Water Tank Design Aci 318 05 Amp 350 01
Water Tank Design Aci 318 05 Amp 350 01
AMY 29-Oct-14 1
Check Date Rev.
MMA 29-Oct-14 0
PROJECT TITLE: PRINCE MAJED PALACE
DESIGN OF UNDERGROUND WATER TANK
CASE 1 : SOIL
-
Moment Earth Pressure Surcharge
d =332 mm
𝑴𝒖−
𝑹𝒖 = =.541
𝒃𝒅𝟐
% of seel (ρ) =.00132 ACI 350-01 section 14.3.2
% of seel (ρ) minmum =.00300 Minimum ratio of vertical reinforcement area to
gross concrete area shall be 0.003
2
Area of steel = ρ x b x h =1200 mm
No. of bar =( As/Abar) =6 Bar's
Area of steel Provided =1206 mm2
Space Between Two Bar's " S " =167 mm Use T16 -150 mm c/c
Provided " S " =150 mm
3)Crack widht check :
Mservice = =37 kN.m
dc =58 mm
A= 2x dc x Space =17400 mm2
FS= (Mu/As x d) =93 N/mm2
W=0.011 x Fs x (dc +A)^1/3/1000 =.10272 mm OK ACI 350-01, R10.6.4
GERGELY LUTZ EXPRSSION
Made Date Sheet
AMY 29-Oct-14 1
Check Date Rev.
MMA 29-Oct-14 0
PROJECT TITLE: PRINCE MAJED PALACE
DESIGN OF UNDERGROUND WATER TANK
𝑲𝒂 × 𝜸𝒔𝒐𝒊𝒍 × 𝒉𝟑 𝑲𝒂 × 𝒒 × 𝒉𝟐 × 𝜸𝒔𝒐𝒊𝒍
𝑴𝒔𝒆𝒓𝒗𝒊𝒄 + = + =35 kN.m
𝟏𝟔. 𝟔𝟕 𝟏𝟐𝟖
d =342 mm
𝑴−𝒖
𝑹𝒖 = =.481
𝒃𝒅𝟐
ACI 350-01 section 14.3.2
% of seel (ρ) =.00117 Minimum ratio of vertical reinforcement area to
% of seel (ρ) minmum =.00300 gross concrete area shall be 0.003
d =344 mm
ACI 350-01 section 14.3.2
Area of steel =0.003x b x h =1200 mm2
2
Minimum ratio of horizontal reinforcement area
For one face =600 mm to groos concrete area shall be 0.003
No. of bar =( As/Abar) =5 Bar's
Space Between Two Bar's " S " =188 mm
Provided " S " =175 mm Use T12 -175 mm c/c
7) Base slab :
d =340 mm water pressure on the base slab and weight of the base
Area of steel =0.0018x b x h =720 mm2 will directly counteracted by the ground pressure .The
pressure of water can be safely resisted by the soil
No. of bar =( As/Abar) =2 Bar's under the floor .
Provided " S " =436 mm Hence :
The floor slab or base slab will only requier normal
rienforcement ,so as the enable if to span over any
possible weak pathes at ground .
CASE 2 : WATER
d =342 mm
𝑴−𝒖
𝑹𝒖 = =.824
𝒃𝒅𝟐
% of seel (ρ) =.0020 ACI 350-01 section 14.3.2
% of seel (ρ) minmum =.0030 Minimum ratio of vertical reinforcement area to
Area of steel = ρ x b x h =1200 mm2 groos concrete area shall be 0.003
𝜸𝑾𝒂𝒕𝒆𝒓 × 𝒉𝟑
𝑴𝒔𝒆𝒓𝒗𝒊𝒄 − = =25 kN.m
𝟑𝟑. 𝟓
T20 -200
GRAVEL FILL (1"-6" SIZE) (TYP) 50 THK. BLINDING 50 THK. PROTECTION SCREED (TYP)
1000mm DEEP CONCRETE (TYP)
EMPTY TANK
Water Level
T16 -150
T12 -175
WATER IN SIDE MEMBRANE WITH
PROTECTION BOARD (TYP)
T20 -425
GRAVEL FILL (1"-6" SIZE) (TYP) 50 THK. BLINDING 50 THK. PROTECTION SCREED (TYP)
1000mm DEEP CONCRETE (TYP)