AGS Controls RSCO2 Range Spec Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

v1

AGSRSCO2 PRODUCT SPEC SHEET

RSCO2 Range
CARBON DIOXIDE SENSORS

BLANK VERSION LED VERSION DISPLAY SCREEN

Product Overview:
The RSCO2 Range: Featuring NDIR Carbon Dioxide Sensors designed to monitor and measure vital indoor air
quality environmental parameters with precision and reliability. Engineered to be used across residential,
public, commercial, and light industrial settings, these sensors offer digital & analog outputs and exceptional
performance features.

Key Features:
• Digital RS-485: Modbus RTU or BACnet MS/TP communication protocols
• Analog: 1x 0-10V signals for CO2 (PPM)
• VFC Relay (CO2): 1x SPST 70mA Max

Circuit Board Diagram:

CONNECTION LABEL TERMINATION


120V AC IN POWER LIVE IN L (Line)
N (Neutral)

24V AC/DC INPUT 24V IN +24V


0V (Common GND)

ANALOG OUT/P +10V OUT PPM (CO2 Sensor O/P)

DIGITAL OUT/P RS-485 A+


B-
SH (Shield)

THERMISTOR 10K3 Disabled On This Model

CO2 VFC RELAY RLY 70mA (Open/Close Circuit)

6304 Benjamin Road, Suite 502, Tampa, FL www.agscontrols.com @agscontrols


v1

AGSRSCO2 PRODUCT SPEC SHEET

Technical Specifications
Mechanical
Mechanical
Mounting Wall Mounted
Entry 1/2" DIA Rear Entry
Size (W x H x D) Display Screen - 3.38" x 4.48" x 1.3" / Blank & LED - 3.38" x 4.48" x 0.98"
Weight 0.35lb
Enclosure ABS UL Flame retardant - IP40
Electrical
24V AC/DC Power Rating 12-24VDC (11-32 VDC) / 24VAC, (20-27 VAC) 50-60Hz
110VAC Power Rating Nominal 110VAC, (90-250V AC), 50-60H
Internal Fuse Resettable PPTC 110VAC, 400mA
Communication 127 Units Max
Power Consumption 5W Max

Environmental
Operating Temperature 14°F to 122°F / -10°C to 50°C
Storage 32-86°F / 0°C to 30°C
Room Humidity 0 to 95% RH (continuous) Non-Condensing
Atmospheric Pressure 80 to 110Pa
Altitude <6562ft
Installation Cat (110V Voltage) II (Class 2) Pollution Degree 2
Installation Cat (24V Voltage) III (Class 3) Pollution Degree 2

Inputs / Outputs
Analog Outputs 1x Linear 0-10V/2-10V CO2
Digital Networks BACnet MS/TP or MODBUS RTU (Parity: None Data bit: 8bit Stop bit: 1)
Relay Outputs 1 x SPST 70mA
Cable Spec
Power 22 - 24 AWG
Analog Output 22 - 24 AWG
Relay 22 - 24 AWG
Digital Output 22 - 24 AWG twisted pair + ground, shielded cable with 120 Ω
characteristic impedance.
User Interface
Lanugage English
Optional Display 2.8" TFT
Indication Green: Power (OK) / Yellow: Warning (Pre-Alarm) / Red: Danger (Alarm)

Safety & EMC


Safety IEC 61010-1
Electromagnetic Compatibility FCC
Compliance CE, EMC, RoHS, REACH and WEEE Compliant

CO2 Sensor (PPM)

Sampling: Diffusion Type


NDIR Indication Range: 400 – 5000ppm
Response: t90 <120s
Calibration: ABC Logic Self Calibration
Warm Up Time: ~1 Minute
Accuracy: 5% FS @ 77°F
Lifespan: > 10 Years
Resolution: 1ppm

6304 Benjamin Road, Suite 502, Tampa, FL www.agscontrols.com @agscontrols