Generator Grounding
Generator Grounding
Generator Grounding
Generator Grounding
1
4. Resonant (Arc suppression coil) grounding.
5. Low resistance grounded
6. High resistance grounded/Transformer grounding.
1. Ungrounded systems
If one phase of the system (phase ‘B’) becomes connected to ground due to
a fault, then that phase and the ground will have the same potential. The
voltages in the two healthy phases will then rise to the system phase to
phase voltage. The fault current is restricted by the system (healthy lines)
capacitance to ground current.
2
In reality a fault is seldom solid, but often intermittent in nature (arcing or
re-striking) and there is a danger of transient over voltage. The transient
voltage can reach very high levels (~ six times) the normal phase-to-phase
voltages, which can give cause to insulation failure of one of the healthy
phases. This results in the form of short circuiting. There is also a danger of
a resonance condition if the fault path includes an inductive reactance
equal, or approximately equal, to the capacitive reactance to ground.
Advantages:
Low fault current limited by the system’s capacitance to ground.
The system can be operated, at least for a limited period of time, with
one ground fault present if correctly designed, providing high service
continuity.
Economic earthing scheme.
Disadvantages:
In case of fault, voltages on the healthy phases are equal to line-to-
line voltages, thereby affecting the rating of the surge protective
devices.
Danger of very high over voltages with an intermittent fault. Transient
voltage not controlled.
Difficult to achieve selective ground fault protection.
A second ground fault in another phase would result to phase to phase
short circuit.
Advantages:
Disadvantages:
Very high and potentially destructive fault currents for internal faults.
Complete interruption and possibility of equipment damage. May
cause greater interference with neighboring communication lines.
May cause voltage gradient problems.
Single phase fault escalation to 3-phase fault.
May cause 3rd harmonic voltage1 circulation problems.
1
The voltage of generators has a low content of 3rd harmonic voltage due to the uneven physical distribution of stator-
windings in the generator, which do not produce a fully sinusoidal voltage. The generators should be designed for
minimized 3rd harmonic voltage content by utilizing a 2/3 winding pitch. On the other hand, this usually means over
sizing of the generator and potentially reduced efficiency.
4
3. Low reactance grounded systems
Advantages:
Limits transient and temporary over voltage to values close to those of
a solidly grounded system. Allows the use of lower rated surge
protective equipment.
Lower ground fault current compared to solidly grounded systems.
Disadvantages:
Ground fault current levels, while limited, are still high, with
potentially destructive fault currents.
Low reactance systems may experience circulation of a 3rd harmonic
current.
Resonance conditions might occur. Need of surge protection.
Care should be exercised in rating neutral point equipment
Relatively expensive neutral point equipment.
At resonance, IN = IC
But IN = Vph/XL & IC = 3Vph/XC as illustrated below.
6
If IC is equal to IN there will be no current through the ground, and there
will be no tendency of the arcing grounds to occur.
Advantages
There are advantages of ungrounded neutral system.
It is completely effective in preventing any damage by an arcing
ground.
Disadvantages
Due to varying operational conditions, the capacitance of the network
changes from time to time. Therefore, inductance L of Peterson coil
requires readjustment.
Advantages:
Lower ground fault current compared to solidly grounded systems.
Good control of temporary and transient over voltages.
Easy and selective fault detection.
Disadvantages:
Ground fault current are still at a comparably high level to cause
possible damage.
Care should be exercised in the selection of surge protective
equipment. Low impedance systems may experience the circulation of
a 3rd harmonic current.
7
Relatively expensive neutral point equipment. Costlier than solidly
grounded system.
Advantages:
Limits transient and temporary over voltage to safe values if correctly
designed.
8
Ground fault currents limited to low values, with lower potential
damage for an earth fault.
High enough resistance to inhibit circulation of a 3rd harmonic
current. Relatively inexpensive neutral point equipment.
Easy and selective fault detection with modern relays.
Disadvantages:
May not be applicable to all systems, as the ground fault current
maybe too low to be detected by older types of relays. The equipment
installed in an existing system (e.g. surge arrestors) may also have
voltage ratings that are too low.
High Resistance Grounding normally takes the form of a low ohmic value
resistor connected to the secondary of a distribution transformer with the
primary winding of the transformer connected from the generator neutral to
ground. The advantage of the distribution transformer resistor combination
is that the resistor used in the secondary of the distribution transformer is of
comparatively low ohmic value and of rugged construction as compared to
obtaining the same result by installing a high ohmic, low current resistor
directly in the generator neutral.
9
Fig. Resistance grounding with Distribution Transformer
Utilities generally prefer solidly grounded systems for voltage levels from
69 kV upwards, for their transmission and sub-transmission systems. This
is primarily due to the control of Transient Over Voltages permitting the
use of lower rated insulation and surge protection. At 3.3-33 kV, practices
differ, even between utilities in the same country. Consideration has to be
given to a variety of factors; economics, loads (three-phase or single phase),
service continuity, control of over voltage, and even environmental
considerations. Industrial systems are often resistance grounded - high or
low resistance, or ungrounded for very critical processes. The primary goal
here is service continuity and equipment damage control.
10
Calculation of Neutral Resistor:
And the Capacitance of Cable from generator terminal to CB, Unit Aux.
Transformer, and Generator Transformers can be neglected since they are
in the range of Pico Farad.
Cg = Co + Cs
= 0.385 µF
Xco = 1/ (2πfCg) = 8267.8 Ω
As Shown in Fig. 1, for the Restriking voltage not to exceed 2.5 times the
rated voltage, Rn should be around Xcg.
Hence,
Rn = Xcg = 2756.0 Ω
11
Rating of Distribution Transformer:
During a sustained ground fault, current will flow in the secondary resistor.
The maximum neutral voltage is assumed to be phase to ground voltage.
Isec max = Vsec max / Rsec = 240/3.94 = 61.0 A
Since the Current rating of the calculated Grounding Resistor is high, it can
be significantly reduced by selecting the voltage ratio of the distribution
transformer high i.e. 11/ 3 : 0.480 kV
During a sustained ground fault, current will flow in the secondary resistor.
The maximum neutral voltage is assumed to be phase to ground voltage.
Isec, max = Vsec max / Rsec = 480/15.74 = 30.5 A
This value is the current through the neutral device during a ground fault
condition. Grounding resistor must be rated to withstand the full thermal
current.
12
Duration of Overload Multiple of Rated kVA
10 Sec 10.5
60 Sec 4.7
10 min 2.6
20 min 1.9
2 hr 1.4
Now, the thermal rating of the resistor can be calculated with the
assumption:
if a solid fault occurs so Rfault=0, the power dissipated in the grounding
resistor, Pr, will be:
Pr = E2L-N / Rn = (11000/ 3 ) 2 / 2756.0 = 14.64 kW.
13