General
At present, wireless technology has gradually become an important direction for the
development and application of networks in the industrial Internet in the future due to its
advantages of easy deployment, low construction cost and wide applicable environment.
AWT100 wireless communication terminal is a new wireless data acquisition device launched
by Acrel. The uplink communication includes 2G, 4G, NB, LoRa, LoRaWAN and other
communication modes. The downlink interface provides a standard RS485 data interface,
which can easily connect power meters and RTUs, PLC, industrial computers and other
equipment, only need to complete the initial configuration, you can complete the data
acquisition of MODBUS equipment; at the same time AWT100 series wireless communication
terminal uses a powerful micro-processing chip, with built-in watchdog technology, reliable
performance stable.
Type Description
AWT100-□
2G:2G communication terminal
4G:4G communication terminal
NB:NB-IoTcommunication terminal
Lora:LoRa communication terminal
LW:LoRaWAN communication terminal
Acrel wireless communication terminal
Function Description
■ Support data acquisition of serial port MODBUS RTU protocol, and communicate with Acrel
server through Acrel platform protocol.
■Supports data acquisition for up to 30 MODBUS RTU devices.
■ Supports the acquisition of 5 register address fields for each MODBUS device, each register
address range does not exceed 64.
■ Supports triggering alarms by preset alarm addresses and alarm values for each MODBUS
address range. Each address domain alarm address currently has a maximum of five.
■Support server MODBUS or LoRa transparent communication.
■Support fixed IP and dynamic domain name resolution to connect to the data center.
■Support transparent transmission protocol, universal mode (active rotation, timed reporting),
MQTT protocol, smart power wireless protocol, prepaid wireless protocol
Negotiation, custom development.
■ The functions of the AWT100-LW wireless communication terminal are still under
development, and data can be uploaded to the server through LoRa communication in the
future.
Note: ①The AWT100-2G/NB/4G wireless communication terminal can communicate with the
Acrel server through the Encore platform protocol.
Technical Parameter
Parameter AWT100-LoRa
AWT100-4G AWT100-NB AWT100-2G
name AWT100-LW
LTE-FDD B1 B3 B5 B8
GSM 850
LTE-TDD B34 B38 B39 B40
Working H-FDD B1 B3 B8 EGSM 900 LoRa 460 ~
B41
frequency B5 B20 DCS 1800 510MHz
CDMA B1 B5 B8
PCS 1900
GSM 900/1800M
Dimension Drawings
(2) The network port function (the power and RS485 interface) definition
1 2 3 4 5 6 7 8
POWER
GND NC 485A 485B
(DC12V)
(3)AWT100-2G/NB/4G/LoRa/LW side interface definition
1 2 3 4 5
10 9 8 7 6
1 2 3 4 5 6 7 8 9 10
NC +5V GND 485A NC 485B GND +5V NC
Note:
The two interfaces of the network port and the terminal can only be used one by one and cannot be used at the
same time.
2.(1)Terminals and Wiring of AWT100 Power Module (Selected for AC220V Power Supply)
1 2 3 4 5
10 9 8 7 6
1 2 3 4 5 6 7 8 9 10
NC GND +5V NC +5V GND NC
Panel light definition
1.AWT100-2G/NB/4G wireless communication terminal panel light definition
RUN : If the green indicator light is steady on, the power module is working properly. If the