HIGH-SPEED DC CIRCUIT BREAKERS

FOR FIXED INTALLATIONS (IEEE)


Type UR

DC TRACTION SUBSTATIONS
GENERAL INFORMATION
The UR range of DC circuit breakers has achieved Designed according to IEEE C37.14 and IEEE C.37.16,
worldwide acceptance as a well proven design for use the UR range can be used for Light Rail and Heavy
in fixed installations. It has been regularly upgraded Rail Transit Systems on the North American territory.
and adapted to new standard requirements and for Combining a compact design with a high making and
different applications over the years, continuously breaking capacity, the UR range, with its low number
improving the level of performance and functionality. of parts also guarantees high reliability and low
This has led to an impressive service track record maintenance requirements.
throughout the world for the UR product range.

TYPICAL APPLICATION
(DC TRACTION POWER SUBSTATION)

1 2 2 3 4 5

UR UR UR UR

SW
I> I> I> I>
RC

SW SW SW

1 Interconnecting breaker panel


2 Line breaker panel
3 Rectifier breaker panel
4 Rectifier negative panel

5 Rectifier panel
UR DC high-speed circuit breaker

SW Disconnector

MAIN FEATURES
y Thermal current up to 8,000 A
y Rated voltage 800 VDC and 1,600 VDC (1,200 VDC for UR80)
y Indoor installation
y Bidirectional or unidirectional overcurrent release
y Trip-free direct acting device
y Limited maximum arc voltage
y Electro-magnetic closing with electric or magnetic holding
y Reference standards: IEEE C37.14 and IEEE C37.16
y Also available according to EN 50123–1/–2,
IEC 61992–1/–2 standards
(refer to our specific SG101001BEN brochure)
y Insulation material according to EN 45545-2

2 HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR


MAIN BENEFITS
D Safe with a high insulation level.
D Very low maintenance requirements with high electrical and mechanical endurances.
D Simple design with few moving parts resulting in high reliability.
D High rated short circuit making and breaking capacity.
D A large number of different options to match the various application requirements.
D Proven design with worldwide experience and acceptance.

PRODUCT RANGE
U [V=]
1,600

1,200
(1) (1)
UR26-82 UR40-82 UR46-82 UR60-82 UR80-82
800 ANSI
Arc chute 82

f e d a b c d

UR26-81 UR40-81 UR46-81 UR60-81 UR80-81


Arc chute 81 I [A]
2,900 3,200 4,000 6,000 8,000
tc/TNc 1 d
0.9 TNc [ms]
0.8 16
0.7 e
0.6 31.5
0.5 >63
0.4
0.3  Also tested at 1,200 VDC
(1)

0.2

BREAKING CURRENT PARAMETERS


0.1 f
0
0 0.4 0.6 0.8 1 Iss/INss
2INe/INss

BREAKING CURRENT PARAMETERS


I Iss = Prospective sustained short-circuit current
tc
Îss >1.42Iss Typical duty f Îss = Peak of Iss
di/dt = Initial current rate of rise
Iss
Id = Setting of maximum current release
0.63 Iss
Icut off = Cut-off current
di/d

Icut off Typical duty e and d


t

tc = Time-constant of the circuit


Id
ti = Opening time
t
V
Uarc = Maximum arc voltage
Uarc
UNe UNe = Rated operational voltage
ti t

OPENING TIME TI
t i 20
[ms] Relationship between opening time tl and the initial rate of rise of
18
current di/dt for direct instantaneous overcurrent release.
16 UR40/46

14
UR26 Example for a di/dt of 3x106 A/s:
UR60/80
12 - for UR26: ti ~ 4.3 ms,
10
8 - for UR60/80: ti ~ 4.1 ms.
6
4 Note: for a shorter opening time on low di/dt, the “indirect release”
2 (shunt trip) option can be used (refer to “Options” section page 9).
0
3.105 5 7 106 3 5 7 107 3
di/dt [A/s]

HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR 3


t l 20
[ms]
DATA FOR PRODUCT SELECTION
Symbol Unit UR26 UR40 UR46 UR60 UR80
MAIN HIGH VOLTAGE CIRCUIT
Frame size current 2,150 3,200 4,000 6,000 8,000
Rated voltage
- arc chute type 81 UNe [VDC ] 800 800 800 800 800
- arc chute type 82 1,600 1,600 1,600 1,600 1,200
Rated continuous current (1)
- IEEE UNm [VDC ] 2,150 3,200 4,000 6,000 8,000
- EN 50123 / IEC 61992 (for information only) 2,600 4,000 4,600 6,000 8,000
Rated peak & sustained short-circuit current for test a [kA/kA]
- at 800 VDC (2) 200/120 200/120 200/120 200/120 200/120
- at 1,200 V DC (2) - - 132/80 132/80 132/80
- at 1,600 VDC (2) 100/60 100/60 100/60 100/60 -
Short circuit value for tests b/c/d [kA]
- at 800 VDC (2) (time constant 210 ms) 52.6/31.2/17.9
- at 1,200 VDC (2) (time constant 210 ms) - - 49.0/35.3/22.6
- at 1,600 VDC (2) (time constant 66 ms) 44.3/35.0/ 25.0 -
Peak & rated short-time current [kA] - - - 75/53 or 75/53 or
50/35 (5) 50/35 (5)
Overcurrent trip range (bidirectional) (3)
[kA] 1.4-8.0 2-15 2-15 6-18 8-24
Reverse overcurrent trip value (unidirectional) [kA] - - - 6 or 4-10 (5) 6 or 4-10 (5)
Power frequency withstand voltage (IEEE) (60 Hz, 1 min) (4) [kV]
- arc chute type 81 12 12 12 12 12
- arc chute type 82 12 12 12 12 12
(1)
At Tamb = +40°C and tested with high voltage connections according to standard IEEE C37.14 –2015. • (2) According to IEEE C37.14-2015. • (3) For range selection, refer to the table
page 6. • (4) Values applicable for factory tests on serial products. • (5) Short-time withstand current value is function of the selected tripping range, and vice and versa.

LOW VOLTAGE CIRCUIT


Control circuit
Nominal supply voltage (6) Un [VDC ] 110, 125
Range of voltage [0.7 - 1.25] Un [0.8 - 1.1] Un
Closing power (7) [W]/[s] 1,300/1 (E) | 1,300/1 (M) (7) 3,200/1 (E) | 2,600/1 (M)
Holding power (8) [W] 2.3 (E) | 0 (M) 30 (E) | 0 (M)
Opening power (8) [W]/[s] 25/1 (M) 700/1 (M)
Mechanical opening time on opening order (8) (9) to [ms] 15 - 30 (E) | 5 - 75 (M) 15 - 30 (E) | 5 - 75 (M)
Mechanical closing time (8) (9) tc [ms] ~ 150 (E)(M) ~ 150 (E)(M)
(6)
The breaker can also be controlled with a rectified AC control voltage. • (7) (E) E-type: Electric holding | (M) M-type: Magnetic holding.• (8) At Un and Tamb = +20°C. • (9) Starting when
the signal is received by the coil.
Auxiliary contacts
Type of contacts (refer to definition on page 10) Potential free (PF) or change-over (CO)
Number of auxiliary contacts 5a + 5b
Rated voltage [VDC ] 24 to 220
Conventional thermal current Ith [A] 10
Switching categories according to EN 60947 (silver contacts) [A] AC-15 230 VAC 1.0 A
[A] DC-13 110 VDC 0.5 A
Minimum let-through current at 24 VDC (10) [mA] ≥ 10

(10)
For a dry and clean environment.
Low voltage interface
Type of connection (11) Harting type Han® 32 EE
(11)
For mobile connector information refer to page 9.
OPERATING CONDITIONS
Installation Indoor
Altitude [m] ≤ 2,000 (12)
Working ambient temperature (13) Tamb [°C] - 25 to + 40
Humidity Class 5k2
Minimum mechanical durability N Opera- 4x50,000 8x25,000 8x25,000 4x20,000 4x20,000
tions
(12)
For altitude >2,000 m, please contact Sécheron. • (13) For ambient temperature outside of the range, please contact Secheron.

4 HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR


DIRECT OVERCURRENT RELEASE SELECTION
AVAILABLE TRIPPING DEVICES
Available setting ranges (in kA) with their corresponding codification

Designation code (1)


UR26 UR40 UR46 UR60 UR80 type Standard Options
1.4 - 2.7 - - - - DV1 A
2.0 - 5.0 2.0 - 5.0 2.0 - 5.0 - - DV2 B (1)
For selection page 16.
2.0 - 8.0 2.0 - 8.0 2.0 - 8.0 - - DS1 D
(2)
- 4.0 - 15.0 4.0 - 15.0 - - DS2 F Unidirectional overcurrent
- 4.0 - 10.0 4.0 - 10.0 - - DV2 G release. Tripping direction
- - - 6.0 - 10.0 - J A  B. ÎNcw/INcw = 75/53 kA.
- - - 9.0 - 14.0 - K (3)
Unidirectional overcurrent
13.0 - 18.0 - L release. Tripping direction
- - - - 8.0 - 14.0 N B A ÎNcw/INcw = 75/53 kA.
- 12.0 - 18.0 O (4)
Unidirectional overcurrent
- - - - 16.0 - 24.0 P release. Tripping direction
6.0 (2) 6.0 (2) U A  B. ÎNcw/INcw= 50/35 kA.
- - - 6.0 (3) 6.0 (3) W (5)
Unidirectional overcurrent
4.0 - 8.0 (4) 4.0 - 8.0 (4) 1
release. Tripping direction
4.0 - 8.0 (5) 4.0 - 8.0 (5) 2 B A. ÎNcw/INcw= 50/35 kA.
4.0 - 10.0 (4) 4.0 - 10.0 (4) 3
4.0 - 10.0 (5) 4.0 - 10.0 (5) 4

AVAILABLE TRIPPING DEVICES


UR26/40/46 UR60/80
Standard tripping device Standard tripping device

Tripping device

B
DS tripping device DV tripping device

Setting of maximum current release

Specific configurations for rectifier circuit breakers

For unidirectional circuit-breakers,


different configurations can be selected
based on the breaker’s HV busbar (A or B)
connected to the rectifier’s output.
Tripping device
Unidirectional breaker
HV connection configuration
standard Optional
Code W Code U (1)
Setting of maximum current release No trip direction with
ÎNcw/INcw = 75/53 kA (250 ms) AB BA

Trip direction with trip setting 6 kA BA AB


I>
(1)
same prinicple for codes 1, 2, 3 & 4 with information
given in the table ‘’Available tripping devices’’ .

HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR 5


UR26-81/82

238

R4

INFORMATION FOR PRODUCT INTEGRATION


90
UR26-81/82 UR40/46-81/82 UR26/40/46-81/82
617
238
168
419
69

MAIN DIMENSIONS FOR UR26/40/46

51
R4
90
UR26-81/82 UR40/46-81/82 UR26/40/46-81/82

5
Dimensions without tolerances are
617 (1) indicative. All dimensions are in mm. The
238

784

23
168 maximum allowed flatness deviation of the
419 (2) 4x
69 support frame is 0.5 mm.

D 95 100

51
160 40
R4 56 240
HV connections for

386
90
UR26/40/46

5
23

E
40 25 50 25
4x Ø11

784

25

30
160 40 160 C
194 320 B

D 95 100
56 240 379

50

20 50
A

386

25
40 25 50 25 4x Ø14 4x Ø18
HV
23

E
4x Ø11 LV
25

30
50

20 50

160 40 160 C (1)


Arc chute 82
56 240 379 194 320 B (2)
Arc chute 81
25

A
4x Ø14 4x Ø18 UR60
40 25 350
MAIN DIMENSIONS FOR UR60/80
50 25
238
25

30
50

20 50

UR60 UR80 UR60/80


25

350 617 (1)


4x Ø14 238 4x Ø18 238
419 (2)
Dimension A [mm]
69
51

Standard closing device (3)


177
Electric holding 718
UR60 UR80 UR60/80 Magnetic holding 756
350 617
238 238 Specific closing device (4)
783

419
177 50
30

69 Electric holding 748


51
50.5

23
Magnetic holding 748
120
60

4x
25
HV HV 39
120

(1)
Arc chute 82
HV
23

(2) 160 40
Arc chute 81
783

4x Ø11 LV 8x Ø18 56 240


177 50 (3)
A ll breaker configurations excepted
30

39 39 320 182 optional configuration of unidirectional


75.5
50.5

160 40
120
60

A breaker.
160 40 240
56 25 (4) 
Optional configuration of unidirectional
240 411
breaker
120
23

25
4x Ø11 8x Ø18 UR26-64S
Dimensions
[mm] UR26 UR40 UR46 420
25

39 39 320 182 320


75.5

160 40
25 645 240 760 A 760
UR26-64S
160 40 UR40-64S UR26/40-64S
50

56 420240 131 411 246 700 246


25

25

320
131 176 176
4x Ø14
50

20 30 40
25

176 176 177


4x Ø14 50 25
25
UR26-64S UR40-64S UR26/40-64S
30

420 700
25

WEIGHTS
50 25 320
20 50
25 50
20 50 30

1025

140,5
4x Ø14 Weights (1) [kg] ± 5% (1) 4x Ø18 circuit 90breaker
eights for standard
W 90
without any option.
UR26 UR40 UR46 UR60 UR80
D 95 100

4x Ø18 90 90
50 25
With arc chute 81 77 98 110 139 150
371

23
30

With arc chute 82 87 108 120 149 160 4x


1025

140,5
23
20 50

23

6 4x Ø11
HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR 160 40
56
100

4x Ø18 90 160 40 90 160 C 240


INSULATION DISTANCES FOR UR26/40/46/60/80
UR..81/82S
Grid with 50% opening
The DC circuit-breakers have
(correspond to IP20)
been homologated according
to IEEE C37 in cubicle’s
configurations with insulation
538 975 panels on the area where
dimensions are indicated in
the below’s representation and
1675

for short-circuit conditions as


defined page 4.

Correspond to cubicle For particular cubicle


width 600 mm configuration and short-circuit
conditions, please contact
Sécheron.

ARC CHUTE INSTALLATION


Opening to Opening to LV connector Vertical removal
LV connector side opposite side UR60/80 (arc chute 81)
UR26/40/46 (arc chutes 81/82) UR26/40/46 (arc chutes 81/82)
UR60/80 (arc chute 82)

S
V=
+
E1 F1
Rp
Rs
LOW VOLTAGE CONTROL DIAGRAM UR26/36/40/46
UR26/36/40/46
UR26/36/40/46
S
S
V=
V= S
V=
+
FF1 2 E2
+ E11 F1
+ E
E1 Rp F1
–Rp
ELECTRIC HOLDING MAGNETIC HOLDING
Rp
Rs
Rs
Rs

E-TYPE M-TYPE The UR range is equipped with a


y The circuit breaker remains y The circuit breaker remains solenoid
––
F
F
F coil toEEE perform the usual
2
2
2
2
2
2

closing andUR26/40/46
opening operations.

closed with a reduced ‘’holding’’ closed without any control
current. To open the circuit current. To open the circuit Two
UR60/80different types of closing
UR60/80
UR60/80 S
A
A
A C breaker E the holding current
S
S is breaker
A
A
A itB
Bis necessary to
D reverse devices
V=
V= are
S
S
S available: with electric
V=
IIIee B
B C D
D E V=
V= S IIIee C
C D V= +
B C D E V= B C D
holding
+
+ E
E(E-type) or with magnetic
1 F1
cut-off. the polarity of the current flowing
e + e + E Rp
1
100% + 100% E 1
100% + F 100% 1
100% F F
100%
through the closing coil. holding (M-type). F F
F
Rs
1
1
1

y With E-type closing device, R1


the Rs
Rs
G
G R1
circuit breaker cannot remain y With the M-type closing device,
G R1 F Rs
F222
F
t [s] tt [s]
[s]
~ 5%
~ 5%
~ 5%
0 0,5 1
closed iftt [s]
the low––voltage supply
[s] the circuit
~ 20%
20%
0
0
0
breaker remains closed t [s]
––
E
E222
E F2 E2
0 0,5 1 – ~ –
1 is lost. when 00the0,5
0,5low
1 voltage supply is
0 0,5 ~ 20% 0 0,5 1
1 t
t c
tcc ttc+0.5
t +1
tc+1
c –
lost. It requires the control
+0.5 tc+1
tcc+0.5
voltage Legend
to be present to open. Customer scope
UR26/40/46/60/80 UR60/80
A A Sécheron scope S
E S B C D V=
B C Only for
+ UR26 to UR46
Ie D V=
e I S pour UR60/80
Maintien magnétique
Maintien magnétique
V= pour
+ Maintien magnétique pour UR60/80
UR60/80 A
A E1
(maintien
100%
(maintien +
électrique
électrique idem que
que UR26-36-40-46) A
00% F E1 idem
(maintien électrique idem que UR26-36-40-46)
F1
UR26-36-40-46) F1
Rp
E, BBBF
: control contacts
Rs F,GC
C : control contacts Rs
G R1
R1C : holding resitor
F2
t [s]RsD
D : serial resistor
~ 5% t [s] D

RUR 0 F2 E2 RpE : parallel

resistor E2
0 0,5 1 ~ 20%– E
S E : automatic circuit breaker
0 0,5 1 tc tc+1
tc+0.5

HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR 7


UR26/40/46
Schéma SG100318P1
Schéma SG100318P1 Type :: 5O-4S
Type 5O-4S -- Indirect
Indirect

Standard: HSHR430397P0001
Standard: HSHR430397P0001
19
19
20
20
II
1917
19 17 15
1513
13 11
11 99 77 55 33 11 17 15
17 1513
13 11
11 99 77 55 33 11
21
21 21
21

22
22 22
22
2018
20 18 16
1614
14 12
1210
10 88 66 44 22 18 16
18 1614
14 12
1210
10 88 66 44 22

II>> II>>
TYPICAL VALUE FOR CLOSING COILS - UR26/40/46

Schéma SG100312P1
Schéma SG100312P1 Type :: 4O-4S
Type 4O-4S -- Config
Config C
C Schéma Coil characteristics
Schéma SG100312P1
SG100312P1 Type :: 4O-4S
Type 4O-4S -- Config
Config D
D
Closing pulse opening pulse M-type
holding E-type
(WI)
(WI)
1917
19 17 1513
13 11
11 99
0.53 to
7 5 1
1s (I(>)
19
I>)
1917
17 1513
15 13 11
11 99 77 55 33 11
0,5 to 1s
15 7 5 3 1
21
21 21
21

Un Inom Imin E Imin M Imax R1 Inom Imin Imax Rs Rp Inom Imin Imax

18
18
22
22 [VDC] [A]
1614
16 14 12
1210
10
[A]
88 66 44 22
[A] [A] 1818 [Ω]
22
22 [A] 1614
16 14 12
1210
[A]
10 88 66
[A]
44 22
[Ω] [Ω] [A] [A] [A]

110II>> 11.7 6.3 7.0 19.9 210 II>> 0.5 0.4 0.6 40 20 1.6 1.0 2.3

125 10.5 5.6 6.3 17.8 272 0.4 0.3 0.6 52 26 1.4 0.9 2.0

Schéma SG10317P1
SG10317P1
Typecan
:: 4O-3S
4O-3S - Indirect
Indirect ++ config
config Schéma SG10317P1
SG10317P1 Type :: 4O-3S
4O-3S -- Indirect
Indirect ++ config
config D
D
Schéma Type
The breaker
19
19
also -be controlled withCCa rectified
Schéma AC control voltage. Type 19
19
(WI)
(WI) 20
20
II (I(>)
I>) 20
20
II
1817
18 17 13 11
13 11 99 77 55 33 11 1817
18 17 13 11
13 11 99 77 55 33 11
21
21 21
21

TYPICAL VALUE FOR CLOSING COILS - UR60/80


22
22 14 12
1210
10 16 22
22
16
16 14 88 66 44 22 16 14 12
14 1210
10 88 66 44 22

II>> Coil characteristics


II>>
E-type M-type
Closing pulse Closing pulse
holding opening pulse
0.5 to 1s 0.5 to 1s
Un Inom Imin E Imax R1nom Inom (1) Imin (1) Imax (1) Inom Imin M Imax Rsnom Inom Imin Imax
[VDC] [A] [A] [A] [Ω] [A] [A] [A] [A] [A] [A] [Ω] [A] [A] [A]
110 25.0 16.6 33.2 56 1.8 1.5 2.0 21.3 13.5 28.3 15 5.4 4.1 6.3
125 22.5 14.9 29.9 75 1.6 1.3 1.7 18.4 11.7 24.5 18 5.0 3.8 5.8

(1)
With selected economy resistor The breaker can also be controlled with
a rectified AC control voltage.

HARTING
LOW VOLTAGE CONTROL DIAGRAM
FOR HARTING TYPE HAN®32 EE CONNECTOR (STANDARD)

The following wiring schemes represent the low voltage connector


Only the pins related to your selected
configuration page 12 will be wired
according to the below’s pin assignment.
pins assignement in function of the selected connectors and the

HARTING
The connector will be delivered with all 32
configuration chosen for standard or optional functions. pins even if not all wired.
Brochure

HARTING
HARTIN
Standard: xxxxx
Standard: xxxxx Standard: xxxx
Standard: xxxx Legend

HARTING HARTIN HA
ANSI

a b a b (WI) I> I (I>) (WI) Circuit breaker

HARTIN
main contact

HART
23
23 23
23
II II

HARTING HA
24
24 24
24

Brochure Brochure
b b a b a b (WI) I> Direct
I (overcurrent
I>) (WI) release

HARTIN
1917
19 17 15
1513
13 11
11 99 77 55 33 11 1514
15 14 12
1211
11 99 88 66 55 33 22
21
21 21
a 21 a

HARTIN
Low voltage connector

HAR
a b a b (WI) I> I (I>) (WI)

Brochure Brochure
HARTING
b b
interface (male pin)

HARTIN H
a a
22 22 1a+1b I>
(WI) - Switch PF I (I>)

Brochure Brochure
22 22 a b a b (WI)
2018
20 18 16
1614
14 12
1210
10 88 66 44 22 b 13
13 10 b
10 77 44 11

HARTHA
II>> II>>

H
a a
a b a b b (WI)b I> - Switch
1a+1b I CO(I>) (WI)

Brochure Brochure
HARTINGHAR H
a a
I> I Indirect overcurrent release

Brochure Brochure
a b a b (WI) b(I>) (WI)

HARTING
b

H
Harting type HAN 32 EE ® a a

HAR
Type : PF Type : CO Circuit
b abreaker
(WI) closing
I> coil I

Brochure Brochure
b b a b (I>) (WI)
(Standard)

Brochure Brochure HAR H


Wear
I> b indicator
(I>) switch
Brochure

a a
a b a b (WI) I (WI)
AUXILIARY CONTACTS AUXILIARY CONTACTS
Brochure Brochure
(option) b

HAR
(SWITCH PF) (SWITCH CO) Overcurrent release

HA
a a
Standard: xxxxx
Standard: xxxxx Standard: xxxx
Standard: xxxx a b a b (WI) I> b
I b(I>) (WI)
detector switch (option)

HART
a a
23
23 23
23
II II

Brochure Brochure
(I(>)
I>) (WI)
(WI) (I(>)
I>) (WI)
(WI) b b
EN

24
24 24
24
Note:
3129
31 29 2725
27 25 1917
19 17 15
1513
13 11
11 99 77 55 33 11 3129
31 29 2725
27 25 1514
15 14 12
12a11
11 99 88 66a 55 33 22
21
21 21
21 - Low voltage connectors are delivered
with all pins mounted, even if not all
wired.
22
22 22
22
3230
32 30 2826
28 26 2018
20 18 16
1614
14 12
1210
10 88 66 44 22 3230
32 30 2826
28 26 13
13 10
10 77 44 11
- Indirect release coils BIM6 & BIM8 are
II>> II>> connected to a low voltage connector
while BIM5 & BIM7 are connected to a
terminal block (refer to page 10).

8 HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR


Légende
OPTIONS
(SUBJECT TO ADDITIONAL COSTS)

MOBILE CONNECTOR - UR26/40/46/60/80


Mobile connector (without cable)
Auxiliary switches Fixed Number of pin
Control
connector (delivered with connector) Cable Sécheron’s
voltage Connector
type Size Size gland number
Device Number Type
2.5 mm² 1.5 mm²
UR26/40/46
(with or without Harting
ECO-Drive) 5a+5b PF 110, 125 VDC 2 30 M32 SG104063R10100
with options HAN® 32 EE
( or ) and

UR60/80 Harting
(without 5a + 5b PF 110, 125 VDC 2 30 M32 SG104063R10100
ECO-Drive) HAN® 32 EE

Note: crimping tools are not in the scope


The breaker can also be controlled with a of Sécheron
rectified AC control voltage.

ECO-DRIVE INTEGRATED CONTROL MODULE


UR26/40/46
ECO-Drive ECO-Drive is a compact control
module integrated with UR circuit
breakers, to manage closing-
holding sequences with electric
control. ECO-Drive is set on the
UR breaker’s closing device.

MAIN BENEFITS
D No need of additional hardware to control the breaker.
D Compact integration.
D Reduction of overall installation costs.
D Reduction of operational costs with lower power consumption.
D Reduction of the risks to damage the closing coil.
D Full compliance with EN 50121-3-2 standards for EMC
D Full compliance with EN 50155 § 5.1.1.2 class S2
(short interruption of voltage supply).
D Full compliance with EN 50155 § 5.1.3 class C1 (supply change over).

- Available for UR26/40/46


- Available for closing device
with E-type holding

HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR 9


 OW VOLTAGE WIRING DIAGRAM
L
HARTING CONNECTOR

19 17 15 13 11 9 7 5 3 1
28
k0
+
26 Vbat P Harting connector
Un
25 Vbat N 4
- C Customer’s scope
27
k1
22 ORDP
D Sécheron’s scope
+ 3
UEF
- 21 ORDN
20 18 16 14 12 10 8 6 4 2
Note: Certain option combination might
not be compatible. Please check with
Sécheron.

TECHNICAL DATA

Control circuit (1)


 ontrol voltage UEF and supply voltage Un
C
can be different
Nominal supply voltage (1)
UN [VDC ] 110 (2)
At Un and Tamb = +20°C
Nominal control voltage (1) UEF [VDC ] 110 (3)
Starting when the signal is received by the
Range of voltage [ 0.7 - 1.25 ] Un coil

Idle (standby) power [W] < 1.6


Nominal closing power (2) Pc [W]/[s] 1,300/0.5
Nominal holding power (2) [W] <8
Nominal opening power (2) [W] < 1.6
Mechanical opening time on opening order (3) [ms] 15-30
Mechanical closing time on closing order (2)(3) Tc [ms] ~150

BIM INDIRECT RELEASE (SHUNT TRIP)


WITH INTEGRATED MANUAL RELEASE
The indirect release enables to shorten the
opening time when required by specific
application. The choice of the relevant
Opening time Control mode type has to be validated by Sécheron prior
quoting. This device can also be manually
BIM5 4 - 6 ms CID-3(1) activated.
UR26/40/46
BIM6 12 - 19 ms Direct battery 77-140 VDC
BIM7 4 - 6 ms CID-3(1) (1)
 ot included in the DC circuit breaker - To
N
UR60/80 be ordered separately
BIM8 12 - 19 ms Direct battery 77-140 VDC

BIM5 & BIM6 - UR26/40/46 BIM7 & BIM8 - UR60/80

The terminal block allows the connection between The terminal block allows the connection between
2.5 mm² cables from the BIM5 and 2.5 mm² cables 2.5 mm² cables from the BIM7 and 2.5 mm² cables
from the battery and 6 mm² cables from the CID-3. from the battery and 6 mm² cables from the CID-3.
BIM6 is directly connected to the low voltage BIM8 is directly connected to the low voltage
connector. connector.

Terminal block Terminal block


for BIM5 for BIM7
(rear view) (rear view)

Cables from CID-3 or from Cables from CID-3 or from


battery (customer’s scope) battery (customer’s scope)
10 HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR
MANUAL RELEASE
Manual releases are safety devices designed to withdrawing from the panel the trolley on which the
guarantee that the breaker is in OPEN position so as breaker is installed. The horizontal release must be
to access the breaker’s panel -e.g. for maintenance. manually actuated from the front side of the panel
The vertical release is automatically actuated while door before opening it.

UR26/40/46 UR60/80

vertical release horizontal release vertical release horizontal release

actuation actuation actuation actuation

MANUAL CLOSING DEVICE


UR26/40/46 UR60/80 The manual closing device,
mainly used for maintenance
operations, enables to close and
open the circuit breaker without
low voltage supply and under no
load.

CONTACT WEAR INDICATOR (WI) OR


OVERCURRENT RELEASE DETECTOR (I>)
UR26/40/46
Installed on the rear side of the circuit breaker closing device, these
options monitor the position of a rod linked to the breaker’s moving
contact, which rod actuates a micro-switch.
Based on the selected configuration the detector informs about:
- ‌the reaching of the wear limit of the main contacts of the circuit
breaker: function ‘’contact wear indicator’’.
- ‌the tripping of the circuit breaker through the overcurrent release:
function ‘’overcurrent release detector’’. These two functions cannot be Contact wear
selected together. indicator

POSITION INDICATOR - UR26/40/46/60/80


A mechanical position indicator actuated
though a rod linked to the circuit-breaker
N SED moving contact gives the position of the
OPE CLO
breaker.

HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, (IEEE) STANDARD, TYPE UR 11


DESIGNATION CODE FOR ORDERING
y Be sure to establish the designation code from our latest version y For technical reasons some variants and options indicated in the
of the brochure by downloading it from our website “www. designation code might not be combined.
secheron.com”. y The bold part of this designation code defines the device type,
y Be careful to write down the complete alphanumerical designation and the complete designation defines the identification number
code with 22 characters when placing your order. of the product, as displayed on the identification plate attached
y The customer shall write down the setting of maximum current to the product.
release value (Id) in its order form.
Example of customer’s choice: UR 40 81 S 1 E E Ø F Ø A C Ø Ø Ø Ø Ø S B
Line: 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

DESIGNATION CODE
Designation Customer’s
Line Description
standard options choice

Signature:
10 Product type UR UR UR
11 Conventional free air thermal current 2,150 A 26
3,200 A 40
4,000 A 46
6,000 A 60
8,000 A 80
12 Rated operational voltage
UR26/40/46/60/80 800 V 81
UR26/40/46/60/80 1,600 V (1,200 V for UR80) 82
13 Application Fixed Installation S S
14 Arc chute installation (Refer to page 7 for selection)
UR26/40/46 (Arc chute type 81/82) Opening on LV connector side 1
UR60/80 (Arc chute type 82)
UR26/40/46- Arc chute type 81/82 Opening on LV connector opposite side 7
UR60/80 - Arc chute 81 Vertical removal 8
15 Control type Electric holding - without ECO-Drive E
Magnetic holding - without ECO-Drive M
Electric holding - with ECO-Drive (1) 4
16 Nominal supply voltage
UR26/40/46/60/80 110 V DC E
UR26/40/46/60/80 125 V DC R
17 Varistor in coil (2) No Ø

Name:
Yes (battery voltage) 1
18 Direct overcurrent release (bidirectional)
UR26 1.4 - 2.7 kA A
UR26/40/46 2.0 - 8.0 kA D
UR40/46 4.0- 15.0 kA F
UR60 13.0 - 18.0 kA L
UR80 16.0 - 24.0 kA P
For other selection, refer to codification table page 5 ..................... ....
Direct overcurrent release (unidirectional) - UR60/80 W
19 Indirect release (shunt trip)
UR26/40/46 (includes horizontal manual release) BIM5 5
UR26/40/46 (includes horizontal manual release) BIM6 7
UR60/80 (includes horizontal manual release) BIM7 4
UR60/80 (includes horizontal manual release) BIM8 6
20 Auxiliary contacts
UR26/40/46/60/80 5a + 5b - (switch PF) A
UR26/40/46 5a + 5b - (switch CO) B
21 LV connector type on circuit breaker No Ø
UR26/40/46/60/80 Harting type HAN® 32 EE C
22 Manual release No Ø
UR26/40/46/60/80 Horizontal 1
UR26/40/46/60/80 Vertical 2
23 Manual closing device (not compatible with line 25 nor 26) No Ø Place and date:
UR26/40/46/60/80 Yes 2
24 Position indicator No Ø
Yes 3
25 Overcurrent release detector (not compatible with line 23 nor 26) No Ø
UR26/40/46 Yes 1
26 Contact wear indicator (not compatible with line 23 nor 25) No Ø
UR26/40/46 Yes 1
27 HV main connections (according to pages 6) Standard S
HV main connection - UR46 (according to pages 6) B
28 Digit for Sécheron internal purpose
UR26/40/46 Arc chute 81 & 82 Q
UR60/80 Arc chute 81 & 82 P

ECO-Drive is only available for UR26/40/46 with Harting HAN® 32 connector and 110VDC control voltage. (2) In case control type “Electric holding with ECO-Drive is selected (line 15),
(1)

select “No” for Varistor on Coil (line 17)


The low voltage connector must be ordered separately:
Harting type HAN® 32 EE: SG104063R10100 Value of the setting of maximum current release value (Id): . . . . . . . . . . . . . . [A]

Sécheron SA www.secheron.com
Rue du Pré-Bouvier 25 Tel: +41 22 739 41 11
SG104309BEN_B09-04.22

1242 Satigny - Geneva Fax: +41 22 739 48 11


CH-Switzerland [email protected]

Copyright© • 2022 • Sécheron SA