Lab 8
Lab 8
Practice work №8
EXPERION INTEGRATION
Almaty, 2024
CONTENT
Introduction .............................................................................................................. 3
1 Purpose of the Work ........................................................................................... 4
2 Practical segment ................................................................................................ 4
2.1 MasterLogic Server Configuration ..................................................................... 4
2.2 ML in QuickBuilder Configuration .................................................................... 5
Conclusion .............................................................................................................. 10
INTRODUCTION
3
1 Purpose of the Work
The objective of this lab is to install Master Logic (ML) Server software on the
Experion Server.
2 Practical part
Before integrating ML Server with Experion PKS, the initial step involves
configuring the MasterLogic Server. The configuration of the MasterLogic Server is
illustrated in Figure 1 below.
4
2.2 ML in QuickBuilder Configuration
In this stage of the practice work, the objective is to configure the Master Logic
Channel, Controller, and Points. This is done using the QuickBuilder application
environment. Initially, the Master Logic component is selected from the component
manager for further utilization. Figure 2 below illustrates the component manager.
5
successfully downloaded. Subsequently, the Master Logic Controller was
configured, as shown in Figure 4 below.
6
Figure 5 above displays the Main Tab of the configured Analog point, with its
PV Source Address set as "MLCON ML03.%WW10$CON#WORD". Moving
forward, in Figure 6 below, the Control Tab of the Analog point is presented.
Additionally, the Setpoint and Output addresses of the point are specified, with
addresses 11 and 12 chosen. Furthermore, in Figure 7 below, the Alarms tab of the
Analog point is presented.
7
As depicted in Figure 7, alarms for the Analog Point have been successfully
configured. The next task is to configure a status point for the ML 200. In Figure 8
below, the Main tab of the Status point configuration is presented.
As displayed in Figure 8 above, a status point has been configured with its PV
source address set as "MLCON ML03.%MX10$CON#BIT". Moving forward, in
Figure 9 below, the Control Tab of the Status Point configuration is presented.
8
As illustrated in Figure 9 above, the Control tab of the Status Point shows the
source and destination addresses of the Output (OP), set as "MLCON
ML03.%MX12$CON#BIT". Moving on, in Figure 10 below, the Alarms tab of the
Status Point configuration is presented.
As depicted in Figure 10 above, a High alarm was configured for the Status
Point at the ON alarm state. The Status Point was successfully configured and
downloaded to the database, marking the completion of the practice work.
9
CONCLUSION
During this practice work, the objective was to integrate the ML200 PLC with
the Experion PKS environment. This task was successfully accomplished by
leveraging the MasterLogic Server application and the Quick Builder environment.
Throughout the process, valuable knowledge was gained on utilizing the
MasterLogic Server application environment and establishing integration between
the ML200 and Experion PKS system.
10
11