Generator Protection
Generator Protection
Dr. O. P. Rahi
Electrical Engineering Department,
National Institute of Technology Hamirpur (H.P), India. 1
Contents
Recap: Basic Principles of Protection
Equipment Protection
Generator Protection
Peculiarities Associated with Generator/Alternator
Generator Faults
Abnormal Running Conditions
Stator Winding Faults
Rotor Faults
Conclusion
2
Alternator
Construction
Armature/Stator
Excitation/Field System/Rotor
Prime Mover
Step up Transformer
UAT
Hydro/Thermal generator
3
Generator Faults
Abnormal Running Conditions
Stator Winding Faults
Rotor Faults
4
Abnormal Running Conditions
Failure of prime mover
Failure of field
Over current (Overloading)
Over speed
Overvoltage
Unbalanced loading
Vibration
Bearing overheating
Voltage regulator failure
5
Stator Winding Faults
Phase to phase fault
Phase to earth fault
Inter turn fault
6
Rotor Faults
Field ground fault
Loss of excitation
Rotor overheating due to unbalanced
3-phase stator currents
7
Stator Protection
%age differential protection
Phase to earth fault protection
Protection against stator inter-turn faults
Stator overheating protection
8
9
10
11
12
%age Differential Protection of Stator
13
Biased Differential Protection
14
Unbalanced Stator Loading Protection
Unbalancing in loading produces negative
sequence currents in the stator circuit.
This current is quite large and causes
overheating in the rotor circuit, especially in
the alternator.
These faults then be cleared by installing a
negative phase sequence relay with the
characteristics to match the withstand curve of
the machine.
15
Protection against Unbalanced Loading
16
Overload Protection/ Protection against
Overheating
18
Stator Earth Fault Protection of
Alternator
Here, one current transformer is connected across the neutral and
earth connection of the alternator.
One protective relay is connected across the current transformer
secondary. The alternator can feed the power system in two
ways, either it is directly connected to the substation bus bar or it
is connected to substation via one star delta transformer. If the
generator is connected directly to the substation bus bars, the
relay connected across the CT secondary, would be an inverse
time relay because here, relay coordination is required with other
fault relays in the system.
But when the stator is connected to the primary of a star Delta
transformer, the fault is restricted in between stator winding and
transformer primary winding, therefore no coordination is
required with other earth fault relays of the system.
19
20
Rotor Earth Fault Protection
The rotor of an alternator is wound by field winding. Any single
earth fault occurring on the field winding or in the exciter circuit is
not a big problem for the machine. But if more than one earth
fault occur, there may be a chance of short circuiting between the
faulty points on the winding. This short circuited portion of the
winding may cause unbalance magnetic field and subsequently
mechanical damage may occur in the bearing of the machine due
to unbalanced rotation.
Hence it is always essential to detect the earth fault occurred on
the rotor field winding circuit and to rectify it for normal
operation of the machine.
There are various methods available for detecting rotor earth fault
of alternator or generator. But basic principle of all the methods is
same and that is closing a relay circuit through the earth fault
path. 21
Three Types of Rotor Earth Fault
Protection
There are mainly three types of rotor earth
fault protection scheme used for this
purpose.
Potentiometer method
AC injection method
DC injection method
22
Potentiometer Method of REFP
23
AC Injection Method of REFP
24
AC Injection Method of REFP
Here, one voltage sensitive relay is connected at any point of the
field and exciter circuit. Other terminal of the voltage sensitive
relay is connected to the ground by a capacitor and secondary of
one auxiliary transformer.
Here, if any earth fault occurs in the field winding or in the exciter
circuit, the relay circuit gets closed via earthed path and hence
secondary voltage of the auxiliary transformer will appear across
the voltage sensitive relay and the relay will be operated.
Disadvantage: There would always be a chance of leakage current
through the capacitors to the exciter and field circuit. This may
cause unbalancing in magnetic field and hence mechanical stresses
in the machine bearings.
25
DC Injection Method of REFP
26
DC Injection Method of REFP
The drawback of leakage current of AC injection method can be
eliminated in DC Injection Method.
Here, one terminal of DC voltage sensitive relay is connected with
positive terminal of the exciter and another terminal of the relay
is connected with the negative terminal of an external DC source.
The external DC source is obtained by an auxiliary transformer
with bridge rectifier.
Here the positive terminal of bridge rectifier is grounded.
In the event of any field earth fault or exciter earth fault, the
positive potential of the external DC source will appear to the
terminal of the relay which was connected to the positive
terminal of the exciter.
In this way the rectifier output voltage appears across the voltage
relay and hence it is operated.
27
Loss of Field or Excitation Protection
of Alternator or Generator
Loss of field or excitation can be caused in the generator due to
excitation failure.
Stand alone generator & Grid Connected generator
In larger sized generator, energy for excitation is often taken
from a separate auxiliary source or from a separately driven DC
generator.
The failure of auxiliary supply or failure of driving motor can also
cause the loss of excitation in a generator. Failure of excitation
that is failure of field system in the generator makes the generator
run at a speed above the synchronous speed.
In that situation the generator or alternator becomes an induction
generator which draws magnetizing current from the system.
28
Two Schemes Protection Against
Loss of Field
In 1st scheme, we use an undercurrent relay connected in shunt
with main field winding circuit. This relay will operate if the
excitation current comes below its predetermined value. If the
relay is to operate for complete loss of field along, it must have a
setting lies well below the minimum excitation current value
which can be 8% of the rated full load current.
In this case a setting of 5% of normal of full load current is
recommended. There is a normally closed contact attached with
the undercurrent relay. This normally closed contact remains open
as the relay coil is energized by shunted excitation current during
normal operation of the excitation system. As soon as there is any
failure of excitation system, the relay coil becomes de-energized
and the normally closed contact closes.
29
Protection Against Loss of Field
For larger generators, it is recommended to trip the machine after a
certain prescribed delay in presence of swing condition resulting from loss
of field. Offset mho relay and under voltage relay
There must be subsequent load shedding to maintain stability of the
system.
In this scheme an automatic imposition of load shedding to the system is
also inherently required if the field is not restored within the described
time delay. The scheme comprises an offset mho relay, and an
instantaneous under voltage relay.
System voltage is the main indication of system stability. Therefore the
offset mho relay is arranged to shut the machine down instantaneously
when operation of generator is accompanied by a system voltage
collapse.
The drop in system voltage is detected by an under voltage relay which is
set to approximately 70 % of normal rated system voltage. The offset
mho relay is arranged to initiate load shedding to the system up to a safe
value and then to initiate a master tripping relay after a predetermined 30
time.
Protection Against Loss of Field
31
Conclusion
Generator Overview
Faults on Generator
Protection of Generator against faults
Next, protection of transformer
32
Thank you
33