MP-V
SmartX IP Controller
MP-V
SmartX IP Controller
Universal inputs For all analog inputs, maximum and minimum levels
The universal inputs are ideal for any mix of can be defined to automatically detect over-range and
temperature, pressure, flow, status points, and similar under-range values.
point types in a building control system.
Triac outputs
As counter inputs, they are commonly used in energy The triac outputs can be used in many applications to
metering applications. As RTD inputs, they are ideal for switch 24 VAC on or off for external loads such as
temperature points in a building control system. As actuators, relays, or indicators. The triac outputs are
supervised inputs, they are used for security isolated from the controller. Triacs are silent and do not
applications where it is critical to know whether or not a suffer from relay contact wear.
wire has been cut or shorted. These events provide a
separate indication of alarms and trouble conditions to
the system.
MP-V
SmartX IP Controller
The MP Series controllers support local trends, • SmartX LCD temperature sensors: Up to four
schedules, and alarms, enabling local operation when sensors are supported
the controller is offline or used in standalone
applications. The maximum total length of the sensor bus is 61 m
(200 ft). For more information, see the SmartX Living
The battery-free power backup of the memory and real- Space Sensors Specification Sheet.
time clock prevents data loss and ensures seamless
and quick recovery after a power failure. Mobile commissioning application
WorkStation allows you to update the firmware of The eCommission SmartX Controllers mobile
multiple MP Series controllers at the same time and with application is designed for local configuration, field
minimum down time. The EcoStruxure BMS server deployment, and commissioning of MP Series
keeps track of the installed firmware to support backup, controllers, and air flow balancing of VAV units. The
restore, and replacement of the controllers and mobile application reduces the commissioning time,
sensors. The server can host controllers of different allows flexibility in project execution, and eliminates
firmware versions. dependencies on network infrastructure.
Sensor bus for living space sensors The mobile application is designed for use with
Android, Apple (iOS), and Microsoft Windows 10
The MP Series controllers provide an interface devices. For more information, see the eCommission
designed for the SmartX Sensor family of living space SmartX Controllers Specification Sheet.
sensors. The SmartX Sensors offer an efficient way to
sense the temperature, humidity, CO2, and occupancy
MP-V
SmartX IP Controller
• WorkStation/WebStation interface
• Script and Function Block programming options
• Device discovery
eCommission SmartX Controllers mobile app
• Engineering efficiency
Using the eCommission SmartX Controllers mobile
application, you can connect to one or many MP Series WorkStation/WebStation interface
controllers. You can connect to a single MP Series WorkStation and WebStation provide a consistent user
controller using the eCommission Bluetooth Adapter experience regardless of which EcoStruxure BMS
connected to a SmartX Sensor. You can connect to a server the user is logged on to. The user can log on to
network of MP Series controllers on the local IP the parent EcoStruxure BMS server to engineer,
network, using a wireless access point or a network commission, supervise, and monitor the MP Series
switch. controller and its I/O as well as its attached SmartX
Sensors. For more information, see the WorkStation and
Device configuration WebStation specification sheets.
With the eCommission SmartX Controllers mobile
application, you can easily discover MP Series Script and Function Block programming options
controllers on the IP network and change each Unique to the industry, the MP Series controllers have
controller's configuration, including the BACnet and IP both Script and Function Block programming options.
network settings, location, and parent server. To save This flexibility assures that the best programming
engineering time, you can save common device method can be selected for the application. Existing
settings and then reuse them for controllers of the same programs can easily be reused between the
model. EcoStruxure BMS server and the controller.
MP-V
SmartX IP Controller
controllers intended for similar applications. You can using the wizards and mass edit functions provided in
then edit the controller application, and the changes the tool and then loaded into your target server. The
are automatically replicated to all controllers, while tool also enables the quick creation of your own
each controller keeps its local values. templates based on MP Series controller applications
that you have developed. This facilitates a standard
WorkStation supports both online and offline approach and drives the ability to easily reuse and
engineering of MP Series controllers. You can make the duplicate common controller applications. For more
configuration changes online or use database mode to information, see the Automated Engineering Tool
make the changes offline. In database mode, the specification sheet.
changes are saved to the EcoStruxure Building
Operation database so that you can apply the changes
to the controllers later.
Part Numbers
Specifications
AC input
Nominal voltage .....................................................................................................................................................24 VAC
Operating voltage range .......................................................................................................................................+/-20 %
Frequency ...........................................................................................................................................................50/60 Hz
Maximum power consumption (MP-V-7A) ................................................................................................................21 VA
Maximum power consumption (MP-V-9A) ................................................................................................................22 VA
Power input protection ...............................................................................................MOV suppression and internal fuse
MP-V
SmartX IP Controller
Environment
Ambient temperature, operating ..................................................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating ..............................................................................................................................................UL94 V-0
Ingress protection rating ............................................................................................................................................IP 20
Mechanical
Dimensions ......................................................................................161 W x 198 H x 63 D mm (6.3 W x 7.8 H x 2.5 D in.)
MP-V
SmartX IP Controller
Communication ports
Ethernet ............................................................................................................................... Dual 10/100BASE-TX (RJ45)
USB ................................................................... USB 2.0, 5 VDC, 2.5 W, 1 device port (mini-B) and 1 host port (type-A)
Sensor Bus ...........................................................................................................................24 VDC, 2 W, RS-485 (RJ45)
Sensor Bus protection ..........................................Transient voltage suppressors on communication and power signals
Communications
BACnet .........................................................................................................BACnet/IP, port configurable, default 47808
...................................................................................................BTL B-AAC (BACnet Advanced Application Controller)a
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet International's home
page.
CPU
Frequency .......................................................................................................................................................... 500 MHz
Type ..........................................................................................................................................ARM Cortex-A7 dual-core
DDR3 SDRAM .......................................................................................................................................................128 MB
NOR flash memory ..................................................................................................................................................32 MB
Memory backup ......................................................................................................................128 kB, FRAM, non-volatile
Damper actuator
Torque rating .............................................................................................................................................6 Nm (53 lbf.in)
Stroke .........................................................................................................................................0° to 90°, fully adjustable
Timing .............Approximately 2 seconds/degree at 60 Hz and 2.4 seconds/degree at 50 Hz for 90° rotation at 24 VAC
Position indication ....................................................................................................................................Visual indication
Damper position feedback ..........................................................................................................................................Yes
Manual override ..................................................................................................................... Push-button clutch release
Damper shaft diameter ...................................................................................12.7 mm (0.5 inch) or 9.5 mm (0.375 inch)
..........................................................................Adapter kit AM-135 is required for 9.5 mm (0.375 inch) diameter shafts.
Damper shaft minimum length (from VAV box) ................................................................................22.2 mm (0.875 inch)
Air flow sensor
Range ........................................................................................................................................0 to 249 Pa (0 to 1 inH2O)
Resolution ................................................................................................................0.33 Pa (0.001 inH2O) at 25°C (77°F)
Accuracy ...............................................................................................±5% of 249 Pa (1.00 inH2O) span at 25°C (77°F)
Universal inputs, UI
Channels, MP-V-7A .......................................................................................................................................... 3, UI1–UI3
Channels, MP-V-9A .......................................................................................................................................... 4, UI1–UI4
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
A/D converter resolution ..........................................................................................................................................16 bits
Universal input protection .............................................................................Transient voltage suppressor on each input
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms
MP-V
SmartX IP Controller
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Supervised inputs
5 V circuit, 1 or 2 resistors
Monitored switch combinations.............................................................Series only, parallel only, and series and parallel
Resistor range ................................................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor must have the same value +/- 5 %
Voltage inputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy...............................................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution................................................................................................................................................................1.0 mV
Impedance..........................................................................................................................................................100 kohm
Current inputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy..........................................................................................................................+/-(0.01 mA + 0.4 % of reading)
Resolution....................................................................................................................................................................1 μA
Impedance .............................................................................................................................................................47 ohm
Resistive inputs
10 ohm to 10 kohm accuracy .......................................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy .....................................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Temperature inputs (thermistors)
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Supported thermistors
Honeywell .............................................................................................................................................................20 kohm
Type I (Continuum) ...............................................................................................................................................10 kohm
Type II (I/NET) .......................................................................................................................................................10 kohm
Type III (Satchwell) ...............................................................................................................................................10 kohm
Type IV (FD) ......................................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt) ....................................................................................................................Linearized 10 kohm
Satchwell D?T......................................................................................................................................Linearized 10 kohm
Johnson Controls .................................................................................................................................................2.2 kohm
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
MP-V
SmartX IP Controller
MP-V
SmartX IP Controller
MP-V-7A
MP-V
SmartX IP Controller
MP-V-9A
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable)
MP-V
SmartX IP Controller
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable), LSZH (Low Smoke Zero Halogen)
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), PVC (Polyvinyl
chloride)
MP-V
SmartX IP Controller
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept This equipment complies with the rules, of the Official Journal of the European Union, for
any interference received, including interference that may cause undesired operation. governing the Self Declaration of the CE Marking for the European Union as specified in the
above directive(s) per the provisions of the following standards: EN 60730-1, EN 60730-2-
Industry Canada 11, and EN 50491-3 Safety Standards.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
WEEE - Directive of the European Union (EU)
Regulatory Compliance Mark (RCM) - Australian Communications and Media This equipment and its packaging carry the waste of electrical and electronic equipment
Authority (ACMA) (WEEE) label, in compliance with European Union (EU) Directive 2012/19/EU, governing the
This equipment complies with the requirements of the relevant ACMA standards made under disposal and recycling of electrical and electronic equipment in the European community.
the Radiocommunications Act 1992 and the Telecommunications Act 1997. These
standards are referenced in notices made under section 182 of the Radiocommunications
Act and 407 of the Telecommunications Act. UL 916 Listed products for the United States and Canada, Enclosed Energy
Management Equipment. UL file E80146.