Power Transformer

The document describes test results from field testing a 80000 kVA 110 kV power transformer. It details measurements of resistance, transformation coefficients, insulation resistance, oil properties, capacitance, no-load current, and lists test equipment. The tests were conducted according to standards and all results were within specification.

Uploaded by

elxan qocayev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views7 pages

Power Transformer

The document describes test results from field testing a 80000 kVA 110 kV power transformer. It details measurements of resistance, transformation coefficients, insulation resistance, oil properties, capacitance, no-load current, and lists test equipment. The tests were conducted according to standards and all results were within specification.

Uploaded by

elxan qocayev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

TRANSFORMER FIELD TEST PROTOCOL

Type : KTPU 123 NC 80000


Power (kVA) : 80000
Voltage (kV) : 110+-2x2,5/15
Factory № : 1LFI4367722610
Frequency
: 50
(Hs)
Phase : 3
Customer :
Contents
1. Measurement of ohmic resistance of circuits 3/7
2.Measurement of transformation coefficient and determination of group
combination 3/7
3.Measurement of insulation resistance 4/7
4.Testing of transformer oil 4/7
5.Measurement of capacitance and tan δ 5/7
6.Measurement of no-load current and power dissipation at low voltage 6/7
7.List of measuring equipment 7/7
T ˚¿¿ = 05°C

Measurement of ohmic resistance of circuits (High voltage)


Position of tap
AN(Ω) BN(Ω) CN(Ω)
changer
1 0,2710 0,2709 0,2725
2 0,2635 0,2633 0,2641
3 0,2560 0,2569 0,2580
4 0,2489 0,2492 0,2498
5 0,2418 0,2410 0,2426

Measurement of ohmic resistance of circuits (Low voltage)


ab (Ω) bc (Ω) ca (Ω)
0,008046 0,008056 0,008068

Measurement of transformation coefficient and determination


of group combination
Status of Voltage (kV) Coefficient AN/ac BN/ab CN/bc
tap changer HV LV of tap changer
HV/LV
1 115,500 4,45 4,46 4,46 4,45
2 112,750 4,34 4,35 4,34 4,35
3 110,000 15,0 4,23 4,23 4,23 4,23
4 107,250 4,13 4,12 4,11 4,12
5 104,500 4,02 4,01 4,01 4,01
6 Group reunion: YnD 11
Measurement of insulation resistance
HV-LV+Tank LV-HV+Tank HV-LV
Time(sec.)
Measured (MOm) Measured (MOm) Measured (MOm)
15 10700 3084 11080
30 14800 3640 16200
45 18700 4150 18900
60 21200 4410 21500
K|¿|¿ 1,98 1,55 1,94

Test voltage: 2.5kV

Nucleus/winding temperature: 05 °C

A simplified connection diagram of the test setup

Testing of transformer oil

Type of transformer oil : NYTRO 10 XN


The breakdown voltage (kV) : >60
tgδ (%) : 0,091 (t=05 °C)

Capacity (C) and tanδ measurement


Test Insulation Test Test compounds Tes Capacity tgδ % İ
No. tests method t (pF)
kV
HV Red Blue Gnd Measured mA
1 C HG + C HL GST-GND H L T G 10 6435,8 0,17 22,569
2 C HG GSTg-RB H L T G 10 1900,02 0,21 5,756
3 C HL UST-R H L T G 10 4535,78 0,19 16,813
4 C HL Test 1 -Test 2 4538,2 16,75
5 C LG + C HL GST-GND L H T G 10 9435,3 0,17 19,256
6 C LG GSTg-RB L H T G 10 5015,3 0,24 12,566
7 C HL UST-R L H T G 10 4420 0,21 6,69
8 C HL Test 5- Test 6 4431,1 7,01

Testing of insulators

Test
Phase Test kV Capacity C 1 (pF) tgδ % I (mA)
No.
1 A 10 201 0,48 0,956
2 B 10 200 0,55 0,975
3 C 10 199 0,48 0,958
4 N 10 198 0,47 0,762
Test kV Capacity C 2 (pF) tgδ % I (mA)
5 A 0,5 178 0,29 0,109
6 B 0,5 172 0,28 0,111
7 C 0,5 175 0,32 0,107
8 N 0,5 301 0,22 0,096

Impressive current density

Test No. Phase Test kV I (mA) P (Vt)


1 AN 10 74,8 618
2 BN 10 55,2 446
3 CN 10 74,9 614

H: HV circle G: Grounding
L: LV circle N: Neutral
Measurement of no-load current and loss at low voltage
Outputs given Short closed Measured values
voltage exits
U,V I, mA P, Vt
a-b b-c 220 44,2 6,41
b-c c-a 220 44 6,21
c-a a-b 220 60,9 8,55

The result: Test results conform to Norms.


List of measuring equipment

Equipment Type Serial number Calibration date


№1. Transformation coefficient and group coupling gauge
Vanguard ATRT-01B 30422 2020
№2. A device for measuring ohmic resistance against direct current
RAYTECH WR14 361-196 2020
№3. Insulation resistance measuring device
MEGGER MIT 1025 1001945101234573 2020
№4. Low-voltage no-load current and loss device
Omicron CPC100 QB462W 2020
№5. Dielectric loss angle and capacitance measuring device
MEGGER DELTA 4010 1463 0613 2020
№6. Fire breakdown voltage tester
MEGGER OTS 100 AF 101250791 2020