SmartX IP Controller MP V Specification Sheet 03 20036 02 en 05.2018

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

EcoStruxure™ Building www.schneider-electric.

com/buildings | 1

MP-V
SmartX IP Controller

Introduction IP connectivity and flexible network topologies


SmartX IP Controller – MP-V is a multi-purpose, fully The MP Series controllers are based on open protocols
programmable, IP based field controller dedicated for that simplify interoperability, IP configuration, and
VAV cooling and heating applications. MP-V integrates device management:
a controller, a damper actuator, and an air flow sensor
in a single compact package for ease of installation. • IP addressing
MP-V can either be used as a standalone BACnet/IP
• BACnet/IP communications
field controller or as part of an EcoStruxure BMS with a
SmartX AS-P or AS-B server or an Enterprise Server as • DHCP for easy network configuration
the parent server. MP-V comes in two models with
different I/O count. The MP Series controllers have a dual-port Ethernet
switch, which enables flexible network topologies:
The MP-V has the following features:
• Star
• IP enabled with dual port Ethernet switch
• Daisy chain
• Integrated damper actuator with feedback signal
• Rapid Spanning Tree Protocol (RSTP) ring
• Factory-calibrated air flow sensor
• High reliability In a star topology, the controller and the parent
EcoStruxure BMS server are individually connected to
• Sensor bus for living space sensors an Ethernet switch. You can reduce the installation time
and cost by daisy-chaining multiple controllers
• Mobile commissioning application
together. You can use an RSTP ring topology when you
• Full EcoStruxure Building Operation software want failures of a single controller to be detected and
support, providing efficient engineering tools recovered quickly and efficiently.

Models with a versatile mix of I/O points


MP-V comes in two models with different I/O point
count and a versatile mix of I/O point types that match a
wide variety of VAV applications.

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 2

MP-V
SmartX IP Controller

I/O Point Types by MP-V Models

I/O Point Types MP-V-7A MP-V-9A


Universal inputs 3 4
Triac outputs 3 3
Analog outputs 1 2

Configurations by I/O Point Types

Configurations Universal Inputs Triac Outputs Analog Outputs


Digital inputs yes - -
Counter inputs yes - -
Supervised inputs yes - -
Voltage inputs yes - -
(0 to 10 VDC)
Current inputs yes - -
(0 to 20 mA)
Temperature inputs yes - -
Resistive inputs yes - -
2-wire RTD temperature inputs yes - -
Digital outputs - yes -
Digital pulsed outputs - yes -
PWM outputs - yes -
Tristate outputs - yes -
Tristate pulsed outputs - yes -
Voltage outputs - - yes
(0 to 10 VDC)
Current outputs - - yes
(0 to 20 mA)

Universal inputs For all analog inputs, maximum and minimum levels
The universal inputs are ideal for any mix of can be defined to automatically detect over-range and
temperature, pressure, flow, status points, and similar under-range values.
point types in a building control system.
Triac outputs
As counter inputs, they are commonly used in energy The triac outputs can be used in many applications to
metering applications. As RTD inputs, they are ideal for switch 24 VAC on or off for external loads such as
temperature points in a building control system. As actuators, relays, or indicators. The triac outputs are
supervised inputs, they are used for security isolated from the controller. Triacs are silent and do not
applications where it is critical to know whether or not a suffer from relay contact wear.
wire has been cut or shorted. These events provide a
separate indication of alarms and trouble conditions to
the system.

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 3

MP-V
SmartX IP Controller

Analog outputs in a room. The SmartX Sensors are available with


The analog outputs are capable of supporting analog different combinations of sensor types and various
voltage or current point types, without the need for covers and user interface options, such as
external bias resistors. Therefore, analog outputs touchscreen, setpoint and override buttons, and blank
support a wide range of devices, such as actuators. covers.

Integrated damper actuator with feedback signal


The integrated damper actuator allows for simplified
installation of MP-V directly over the damper shaft. This
eliminates the need for separate installation, wiring, and
positioning of the damper motor. MP-V uses the same
actuator mechanics as many Schneider Electric VAV
controller models from the Andover Continuum, TAC
Vista, TAC I/A Series, and TAC I/NET product lines. The
feedback signal from the actuator makes it possible to
determine the exact position of the damper. The SmartX Sensors
actuator also features a push button for manual
positioning of the damper during commissioning. The sensor bus provides both power and
communications for up to four sensors that are daisy-
Factory-calibrated air flow sensor chained using standard Cat 5 (or higher) cables. The
maximum number of sensors that can be connected to
The factory-calibrated air flow sensor uses a state-of- a controller varies depending on the sensor model and
the-art technology that requires no air flow from the the combination of cover and sensor base type:
velocity probe. Unlike flow-through sensors, the sensor
does not impose rigid requirements on tubing, dust, or • Blank covers: Up to four sensors of any
filters, and the sensor is not affected by errors induced combination of sensor base types
on the local probe pressure readings. The sensor
requires no maintenance and a minimum of field • 3-button and touchscreen covers:
adjustments. – Up to two sensor bases with CO2 option

High reliability – Up to four sensor bases without CO2 option

The MP Series controllers support local trends, • SmartX LCD temperature sensors: Up to four
schedules, and alarms, enabling local operation when sensors are supported
the controller is offline or used in standalone
applications. The maximum total length of the sensor bus is 61 m
(200 ft). For more information, see the SmartX Living
The battery-free power backup of the memory and real- Space Sensors Specification Sheet.
time clock prevents data loss and ensures seamless
and quick recovery after a power failure. Mobile commissioning application
WorkStation allows you to update the firmware of The eCommission SmartX Controllers mobile
multiple MP Series controllers at the same time and with application is designed for local configuration, field
minimum down time. The EcoStruxure BMS server deployment, and commissioning of MP Series
keeps track of the installed firmware to support backup, controllers, and air flow balancing of VAV units. The
restore, and replacement of the controllers and mobile application reduces the commissioning time,
sensors. The server can host controllers of different allows flexibility in project execution, and eliminates
firmware versions. dependencies on network infrastructure.

Sensor bus for living space sensors The mobile application is designed for use with
Android, Apple (iOS), and Microsoft Windows 10
The MP Series controllers provide an interface devices. For more information, see the eCommission
designed for the SmartX Sensor family of living space SmartX Controllers Specification Sheet.
sensors. The SmartX Sensors offer an efficient way to
sense the temperature, humidity, CO2, and occupancy

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 4

MP-V
SmartX IP Controller

flow balancing, you can generate a report in HTML


format for one or more VAV units. The balancing
parameters associated with each MP-V are stored in
the parent server, which makes it easier to replace the
controller if necessary.

Full EcoStruxure Building Operation software


support
The power of the MP Series controller is fully realized
when it is part of an EcoStruxure BMS, which provides
the following benefits:

• WorkStation/WebStation interface
• Script and Function Block programming options
• Device discovery
eCommission SmartX Controllers mobile app
• Engineering efficiency
Using the eCommission SmartX Controllers mobile
application, you can connect to one or many MP Series WorkStation/WebStation interface
controllers. You can connect to a single MP Series WorkStation and WebStation provide a consistent user
controller using the eCommission Bluetooth Adapter experience regardless of which EcoStruxure BMS
connected to a SmartX Sensor. You can connect to a server the user is logged on to. The user can log on to
network of MP Series controllers on the local IP the parent EcoStruxure BMS server to engineer,
network, using a wireless access point or a network commission, supervise, and monitor the MP Series
switch. controller and its I/O as well as its attached SmartX
Sensors. For more information, see the WorkStation and
Device configuration WebStation specification sheets.
With the eCommission SmartX Controllers mobile
application, you can easily discover MP Series Script and Function Block programming options
controllers on the IP network and change each Unique to the industry, the MP Series controllers have
controller's configuration, including the BACnet and IP both Script and Function Block programming options.
network settings, location, and parent server. To save This flexibility assures that the best programming
engineering time, you can save common device method can be selected for the application. Existing
settings and then reuse them for controllers of the same programs can easily be reused between the
model. EcoStruxure BMS server and the controller.

Field deployment and I/O checkout Device discovery


The eCommission SmartX Controllers mobile The enhanced Device Discovery in WorkStation
application does not require an EcoStruxure BMS enables you to easily identify MP Series controllers on a
server or a network infrastructure to be in place. You BACnet network and to associate the controllers with
can use the mobile application to load the controller their parent server.
application directly into the local MP Series controller
and deploy the controller. The controller application Engineering efficiency
can be created offline using Project Configuration Tool The engineering and maintenance of MP Series
or WorkStation. You can also perform an I/O checkout controllers can be done very efficiently using the
to ensure that the controller's I/O points are configured, EcoStruxure Building Operation reusability features.
wired, and operating correctly. With these features, you can create library items
(Custom Types) for a complete controller application
Air flow balancing that contains programs and all necessary objects such
Using the eCommission SmartX Controllers mobile as trends, alarms, and schedules. The controller
application, you can perform air flow balancing of VAV application in the Custom Types library is reusable
units controlled by MP-Vs. An intuitive workflow across all controllers of the same model. You can use
automatically guides you through the process. After the the controller application as a base for creating new

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 5

MP-V
SmartX IP Controller

controllers intended for similar applications. You can using the wizards and mass edit functions provided in
then edit the controller application, and the changes the tool and then loaded into your target server. The
are automatically replicated to all controllers, while tool also enables the quick creation of your own
each controller keeps its local values. templates based on MP Series controller applications
that you have developed. This facilitates a standard
WorkStation supports both online and offline approach and drives the ability to easily reuse and
engineering of MP Series controllers. You can make the duplicate common controller applications. For more
configuration changes online or use database mode to information, see the Automated Engineering Tool
make the changes offline. In database mode, the specification sheet.
changes are saved to the EcoStruxure Building
Operation database so that you can apply the changes
to the controllers later.

Project Configuration Tool enables you to perform all


the engineering off site, without the need for physical
hardware, which minimizes the time you need to spend
on site. You can run the EcoStruxure BMS servers
virtually and engineer the MP Series controllers, before
you deploy your server and controller applications to
the servers and controllers on site. For more
information, see the Project Configuration Tool
specification sheet.

In addition, you can use Automated Engineering Tool to


facilitate your engineering process when using MP
Series controllers. This tool provides access to a library Library of standard HVAC applications
of standard controller applications. These standard
applications can be quickly configured and customized

Part Numbers

Product Part number


MP-V-7A SXWMPV7AX10001
MP-V-9A SXWMPV9AX10001
Spare terminal blocks for all MP-V models SXWMPVCON10001
(1 x 2-pin, 2 x 3-pin, 2 x 4-pin, 1 x 5-pin, 1 x 6-pin terminal blocks)
Adapter for damper shaft diameter 9.5 mm (0.375 inch) AM-135
eCommission Bluetooth Adapter SXWBTAECXX10001

Specifications
AC input
Nominal voltage .....................................................................................................................................................24 VAC
Operating voltage range .......................................................................................................................................+/-20 %
Frequency ...........................................................................................................................................................50/60 Hz
Maximum power consumption (MP-V-7A) ................................................................................................................21 VA
Maximum power consumption (MP-V-9A) ................................................................................................................22 VA
Power input protection ...............................................................................................MOV suppression and internal fuse

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 6

MP-V
SmartX IP Controller

Environment
Ambient temperature, operating ..................................................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating ..............................................................................................................................................UL94 V-0
Ingress protection rating ............................................................................................................................................IP 20
Mechanical
Dimensions ......................................................................................161 W x 198 H x 63 D mm (6.3 W x 7.8 H x 2.5 D in.)

Weight ........................................................................................................................................................1.13 kg (2.5 lb)


Installation ......................................................................................................................................Over the damper shaft
Terminal blocks ...............................................................................................................................................Removable
Software compliance
EcoStruxure Building Operation software ............................................................................................version 2.0 or later
Agency compliances
Emission ..............................................................RCM; EN 61000-6-3; EN 50491-5-2; FCC Part 15, Sub-part B, Class B
Immunity ..............................................................................................................................EN 61000-6-2; EN 50491-5-3
Safety ........................................................................EN 60730-1; EN 60730-2-11; EN 50491-3; UL 916 C-UL US Listed
Fire performance in air-handling spacesa ........................................................................................................... UL 2043
a) MP-V-7A and MP-V-9A are approved for plenum applications.
Real-time clock
Accuracy, at 25 °C (77 °F) ..............................................................................................................+/-1 minute per month
Backup time, at 25 °C (77 °F) ..................................................................................................................7 days minimum

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 7

MP-V
SmartX IP Controller

Communication ports
Ethernet ............................................................................................................................... Dual 10/100BASE-TX (RJ45)
USB ................................................................... USB 2.0, 5 VDC, 2.5 W, 1 device port (mini-B) and 1 host port (type-A)
Sensor Bus ...........................................................................................................................24 VDC, 2 W, RS-485 (RJ45)
Sensor Bus protection ..........................................Transient voltage suppressors on communication and power signals
Communications
BACnet .........................................................................................................BACnet/IP, port configurable, default 47808
...................................................................................................BTL B-AAC (BACnet Advanced Application Controller)a
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet International's home
page.
CPU
Frequency .......................................................................................................................................................... 500 MHz
Type ..........................................................................................................................................ARM Cortex-A7 dual-core
DDR3 SDRAM .......................................................................................................................................................128 MB
NOR flash memory ..................................................................................................................................................32 MB
Memory backup ......................................................................................................................128 kB, FRAM, non-volatile
Damper actuator
Torque rating .............................................................................................................................................6 Nm (53 lbf.in)
Stroke .........................................................................................................................................0° to 90°, fully adjustable
Timing .............Approximately 2 seconds/degree at 60 Hz and 2.4 seconds/degree at 50 Hz for 90° rotation at 24 VAC
Position indication ....................................................................................................................................Visual indication
Damper position feedback ..........................................................................................................................................Yes
Manual override ..................................................................................................................... Push-button clutch release
Damper shaft diameter ...................................................................................12.7 mm (0.5 inch) or 9.5 mm (0.375 inch)
..........................................................................Adapter kit AM-135 is required for 9.5 mm (0.375 inch) diameter shafts.
Damper shaft minimum length (from VAV box) ................................................................................22.2 mm (0.875 inch)
Air flow sensor
Range ........................................................................................................................................0 to 249 Pa (0 to 1 inH2O)
Resolution ................................................................................................................0.33 Pa (0.001 inH2O) at 25°C (77°F)
Accuracy ...............................................................................................±5% of 249 Pa (1.00 inH2O) span at 25°C (77°F)
Universal inputs, UI
Channels, MP-V-7A .......................................................................................................................................... 3, UI1–UI3
Channels, MP-V-9A .......................................................................................................................................... 4, UI1–UI4
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
A/D converter resolution ..........................................................................................................................................16 bits
Universal input protection .............................................................................Transient voltage suppressor on each input
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 8

MP-V
SmartX IP Controller

Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Supervised inputs
5 V circuit, 1 or 2 resistors
Monitored switch combinations.............................................................Series only, parallel only, and series and parallel
Resistor range ................................................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor must have the same value +/- 5 %
Voltage inputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy...............................................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution................................................................................................................................................................1.0 mV
Impedance..........................................................................................................................................................100 kohm
Current inputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy..........................................................................................................................+/-(0.01 mA + 0.4 % of reading)
Resolution....................................................................................................................................................................1 μA
Impedance .............................................................................................................................................................47 ohm
Resistive inputs
10 ohm to 10 kohm accuracy .......................................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy .....................................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Temperature inputs (thermistors)
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Supported thermistors
Honeywell .............................................................................................................................................................20 kohm
Type I (Continuum) ...............................................................................................................................................10 kohm
Type II (I/NET) .......................................................................................................................................................10 kohm
Type III (Satchwell) ...............................................................................................................................................10 kohm
Type IV (FD) ......................................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt) ....................................................................................................................Linearized 10 kohm
Satchwell D?T......................................................................................................................................Linearized 10 kohm
Johnson Controls .................................................................................................................................................2.2 kohm
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 9

MP-V
SmartX IP Controller

...................................................................................................................-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)


.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
10 kohm, 2.2 kohm, and 1.8 kohm.......................................................-50 to -30 °C: +/-0.75 °C (-58 to -22 °F: +/-1.35 °F)
..........................................................................................................-30 to +100 °C: +/-0.2 °C (-22 to +212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
Linearized 10 kohm .................................................................................-50 to -30 °C: +/-2.0 °C (-58 to -22 °F: +/-3.6 °F)
...............................................................................................................-30 to 0 °C: +/-0.75 °C (-22 to +32 °F: +/-1.35 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
1 kohm ..............................................................................................-50 to +150 °C: +/-1.0 °C (-58 to +302° F: +/-1.8 °F)
RTD temperature inputs
Supported RTDs......................................................................................................................................................Pt1000
Pt1000
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Measurement accuracy ......................................................................-50 to +70 °C: +/-0.5 °C (-58 to +158 °F: +/-0.9 °F)
...............................................................................................................70 to 150 °C: +/-0.7 °C (158 to 302 °F: +/-1.3 °F)
RTD temperature wiring
Maximum wire resistance.........................................................................................................20 ohm/wire (40 ohm total)
Maximum wire capacitance.......................................................................................................................................60 nF
The wire resistance and capacitance typically corresponds to a 200 m wire.
Triac outputs, DO
Channels, MP-V-7A ...................................................................................................................................... 3, DO1–DO3
Channels, MP-V-9A ...................................................................................................................................... 3, DO1–DO3
Output rating (for each triac output) ..................................................................................................................Max. 0.5 A
Voltage......................................................................................................................................................24 VAC +/-20 %
Commons.................................................................................................................................COM (terminal number 18)
The common terminal COM can be connected to 24 VAC or to ground.
Common voltage, high side output.........................................................................................................................24 VAC
Common voltage, low side output .............................................................................................................0 VAC (ground)
Minimum pulse width ..............................................................................................................................................100 ms
Triac output protection ..................................................................................MOV and snubber across each triac output
..........................................................................................................................................MOV from triac COM to ground
Analog outputs, AO
Channels, MP-V-7A ....................................................................................................................................... 1, VO1/CO1
Channels, MP-V-9A .................................................................................................................2, VO1/CO1 and VO2/CO2
Analog output protection ............................................................................Transient voltage suppressor on each output
Voltage outputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy..............................................................................................................................................................+/-60 mV
Resolution.................................................................................................................................................................10 mV

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 10

MP-V
SmartX IP Controller

Minimum load resistance........................................................................................................................5 kohm to ground


Load range........................................................................................................................................................0 to +2 mA
Terminals .....................................................................................................................Voltage Output (VO), Return (RET)
Current outputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy ............................................................................................................................................................+/-0.2 mA
Resolution..................................................................................................................................................................21 µA
Load range.....................................................................................................................................................0 to 650 ohm
Terminals .....................................................................................................................Current Output (CO), Return (RET)

Terminals • Individual 24 VDC power sources to the field must


be current limited to maximum 4 A for UL
Be sure to follow proper installation wiring diagrams compliant installations, and maximum 6 A in other
and instructions, including these instructions: areas.
• MP-V-7A and MP-V-9A have several RET terminals • For more information on wiring, see Hardware
for connection of I/O returns, so a common Reference Guide.
chassis/signal ground rail is optional and may not
be needed.

MP-V-7A

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 11

MP-V
SmartX IP Controller

MP-V-9A

Part Numbers in AMER Region for Network Connectivity Accessories

Product descriptiona Part number (AMER region)


Cat 6 field-term plug, UTP ACTPG6TLU001
Cat 6 pass-through plug, UTP, 100-pack ACTPG6PTU100
Actassi crimping tool ACTTLCPT
Cat 6 cable, UTP, 1000 ft (305 m), CMP, green ACT4P6UCP1ARXGR
Cat 6 patch cord, UTP, 30 ft (9 m), CMP, green ACTPC6UBCP30AGR
Cat 6 patch cord, UTP, 50 ft (15 m), CMP, green ACTPC6UBCP50AGR
Cat 6 patch cord, UTP, 70 ft (21 m), CMP, green ACTPC6UBCP70AGR
Cat 6 patch cord, UTP, 90 ft (27 m), CMP, green ACTPC6UBCP90AGR
Cat 5e pass-through plug, UTP, 100-pack ACTPG5EPTU100
Cat 5e cable, UTP, 1000 ft (305 m), CMP, green ACT4P5EUCP1ARXGR
Cat 5e patch cord, UTP, 30 ft (9 m), CMP, green ACTPC5EUBCP30AGR
Cat 5e patch cord, UTP, 50 ft (15 m), CMP, green ACTPC5EUBCP50AGR
Cat 5e patch cord, UTP, 70 ft (21 m), CMP, green ACTPC5EUBCP70AGR
Cat 5e patch cord, UTP, 90 ft (27 m), CMP, green ACTPC5EUBCP90AGR

a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable)

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 12

MP-V
SmartX IP Controller

Part Numbers in EMEA Region for Network Connectivity Accessories

Product descriptiona Part number (EMEA region)


Cat 6 field-term plug, UTP ACTPG6TLU001
Cat 6 pass-through plug, UTP, 100-pack ACTPG6PTU100
Actassi crimping tool ACTTLCPT
Cat 6 cable, UTP, 305 m (1000 ft), Euroclass D, green VDICD116118
Cat 6 patch cord, UTP, 10 m (32 ft), LSZH, green ACTPC6UBLS100GR
Cat 6 patch cord, UTP, 15 m (49 ft), LSZH, green ACTPC6UBLS150GR
Cat 6 patch cord, UTP, 20 m (65 ft), LSZH, green ACTPC6UBLS200GR
Cat 6 patch cord, UTP, 25 m (82 ft), LSZH, green ACTPC6UBLS250GR
Cat 5e pass-through plug, UTP, 100-pack ACTPG5EPTU100
Cat 5e cable, UTP, 1000 ft (305 m), Euroclass D, green VDICD115118
Cat 5e patch cord, UTP, 10 m (32 ft), LSZH, green ACTPC5EUBLS100GR
Cat 5e patch cord, UTP, 15 m (49 ft), LSZH, green ACTPC5EUBLS150GR
Cat 5e patch cord, UTP, 20 m (65 ft), LSZH, green ACTPC5EUBLS200GR
Cat 5e patch cord, UTP, 25 m (82 ft), LSZH, green ACTPC5EUBLS250GR

a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable), LSZH (Low Smoke Zero Halogen)

Part Numbers in Pacific Region for Network Connectivity Accessories

Product descriptiona Part number (Pacific region)


Cat 6 field-term plug, UTP ACTPG6TLU001
Cat 6 pass-through plug, UTP, 100-pack ACTPG6PTU100
Actassi crimping tool ACTTLCPT
Cat 6 cable, UTP, 305 m (1000 ft), PVC, green 2D4P6IPV3B-GR
Cat 6 patch lead, UTP, 10 m (32 ft), PVC, green RJ6_100PL-GR
Cat 6 patch lead, UTP, 15 m (49 ft), PVC, green RJ6_150PL-GR
Cat 6 patch lead, UTP, 20 m (65 ft), PVC, green RJ6_200PL-GR
Cat 6 patch lead, UTP, 25 m (82 ft), PVC, green RJ6_250PL-GR
Cat 5e pass-through plug, UTP, 100-pack ACTPG5EPTU100
Cat 5e cable, UTP, 305 m (1000 ft), PVC, green 2D4P5IPV3B-GR
Cat 5e patch lead, UTP, 10 m (32 ft), PVC, green RJ5_100PL-GR
Cat 5e patch lead, UTP, 15 m (49 ft), PVC, green RJ5_150PL-GR
Cat 5e patch lead, UTP, 20 m (65 ft), PVC, green RJ5_200PL-GR
Cat 5e patch lead, UTP, 25 m (82 ft), PVC, green RJ5_250PL-GR

a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), PVC (Polyvinyl
chloride)

03-20036-02-en, May 2018


© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 13

MP-V
SmartX IP Controller

Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept This equipment complies with the rules, of the Official Journal of the European Union, for
any interference received, including interference that may cause undesired operation. governing the Self Declaration of the CE Marking for the European Union as specified in the
above directive(s) per the provisions of the following standards: EN 60730-1, EN 60730-2-
Industry Canada 11, and EN 50491-3 Safety Standards.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
WEEE - Directive of the European Union (EU)
Regulatory Compliance Mark (RCM) - Australian Communications and Media This equipment and its packaging carry the waste of electrical and electronic equipment
Authority (ACMA) (WEEE) label, in compliance with European Union (EU) Directive 2012/19/EU, governing the
This equipment complies with the requirements of the relevant ACMA standards made under disposal and recycling of electrical and electronic equipment in the European community.
the Radiocommunications Act 1992 and the Telecommunications Act 1997. These
standards are referenced in notices made under section 182 of the Radiocommunications
Act and 407 of the Telecommunications Act. UL 916 Listed products for the United States and Canada, Enclosed Energy
Management Equipment. UL file E80146.

www.schneider-electric.com

03-20036-02-en, May 2018