Tecnair H Humidifier User Manual Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

BUILT IN IMMERSED ELECRODES HUMIDIFIER

USER MANUAL

THIS MANUAL REFERS TO THE FOLLOWING UNITS:


DIRECT EXPANSION AND CHILLED WATER AIR CONDITIONERS WHIT
ACCESSORY “INTERNAL HUMIDIFIER”

TECNAIR LV S.p.A
www . tecnairlv . it Via Caduti della Liberazione 53 Manual code 75803107B.0807
info @ tecnairlv . it 21040 UBOLDO (VA) “VERSIONE ORIGINALE”
Tel. +39029699111 / Fax +390296781570
Manual code 75803107B.0807
Page 2 of 24
INDEX

1 PURPOSE OF THIS MANUAL 5


2 COMPONENTS DESCRIPTION 6
3 PIPE CONNECTION AND INLET WATER CARACTERISTIC 8
3.1 PIPE CONNECTIONS 8
3.2 WATER CIRCUIT CARACTERISTIC 8
3.3 INLET WATER CARACTERISTIC 9

4 OPERATING PRINCIPLES, CONTROL AND OTHER FUNCTIONS 10


4.1 ATER CONDUCTIVITY CONTROL 10
4.2 HIGH LEVEL SENSOR 10
4.2.1 FOAM PRESENCE CONTROL 10
4.3 CURRENT PEAK VALUE CONTROL 10
4.4 DRAINING MODE 11
4.4.2 MANUAL DRAINING MODE 11
4.5 PRE-WASH FUNCTION 11

5 HUMIDIFIER ALARM 12
5.1 µAC MICROPROCESSOR (CP4) 12
5.2 pCO MICROPROCESSOR 14

6 MAINTENANCE AND CYLINDER REPLACING 16


6.1 HUMIDIFIER COMPONENT DESCRIPTION (MAINTENANCE) 16
6.2 PERIODICAL MAINTENANCE 17
6.3 REPLACING THE CYLINDER 17
6.4 OTHER IDRAULIC COMPONENT MAINTENANCE 18

7 TROUBLE ANALYSIS 19
7.1 CHECK AND SOLVE THE HUMIDIFIER PROBLEM 19

8 NOTE 22

Manual code 75803107B.0807


Page 3 of 24
Manual code 75803107B.0807
Page 4 of 24
1 PURPOSE OF THIS MANUAL
This handbook introduces you to the installation, use and maintenance procedure of the internal humidifier.
In the following chapter we will explain some points of extreme importance so to allow you to use this unit in the
best way.
Therefore TECNAIR LV suggests you to take a deepened reading of this handbook.
Some of the arguments refer to operation modality, components and accessories of the unit that are not
described in this handbook.
For these TECNAIR LV suggests to read the MICROPROCESSOR USE handbook, placed in the unit.
If, after the reading of this handbook, you still find yourselves in a situation of difficulty do not hesitate to contact
our after sales service:

After sales office


Tel. +39029699111/Fax +390296781570
@ : aftersales @ tecnairlv . it

Manual code 75803107B.0807


Page 5 of 24
2 COMPONENTS DESCRIPTION
The internal humidifier whit immersed electrodes are following made:

N° DESCRIPTION
1 Bearing frame
2 Cylinder
3 Drain solenoid valve
4 90° revolving drain connection
4a Straight drain connection (optional)
5 Conductimeter + Fill tank
6 Fill solenoid valve

Component details:

N° DESCRIPTION
1 Fill solenoid valve
2 Flow rate limit device
3 Supply pipe
4 Fill pope
5 Overflow pipe
6 Conductivity measuring electrodes
7 Fill tank – overflow device*
8 High level electrodes
9 Steam outlet
10 Elecrodes (2/6 mono-phase, 3/6 three-
phase)
11 Cylinder casing
12 Bottom filter
13 Drain solenoid valve

* Device used to avoid water overflowing from the fill tank above the safety level (for example if there are a
malfunction of the controller or a likage on the fill valve).
The fill tank is equipped whith an overflow septum that discharges the excess water through a special pipe. The
overflow septum is located in a lower position then the fill one ( -40mm) to avoid back-flow into the fill pipe.

Manual code 75803107B.0807


Page 6 of 24
µAC electronic regulation board:

pCO elecronic regulation board end TAM:

PCOUMID200 EXTERNAL TAM

Manual code 75803107B.0807


Page 7 of 24
3 PIPE CONNECTION AND INLET WATER CARACTERISTIC

3.1 PIPE CONNECTIONS

During the installation of the unit is requested the connection of the inlet water pipe (see picture below) whith the
follow caracterisc. The draining pipe is installed by TECNAIR LV.

3.2 WATER CIRCUIT CARACTERISTIC

These condition satisfy a good idric circuit:

‰ Line interrupted by a intercept water tap


‰ Installation of a mechanical filter on the inlet water
‰ Water temperature and pressure on the accettable limit

IMPORTANT WARNING: upon installation completion, drain the supply pipe for approximately 30 minutes by
piping the water direcly into the drain connection without sending it into the umidifier. This operation avoid any
possible residual product that could clog the fill valve and/or produce foam during boiling.

Manual code 75803107B.0807


Page 8 of 24
3.3 INLET WATER CARACTERISTIC
The humidifier need normal water whit the following caracteristic:

‰ Pressare between 0.1 and 0.8 Mpa (1-8 bar, 14.5-116 PSI)
‰ Temperature between 1 and 40 °C
‰ Istant flow rate not lower than the fill solenoid valve rated flow rate (0.6 – 1.2 l/m)
‰ Connection type ¾”G Male

LIMIT VALUES FOR MEDIUM-HIGH CONDUCTIVITY SUPPLY WATER OF A LIMITS


HUMIDIFIER WITH IMMERSED ELECTRODES Min. Max.
Hydrogen ions pH - 7 8,5
Specific conductivity at 20 °C σR, 20 °C - µS/cm 300 1250
Total dissolved solids TDS - mg/1 (¹) (¹)
Dry residue at 180 °C R180 - mg/1 (¹) (¹)
Total hardness TH - mg/l CaCO3 100 (²) 400
Temporary hardness - mg/l CaCO3 60(³) 300
Iron + Manganese - mg/l Fe Mn 0 0,2
Chlorides - Ppm Cl 0 30
Silica - mg/l SiO2 0 20
Residual chlorine - mg/l Cl 0 0,2
Calcium sulphate - mg/l CaSO4 0 100
Metallic impurities - mg/l 0 0
Solvents, diluents, soaps, lubricants - mg/l 0 0

LIMIT VALUES FOR MEDIUM-LOW CONDUCTIVITY SUPPLY WATER OF A LIMITS


HUMIDIFIER WITH IMMERSED ELECTRODES Min. Max.
Hydrogen ions pH - 7 8,5
Specific conductivity at 20 °C σR, 20 °C - µS/cm 125 500
Total dissolved solids TDS - mg/1 (¹) (¹)
Dry residue at 180 °C R180 - mg/1 (¹) (¹)
Total hardness TH - mg/l CaCO3 50 (²) 250
Temporary hardness - mg/l CaCO3 30(³) 150
Iron + Manganese - mg/l Fe Mn 0 0,2
Chlorides - Ppm Cl 0 20
Silica - mg/l SiO2 0 20
Residual chlorine - mg/l Cl 0 0,2
Calcium sulphate - mg/l CaSO4 0 60
Metallic impurities - mg/l 0 0
Solvents, diluents, soaps, lubricants - mg/l 0 0

(1) Values depending on specific conductivity; in general: TDS ≅ 0.93 * σ20; R180 @ 0.65 * σ20
(2) not lower than 200% of chlorides content in mg/l of Cl-
(3) not lower than 300% of chlorides content in mg/l of Cl-
Warning: no relation can be demonstrated between water hardness and conductivity.

IMPORTANT WARNING! DO NOT TREAT WATER WHITH SOFTENERS!

This could cause corrosion of the electrodes or the formation of foam, leading to potential operative problem or
failure.

Avoid:

1. Using well water, industrial water or water drawn from cooling circuits; in general, avoid using potentially
contaminated water, either from a chemical or bacteriological point of view.
2. Adding disinfectants or corrosion inhibiters to water, as these substances are potentially irritant.

Manual code 75803107B.0807


Page 9 of 24
4 OPERATING PRINCIPLES, CONTROL AND OTHER FUNCTIONS

4.1 ATER CONDUCTIVITY CONTROL

The humidifier have a double control on the water conductivity. The first is made directly on the inlet water and
the second on the cylinder water during the boiling.
The inlet water conductivity value is compared with two alarm threshold for the pre- alarm end alarm of high
conductivity.
Is necessari don’t go over this threshold to not compromise the good working of the humidifier, in this case the
software give a pre-alarm end if the problem continue stop completely the production.
The second control is made direcly on the water of the cylinder. During the boiling and the evaporation the
conductivity of the water increase for the concentration of the salts. This measuring is indirect by the reduction time of the
current from the nominal value to the -5%. This time is compared whith a nominal one (one for each cylinder) and, if it is
lower is make a draining (dilution draining) of a certain quantity of water and re-fill a lower conductivity fresh water.
Shuld remeber that the value of conductivity under the I/O loop is the inlet water value and it is re-fresh at each
filling phases.

4.2 HIGH LEVEL SENSOR

The high level alarm can be made by one of the following problem:
‰ Total filling of the cylinder – whith humidifier OFF – foe a leakage on the fill solenoid valve
‰ For the high level on the first start-up filling
‰ For the cylinder full of limestone
‰ For the foam on the cylinder, totally indipendent by the water level

For all of these problem the internal algorithm start a specific procedure to come beck to the normal working. On the
last three case the humidifier start the low production phase.

4.2.1 FOAM PRESENCE CONTROL

If the high level sensors are touched by the water, the internal function are not able to recognise if it is water or
foam.
If after few draining cycle and few stabilization cycle the sensors are already covered, then start the anti-foam
cycle (if the alarm situation remain the umidifier start a complete washing cycle [complete draining Æ complete fill Æ
complete draining])
If after the wasing cycle, the electrodes are already covered and another cycle is necessary, then the system
give the alarm of PRESENCE OF FOAM.

4.3 CURRENT PEAK VALUE CONTROL

Any time the humidifier is activated is possible see, for a short time, a big peak value of current.
On the system, this peak value of current, can be accepted for the first 60 second whith this limitation:

‰ If the current is In*170% bigger then the nominal one, there are a HIGH CURRENT DRAINING. At the end of the
draining the humidifier restart.
‰ On the first 60 sec. for the second time , or over the 60 sec. for the first time, if the current is In*150% bigger then
the nominal one, there are a 30 second draining. At the end of the draining there are a “HIGH CURRENT” alarm.
‰ Over the 60 sec. if the current is alwais In*130% bigger then the nominal one. there are a HIGH CURRENT
DRAINING for 5 seconds. At the end of the draining the humidifier restart. If the problem remain there are a “HIGH
CURRENT” alarm.

Manual code 75803107B.0807


Page 10 of 24
4.4 DRAINING MODE

The draining is activated for depends on several factors (es. High level, high current , etc.) the difference
between the draining type is the drain time.
The type of draining (DRAIN_MODE) are the follow:

‰ Set-point reduction draining.


‰ Drain for no current whith full cylinder.
‰ First high current drain
‰ Second high current drain on the first 60 sec.
‰ Drain before the enabling
‰ Default drain

4.4.1 AUTOMATIC DRAIN MODE

The humidifier have the follow automatic drain mode:

‰ Set-point reduction drain: during this mode, in case the reduction of the set-point is more then 33%, the
humidifier drain a little bit of water. This function is usefull to produce immediately the right quantity of steam
wen the set-point is drastically reduced. This function is always active.

‰ Inactivity drain: the inactivity drain is usefull to empty the cylinder when the humidifier don’t produce steam for
a longer period (default 1 day). The function is actived by default, is possibile disabile and ch’ange the periode
by the user loop.

‰ Periodic drain: During the normal working, if the water is heavy hardness, the humidifier empty the cylinder
after a settable period (default 24 hours). This function is usefull to drain the limeston and increase the life of the
cylinder. in modo da favorire la fuoriuscita dei sedimenti.The function is actived by default, is possibile disabile
and ch’ange the periode by the user loop.

‰ Diluition drain under tension: During the steam production, the cumul of salt increase the internal conductivity
and, for a good working, have to stay under certain limit. To make this the humidifier, in automatic way, make a
little drain at the right time (called “Diluition drain”) and fill a new water with a lower conductivity. During this
drein by default the power is stopped, in this way the drained water have not tension. In this little period the
production is stopped. Is possible make the drain with tension, whith the main power on, disabling the
parameter: Drain without tension.

4.4.2 MANUAL DRAINING MODE

The manual draining is usefull durino the maintenance, and any other activity on the cylinder, to remove any
presence of water inside the cylinder.
The draining is different by the microprocessor installed:

‰ µAC: To make the comlete draining you have to press the apposite key inside the elecrical panel for minimum
120s (see electrical wiring diagam).

‰ pCO: To make the comlete draining you have to enable the apposite parameter on the maintenance loop for
minimum 120s. At the end of the draining disabile the parameter. (See the use manual of the microprocessor).

4.5 PRE-WASH FUNCTION

Is possible enable this function during the periodic maintenance. This function have two different working
phases:

‰ Whith power OFF, the drain valve and the fill valve are opened for a certain time how depends on the cylinder
capacity. This phase is necessary to clean-up the pipe and the solenoid valve.

‰ Three full filling phases and relative draining phases whith the power on. This phase is necessary to clean-up
the wall and the electrodes of the cylinder.

Manual code 75803107B.0807


Page 11 of 24
5 HUMIDIFIER ALARM
In this chapter are explaned all the alarm how you can have on the humidifier, the possible reasons and the
solution.

5.1 µAC MICROPROCESSOR (CP4)

On the µAC microprocessor (CP4 humidifier board) the alarm are signalled by a flashing red led. The number of
flashing give the possibility to understand the alarm type. In the table you can reach the explanation of the flashing.

Red LED Alarm


Description & causes Solution
flashes Type Reset Alarm relay
Electrodes over-current:
1 Water conductivity too high
(usually after a short stop) 1 Drain some water and re-start
2 High water level due to a 2 Verify if the fill valve is properly
2 Short Block Manual Active
drain valve malfunction working
3 High water level due to a fill 3 Check for any leakage of the fill valve
valve malfunction when the unit is OFF
4 Electrodes malfunction
1 Check the esternal signal:Type (V o
Not current on the elecrodes:
mA)? Value? Connection?
3 Short when the uniti s on the steam is Block Manual Active
2 Swich OFF the unit, disconnect the
not produced
power and check the internal wiring
1 Download the correct konfiguration by
Humiset
4 Short Internal memory error Block Manual Active
2 If the problem remain please contact
Carl assistance
1 Control the parameter B6 by the
RS485 connection
2 Switch OFF the unit and wash the
conductivity elecrodes
High conductivity on the inlet 3 If the problem persists, change the
5 Short Block Manual Active
water source of supply water or install a
suitable treatment system
(demineralisation, even partial).
NOTE: the problem will not be solved
by softening the supply water.
Do maintenance and/or replace the
2 Long Cylinder depleted Signal Manual -
cylinder
1 Check that the fill pipe from the mains
to the humidifier and the internal pipe
are not blocked or bent and that there
is sufficient supply pressure (0.1 to 0.8
MPa);
2 Check the fill valve is properly
working;
3 Long Lack of supply water Disable Manual Active
3 Check for counter-pressure onto the
steam hose higher than the maximum
limit, preventing the entry by gravity of
supply water into the cylinder;
4 Check that the steam outlet pipe is not
is choked and that there is no
condensate inside it
Cylinder completely depleted or excessive
4 Long Excessive production reduction Disable Manual Active
foam. Do maintenance to the cylinder
Check the drain circuit and the proper
5 Long Drain malfunction Disable Manual Active
operation of the drain valve
1 Download the correct konfiguration by
Humiset
6 Long User parameters error Block Manual Active
2 If the problem remain please contact
Carl assistance

Manual code 75803107B.0807


Page 12 of 24
1 Check the conductibility of the supply
water
2 Check the limit set by parameter b5
Supply water high conductivity via RS485
7 Long Signal Manua -
pre-alarm 3 If necessary, install a suitable
demineralizer.
NOTE: the problem will not be solved
by softening the supply water.
1 Check the connection to the external
External command signal
regulator
8 Long not properly connected Disable Manua Active
2 Check the settings of parameters A0
(only 2 to 10V)
and A2 via RS485
With the OEM turned off:
Cylinder full with production 1 Check for any leaks from the fill valve
9 Long Disable Manual Active
not in progress or the condensate return pipe
2 Check that the level sensors are clean
Foam is usually caused by surfactants in
the water (lubricants, solvents, detergents,
water treatment agents, softeners) or an
excessive concentration of dissolved salts:
1 Drain and clean the water supply
10 Long Foam inside the cylinder Signal Manua -
pipes
2 Clean the cylinder
3 Check for the presence of softeners
(in this case, use another type of
supply water or reduce the softening)
Cylinder almost completely Do maintenance and/or replace the
11 Long Signal Manua -
depleted cylinder

Manual code 75803107B.0807


Page 13 of 24
5.2 pCO MICROPROCESSOR

On the pCO microprocessor the alarm reaching is automatic by the software. The problem are explaned in the
alarm mask of the display. In the follow table are explaned the type of alarm:

ALARM CAUSES SOLUTION RESET ACTION

This alarm incoming:


1 Check the pressure of the fill pipe
1 During the fill if: water (0.1÷0.8 MPa, 1÷8 bar);
Cylinder
• The maximum fill time is spired 2 Check the fill valve state; Production
empty of Manual
• If there are a strange value. 3 Check if the steam pipe haven’t a high stopped
water
2 If during the pre-wash the water counterpressure or a narrowing
level don’t tuch the high level passage
electrodes.

This alarm incoming if, durino the low


Low
production phases, the current at the Cylinder full of limestone or too high foam. Production
production Manual
end of the filling is lower then a Make the maintenance of the cylinder stopped
alarm
calculated threshold.

This alarm incoming during the drain:

1 If the current do not decrease; Production


Drain alarm Check the drain valve or the drain pipe Manual
2 If during a foam problem or a pre- stopped
wash the water tuch the high level
sensor.

This alarm icoming if the threshold are Check and wash the conductivity sensor
High exeed for 60 minute during the and, if the problem persist, change the type
Production
conductivity production or immediately if the water of water quality Manual
stopped
alarm supply conductivity are 3 time bigger NOTE : The problem are not solved by
then the threshold. the water softeners.

It appear at the follow situations:


1 During the fill state.
2 If the difference between the initial
current and the measuring current
Low current Whit the unit OFF and the main power OFF Production
is different of a limit calculed by Manual
alarm check the internal wiring connection stopped
the target current, or if is at full
3 If the water touch the high level
4 If the current is minor then a limit
calculated on the target current

It appear at the follow situations:


1 If before 60 seconds there are one
second peack of current over the
150% of the nominal, there are a 1 Check the drain valve working
High current draining of 30s. At the and of the 2 Check if there are some lickages on Production
Manual
alarm draining the Humidificator was the fill valve stopped
stopped and the unit give the 3 Drain some water and restart the unit
alarm.
2 If, over the first 60s, the current
reach the 130% of the nominal.

Manual code 75803107B.0807


Page 14 of 24
This alarm incoming:

1 If after a the anti-foam cycle 1 Wash the fill pipe


(Drain Æ Fill Æ Drain) the water 2 Wash the cylinder Production
Foam alarm Manual
tuch the high level sensor; 3 Check the presence of a salt reducer stopped
2 If after a complete washing the and disable them
high level sensor are already
tuched.

This alarm incoming if the water


tuch the high level sensor when:
Cylinder full Check if the fill valve have no lickage or the Production
1 the unit is in OFF position or the Manual
of water elecrodes are clean. stopped
humidifier is disabled;
2 the first phase of the pre-wash are
not finished

This alarm incoming if after some


Full cylinder cycle of stabilizing the production
Make the periodical maintenance Manual Only signal
pre-alarm parameter are higher that certain
internal parameter.

This alarm incoming if after 3 hours


Full cylinder after the full cylinder pre alarm the
Change or wash the cylinder Manual Only signal
alarm parameter are already over the
threshold

Manual code 75803107B.0807


Page 15 of 24
6 MAINTENANCE AND CYLINDER REPLACING

CAUTION!
BEFORE ALL WORKS PUT THE MAIN SWITCH
IN POSITION “O”

6.1 HUMIDIFIER COMPONENT DESCRIPTION (MAINTENANCE)

In the table are descripted the component:

N° DESCRIPTION
1 Main structure
2 Cylinder blocking system
3 Fill box + conductimeter
4 Full pipe
5 Cylinder fill pipe
6 Fill box pipe
7 Fill valve
8 Fill/drain group
9 O-Ring
10 90° revolving drain connection
11 Straight drain connection (optional)
12 Drain valve

Manual code 75803107B.0807


Page 16 of 24
6.2 PERIODICAL MAINTENANCE

The humidifier need some periodical checking to increase the life of the cylinder and improve the working
modus. The checking are be made as follow:

‰ Every fortnight and no more than 300 working hours


For both the disposable and openable cylinders, check that no significant water leak is present and verify
cylinder operation and the general conditions of the container. Also check that no arc or spark originate between
the electrodes when the machine is operating.
‰ Every three months and no more than 1,000 working hours
For disposable cylinders, verify cylinder operation, check that no significant water leak is present and replace
the cylinder, if required. For openable cylinders, check the container for markedly blackened areas: in case they
are present, check the scale condition of the electrodes and, if necessary, replace them together with the O-
rings and the cover gasket.
‰ Every year and no more than 2,500 working hours
For disposable cylinders, replace the cylinder. For openable cylinders, check that no significant water leak is
present, verify cylinder operation and the general conditions of the container. Also check the container for
markedly blackened areas: in case they are present, replace the electrodes together with the O-rings and the
cover gasket.

After extended use or due to the use of water with a high salt content, the solid deposits that form naturally on
the electrodes might spread until they cover the cylinder internal wall. In case particularly conductive deposits form, the
heat consequently produced might overheat plastic and melt it; in the most severe cases, heat might perforate plastic,
causing the water to leak from the cylinder to the tank.
As a precaution, check the quantity of deposits and verify that no deformation or blackening is present on the
wall of the cylinder, otherwise replace it.

6.3 REPLACING THE CYLINDER

IMPORTANT WARNING: the cylinder might be hot: before touching it, let it cool or use protective gloves.

The duration of the cylinder depends on different factors, including: complete filling with limestone and/or partial
or total corrosion of the electrodes, proper use and dimensioning of the humidifier, working output, water quality, careful
and regular maintenance.
After a variable period is necessary replace the cylinder. To made this operation in the proper way please
respect the following instruction.

IMPORTANT WARNING: all service and/or maintenance operations must be carried out by specialist and
qualified personnel aware of the necessary precautions.

To replacing the cylinder:

1) Place the unit in OFF position


2) Completely drain the water contained in the cylinder
3) Turn the appliance off and open the mains knife switch (safety procedure)
4) Remove the steam pipe from the cylinder
5) Disconnect the electrical connections from the top of the cylinder
6) Release the cylinder from the fasteners and lift it for removal
7) Assemble the new cylinder on the humidifier operating in reverse order.

Manual code 75803107B.0807


Page 17 of 24
6.4 OTHER IDRAULIC COMPONENT MAINTENANCE

WARNING:

1) For the plastic component washing do not use solvent or aggressive agent;
2) To remove the limeston you can use vinegar or vinegar acid at 20%, after you can wash whit water.
3) After the changing or the control of the component please check if all the connection are made in the
right way. Start-up the unit and make some pre-wash cycle, then check if there are some water filling.

‰ Filling valve: Disconnect the pipe and the elecric wire, remove the valve and check if the filter are clean; If
necessary, wash it whit water and a soft brush.

‰ Fill/Drain group: Chek and wash the cylinder connection whith water. Check the O-ring status; if necessari
change it.

‰ Draining valve: Disconnect the elecric wire and the draining pipe, remove the valve by the screw, wash it whit
water and a soft brush.

‰ Fill box and conducimeter: Check if there are some limeston iside the connection and on the elecrodes; Wash
it whit water.

‰ Fill and high level pipe: Check if there are some limeston iside and wash it whit water.

Manual code 75803107B.0807


Page 18 of 24
7 TROUBLE ANALYSIS

CAUTION!
BEFORE ALL WORKS PUT THE MAIN SWITCH
IN POSITION “O”

The following chapter aims at assisting the operator in searching possible troubles in the unit equipment.
Starting from the type of problem in question, indication is given of the possible sequential causes of the trouble itself and
the possible remedies. The description of the causes is general, so it takes into consideration the most complete possible
versions of the units; the operator shall take care to identify, from time to time, only the matters of interest and/or the
functions actually featured in the unit in question.
Any intervention on the unit shall be carried out only by competent skilled personnel.
We recommend not executing any kind of operation if you have not enough knowledge of the unit working
principle.

7.1 CHECK AND SOLVE THE HUMIDIFIER PROBLEM

Legend of the failure diagram:

FAILURE FUNCTION

CAUSE REMEDY

Manual code 75803107B.0807


Page 19 of 24
NON WATER SHORT-
CHARGING CIRCUITED
CYLINDER

LACK OF TENSION FAILURE OF THE LACK OF WATER


IN CHARGING CHARGING VALVE TOO CONDUCTIVE
SOLENOID SOLENOID WATER

CHE CK THE DISCONNECT AND PROVIDE A


HUMIDIFIER‘S REPLACE THE SOFTENER
ELECTRONIC SOLENOID ACCORDING TO
CARD THE ACCEPTED
VALUES

CHECK THE
CONTACTOR’S
CONSENT

PRESENCE OF
POLYPHOSPHATE
MEASURING
DEVICES

CHECK WATER CLEAN PRESSURE CLEAN WATER ELIMINATE


TAPS REDUCER AT CHARGING VALVE MEASURING
CHARGING VALVE FILTER DEVICES
OUTLET

Manual code 75803107B.0807


Page 20 of 24
CONTINUOUS LACK OF BOIL
WATER
DISCHARGE

TOO FULL FOAM IN THE TOO FULL OPEN LACK OF OPEN MAGNETOTH RUN-DOWN
CYLINDER DUE TO CYLINDER CYLINDER DUE DISCHARGING WATER DISCHARGIN ERMIC CYLINDER
MAGNETOTHERMIC TO LOW WATER VALVE DISC G VALVE DISC SWITCH
SWITCH CONDUCTIVITY INTERVENTIO
INTERVENTION N

MANUALLY MANUALLY PUT SALT IN THE CLEAN SOLENOID MANUALLY DISCONNECT AND
DISCHARGE AND DISCHARGE THE FILLING BAC AND FILLING BAC DISCHARGE AND REPLACE THE
RESTORE THE CYLINDER RESTORE THE CYLINDER
MAGNETOTHERMIC MAGNETOTHERMIC
SWITCH SWITCH

CHECK WATER CLEAN FILTER AND CLEAN SOLENOID


TAPS WATER AND DISCHARGING
DISCHARGING VALVE
VALVE

TOO FULL NON WATER THE WATER


CYLINDER DISCHARGE RUN OVER THE
BAC

MAGNETOTHERMI LOW WATER DEFECTIVE LACK OF TENSION CLOGGED AND VERY SMALL
C SWITCH CONDUCTIVITY DISCHARGING IN DISCHARGING COUNTERINCLINED DISCHARGING
INTERVENTION VALVE SOLENOID SOLENOID DISCHARGING PIPELINE
PIPELINE

MANUALLY CLEAN AND DISCONNECT AND


DISCONNECT THE CHECK THE
DISCHARGE AND ELIMINATE THE REPLACE THE
SOLENOID AND HUMIDIFIER’S
RESTORE COUNTER- PIPELINE
REPLACE IT ELECTRONIC
INCLINATION
CARD

Manual code 75803107B.0807


Page 21 of 24
8 NOTE

Manual code 75803107B.0807


Page 22 of 24
Manual code 75803107B.0807
Page 23 of 24
Manual code 75803107B.0807
Page 24 of 24

You might also like