Application Guidelines
Application Guidelines
Overview
This document describes the methodology recommended by InduSoft when creating applications with InduSoft Web Studio
(IWS). The suggestions and tips described in this document apply to most of the real-world applications. However, different rules
may apply when necessary (e.g. to comply with different customers standards).
Recommendations
Page 1/5
Tech Note – Application Guidelines
July 14, 2017 – Rev. E
Remove all tags not used on the application (Home > Tags > Remove unused tags). Make sure that you do not remove
tags that can be used indirectly during the runtime (e.g.: Using @TagName indirect tag syntax or built-in functions like
$GetTagValue()).
Execute the “Home > Verify” command and check for errors in the Output (Log) window. Fix the errors, and run the
Verify Application command again. Repeat this procedure until all errors are solved.
Delete the trend history files from the \HST sub-folder of the application, unless this data cannot be lost.
Delete the alarm/event history files from the \Alarm sub-folder of the application, unless this data cannot be lost.
Delete any file generated by the application, such as recipe files, reports, and database files that were created only to
test the application.
Create a backup of the application (compact the application folder, including all files and sub-folders), and store it in the
appropriate place.
Make sure that all tags that should hold independent values on each Thin Client station are configured with Scope
“Local” instead of “Server”. Scope is a tag property.
Review the “Quality Feedback Service” settings section from the Project Settings > Preferences dialog. Usually, it is
recommended to enable the option to “Generate dump files when an unexpected error happens”, so the cause of the
error can be investigated after analyzing the dump files. However, it is important to make sure to monitor the
\Web\Dump sub-folder of the application and make sure to send the dump files (if any) in this folder to your software
vendor.
Delete the dump files (if any) from the \Web\Dump sub-folder before deploying the application.
General:
Assess risks associated with the development, deployment, and operation of the application and take actions to prevent
or mitigate foreseeable issues. For example, if the application saves data into history files/databases, create a method
to manage the data before running out of resources (storage memory).
The application’s documentation (description and comments), as well as the tag names, must be written in English,
unless requested otherwise for the end user.
Write an objective description for each worksheet created in the project.
Avoid creating file names with the space character (e.g. application name, screen name, recipe name or report name).
Avoid using accentuation (e.g. ~, ^, `, and so forth) anywhere in the application (including file names).
Although IWS is not case sensitive, it is recommended to follow the same standard for tags and expressions throughout
the whole application (e.g. UserName, Str2Asc(), and so forth).
Avoid adding space characters at the beginning or at the end of labels, captions or descriptions. It may cause problems
when translating the application to different languages.
Keep in mind that the background tasks are executed on the Server only (not on the Thin Client stations).
Avoid using synchronous methods that potentially takes a long time to be executed, such as the Math() function, Wait()
function, or recursive loops. Keep in mind that the execution of each task (thread) is sequential. For example, when
calling the Wait() function in a Math(), the whole cycle of execution for all Math sheets is “paused” until the wait()
function returns.
Avoid calling synchronous functions that display dialogs (e.g. RDFileN() built-in function, MsgBox VBScript function) from
background tasks (math sheets or scheduler sheets). The task that executed the function will be paused until the user
closes the dialog. Keep in mind that scripts executed with the built-in function $RunGlobalProcedureOnServer() are
executed on the Server (background), even when called from the screens (Viewer).
Page 2/5
Tech Note – Application Guidelines
July 14, 2017 – Rev. E
Avoid using the Changed() function. Use the Scheduler module instead. The Changed() built-in function is kept in the
product for legacy reasons only. Use the Scheduler module or local variables in a script to detect that a tag changed.
Avoid hard-coding paths, unless when necessary. Files saved and stored in the application’s directory can be accessed
using the built-in function GetAppPath(), which returns the current path of the application. Using this approach, access
to files will keep working even if you move the application to a different directory.
Use Recipes (XML format) to store configurable settings that should be loaded in specific events (e.g.: when loading the
application). Alternatively, you can also use an external database for higher flexibility.
Organize the procedures defined in the Global > Procedures interface using the '$region:<GroupName> syntax to group
functions and sub-routines in the same sub-folder of the Project Explorer. Alternatively, use different Procedure files to
organize your functions and sub-routines in isolated libraries.
Avoid using project tags in procedures that are designed to be used as generic libraries across different projects.
Use the Output window (Log window) to monitor the communication with the external devices (Field Read Commands,
and Field Write Commands) to make sure that the communication is flawless. Depending on the driver configuration (no
simultaneous connections), communication errors (e.g.: timeout, invalid block size, and so forth) in one communication
group will decrease the overall communication performance.
Use the $Ext() built-in function to translate text that may be displayed in external dialogs, such as message boxes
launched by the VBScript MsgBox function.
Avoid repeating the same logic in scripts. Instead, create procedures (functions or sub-routines) in the Global >
Procedures or Graphic Scripts libraries.
When writing scripts in the VBScript that might fail during the runtime (e.g.: initialize an external COM Server object),
use the VBScript “On Error Resume Next” and “On Error Goto 0” statements to handle the errors gracefully. In this case,
check for error and create a mechanism to notify the user if it occurs (e.g.: alarm message).
Whenever using a built-in function to open a database connection (e.g.: DBCursorOpenSQL, DBCursorOpen), make sure
that the built-in function to close the database connection is eventually called (DBCursorClose). Opening connections
continuously and not closing them will cause “memory leak” and it will eventually crash the system for lack of resources.
You can configure a string tag between curly braces (e.g.: {ConnectionString}) on database settings for tasks and objects
(e.g.: Project > Options > Default Database) as well as for Database built-in functions (Project Explorer > Tasks >
Database/ERP > Connections). Therefore, you can set the string tag dynamically in a single location (e.g.: on the Startup
script), centralizing the configuration. Moreover, if the Connection String includes paths for files stored in an application
sub-folder, you can build the Connection String value dynamically, concatenating the application folder with the built-in
function $GetAppPath().
Applications for Touch-screen devices:
Enable the Virtual Keyboard from the Project Settings dialog.
Do not use the “Right-click” events and avoid using the Double-click event from the Command dynamic.
Design objects that support interactions from the user (e.g.: buttons, scroll bars, sliders) with an appropriate size to be
operated from a touch-screen device, which does not offer the same precision of a mouse pointer.
Tags Database:
Create Classes in the Tags Database to encapsulate properties from a specific device, object or area of equipment of the
process.
Create array tags when the same property is applied to many instances of the same device, object or area of equipment of
the process.
Page 3/5
Tech Note – Application Guidelines
July 14, 2017 – Rev. E
Add an objective description to all tags created in the tags database. The description must be objective and provide
minimum information for future maintenance of the project.
Avoid creating tags to hold information that is available in the tag fields (e.g. HiLimit, AlrStatus, TimeStamp, Quality, and so
forth).
The tag name should be as short as possible, but it must be long enough to be meaningful, indicating the value that the tag
handles.
Avoid using retentive values or retentive parameters for many tags. Doing so may decrease the performance of the system,
because the tag values must be saved in disk whenever the tags change of value. If it is necessary to keep the value of many
tags retentive, study the feasibility of using the Recipe task to save the values at a suitable rate.
Graphics:
Use groups of screens when applicable to avoid replication of objects and configuration. Information that should be
available continuously to the operator should be configured in one or more screens that are always open and visible. For
instance, use a Header screen, which displays the logo of the company, date, time, username, main menu and so forth.
Do not duplicate screens that are identical or very similar. Use features such as indirect tags and indexed array tags to
display different information from the same screen.
If the application must be translated to different languages during runtime, make sure that the interface is designed to
accommodate the text in all supported languages—and not only in the original language used to created the screens.
When designing screens with many static graphics, study the feasibility of using a background graphic (instead of several
graphic objects) to increase the performance during runtime. If more than one screen uses the same background, use the
Shared Image option from the Screen Attributes dialog.
Consider using Linked Symbols to any interface that is used more than once in the application (e.g.: pump icons, PID
faceplates, and so forth).
Avoid using spaces or special characters in screen names to avoid incompatibility with third-party Web Servers.
Store linked pictures into the \Web\Resources sub-folder of the application. Avoid absolute paths in Linked Pictures (use
relative paths from the aforementioned sub-folder).
Page 4/5
Tech Note – Application Guidelines
July 14, 2017 – Rev. E
since it avoids the need to pool data between the Client and the Server. However, depending on the nature of the process, it
may overload the communication network, especially if many items are changing continuously. In order to avoid
unnecessary communication traffic, it is strongly recommended to configure a “Dead Band”, so only material information is
exchanged.
The communication between the Server and Thin Clients is driven by exception events (tag changes). It optimizes the
communication and avoids pooling between the Server and the Thin Client stations. However, if tags monitored on the Thin
Client stations change too frequently, it is recommended to increase the “Send Period” setting to minimize the traffic in the
network.
InduSoft Web Studio allows the user to save history data either in the proprietary history files (binary files) or in an external
SQL Relational Database, such as Microsoft SQL Server, Oracle, MySQL and so forth. SQL Relational Databases support
flexible queries that optimize the data retrieval from a large database. Therefore, for applications that require history for a
large number of tags saved at a high frequency and kept for a long period of time, it is recommended to use an external SQL
Relational Database to store the data.
The Trend Control is able to retrieve data from the proprietary history files and also from external SQL Relational Databases.
Depending on the architecture of the application and schema of the database tables, it will be more efficient to configure
the Data Source “Database” instead of using the Data Source “Tags” to retrieve data from the external SQL relational
database. Using the data source “Database”, the user can customize the queries to optimize the data retrieval according to
the particular schema of the database tables and type of data required by the user.
Avoid writing scripts that are executed continuously in the “Screen_WhileOpen” sub-routine of screens or in the
“Graphics_WhileRunning”, unless when necessary. Scripts configured in these sub-routines are continuously executed by the
Viewer module and, therefore, competes for the resources to uptime the screens with optimum performance.
The scripts configured in the “Screen_OnOpen” sub-routine of screens are executed before displaying the screen. Therefore,
scripts that potentially take a long time may delay the screen appearance.
Pictures, such as bitmaps demand more resources than native objects and can decrease the performance when opening and
updating screens with large pictures or with a large number of pictures. As much as possible, use efficient picture formats
(e.g.: PNG instead of BMP).