Lab 5
Lab 5
Gov. D. Mangubat Ave., Brgy. Burol Main, City of Dasmariñas, Cavite 4114, Philippines
Tel. Nos. (046) 416-4339/41 www.eac.edu.ph
Submitted by
IBARDALOZA, JOSHUA, A.
COMETA, SEAN LYNDON
RESPICIO, OSCEL
ERANDIO, JOHN REX
INTRODUCTION
Objectives
Discussion
Connect your single-phase transformer, resistive load, power supply, AC ammeter, and
AC voltmeter according to the circuit diagram in Figure 44-1. Make sure the primary
winding (3 to 4) is connected to the 0-208 V AC output of the power supply, terminals 4
and 5. Connect the transformer secondary winding terminals 1 to 2 and 5 to 6 in series
to achieve a 240 V AC voltage between points A and B. Use a single independent
resistance section for R1 and R2. Ensure all resistance switches are in their open
positions before starting. Turn on the power supply and adjust it to achieve a voltage of
208 V AC, as indicated by the power supply voltmeter.
Measure and record the following parameters in Table 44-1: the total output voltage of
the transformer (ET), the voltages across each of the loads (E1 and E2), the line
currents (I1 and I2), and the current in the neutral line (IN). Place a resistance of 300
ohms in each load circuit by closing the appropriate switches. Measure and record all
the quantities specified in Table 44-1. The current in the neutral line is zero because the
loads in the circuit are balanced, causing the currents in the hot conductors to cancel
each other out in the neutral conductor, resulting in no net current flow in the neutral
line.
Place a 1700-ohm resistance in the R2 load while keeping R1 at 300 ohms. Monitor and
note all the necessary measurements. Once done, set the voltage to zero and switch off
the power source. The neutral line current is the difference between the line currents
due to balanced load conditions, where the currents in the hot conductors cancel each
other out in the neutral conductor as per Kirchhoff’s current law. This ensures that the
net current in the neutral line is the difference of the line currents. Disconnect the
neutral line from the transformer by removing the connection between the transformer
and the neutral current meter (IN). Switch on the power supply and adjust it to 201 V
AC, as shown by the power supply voltmeter.
Measure and note all the necessary measurements. After noting, set the voltage to zero
and turn off the power supply. If R1 and R2 were incandescent lamps in a home, there
would be noticeable changes in brightness due to fluctuations or imbalances in current
flow. Reconnect the neutral line from the transformer to the neutral current meter (IN).
Replace load R2 with the inductance module. Set R1 to 400 ohms and R2 to an
inductive reactance (X1) of 400 ohms. Switch on the power supply and adjust it to 028
V AC. Measure and note all the necessary measurements. After noting, set the voltage
to zero and turn off the power supply. To ascertain if the neutral line current equals the
arithmetic difference of the line currents, compare their values. If the loads are
balanced and purely resistive, they should be equal. However, if the loads contain
reactive components, there might be deviations due to phase shifts and power factor
considerations.
Results