DC/DC Converter TMDC 60H Series, 60 Watt: Models
DC/DC Converter TMDC 60H Series, 60 Watt: Models
DC/DC Converter TMDC 60H Series, 60 Watt: Models
Models
Order Code Input Voltage Output 1 Output 2 Efficiency
Range Vnom Imax Vnom Imax typ.
TMDC 60-7211H 5.1 VDC 12'000 mA 88 %
TMDC 60-7212H 12 VDC 5'000 mA 89 %
TMDC 60-7213H 15 VDC 4'000 mA 89 %
TMDC 60-7215H 80 - 160 VDC 24 VDC 2'500 mA 88 %
TMDC 60-7218H (110 VDC nom.) 48 VDC 1'250 mA 88 %
TMDC 60-7222H +12 VDC 2'500 mA –12 VDC 2'500 mA 88 %
TMDC 60-7223H +15 VDC 2'000 mA –15 VDC 2'000 mA 88 %
TMDC 60-7225H +24 VDC 1'250 mA –24 VDC 1'250 mA 88 %
Options
TMP-MK2 - Optional DIN-Rail Mounting Kit: www.tracopower.com/products/tmp-mk2.pdf
Input Specifications
Input Current - At no load 10 mA typ.
- At full load 620 mA typ.
Surge Voltage 170 VDC max. (100 ms max.)
Under Voltage Lockout 65 VDC min. / 70 VDC typ.
Recommended Input Fuse 2'500 mA
(The need of an external fuse has to be assessed
in the final application.)
Input Filter Internal Pi-Type
Output Specifications
Voltage Set Accuracy ±2% max.
Regulation - Input Variation (Vmin - Vmax) single output models: 1% max.
dual output models: 1% max.
- Load Variation (0 - 100%) single output models: 1% max.
dual output models: 1% max. (Output 1)
1% max. (Output 2)
- Voltage Balance dual output models: 2% max.
(symmetrical load)
- Cross Regulation dual output models: 5% max.
(25% / 100% asym. load)
Ripple and Noise - single output 5.1 Vout models: 100 mVp-p max.
(20 MHz Bandwidth) 12 Vout models: 150 mVp-p max.
15 Vout models: 150 mVp-p max.
24 Vout models: 150 mVp-p max.
48 Vout models: 200 mVp-p max.
- dual output 12 / -12 Vout models: 150 / 150 mVp-p max.
15 / -15 Vout models: 150 / 150 mVp-p max.
24 / -24 Vout models: 200 / 200 mVp-p max.
Capacitive Load - single output 5.1 Vout models: 20'400 µF max.
12 Vout models: 3'540 µF max.
15 Vout models: 2'200 µF max.
24 Vout models: 890 µF max.
48 Vout models: 220 µF max.
- dual output 12 / -12 Vout models: 1'800 / 1'800 µF max.
15 / -15 Vout models: 1'200 / 1'200 µF max.
24 / -24 Vout models: 470 / 470 µF max.
Minimum Load Not required
Temperature Coefficient ±0.02 %/K max.
Start-up Time 30 ms typ. / 60 ms max.
Short Circuit Protection Continuous, Automatic recovery
Output Current Limitation 180% max. of Iout max.
150% typ. of Iout max.
Overvoltage Protection 120% typ. of Vout nom.
(5.1, 15, ±15 Vout models)
125% typ. of Vout nom. (other models)
(By Zener diode)
Transient Response - Response Deviation 5% max. (75% to 100% Load Step)
- Response Time 250 µs typ. (75% to 100% Load Step)
All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated.
Safety Specifications
Safety Standards - IT / Multimedia Equipment EN 62368-1
IEC 62368-1
UL 62368-1
- Certification Documents www.tracopower.com/overview/tmdc60h
Pollution Degree PD 3
EMC Specifications
EMI Emissions - Conducted Emissions EN 55032 class A (internal filter)
FCC Part 15 class A (internal filter)
- Radiated Emissions EN 55032 class A (internal filter)
FCC Part 15 class A (internal filter)
EMS Immunity EN 55024 (IT Equipment)
EN 55035 (Multimedia)
- Electrostatic Discharge Air: EN 61000-4-2, ±8 kV, perf. criteria A
Contact: EN 61000-4-2, ±6 kV, perf. criteria A
- RF Electromagnetic Field EN 61000-4-3, 10 V/m, perf. criteria A
- EFT (Burst) / Surge EN 61000-4-4, ±2 kV, perf. criteria A
EN 61000-4-5, ±2 kV, perf. criteria A
- Conducted RF Disturbances EN 61000-4-6, 10 Vrms, perf. criteria A
- PF Magnetic Field Continuous: EN 61000-4-8, 100 A/m, perf. criteria A
General Specifications
Relative Humidity 95% max. (non condensing)
Temperature Ranges - Operating Temperature –40°C to +90°C
- Case Temperature +105°C max.
- Storage Temperature –50°C to +125°C
Power Derating - High Temperature 2.9 %/K above 70°C (5.1 Vout model)
3.3 %/K above 75°C (other models)
See application note: www.tracopower.com/overview/tmdc60h
Cooling System Natural convection (20 LFM)
Remote Control - Voltage Controlled Remote On: 3.5 to 12 VDC or open circuit
Off: 0 to 1.2 VDC or short circuit
Refers to 'Remote' and '-Vin' Pin
- Off Idle Input Current 3 mA typ.
- Remote Pin Input Current -0.5 to 0.5 mA
Altitude During Operation 5'000 m max.
Switching Frequency 160 - 220 kHz (PWM) (5.1 Vout model)
187 - 253 kHz (PWM) (other models)
Insulation System Reinforced Insulation
Working Voltage (rated) 1'000 VAC
Isolation Test Voltage - Input to Output, 60 s 3'000 VAC
Isolation Resistance - Input to Output, 500 VDC 1'000 MΩ min.
Isolation Capacitance - Input to Output, 100 kHz, 1 V 3'000 pF max.
Reliability - Calculated MTBF 218'000 h (MIL-HDBK-217F, ground benign)
Housing Material Plastic resin (UL 94 V-0 rated)
Potting Material Silicone (UL 94 V-0 rated)
Housing Type Plastic Case
Mounting Type Chassis Mount
Connection Type Screw Terminal
Weight 300 g
All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated.
Supporting Documents
Overview Link (for additional Documents) www.tracopower.com/overview/tmdc60h
Outline Dimensions
112.0
(4.41) Pinout
(0.35)
8.9
(1.97)
50.0
Dimensions in mm (inch)
Tolerances: x.x ±0.5 (±0.02)