0% found this document useful (0 votes)
12 views27 pages

04 Standards

Uploaded by

cris
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views27 pages

04 Standards

Uploaded by

cris
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

Power

 Quality  and  Harmonics  Analysis  (FIEC05967)  

   Standards  

Síxifo  Falcones,  PhD.  


FIEC-­‐ESPOL  
CBEMA  and  ITIC  Curves  [3]  
• Computer  equipment  sensiTvity  to  sags  and  swells  can  be  
charted  in  curves  of  acceptable  sag/swell  amplitude  
versus  event  duraTon.  In  the  1970s,  the  Computer  
Business  Equipment  Manufacturers  AssociaTon  (CBEMA)  
developed  a  curve  uTlizing  historical  data  from  mainframe  
computer  operaTons,  showing  the  range  of  acceptable  
power  supply  voltages  for  computer  equipment.  The  
horizontal  axis  shows  the  duraTon  of  the  sag  or  swell,  and  
the  verTcal  axis  shows  the  percent  change  in  line  voltage.    
• In  the  1990s,  the  InformaTon  Technology  Industry  Council  
(ITIC)  curve  was  developed  by  a  working  group  of  CBEMA.  
In  recent  years,  the  ITIC  curve  has  replaced  the  CBEMA  
curve  in  general  usage  for  single-­‐phase,  120-­‐V,  60-­‐Hz  
systems.    
Acceptable Rated

Perc
0
power supply voltage

8.33 ms
−50

CBEMA  and  ITIC  Curves  [3]   −100


0.0001 0.001 0.01 0.1
Undervoltage conditions

Time (sec)
1 10 100 1000

Figure 2.5 The CBEMA curve [2.5].


[© 2004,
Power-Quality Standards 19 IEEE, reprinted with permission]

250 250

200 200

Overvoltage condition Overvoltage conditions

Percent change in bus voltage


Percent change in bus voltage

150 150
0.5 cycle

0.5 cycle
100 100

50 50
± 10%
Acceptable Rated Acceptable Rated
0 0
power supply voltage power supply voltage
8.33 ms

8.33 ms
−50 −50
Undervoltage conditions Undervoltage conditions

−100 −100
0.0001 0.001 0.01 0.1 1 10 100 1000 0.0001 0.001 0.01 0.1 1 10 100 1000
Time (sec) Time (sec)
Figure 2.5 The CBEMA curve [2.5]. Figure 2.6 The ITIC curve [2.5].
[© 2004, IEEE, reprinted with permission] [© 2004, IEEE, reprinted with permission]

CBEMA  Curve   ITIC  Curve  


250

200
CBEMA  and  ITIC  Curves  [5]  
• The  CBEMA  curve  and  ITIC  curve  differ  in  the  
way  their  regions  are  presented.  CBEMA  is  a  
conTnuous  curve,  whereas  ITIC  has  a  series  of  
verTcal  and  horizontal  lines.  The  ITIC  curve  
has  an  expanded  acceptable  region  compared  
to  the  CBEMA  curve.  Both  these  curves  have  
been  accepted  as  standards  and  published  in  
the  latest  versions  of  IEEE  Std.  446  and  IEEE  
Std.  1100    
CBEMA  Curve  Regions  
Another set of methods adopted by Electric Power Research
PQ  Index  
Institute (EPRI) known as EPRI 2D and 3D Histograms [7] and
• EPRI indices
Reliable   Power  (e.g.
Meters  SARFIx) [8].
(RPM)  
Reliable has  developed  
Power Meters a   (RPM) has developed [9] a technique
technique  for  determining  
for
an  determining an index using CBEMA curve overlays (Fig. 1)
index  using  CBEMA  
curve  ois
which verlays  
known which  
as ithe
s   Power Quality Index (PQI) that is used
known  as  the  Power  
toQuality  
coverIndex  both(PQI)  
overvoltage
that  is   and undervoltage events.
used  
Supposeto  cover  an
both  
under voltage or over voltage event has co-
overvoltage  and  
ordinates
undervoltage   (t,V).
events.  Define
  the corresponding CBEMA voltage
as voltage on the CBEMA curve corresponding to
• The  RPM  PQ  Index  
corresponds  
duration t. to  an  event  
severity  index.  
The RPM PQI the event is given by

(1)

The RPM PQ Index corresponds to an event severity index


PQ  Measurement  Output:  
 ITIC  Magnitude-­‐DuraTon  Scaaer  Chart  
Figura 1.10. Curva CBEMA

PQ  Standards  by  Topic  [4]  


1.5. NORMAS Y ESTANDARES

La Tabla 1.2 muestra los estándares de calidad de la energía relacionados a distintos tópicos de estudio
y/o análisis.

Tabla 1.2. Estándares de calidad de la energía por tópico


Tópico Estándares
Grounding IEEE Std 446, IEEE Std 141, IEEE Std 142, IEEE Std 1100, ANSI/NFPA 70
Powering ANSI C84.1, IEEE Std 141, IEEE Std 446, IEEE Std 1100, IEEE Std 1250
Surge protection IEEE C62 series, IEEE Std 141, IEEE Std 142, NFPA 78, UL 1449
Harmonics IEEE Std C57.110, IEEE Std 519, IEEE P519a, IEEE Std 929, IEEE Std 1001
Disturbances ANSI C62.41, IEEE Std 1100, IEEE Std 1159a, IEEE Std 1250
Life/fire safety FIPS PUB94, ANSI/NFPA 70, NFPA 75, UL 1478, UL 1950
Mitigation IEEE Std 446, IEEE Std 1035, IEEE Std 1100, IEEE Std 1250, NEMA-UPS
equipment
Telecommunications FIPS PUB94, IEEE Std 487, IEEE Std 1100
Equipment
Noise control FIPS PUB94, IEEE Std 518, IEEE Std 1050
Utility interface IEEE Std 446, IEEE Std 929, IEEE Std 1001, IEEE Std 1035
Monitoring IEEE Std 1100, IEEE Std 1159
Load immunity IEEE Std 141, IEEE Std 446, IEEE Std 1100, IEEE Std 1159a, IEEE P1346
System reliability IEEE Std 493
IEEE Std. 1159-1995
2.2.1. Forma Trigonométrica de la Serie de Fourier

Si la función f(t) es una función


Calidad deperiódica,
la Energíaentonces se puedeArmónico
y Análisis representa
de la forma
Fourier  Series  trigonometric   FCorm  
f (t) =C +∑ Cos ( nω t[−3]  
θ )

ma Trigonométrica de la SerieCalidad
de Fourier
0 n 0 n
n =1
de la Energía y Análisis Armónico en Sistemas Eléctrico
donde
C 0 = 12 a0
n f(t)
ma If  f(t)  
es una
Trigonométrica is  afunción
 periodic   funcTon,  
periódica,
de la Serie it  centonces
de Fourier an  be  represented  
Cn = a
se puede
2
 
as:representar
+b 2
por una s
n n

ión f(t) es una función periódica, entonces


∞ se puede representar por una serie trigonométric
θ n = tan ( an )
f ( t ) = C∞ 0 + ∑C n Cos ( nω0 t − θ n )
−1 b n
a
f ( t ) = C 0 + ∑C n Cos
n =1( nω t − θ )
0 n ω =
2π (2.3)
0
n =1 T

10 =y 2 a0
1
C0 C
= a 2 0 T/2

a0 = 2
T ∫ f ( t ) dt
= n a= + ba
Cn C 2
n
22
nn +b 2
n
−T / 2

T/2 (2.4)
θ n = tan −1
θn
( ) b
= tan −1 ( n )
bn
an
an = 2
T ∫ f ( t )Cos ( nω t ) dt
−T / 2
0

an

T/2

ω0 = bn = 2
∫ f ( t ) Sen( nω t ) dt

T 0
T −T / 2

ω0 =
LaTfigura 2.2. muestra una forma gráfica de interpretar las serie de Fourier
a n = T2 ∫ f ( t )Cos ( nω t ) dt
0 (2.5)
−T / 2

Representación   b =
n
2
T
T/2
d(e  
∫ f ( t ) Sen los  Coeficientes  de  
nω t ) dt
0

la   S erie   d e   F ourier   [ 3]  
−T / 2

La figura 2.2. muestra una forma gráfica de interpretar las serie de Fourier

magnitud

real
tiempo

C0

imag
C1

C3

C5

C7

frecuencia
Figura 2.2. Representación de los coeficientes de la serie de Fourier

__________________________________________________________________________________________________
Calidad de la Energía y Análisis Armónico en Sistemas Eléctricos
screta de Fourier
Forma  Complejas  y  Discreta   f (t ) = ∑dF e  
e la  Serie  
donde los coeficientes de esta serie esta dados
∞ por
jnωt
a de Fourier (TDF) es obtenida de la transformada de Fourier de una función n
T /2
n = −∞1
un intervalo de tiempo [0, T ]. La TDF de una función discreta f [n] esta dada

donde representar
gonométrica se puede los coeficientes
de   F
por ladeforma
ourier  
esta serie esta dados
compleja
 
por
dada por:
Fn =
T
−T / 2
f (t )e − jnωt dt

2.2.3. Transformada Discreta de Fourier


N −1


T /2
1 ∞
F [kf](=t ) = fF[ne]e

1

− jkn 2π / N
jnωt = 0,1,2,3,..., N
Lak transformada − 1 de Fourier
discreta )e − jnωt dtde la transformada de
Fn = (TDF) fes(tobtenida
N n
n =0
n = −∞ de tiempo [0, T ]. La TDF de una función
muestreada (discreta) en un intervalo T −T / 2
por por F [k ],
sta dados porN −1 2.2.3. Transformada Discreta de Fourier

N −1
f [n] = F [k ]e jkn 2π / N
n = 0,1,2,3,..., N − 1 F [k ] =
1

f [n]e − jkn 2π / N k = 0,1,2,3,..., N − 1
1 k = 0 La transformada discreta de Fourier (TDF)Nesn =obtenida de la transformada de Fo
T /2


0

inversa porde tiempo [0, T ]. La TDF de una función di


− jnωt
Fn = f (muestreada
t )e dt (discreta) en un intervalo
y la transformada
T
muestras. −T / 2 por F [k ], N −1

La  transformada  rápida  de  Fourier  (FFT)   f [n] = ∑


es  Fu[kn  
]e algoritmo  
n = 0,1,p
jkn 2π / N
2,ara  
3,..., N − 1
ue F [k ] es la contraparte de Fn , y f [n] la contraparte deN −f1 (t ) .
ourier
resolver  la  TDF  de  una  maera   más  
1 rápida  y  eficiente.  Se  puede  
F [k ] = ∑ f [n ]e − jkn 2π / N k = 0,1,2,3,..., N − 1
k =0

(TDF) es demostrar  
obtenida de qlaue   la   TDF  
transformada
donde Nr esequiere  
eldenumero
Fourier Nmuestras.
de ^2  
N =m
de nuna0 ulTplicaciones,  
función mientras  
de tiempo [0l,a  
que   Ty]F.laFT  
La TDF de unainversa
requiere   sfunción
olamente   f [n] esta dada mulTplicaciones  
discreta2*N*log2(N)  
de hacer notar1
transformada por
Se debe que F [k ] es la contraparte de F , y f [n] la contraparte d
n
para  obtener  el  mismo  resultado.    N −1
N −1   f [n] = ∑ F [k ]e jkn 2π / N n = 0,1,2,3,..., N − 1
f [n ]e − jkn 2π / N k = 0,1,2,3,..., N − 1 k =0
Figura 4.1. Rectificador trifásico
Six-­‐pulse  RecTfier:  AC  Current  
La generación de armónicas en este caso depende de la operación del propio rectificador y

Harmonics  Content  
que alimenta, a continuación se muestran una serie de simulaciones en las cuales se
comportamiento de este rectificador ante diferentes condiciones de operación.

Caso 1: Resistencia de 1 Ω , α=0o 25

i a (t) i b (t) i c (t)


%
20

15

0
10

a) Corrientes en el lado de CA 00 10 20 b) Voltajes


30 40 en el
50 lado
60 de CD
70

arm ónica
________________________________________________________________________________________
ITM-PGIIE 37 c) Corrientes del lado de CA
Figura
V
V1
N
distorsión están definidos en % de cantidades eléctricas, estos valores son muy
conocer el grado de contaminación
N delalas
Para redes eléctricas.
corriente
∑ V h
2


Harmonic  DistorTon  V Indexes  
h=2
V 2
h
THD = × 100 V
n Armónica h=2
THD Total
1
= × 100 (3.3) N
V
V1
Para la corriente
∑I
h=2
2
h

THDI = × 100
I1
N

∑I
N

∑VN 2 2
h Para armónicas individuales h
h=2
THDV = h=2
×2100 THDI = × 100
(3.3)
V1 ∑I h I1 V
h=2 IHDh = h × 100
THDI = × 100 (3.4)
V1
e Voltage  Total  Harmonic  
ID
Para armónicas
1
istorTon    (THDv)  
individuales Current  Total  Harmonic   DistorTon  (THDi)  
3.2.2. Distorsión Total de Demanda
uales N Vh
∑ I 2 × 100 IHDh =
h V N


h=2 1
THD I = × 100 I h2
(3.4)
V
× 100I 1
= hDistorsión
IHDh3.2.2. Total de Demanda TDD = I (3.5)
h=2
× 100
V1 dem − max
individuales
Individual  Harmonic  DistorTon  (IHD)   Total  DN emand  DistorTon  (TDD)  
l de Demanda
Vh

3.2.3. Interferencia Telefónica I 2
h=2
h

IHDh = × 100 TDD = × 100



(3.5)
V I
N 1 dem − max
I .T . = (
∑ h hI TIF )2

∑I 2

h=2
h h =1
Factor  K  [3]    
Calidad de la Energía y Análisis Armónico
• En  la  gran  mayoría  de  los  casos  cuando  un  transformador   alimenta  cargas  no  
lineales,  este  transformador  se  sobrecalentamiento  aun  cuando  no  ha  alcanzado  sus  
KVA  
Se nestima ominales.  
que   el calentamiento de los transformadores debido a las armónica
• Se   esTma  que  eall  ccuadrado
proporcional alentamiento   de ladarmónica
e  los  transformadores  
multiplicadodebido   por lasa  lpérdidas
as  armónicas  
que estaes   produ
directamente  proporcional  al  cuadrado  de  la  armónica  mulTplicado  por  las  pérdidas  
aparece
que   esta  pelroduce,  
factor K de  el cual
esta   es aplicado
manera   aparece  a transformadores.
el  factor  K  el  cual  es  aplicado  a  
transformadores.    
• Estefactor  
Este   factorK  vK viene
iene   especificado
especificado   en  los  en losde  
datos   datos
placa  de
de  aplaca
lgunos   detransformadores,  
algunos transformad
indicando  
capacidadla  del capacidad  
transformador del  transformador  
para alimentar para  cargas
alimentar   no clineales
argas  no  sin
lineales  
exceder sin   la temper
exceder  
a la cualla  están
temperatura  
diseñados, de  oesto
peración  
es: a  la  cual  están  diseñados,  esto  es:    

∞ 2
⎛ Ih ⎞ 2
Factor K = ∑h =1
⎜⎜
⎝ I rms
⎟⎟ h

• La  
Donde corriente   de  la  expresión  
la corriente es  la  corriente  
de la expresión (3.8) es de  la
la  ccorriente
arga  no  lineal  
de la la  cual  no
carga será  
linealo  es   la cual se
alimentada  por  el  transformador.    
por el transformador.
• Los  factores  K  más  comunes  de  transformadores  son  de  4  y  13,  los  cuales  son  
uTlizados  para  alimentar  cargas  que  uTlizan  recTficación  principalmente.    
Los factores K más comunes de transformadores son de 4 y 13, los cuales son utiliza
cargas que utilizan rectificación principalmente.
IEEE  Standard  519  
• IEEE  Standard  519  [2.1]  (denoted  IEEE  Std.  519-­‐1992)  is  
Ttled  “IEEE  Recommended  PracTces  and  Requirements  
for  Harmonic  Control  in  Electrical  Power  Systems.”  
• The  abstract  of  this  standard  notes  that  power  
conversion  units  are  being  used  today  in  industrial  and  
commercial  faciliTes,  and  there  are  challenges  
associated  with  harmonics  and  reacTve  power  control  
of  such  systems.  
• The  standard  covers  limits  to  the  various  disturbances  
recommended  to  the  power  distribuTon  system.  The  
1992  standard  is  a  revision  of  an  earlier  IEEE  work  
published  in  1981  covering  harmonic  control.    
SelecTon  of  the  Point  of  Common  
Coupling  (PCC)    
• El  PCC  (Point  of  Common  Coupling)  es  el  punto  donde  otros  
usuarios  pueden  ser  conectados  con  el  sistema.  El  PCC  puede  ser  
localizado  en  el  lado  primario  o  secundario  del  transformador,  
dependiendo  de  donde  estén  conectados  el  resto  de  los  usuarios.    
• Es  importante  tomar  en  cuenta  la  conexión  del  transformador.  Una  
conexión  estrella-­‐delta  hace  que  las  armónicas  de  secuencia  cero  
en  el  lado  de  la  delta  (secundario)  no  circulen  hacia  la  estrella  
(primario).    
The voltage Customer #2 sees at the service entrance is the voltage
at the “point of common coupling,” often abbreviated as “PCC.” The har-

IEEE  Std.  519  Voltage  DistorTon  Limits  


monics drawn by Customer #1 cause voltage distortion at the PCC, due
to the voltage drop in the line resistance and reactance due to the har-
monic current.
• The  
Shown basic   themes  
in Figure of  are
2.2 IEEE   Standard  
harmonic 519  has  tlimits
distortion wo  components.  
found in IEEE 519
•forFirst,  
harmonic the  uTlity   has  the  limits
distortion responsibility  
at the point to  produce  
of common good  coupling.
quality   The
voltage  
voltage sine  waves.  
harmonic distortion   limits apply to the quality of the power the
Secondly,  
•utility must edeliver nd-­‐use  to
customers  
the customer.have  tFor
he  rinstance,
esponsibility  
for systems to  limit  tof
he  less
harmonic  
than 69 kV, IEEE currents  
519their   circuits  
requires draw  
limits of f3rom   the  line.  
percent harmonic   distortion
for an individual frequency component and 5 percent for total harmonic
distortion.

Table 11.1
Voltage Distortion Limits

Individual Voltage Total Voltage


Bus Voltage at PCC Distortion (%) Distortion THD (%)

69 kV and below 3.0 5.0


69.001 kV through 161 kV 1.5 2.5
161.001 kV and above 1.0 1.5

NOTE: High-voltage systems can have up to 2.0% THD where the cause is an HVDC
terminal that will attenuate by the time it is tapped for a user.
Figure 2.2 Voltage harmonic distortion limits from IEEE Std. 519-1992, p. 85 [2.1].
Power-Quality Standards 17
IEEE  Std.  519  Current  DistorTon  Limits  
Table 10.3
Current Distortion Limits for General Distribution Systems
(120 V Through 69 000 V)

Maximum Harmonic Current Distortion


in Percent of IL

Individual Harmonic Order (Odd Harmonics)

ISC/IL <11 11≤h<17 17≤h<23 23≤h<35 35≤h TDD

<20* 4.0 2.0 1.5 0.6 0.3 5.0


20<50 7.0 3.5 2.5 1.0 0.5 8.0
50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<1000 12.0 5.5 5.0 2.0 1.0 15.0
>1000 15.0 7.0 6.0 2.5 1.4 20.0

Even harmonics are limited to 25% of the odd harmonic limits above.

Current distortions that result in a dc offset, e.g., half-wave converters, are not allowed.

*All power generation equipment is limited to these values of current distortion, regardless of
actual ISC/IL.

Where
ISC ! maximum short-circuit current at PCC.
IL ! maximum demand load-current (fundamental frequency component) at PCC.
Harmónicos  en  ConverTdores  Basados  
4 Chapter One
en  Conmutación  por  Línea  
4 Chapter One
70 Chapter Five

D1 D1 D3 D3 D5D5
a +
aThree-Phase b
Three-Phase
ia
b service c IL load
service
a
b c D2
IL VL
D4 D6 IL load
c
D2 D4 − D6

(a)
(a)
ia(t) Phase
current (a)
IL
IL
Phase
current ω
90° 180° 270° 360° Electrical
60 120 180 240 300 360 degrees
−IL
IL
−IL
(b)
Spectrum for ideal
(b)three-phase bridge Electrical
1.20
60 120 A180
Figure 1.3 three-phase
240bridge300rectifier.
360 degrees
(a) The circuit. (b) The ideal
phase current drawn by a three-phase bridge rectifier.
1.00

−IL 0.80
Amplitude

adjustable speed drives. The electrical diagram of a three-phase bridge


rectifier is shown in Figure 1.3a. Each of the six diodes ideally conducts
0.60
current for 120 degrees
(b) of the 360-degree cycle. The load is shown as a
0.40
current source that maintains the load current, IL, at a constant level—
Figure 1.3 A three-phase
for example,bridge rectifier.
by an ideal (a) The
inductor. Thecircuit. (b) The
three-phase ideal source has
voltage
0.20
phase current drawn by a three-phase bridge rectifier.
the waveform of Figure 1.2. The resultant current in one source phase
0.00 is shown in Figure 1.3b. The current is highly distorted, as compared
1to a2sine3 wave,
4 and
5 can6 distort
7 8 the9 voltages
10 11 of12 the 13 14 system.
supply
Harmonic number (N)
As will be discussed in Chapter 4, the square-wave rectifier load cur-
Harmonic Current Sources 71

Twelve-­‐pulse  RecTfier  SimulaTon  


Y/Y
Six-pulse
rectifier
Harmonic Current Sources 71

ia
a Six-pulse
Y/Y rectifier
b ia IL
a
c
b IL
c L
Six-pulse LOAD
∆/Y rectifier L
Six-pulse R
LOAD
∆/Y rectifier
R

(a)
(a)
ia(t)
ia(t)

t
t

(b)
Magnitud  de  las  Corrientes  Ai rmónicas  
Calidad de la Energía y Análisis Armónico en Sistemas Eléctricos
R (t) LR
+
VR (t)
-
del  TCR  Monofásico  vs  aÁngulo  de  
RES ESTÁTICOS DE POTENCIA
VS (t)

Conducción    
státicos utilizan tiristores para el control de la potencia reactiva. Los cuales son
ntrol de potencia reactiva y así mismo para el control de voltaje en redes de
mente. La figura 4.8. presenta el modelo de un TCR monofásico. Figura 4.8. TCR monofásico

0 .1 5
3a a r m ó n ic a
m ag. 5a a r m ó n ic a
+ p .u . 7a a r m ó n ic a
iR (t) LR VR (t) 0 .1 0 9a a r m ó n ic a

-
VS (t)

0 .0 5

Figura 4.8. TCR monofásico


Thyristor  Controled  Reactor  (TRC)   0
0 50 100 150 200
0 .1 5
3a a r m ó n ic a á n g u lo d e c o n d u c c ió n ( g r a d o s )
ag. 5a a r m ó n ic a Figura 4.9. Magnitud de las corrientes armónicas del TCR monofásico contra ángulo de
.u . 7a a r m ó n ic a
9a a r m ó n ic a Como se puede observar, el TCR inyecta diferentes armónicas dependiendo del ángu
0 .1 0
algunas armónicas (múltiplos de tres) se pueden eliminar si se tiene un TCR trifásico
delta.
Static VAR compensator (SVC)
HV  bus  
T  
X/2 X/2

TSC  
TCR   IQ Z

n Es una reactancia variable


n Se basa en Tiristores
n Tiene dos componentes:
n Thyristor Controlled Reactor (TCR)
n Thyristor Switched Capacitor (TSC)
Thyristor  Switched  Capacitor  (TSC)  

• Discrete  variaTon  of  capaciTve  reactance  to  generate  


reacTve  power.  
• Each  thyristor  conducts  during  the  whole  half  wave.  
Thyristor  Controlled  Reactor  (TCR)  

ConTnuous  variaTon  of  


inducTve  reactance  in  order  to  
absorb  reacTve  power.  
SVC:  Generated  ReacTve  Power  

• AddiTonal  capacitors  shir  the  curve  


verTcaly.  
V-­‐I  CharacterisTcs  of  the  SVC  
References  
M.  Madrigal,  “Calidad  de  la  Energía  y  Análisis  Armónico  en  Sistemas  Eléctrico.”  
A.  Kusko,  M.  Thompson,  “Power  Quality  in  Electrical  Systems.”  
IEEE  Standard  519,  “IEEE  Recommended  PracTces  and  Requirements  for  Harmonic  
Control  in  Electrical  Power  Systems.”  
IEEE  Standard  1159,  “IEEE  Recommended  PracTce  for  Monitoring  Electric  Power  
Quality.”    
GO.TECH  Brasil,  EFICIÊNCIA  E  QUALIDADE  DE  ENERGIA,  
hap://www.gotechbrasil.com.br  
PQView,  ITI  (CBEMA)  Magnitude-­‐DuraTon  Scaaer  Chart,  hap://www.pqview.com  
H.  M.  S.  C.  Herath,  Student  Member,  IEEE,  Victor  J.  Gosbell,  Member,  IEEE,  and  Sarath  
Perera,  Member,  IEEE  ,  Power  Quality  (PQ)  Survey  ReporTng:  Discrete  Disturbance  
Limits,  IEEE  TRANSACTIONS  ON  POWER  DELIVERY,  VOL.  20,  NO.  2,  APRIL  2005  ,pp  
851-­‐858.  
Tom  Lecklider,  Senior  Technical  Editor,  March  2007,  Measuring  Power  CorrupTon,  
EvaluaTon  Engineering,  hap://www.evaluaTonengineering.com  

You might also like