MICROGRID SOLUTION
with Fronius Inverter and
Victron Energy 1
1 Fronius Inverter
4 Victron GX component
DAVID HANEK
MICROGRID EXPERT
CONFIGURATION DIAGRAM:
PV GENERATOR
FRONIUS INVERTER
INVERTER /
CHARGER GX COMPONENT
Power path
Communication path LOW VOLTAGE BATTERY
OR
OPTIONAL
∆f=1.7Hz
100%
P/Pm
0
46 Hz 50 Hz 51 Hz 52 Hz 53 Hz
Frequency
For system monitoring, inverters that are equipped with a communication card (Datamanager or
inverter integrated) communicate with the Victron GX component via WLAN or LAN using the
Modbus TCP/JSON protocol.
VICTRON COMMUNICATION The Victron products are all automatically recognized and visualized by the GX device. Communi-
cation between the products and GX device can be established as follows:
/ MultiPlus or Quattro via VE.Bus (RJ45 UTP cable)
/ SmartSolar MPPT via VE.Direct (all models - VE.Direct cable) or VE.Can
(large models - RJ45 UTP cable)
/ CAN bus batteries via CAN bus cable (CAN bus BMS type A or B)
FRONIUS INVERTER The Fronius inverter has a special MicroGrid setup (MG 50/ MG 60) with various functions that
SETUP ensure stable operation of the MicroGrid. This can be set on the display of the Fronius inverter.
DIMENSIONING THE The maximum output power of the Fronius inverter must not exceed the maximum power of the
COMPONENTS Victron inverter/charger. Fronius specifies the AC output power in kW, whereas Victron specifies
it in kVA.
The ratio of kW to kVA must always be 1:1!
Practical example:
Three Victron Quattro with an AC output power of 8 kVA each are connected in parallel (=24 kVA
AC output power). This means that the total installed AC output power (PACmax) of the Fronius
inverters must not exceed 24 kW.
MULTIPLE FRONIUS If several SnapINverters are connected in the system, which need to be controlled for e.g. in regards
INVERTERS of export limitation, they must be connected via the so-called Fronius Solar.Net ring. Connections
from „IN“ to „OUT“ connector need to use a shielded cable (CAT5 or higher).
Feedback on the successful configuration of the Fronius Solar.Net ring can be obtained via the
DATCOM status on the LCD screen. If several Fronius inverters have a Datamanager, the „master/
slave“ position of the Datamanagers must be set correctly. Multiple GEN24 & GEN24 Plus inverters
All information is without guarantee in spite of careful editing - liability excluded. Copyright © 2011 Fronius™. All rights reserved.
have to be connected via Modbus RTU (RS-485) in case of export limitation or external curtailment
is required.
SYSTEM MONITORING The system monitoring of the MicroGrid can be implemented via the Fronius Solar.web online tool
Text and images correspond to the current state of technology at the time of printing. Subject to modifications.
or via the Victron VRM portal.
THREE BUSINESS UNITS, ONE GOAL: TO SET THE STANDARD THROUGH TECHNOLOGICAL ADVANCEMENT.
What began in 1945 as a one-man operation now sets technological standards in the fields of welding technology, photovoltaics and battery charging. Today, the
company has around 5,660 employees worldwide and 1,321 patents for product development show the innovative spirit within the company. Sustainable
development means for us to implement environmentally relevant and social aspects equally with economic factors. Our goal has remained constant throughout:
to be the innovation leader.
Further information about all Fronius products and our global sales partners and representatives can be found at www.fronius.com
EN v05 Sep 2023