.03

Range for
5°C
25°C SCOP 3.97
0°C
20°C Color (General) Warm Gray
Exterior
15°C -5°C RAL Code (Classic) RAL 7044

OUTDOOR UNITS
10°C Heat
-10°C Type Wide Louver Plus
Exchanger
5°C
-15°C Type BLDC Inverter Twin Rotary
0°C
Combination x No. (Inverter) x 1
-20°C
-5°C
Compressor Motor Output x Number W x No. 4,000 x 1
-10°C -25°C
10°C 15°C 20°C 25°C 27°C 30°C
Oil Type FW68D (PVE)
-15°C
10°C 14°C 15°C 20°C 25°C 27°C 30°C Indoor Temperature (°C DB) Oil Charge cc 1,300
Type Axial Flow Fan
Indoor Temperature (°C WB)
Motor Output x Number W x No. 124 x 1

M U LT I V S
Fan Air Flow Rate (High) m3/min x No. 60
Simultaneous Cooling Simultaneous Heating
Drive DC INVERTER
30°C 20°C
Discharge Side / Top Side
27°C
16°C
25°C Pipe Liquid Pipe mm (inch) Ø9.52 (3/8)
15°C
Connection
Range for continuous operation

Outdoor Temperature (°C WB)

Gas Pipe mm (inch) Ø15.88 (5/8)


Range for pull down operation
Outdoor Temperature (°C DB)

20°C
Range for continuous operation
Range for pull down operation

10°C Dimensions (W x H x D) mm x No. 950 × 834 × 330


15°C
Dimensions (W x H x D) - Shipping mm x No. (1,065 x 918 x 461) x 1
10°C
5°C Net Weight kg x No. 70
5°C
Shipping Weight kg x No. 77 x 1
0°C
0°C
Sound Cooling dB(A) 50
Pressure Level Heating dB(A) 52
-5°C
-5°C
-10°C Sound Power Cooling dB(A) 72
Level Heating dB(A) 75
-15°C -10°C
mm2 x No.
10°C 14°C 15°C 20°C 25°C 27°C 30°C 10°C 15°C 20°C 25°C 30°C Communication Cable 2C x 1.0 ~ 1.5
(VCTF-SB)
Indoor Temperature (°C WB) Indoor Temperature (°C DB) Refrigerant Name R410A
Precharged Amount in
kg 1.8
Refrigerant factory
t-CO2eq 3.758
Note
1. These figures assume the following operating conditions : Equivalent piping length : 7.5m Control Electronic Expansion Valve
Level difference : 0m
2. Range of pull down operation : If the relative humidity is too high, cooling capacity can be decreased by the sensible 220-240 , 1 , 50
Power Supply Ø, V, Hz
220, 1, 60
Number of Maximum Connectable Indoor Units 8
Position of Sound Level Measuring
Note Note
1. These figures assume the following operating conditions : 1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct.
Equivalent piping length : 7.5m - Refer to EUROVENT certification regulation for more detail test conditions.
Level difference : 0m - Refer to EUROVENT website for test values connected Ceiling Cassette type indoors.
2. Performances are based on the following conditions :
- Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB
1.5m

- Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB
3. The maximum combination ratio is 160%.
1m 4. Wiring cable size must comply with the applicable local and national codes.
5. Due to our policy of innovation some specifications may be changed without notification.
6. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditons during operation.
7. Power factor could vary less than ±1% according to the operating conditions.
8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
072 073
M U LT I V S H E AT P U M P
ARUN050GSS0 / ARUN060GSS0 ARUN040LSS0 / ARUN050LSS0
M U LT I V S H E AT P U M P
ARUN060LSS0

LG participates in the ECP programme LG participates in the ECP programme


for EUROVENT VRF program. for EUROVENT VRF program.
Check ongoing validity of certification Check ongoing validity of certification
: www.eurovent-certification.com : www.eurovent-certification.com

HP 5 6 HP 4 5 6
Model Name ARUN050GSS0 ARUN060GSS0 Model Name ARUN040LSS0 ARUN050LSS0 ARUN060LSS0
Cooling (Rated) kW 14.0 15.5 Cooling (Rated) kW 12.1 14.0 15.5
Capacity Capacity
Heating (Rated) kW 16.0 18.0 Heating (Rated) kW 12.5 16.0 18.0
Cooling (Rated) kW 4.59 5.17 Cooling (Rated) kW 3.39 4.59 5.17
Input Input
Heating (Rated) kW 4.18 5.00 Heating (Rated) kW 2.75 4.18 5.00
EER 3.05 3.00 EER 3.57 3.05 3.00
SEER 7.40 7.53 SEER 7.42 7.40 7.53
COP Rated Capacity 3.83 3.60 COP Rated Capacity 4.55 3.83 3.60
SCOP 4.16 4.35 SCOP 4.30 4.16 4.35
Color (General) Warm Gray Warm Gray Color (General) Warm Gray Warm Gray Warm Gray
Exterior Exterior
RAL Code (Classic) RAL 7044 RAL 7044 RAL Code (Classic) RAL 7044 RAL 7044 RAL 7044

OUTDOOR UNITS
Heat Heat
Type Wide Louver Plus Wide Louver Plus Type Wide Louver Plus Wide Louver Plus Wide Louver Plus
Exchanger Exchanger
Type BLDC Inverter Twin Rotary BLDC Inverter Twin Rotary Type BLDC Inverter Twin Rotary BLDC Inverter Twin Rotary BLDC Inverter Twin Rotary
Combination x No. (Inverter) x 1 (Inverter) x 1 Combination x No. (Inverter) x 1 (Inverter) x 1 (Inverter) x 1
Compressor Motor Output x Number W x No. 4,000 x 1 4,000 x 1 Compressor Motor Output x Number W x No. 4,000 x 1 4,000 x 1 4,000 x 1
Oil Type FW68D (PVE) FW68D (PVE) Oil Type FW68D (PVE) FW68D (PVE) FW68D (PVE)
Oil Charge cc 1,300 1,300 Oil Charge cc 1,300 1,300 1,300
Type Axial Flow Fan Axial Flow Fan Type Axial Flow Fan Axial Flow Fan Axial Flow Fan
Motor Output x Number W x No. 124 x 2 124 x 2 Motor Output x Number W x No. 124 x 2 124 x 2 124 x 2

M U LT I V S
Fan Air Flow Rate (High) m3/min x No. 110 110 Fan Air Flow Rate (High) m3/min x No. 110 110 110
Drive DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top Side Side Discharge Side / Top Side Side Side

Pipe Liquid Pipe mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Pipe Liquid Pipe mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Connection Gas Pipe mm (inch) Ø15.88 (5/8) Ø19.05 (3/4) Connection Gas Pipe mm (inch) Ø15.883(5/8) Ø15.88 (5/8) Ø19.05 (3/4)
Dimensions (W x H x D) mm x No. 950 × 1,380 × 330 950 × 1,380 × 330 Dimensions (W x H x D) mm x No. 950 × 1,380 × 330 950 × 1,380 × 330 950 × 1,380 × 330
Dimensions (W x H x D) - Shipping mm x No. (1,065 x 918 x 461) x 1 (1,065 x 918 x 461) x 1 Dimensions (W x H x D) - Shipping mm x No. (1,065 x 918 x 461) x 1 (1,065 x 918 x 461) x 1 (1,065 x 918 x 461) x 1
Net Weight kg x No. 94 94 Net Weight kg x No. 96 96 96
Shipping Weight kg x No. 106 106 Shipping Weight kg x No. 108 108 108

Sound Cooling dB(A) 51 52 Sound Cooling dB(A) 50 51 52


Pressure Level Heating dB(A) 53 54 Pressure Level Heating dB(A) 52 53 54

Sound Power Cooling dB(A) 72 72 Sound Power Cooling dB(A) 72 72 72


Level Heating dB(A) 76 77 Level Heating dB(A) 76 76 77
mm2 x No. mm2 x No.
Communication Cable 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 Communication Cable 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
(VCTF-SB) (VCTF-SB)
Refrigerant Name R410A R410A Refrigerant Name R410A R410A R410A
Precharged Amount in Precharged Amount in
kg 3.0 3.0 kg 3.0 3.0 3.0
Refrigerant factory Refrigerant factory
t-CO2eq 6.263 6.263 t-CO2eq 6.263 6.263 6.263
Control Electronic Expansion Valve Electronic Expansion Valve Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
220-240 , 1 , 50 220-240 , 1 , 50 380-415 , 3 , 50 380-415 , 3 , 50 380-415 , 3 , 50
Power Supply Ø, V, Hz Power Supply Ø, V, Hz
220, 1, 60 220, 1, 60 380, 3, 60 380, 3, 60 380, 3, 60
Number of Maximum Connectable Indoor Units 10 13 Number of Maximum Connectable Indoor Units 8 10 13

Note Note
1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct. 1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct.
- Refer to EUROVENT certification regulation for more detail test conditions. - Refer to EUROVENT certification regulation for more detail test conditions.
- Refer to EUROVENT website for test values connected Ceiling Cassette type indoors. - Refer to EUROVENT website for test values connected Ceiling Cassette type indoors.
2. Performances are based on the following conditions : 2. Performances are based on the following conditions :
- Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB - Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB
- Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB - Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB
3. The maximum combination ratio is 160%. 3. The maximum combination ratio is 160%.
4. Wiring cable size must comply with the applicable local and national codes. 4. Wiring cable size must comply with the applicable local and national codes.
5. Due to our policy of innovation some specifications may be changed without notification. 5. Due to our policy of innovation some specifications may be changed without notification.
6. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 6. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard. Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditons during operation. Therefore, these values can be increased owing to ambient conditons during operation.
7. Power factor could vary less than ±1% according to the operating conditions. 7. Power factor could vary less than ±1% according to the operating conditions.
8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
074 075
M U LT I V S H E AT R E C O V E R Y
ARUN080LSS0 / ARUN100LSS0 ARUB060GSS4
M U LT I V S H E AT P U M P
ARUN120LSS0

LG participates in the ECP programme LG participates in the ECP programme


for EUROVENT VRF program. for EUROVENT VRF program.
Check ongoing validity of certification Check ongoing validity of certification
: www.eurovent-certification.com : www.eurovent-certification.com

HP 8 10 12 HP 6
Model Name ARUN080LSS0 ARUN100LSS0 ARUN120LSS0 Model Name ARUB060GSS4
Cooling (Rated) kW 22.4 28.0 33.6 Cooling (Rated) kW 15.5
Capacity Capacity
Heating (Rated) kW 24.5 30.6 36.7 Heating (Rated) kW 18.0
Cooling (Rated) kW 8.45 12.44 15.27 Cooling (Rated) kW 5.74
Input Input
Heating (Rated) kW 6.96 8.50 12.23 Heating (Rated) kW 5.14
EER 2.65 2.25 2.20 EER 2.70
SEER 7.13 6.28 6.50 SEER 5.92
COP Rated Capacity 3.52 3.60 3.00 COP Rated Capacity 3.50
SCOP 4.53 4.21 4.32 SCOP 3.79
Color (General) Warm Gray Warm Gray Warm Gray Color Warm Gray
Exterior Exterior
RAL Code (Classic) RAL 7044 RAL 7044 RAL 7044 RAL Code (Classic) RAL 7044

OUTDOOR UNITS
Heat Heat
Type Wide Louver Plus Wide Louver Plus Wide Louver Plus Type Wide Louver Plus
Exchanger Exchanger
Type Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Combination x No. (Inverter) x 1 (Inverter) x 1 (Inverter) x 1 Combination x No. (Inverter) x 1
Compressor Motor Output x Number W x No. 4,200 x 1 5,300 x 1 5,300 x 1 Compressor Motor Output x Number W x No. 4,200 x 1
Oil Type FW68D (PVE) FW68D (PVE) FW68D (PVE) Oil Type FW68D (PVE)
Oil Charge cc 2,400 2,600 3,400 Oil Charge cc 1,700
Type Propeller fan Propeller fan Propeller fan Type Axial Flow Fan
Motor Output x Number W x No. 124 x 2 250 x 2 250 x 2 Motor Output x Number W x No. 124 x 2

M U LT I V S
Fan Air Flow Rate (High) m3/min x No. 140 190 190 Fan Air Flow Rate (High) m3/min x No. 110
Drive DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER
Discharge Side / Top Side Side Side Discharge Side / Top Side

Pipe Liquid Pipe mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø12.7 (1/2) Liquid Pipe mm (inch) Ø9.52 (3/8)
Pipe
Connection Gas Pipe mm (inch) Ø19.05 (3/4) Ø22.2 (7/8) Ø28.58 (1-1/8) Connection Low Pressure Gas Pipe mm (inch) Ø19.05 (3/4)
#1
Dimensions (W x H x D) mm x No. 950 × 1,380 × 330 1,090 × 1,625 × 380 1,090 x 1,625 x 380 High Pressure Gas Pipe mm (inch) Ø15.88 (5/8)
Dimensions (W x H x D) - Shipping mm x No. (1,065 x 918 x 461) x 1 (1,065 x 918 x 461) x 1 (1,065 x 918 x 461) x 1 Dimensions (W x H x D) mm x No. 950 × 1,380 × 330
Net Weight kg x No. 115 142 155 Dimensions (W x H x D) - shipping mm x No. (1,140 x 1,549 x 466) x 1
Shipping Weight kg x No. 127 158 171 Net Weight kg x No. 118

Sound Cooling dB(A) 57 58 60 Shipping Weight kg x No. 132


Pressure Level Heating dB(A) 57 58 60 Sound Cooling dB(A) 56
Pressure
Sound Power Cooling dB(A) 78 77 78 Level Heating dB(A) 58
Level Heating dB(A) 81 79 82 Sound Power Cooling dB(A) 76
mm2 x No. Level Heating dB(A) 78
Communication Cable 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
(VCTF-SB)
mm2 x No.
Refrigerant Name R410A R410A R410A Communication Cable 2C x 1.0 ~ 1.5
(VCTF-SB)
Precharged Amount in Refrigerant Name R410A
kg 3.5 4.5 6.0
Refrigerant factory
Precharged Amount in
t-CO2eq 7.306 9.394 12.525 kg 3.5
Refrigerant factory
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve t-CO2eq 7.306
380-415 , 3 , 50 380-415 , 3 , 50 380-415 , 3 , 50 Control Electronic Expansion Valve
Power Supply Ø, V, Hz
380 , 3 , 60 380 , 3 , 60 380 , 3 , 60 Power Supply Ø, V, Hz 220-230-240 , 1 , 50/60
Number of Maximum Connectable Indoor Units 13 16 20 Number of Maximum Connectable Indoor Units 13

Note Note
1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct. 1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct.
- Refer to EUROVENT certification regulation for more detail test conditions. - Refer to EUROVENT certification regulation for more detail test conditions.
- Refer to EUROVENT website for test values connected Ceiling Cassette type indoors. - Refer to EUROVENT website for test values connected Ceiling Cassette type indoors.
2. Performances are based on the following conditions : 2. Performances are based on the following conditions :
- Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB - Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB
- Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB - Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB
3. The maximum combination ratio is 160%. 3. The maximum combination ratio is 160%.
4. Wiring cable size must comply with the applicable local and national codes. 4. Wiring cable size must comply with the applicable local and national codes.
5. Due to our policy of innovation some specifications may be changed without notification. 5. Due to our policy of innovation some specifications may be changed without notification.
6. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 6. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard. Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditons during operation. Therefore, these values can be increased owing to ambient conditons during operation.
7. Power factor could vary less than ±1% according to the operating conditions. 7. Power factor could vary less than ±1% according to the operating conditions.
8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)
076 077
M U LT I V S
Energy Savings Energy Savings
M U LT I V S

Energy consumption can be reduced as indoor heat is absorbed and transferred to hot water supply. Energy consumption can be reduced as indoor heat is absorbed and transferred to hot water supply.

Conventional MULTI V S Heat Recovery with HYDRO KIT


Absorbed heat is released to outdoor air. Absorbed heat from indoor space is used for making hot water.

Heat Heat Transfer Heat Transfer


Released

HR Unit

Heat Heat
Absorption Absorption

Conventional

Heat Recovery

OUTDOOR UNITS
Hot water Hot water

Boiler Domestic HYDRO KIT Domestic


(Gas or Electric) Hot Water Tank Hot Water Supply Cooling Hot Water Tank Hot Water Supply Cooling

M U LT I V S
078 079
W H Y M U LT I V S R 3 2
Compact Size & Light Weight
Its compact size and light weight make it easy to install and optimize space. (5/6HP)

- Air cooled VRF Heat pump


- 9.0 ~ 15.5kW (based on cooling capacity)
- Both 1Ø, 220 ~ 240V, 50Hz and 3Ø, 380 ~ 415V, 50Hz
23%
- Side discharge outdoor unit Light Weight

546mm

Previous New

Less Refrigerant Charge


LG reduced refrigerant charge by applying environment-conscious refrigerant R32.

OUTDOOR UNITS
Total amount : 5.6 kg

Lower Global Warming Potential (GWP)


WHY R32 REFRIGERANT

Factory Charging : 3 kg

Total amount : 4.3 kg


Factory Charging : 2 kg
23%
What is GWP? Global Trend and EU Regulation for F-Gas

Global Warming Potential is a measure that allows for an HFC* Phase Down 79% by 2030.
accurate comparison of the environmental impact of different 100
93
% Phase down of HFC Consumption

M U LT I V S
gases. GWP measures how much energy the emissions of 1 ton 90 79%
of a gas will absorb over a given period of time, relative to the 80
HFCs refrigerants
70 63
emissions of 1 ton of carbon dioxide (CO2). should be reduced
60
50 45 by 79% by 2030
Previous New
40 compared to 2013.
30
21
20 * Hydrofluorocarbon : One ※ IDU (Wall Mounted Unit) : 5 kBtu/h, 8 EA
of the alternative freon ※ This result can be different depending on actual environment
10
gas that does not harm
R410A R134a R32 N2O CH4 the Earth's ozone layer
2014 2016 2018 2020 2022 2024 2026 2028 2030 2032
2,088 GWP 1,430 GWP 675 GWP 298 GWP 25 GWP
Year

Cost Savings with R32 Corrosion Resistance Black Fin


Enhanced Coating Layers
Higher Efficiency Reduced Equipment Sizes Less Refrigerant Charge Reduced Refrigerant Volume The black coating with enhanced epoxy resin is applied for strong protection from various corrosive external conditions such as salt contamination and
air pollution. Moreover, the hydrophilic film keeps water from accumulating on the heat exchanger’s fin, minimizing moisture buildup and eventually
Savings on cost of Savings on product purchase Savings on cost of injecting & Savings on refrigerant purchase making it even more corrosion resistant.
energy consumption. and labor cost for installation replacing refrigerant. and recycling costs.
and maintenance.

Hydrophilic Coating (Water flow)


The Hydrophilic coating minimizes moisture buildup on the fin.

Complex Resin (Corrosion resistant)


The Black coating provides strong protection from corrosion.

Aluminum fin

※ Verification of corrosion resistance performance


- Test Method B of ISO 21207
- ASTM B117 / ISO 9227 (10,000 hours)

080 081
NOTE
I N N O V AT I V E T E C H N O L O G I E S

R1 Compressor is one that combines high-efficiency, low sound characteristics of the scroll and the simple compressing structure of
the rotary compressor. This technology enables a highly efficient compact model.

Centrifugal oil return


& Oil separating guide
for oil discharge reduction

Extended Operation Range


(max 150Hz)
- Higher Cooling Performance

Shaft-through Structure
& Support both ends of shaft
- Solid compressor operation assuring higher durability

OUTDOOR UNITS
Bottom Compression - Lower Noise & Vibration (Max 4dB(A) ↓)
& Simple Structure - Less Weight (20% ↓)
- Superior Reliability

Conventional Compressor

M U LT I V S
Scroll : High efficiency / Low sound Revolutionary Scroll : High
 efficiency /
(Continuous compression, but complex structure) Stable & Simple Structure

Hybrid Scroll Shape

compression (LG patent)*


part(upper) * Patent registration
number (S.Korea :
10-1059880, USA :
RE46106)

Motor compression part


Motor
Compression parts
sub-frame (upper → lower)
Scroll penetrated by shaft
Oil
→ remove tilting moment

Simple structure :
without sub-frame
Rotary : Simple structure Oil feeding structure better than
(Compression per 1 rotation ) previous scroll

Oil

Motor Extended operation (Max 150Hz)


Low noise & Vibration (Max 4dB(A)↓)
compression Less weight (20%↓)
part (lower)

Oil Compact model


compression part (Size 40%↓, Weight 25%↓)

082 083
M U LT I V S H E AT P U M P R 3 2
ZRUN030GSS0 / ZRUN040GSS0 ZRUN030LSS0 / ZRUN040LSS0
M U LT I V S H E AT P U M P R 3 2
ZRUN050GSS0 / ZRUN060GSS0 ZRUN050LSS0 / ZRUN060LSS0

LG participates in the ECP programme LG participates in the ECP programme


for EUROVENT VRF program. for EUROVENT VRF program.
Check ongoing validity of certification Check ongoing validity of certification
: www.eurovent-certification.com : www.eurovent-certification.com

HP 3 4 5 6 HP 3 4 5 6
Model Name ZRUN030GSS0 ZRUN040GSS0 ZRUN050GSS0 ZRUN060GSS0 Model Name ZRUN030LSS0 ZRUN040LSS0 ZRUN050LSS0 ZRUN060LSS0
Cooling (Rated) kW 9.0 12.1 14.0 15.5 Cooling (Rated) kW 9.0 12.1 14.0 15.5
Capacity Heating (Rated) kW 9.0 12.1 14.0 15.5 Capacity Heating (Rated) kW 9.0 12.1 14.0 15.5
Heating (Max) kW 10.0 14.2 16.0 18.0 Heating (Max) kW 10.0 14.2 16.0 18.0
Cooling (Rated) kW 2.81 4.26 4.90 5.64 Cooling (Rated) kW 2.81 4.26 4.90 5.64
Input Input
Heating (Rated) kW 2.09 3.03 3.48 3.95 Heating (Rated) kW 2.09 3.03 3.48 3.95
EER (Rated) 3.20 2.84 2.86 2.75 EER (Rated) 3.20 2.84 2.86 2.75
SEER 5.70 6.69 6.44 6.59 SEER 5.70 6.69 6.44 6.59
COP (Rated) 4.30 4.00 4.02 3.92 COP (Rated) 4.30 4.00 4.02 3.92
SCOP 3.90 3.87 3.81 4.07 SCOP 3.90 3.87 3.81 4.07
Color Warm Gray Warm Gray Warm Gray Warm Gray Color Warm Gray Warm Gray Warm Gray Warm Gray
Exterior Exterior

OUTDOOR UNITS
RAL Code RAL 7044 RAL 7044 RAL 7044 RAL 7044 RAL Code RAL 7044 RAL 7044 RAL 7044 RAL 7044
Heat Exchanger Type Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Type Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus
Type LG Inverter Scroll LG Inverter Scroll LG Inverter Scroll LG Inverter Scroll Type LG Inverter Scroll LG Inverter Scroll LG Inverter Scroll LG Inverter Scroll
Combination x No. (Inverter) x 1 (Inverter) x 1 (Inverter) x 1 (Inverter) x 1 Combination x No. (Inverter) x 1 (Inverter) x 1 (Inverter) x 1 (Inverter) x 1
Compressor Motor Output x Number W x No. 3,198 x 1 3,198 x 1 3,198 x 1 3,198 x 1 Compressor Motor Output x Number W x No. 3,198 x 1 3,198 x 1 3,198 x 1 3,198 x 1
Oil Type FW68D (PVE) FW68D (PVE) FW68D (PVE) FW68D (PVE) Oil Type FW68D (PVE) FW68D (PVE) FW68D (PVE) FW68D (PVE)
Oil Charge cc 1,100 1,100 1,100 1,100 Oil Charge cc 1,100 1,100 1,100 1,100
Type Axial Flow Fan Axial Flow Fan Axial Flow Fan Axial Flow Fan Type Axial Flow Fan Axial Flow Fan Axial Flow Fan Axial Flow Fan
Motor Output x Number W x No. 124 x 1 124 x 1 198 x 1 198 x 1 Motor Output x Number W x No. 124 x 1 124 x 1 198 x 1 198 x 1

M U LT I V S
m3/min x m3/min x
Fan Air Flow Rate (High) 60 60 80 80 Fan Air Flow Rate (High) 60 60 80 80
No. No.
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Discharge Side / Top Side Side Side Side Discharge Side / Top Side Side Side Side

Pipe Liquid Pipe mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Pipe Liquid Pipe mm (inch) Ø9.52(3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Connection Gas Pipe mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø19.05 (3/4) Connection Gas Pipe mm (inch) Ø15.88(5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø19.05 (3/4)
Dimensions (W x H x D) mm x No. 950 × 834 × 330 950 x 834 x 330 950 x 834 x 330 950 × 834 × 330 Dimensions (W x H x D) mm x No. 950 × 834 × 330 950 x 834 x 330 950 x 834 x 330 950 × 834 × 330
Dimensions (W x H x D) - Shipping mm x No. 1,147 x 919 x 461 1,147 x 919 x 461 1,147 x 919 x 461 1,147 x 919 x 461 Dimensions (W x H x D) - Shipping mm x No. 1,147 x 919 x 461 1,147 x 919 x 461 1,147 x 919 x 461 1,147 x 919 x 461
Net Weight kg x No. 64.7 64.7 71.6 71.6 Net Weight kg x No. 64.7 64.7 71.6 71.6
Shipping Weight kg x No. 73.7 73.7 79.6 79.6 Shipping Weight kg x No. 73.7 73.7 79.6 79.6

Sound Pressure Cooling dB(A) 51 51 57 57 Sound Pressure Cooling dB(A) 51 51 57 57


Level Heating dB(A) 55 55 60 60 Level Heating dB(A) 55 55 60 60

Sound Power Cooling dB(A) 67 67 70 71 Sound Power Cooling dB(A) 67 67 70 71


Level Heating dB(A) 70 71 74 75 Level Heating dB(A) 70 71 74 75
mm2 x No. mm2 x No.
Communication Cable 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 Communication Cable 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
(VCTF-SB) (VCTF-SB)
Refrigerant name R32 R32 R32 R32 Refrigerant name R32 R32 R32 R32
Precharged Amount kg 1.5 1.5 2.0 2.0 Precharged Amount kg 1.5 1.5 2.0 2.0
Refrigerant t-CO2eq 1.013 1.013 1.350 1.350 Refrigerant t-CO2eq 1.013 1.013 1.350 1.350
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control Control
Valve Valve Valve Valve Valve Valve Valve Valve
Power Supply Ø, V, Hz 220 - 230 - 240 , 1 , 50 220 - 230 - 240 , 1 , 50 220 - 230 - 240 , 1 , 50 220 - 230 - 240 , 1 , 50 Power Supply Ø, V, Hz 380 - 400 - 415, 3, 50 380 - 400 - 415, 3, 50 380 - 400 - 415, 3, 50 380 - 400 - 415, 3, 50
Number of maximum connectable indoor units 6 8 10 13 Number of maximum connectable indoor units 6 8 10 13

Note
Note
1. Due to our policy of innovation some specifications may be changed without notification. 4. Performances are based on the following conditions : 4. Performances are based on the following conditions :
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric • Cooling : Indoor Ambient Temp 27°CDB / 19°CWB, Outdoor Ambient Temp 35°CDB / 24°CWB • Cooling : Indoor Ambient Temp 27°CDB / 19°CWB, Outdoor Ambient Temp 35°CDB / 24°CWB
2. Wiring cable size must comply with the applicable local and national codes. And “Electric
characteristics” chapter should be considered for electrical work and design. Especially the • Heating : Indoor Ambient Temp 20°CDB / 15°CWB, Outdoor Ambient Temp 7°CDB / 6°CWB • Heating : Indoor Ambient Temp 20°CDB / 15°CWB, Outdoor Ambient Temp 7°CDB / 6°CWB
characteristics” chapter should be considered for electrical work and design. Especially the
power cable and circuit breaker should be selected in accordance with that. • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m. • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard. 5. EUROVENT Test Condition : 5. EUROVENT Test Condition :
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard. • Performance values on the this PDB are based on Ceiling mounted cassette combination. • Performance values on the this PDB are based on Ceiling mounted cassette combination.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditons during operation. •R efer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit • Refer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit
Therefore, these values can be increased owing to ambient conditons during operation.
combination and more detail test conditions. combination and more detail test conditions.
6. The maximum combination ratio is 160%. 6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases. (R32, GWP (Global warming potential) = 675) 7. This product contains Fluorinated greenhouse gases. (R32, GWP (Global warming potential) = 675)