Leroy Somer Main Alternators
Leroy Somer Main Alternators
Leroy Somer Main Alternators
3 - DERATING............................................................................................................................................ 3
4 - WINDING............................................................................................................................................... 4
5 - GENERAL FEATURES......................................................................................................................... 4
5.1 - Standards..................................................................................................................................................4
8 - RECONNECTIONS 50Hz...................................................................................................................... 6
8.1 - Winding 6S or 6 standard (voltage: 190 - 200 - 208 V / 220 - 230 - 240 V / 380 - 400 - 415 V)....................7
8.5 - Dedicated winding M (dedicated 1-phase - voltage: 110 - 120 V / 220 - 240 V)........................................ 11
9 - RECONNECTIONS 60Hz.................................................................................................................... 12
9.1 - Winding 6S or 6 standard (voltage: 190 - 208 V / 220 - 240 V / 380 - 416 V).............................................13
9.2 - Winding 6S or 6 standard (voltage: 220 - 240 V / 254 - 277 V / 440 - 480 V).............................................14
9.3 - Winding 8S or 8 specific (voltage: 190 - 208 V / 220 - 240 V / 380 - 416 V)...............................................15
9.6 - Dedicated winding M or M1 (dedicated 1-phase - voltage: 115 - 120 V / 230 - 240 V)..............................18
INTRODUCTION
This catalogue is a summary of ratings for the TAL low voltage range at the most common voltages around the world.
For other voltages, please consult Nidec Leroy-Somer.
3 - DERATING
Multiply nominal rating by derating factors indicated in the following table.
Ambient T °C 25 40 45 50 55 60 (*)
4 - WINDINGS
The windings proposed by Nidec Leroy-Somer in this document are in 2/3 pitch.
- Standard winding No.: 6S (6 wires) or 6 (12 wires)
- Winding M or M1, dedicated 1-phase winding (4 wires)
“S” after the winding number means “6 leads” ex: 6S.
“T” or “+” after winding give an information about the saturation level of the stator.
5 - GENERAL FEATURES
5.1 - Standards
Nidec Leroy-Somer TAL alternators meet all key international standards and regulations, including IEC 60034, NEMA MG 1.32-33,
ISO 8528-3, CSA C22.2 n°100-14 and UL 1446 (UL 1004 on request). Also compliant with IEC 61000-6-2, IEC 61000-6-3,
IEC 61000-6-4, VDE 0875G, VDE 0875N and EN 55011, group 1 class A for European zone.
Nidec Leroy-Somer TAL alternators can be integrated in EC marked generator sets, and they bear EC, UKCA and CMIM markings.
They are designed, manufactured and marketed in an ISO 9001 and ISO 14001 quality assurance environment.
Alternators TAL 040 TAL 042 TAL 044 TAL 046 TAL 0473 TAL 049
- Frequency
TAL alternators may operate either 50 or 60 Hz.
- Power factor: P.F.
TAL alternators are designed to operate between 0.8 and 1 power factor.
- Waveform
Total harmonic distorsion (THD), at no load or linear load is less than 5% according to IEC.
TIF/Telephone influence factor according to NEMA is less than 50.
- Transient features
Transient voltage dip for rated step load at 0.8 power factor is less than 18 %.
Recovery time for a 20 % transient voltage dip is less than 0.5 s.
- Parallel operation
TAL 044, TAL 046, TAL 0473 and TAL 049 alternators can operate in parallel with other alternators with AREP+ or PMG.
- Overload acceptance
TAL alternators can be overloaded according to NEMA.
- 1-phase operation
TAL 040, TAL 042 and TAL 044 alternators can be supplied with a dedicated 1-phase winding (code M or M1).
50 Hz 60 Hz
Type
380V 400V 415V All voltages
TAL 040 1 1 1 1
TAL 042 0.97 1 except 0.97 for TAL 042 G 1 except 0.97 for TAL 042 G 1 except 0.97 for TAL 042 G
TAL 044 1 except 0.97 for TAL 044 K 1 except 0.97 for TAL 044 K 1 except 0.97 for TAL 044 K 1 except 0.97 for TAL 044 K
TAL 046 1 except 0.97 for TAL 046 H 1 except 0.97 for TAL 046 H 1 except 0.97 for TAL 046 H 1 except 0.97 for TAL 046 H
1 except 0.95 1 except 0.95 1 except 0.95 1 except 0.95
TAL 0473
for TAL 0473 A, D & F for TAL 0473 D & F for TAL 0473 D & F for TAL 0473 D & F
TAL 049 1 1 1 1
7 - PRODUCT DESCRIPTION
The machine name is defined according to various criteria (see below).
Example of description for:
TAL 044 A M6S/4
• TAL: Range
• 044: Frame size
• A: Core length
• M: Excitation system (M, or L wind.9: AREP+ / J: SHUNT or SHUNT + PMG)
• 6S/4: Winding number / number of poles
8 - RECONNECTIONS 50 Hz
Connections
Number of
6 6 12 12 12 6 12
wires
Winding
6S or 6 380-400-415 V 220 - 240 V 380-400-415 V 220 - 240 V 190 - 208 V 220 - 240 V 220 - 240 V
(page 7) (page 7) (page 7) (page 7) (page 7) (page 10) (page 10)
standard
Winding
6S or 6 440 V 440 V 220 V
- - - -
(page 8) (page 8) (page 8)
standard
Winding
9S or 9 500 - 525 V 500 - 525 V
- - - - -
specific (page 9) (page 9)
(on request)
Winding M specific, dedicated 1-phase 220 - 240 V (page 11) 110 - 120 V (page 11)
4 wires SE (serie) PA (parallel)
1500 R.P.M. - P.F. 0.8 380 - 400 - 415 V 190 - 200 - 208 V 220 - 230 - 240 V
8.1 - Winding 6S or 6 standard kVA @ 190V, 220V, 380V kVA @ 200V, 230V, 400V kVA @ 208V, 240V, 415V
40 °C 27 °C 40 °C 27 °C 40 °C 27 °C
Excitation 40 °C cont. St.by St.by 40 °C cont. St.by St.by 40 °C cont. St.by St.by
TYPE SHUNT AREP+ PMG wires H : 125 K F : 105 K H : 150 K H : 163 K H : 125 K F : 105 K H : 150 K H : 163 K H : 125 K F : 105 K H : 150 K H : 163 K
TAL 040 C J6S/4 M6S/4 - 6/12 12.5 11.5 13.5 14 12.5 11.5 13.5 14 12.5 11.5 13.5 14
TAL 040 E J6S/4 M6S/4 - 6/12 17.5 16 18.5 19.5 17.5 16 18.5 19.5 17.5 16 18.5 19.5
TAL 042 A J6S/4 M6S/4 Option 6/12 25 23 26.5 27.5 25 23 26.5 27.5 25 23 26.5 27.5
TAL 042 B J6S/4 M6S/4 Option 6/12 27 24.5 28.5 30 27 24.5 28.5 30 27 24.5 28.5 30
TAL 042 E J6S/4 M6S/4 Option 6/12 39.5 36 42 43.5 40 36.5 42.5 45 40 36.5 42.5 45
TAL 042 F J6S/4 M6S/4 Option 6/12 43 39 45.5 47.5 45 41 47.5 50 45 41 47.5 50
TAL 044 D J6S/4 M6S/4 Option 6/12 100 91 106 110 100 91 106 110 100 91 106 110
TAL 044 E * J6S/4 M6S/4 Option 6/12 125 114 133 138 125 114 133 138 125 114 133 138
TAL 044 H * J6S/4 M6S/4 Option 6/12 135 123 143 150 135 123 143 150 135 123 143 150
TAL 044 J J6S/4 M6S/4 Option 6/12 150 137 159 165 150 137 159 165 150 137 159 165
TAL 044 K * J6S/4 M6S/4 Option 6/12 165 150 175 182 165 150 175 182 165 150 175 182
TAL 044 L J6S/4 M6S/4 Option 6/12 180 164 191 200 180 164 191 200 180 164 191 200
TAL 044 M J6S/4 M6S/4 Option 6/12 192 175 204 211 200 182 212 220 200 182 212 220
TAL 046 C * J6S/4 M6S/4 Option 6/12 230 209 244 253 230 209 244 253 230 209 244 253
TAL 046 D * J6S/4 M6S/4 Option 6/12 240 218 254 264 250 228 265 275 250 228 265 275
TAL 046 E * J6S/4 M6S/4 Option 6/12 275 250 292 303 275 250 292 303 275 250 292 303
TAL 046 F * J6S/4 M6S/4 Option 6/12 290 264 307 319 300 273 318 330 300 273 318 330
TAL 046 G J6S/4 M6S/4 Option 6/12 325 296 345 360 325 296 345 360 325 296 345 360
TAL 046 H J6S/4 M6S/4 Option 6/12 350 318 371 385 365 332 387 400 365 332 387 400
TAL 0473 A J6S/4 M6S/4 Option 6/12 390 355 413 429 410 375 435 450 410 375 435 450
TAL 0473 B J6S/4 M6S/4 Option 6/12 455 415 480 500 455 415 480 500 455 415 480 500
TAL 0473 C J6S/4 M6S/4 Option 6/12 500 455 530 550 500 455 530 550 500 455 530 550
TAL 0473 D J6S/4 M6S/4 Option 6/12 525 478 557 578 550 500 585 600 550 500 585 600
TAL 0473 E * J6S/4 M6S/4 Option 6/12 600 545 635 660 600 545 635 660 600 545 635 660
TAL 0473 F * J6S/4 M6S/4 Option 6/12 645 587 684 710 660 600 700 730 660 600 700 730
TAL 049 B J6S/4 M6S/4 Option 6/12 730 665 775 805 730 665 775 805 730 665 775 805
TAL 049 C J6S/4 M6S/4 Option 6/12 820 745 870 910 820 745 870 910 820 745 870 910
TAL 049 D J6S/4 M6S/4 Option 6/12 910 830 965 1010 910 830 965 1010 910 830 965 1010
TAL 049 E J6S/4 M6S/4 Option 6/12 1000 910 1060 1100 1000 910 1060 1100 1000 910 1060 1100
1500 R.P.M. - P.F. 0.8 440 V (maximum voltage) 220 V (maximum voltage)
TAL 044 E * J6S/4 M6S/4 Option 6/12 113 103 120 124
TAL 044 H * J6S/4 M6S/4 Option 6/12 122 111 129 134
TAL 044 J J6S/4 M6S/4 Option 6/12 135 123 143 149
TAL 044 K * J6S/4 M6S/4 Option 6/12 138 126 150 157
TAL 044 L J6S/4 M6S/4 Option 6/12 171 156 181 188
TAL 044 M J6S/4 M6S/4 Option 6/12 192 175 204 211
TAL 046 C * J6S/4 M6S/4 Option 6/12 219 199 232 241
TAL 046 D * J6S/4 M6S/4 Option 6/12 238 217 252 262
TAL 046 E * J6S/4 M6S/4 Option 6/12 261 238 277 287
TAL 046 F * J6S/4 M6S/4 Option 6/12 285 259 302 314
TAL 046 G J6S/4 M6S/4 Option 6/12 309 281 328 340
TAL 046 H J6S/4 M6S/4 Option 6/12 347 316 368 382
TAL 0473 A J6S/4 M6S/4 Option 6/12 400 364 424 440
TAL 0473 B J6S/4 M6S/4 Option 6/12 445 405 472 490
TAL 0473 C J6S/4 M6S/4 Option 6/12 455 414 482 500
TAL 0473 D J6S/4 M6S/4 Option 6/12 540 491 572 594
TAL 0473 E * J6S/4 M6S/4 Option 6/12 500 455 530 550
TAL 0473 F * J6S/4 M6S/4 Option 6/12 630 573 668 693
TAL 049 B J6S/4 M6S/4 Option 6/12 665 605 705 730
TAL 049 C J6S/4 M6S/4 Option 6/12 810 735 860 890
TAL 049 D J6S/4 M6S/4 Option 6/12 820 745 870 900
TAL 049 E J6S/4 M6S/4 Option 6/12 950 865 1005 1045
TAL 040 C - L9S/4 - 6/12 12.5 11.5 13.5 14 12.5 11.5 13.5 14
TAL 040 E - L9S/4 - 6/12 17.5 16 18.5 19.5 17.5 16 18.5 19.5
TAL 042 B - L9S/4 Option 6/12 27 24.5 28.5 29.5 27 24.5 28.5 29.5
TAL 044 E * - L9S/4 Option 6/12 125 114 133 138 105 96 111 116
TAL 044 H * - L9S/4 Option 6/12 135 123 143 149 123 112 130 135
TAL 044 J - L9S/4 Option 6/12 150 137 159 165 143 130 152 157
TAL 044 K * - L9S/4 Option 6/12 165 150 175 182 161 147 171 177
TAL 044 L - L9+S/4 Option 6/12 180 164 191 198 180 164 191 198
TAL 044 M - L9+S/4 Option 6/12 185 168 196 204 196 178 208 216
TAL 046 C * - L9S/4 Option 6/12 230 209 244 253 230 209 244 253
TAL 046 D * - L9S/4 Option 6/12 242 220 257 266 250 228 265 275
TAL 046 E - L9S/4 Option 6/12 275 250 292 303 260 237 276 286
TAL 046 F - L9S/4 Option 6/12 300 273 318 330 274 249 290 301
TAL 046 G * - L9S/4 Option 6/12 325 296 345 358 325 296 345 358
TAL 046 H * - L9S/4 Option 6/12 365 332 387 402 365 332 387 402
TAL 0473 A L9+S/4 Option 6/12 393 358 417 432 410 373 435 451
TAL 0473 B * - L9S/4 Option 6/12 455 414 482 501 455 414 482 501
TAL 0473 C * - L9S/4 Option 6/12 500 455 530 550 500 455 530 550
TAL 0473 D * - L9S/4 Option 6/12 539 490 571 593 550 501 583 605
TAL 0473 E - L9+S/4 Option 6/12 600 546 636 660 600 546 636 660
TAL 0473 F - L9+S/4 Option 6/12 625 569 663 688 660 601 700 726
TAL 049 B ** - L9S/4 Option 6 730 664 774 803 710 646 753 781
TAL 049 C ** - L9S/4 Option 6 820 746 869 902 820 746 869 902
TAL 049 D ** - L9S/4 Option 6 910 828 965 1001 910 828 965 1001
TAL 049 E ** - L9S/4 Option 6 935 851 991 1029 1000 910 1060 1100
TAL 046 C J6/4 M6/4 Option 6/12 138 126 146 152
TAL 046 D J6/4 M6/4 Option 6/12 150 137 159 165
TAL 046 E J6/4 M6/4 Option 6/12 165 150 175 182
TAL 046 F J6/4 M6/4 Option 6/12 180 164 191 198
TAL 046 G J6/4 M6/4 Option 6/12 195 177 207 215
TAL 046 H J6/4 M6/4 Option 6/12 210 191 223 231
TAL 044 E - - - 4 - - - -
TAL 044 K - - - 4 - - - -
9 - RECONNECTIONS 60 Hz
Connections
Number of
6 6 12 12 12 6 12
wires
Winding
6S or 6 380 - 480 V 220 - 277 V 380 - 480 V 220 - 277 V 190 - 240 V 220 - 240 V 220 - 240 V
(pages 13 et 14) (pages 13 et 14) (pages 13 et 14) (pages 13 et 14) (pages 13 et 14) (page 17) (page 17)
standard
Winding
8S or 8 380 - 416 V 220 - 240 V 380 - 416 V 220 - 240 V 190 - 208 V 220 - 240 V 220 - 240 V
specific (page 15) (page 15) (page 15) (page 15) (page 15) (consult factory) (consult factory)
(on request)
Winding
9S or 9 600 V 347 V 600 V 347 V - - -
specific (page 16) (page 16) (page 16) (page 16)
(on request)
Winding M or M1 specific, dedicated 1-phase 230 - 240 V (page 18) 115 - 120 V (page 18)
4 wires SE (serie) PA (parallel)
1800 R.P.M. - P.F. 0.8 380 - 416 V 190 - 208 V 220 - 240 V
9.1 - Winding 6S or 6 standard kVA @ 190V, 220V, 380V (1) kVA @ 208V, 240V, 416V (1)
40 °C 27 °C 40 °C 27 °C
Excitation 40 °C cont. St.by St.by 40 °C cont. St.by St.by
TYPE SHUNT AREP+ PMG wires H : 125 K F : 105 K H : 150 K H : 163 K H : 125 K F : 105 K H : 150 K H : 163 K
TAL 040 C J6S/4 M6S/4 - 6/12 12.5 11.5 13.5 14 13.5 12.5 14.5 15
TAL 042 A J6S/4 M6S/4 Option 6/12 29 26.5 30.5 32 31.5 28.5 33.5 34.5
TAL 042 C J6S/4 M6S/4 Option 6/12 33.5 30.5 35.5 37 37 33.5 39 40.5
TAL 042 D J6S/4 M6S/4 Option 6/12 37.5 34 40 41.5 40.5 37 43 44.5
TAL 042 E J6S/4 M6S/4 Option 6/12 41.5 38 44 45.5 45.5 41.5 48 50
TAL 044 D J6S/4 M6S/4 Option 6/12 99 90 105 109 108 98 114 119
TAL 044 E * J6S/4 M6S/4 Option 6/12 124 113 131 136 135 123 143 149
TAL 044 H * J6S/4 M6S/4 Option 6/12 134 122 142 147 146 133 155 161
TAL 044 J J6S/4 M6S/4 Option 6/12 148 135 157 163 163 148 173 179
TAL 044 K * J6S/4 M6S/4 Option 6/12 165 150 175 182 179 163 190 197
TAL 044 L J6S/4 M6S/4 Option 6/12 180 164 191 200 195 177 207 215
TAL 044 M J6S/4 M6S/4 Option 6/12 200 182 212 220 215 196 228 237
TAL 046 C * J6S/4 M6S/4 Option 6/12 226 206 240 250 250 228 265 275
TAL 046 D * J6S/4 M6S/4 Option 6/12 245 223 260 270 265 241 281 292
TAL 046 E * J6S/4 M6S/4 Option 6/12 275 250 292 303 300 273 318 330
TAL 046 F * J6S/4 M6S/4 Option 6/12 290 264 307 320 315 287 334 347
TAL 046 G J6S/4 M6S/4 Option 6/12 315 287 334 347 345 314 366 380
TAL 046 H J6S/4 M6S/4 Option 6/12 345 314 366 380 375 341 398 413
TAL 0473 A J6S/4 M6S/4 Option 6/12 450 410 475 495 480 435 510 530
TAL 0473 B J6S/4 M6S/4 Option 6/12 475 430 505 525 510 465 540 560
TAL 0473 C J6S/4 M6S/4 Option 6/12 520 475 550 570 555 505 590 610
TAL 0473 D J6S/4 M6S/4 Option 6/12 560 510 595 615 610 555 645 670
TAL 0473 E * J6S/4 M6S/4 Option 6/12 600 545 635 660 660 600 700 725
TAL 0473 F * J6S/4 M6S/4 Option 6/12 650 590 690 720 715 650 760 785
TAL 049 B J6S/4 M6S/4 Option 6/12 725 660 770 800 795 725 845 875
TAL 049 C J6S/4 M6S/4 Option 6/12 815 740 865 895 890 810 945 980
TAL 049 D J6S/4 M6S/4 Option 6/12 905 825 960 1000 990 900 1050 1090
TAL 049 E J6S/4 M6S/4 Option 6/12 990 900 1050 1089 1083 985 1150 1192
1800 R.P.M. - P.F. 0.8 440 - 480 V 220 - 240 V 254 - 277 V
9.2 - Winding 6S or 6 standard kVA @ 220V, 254V, 440V kVA @ 240V, 277V, 480V
40 °C 27 °C 40 °C 27 °C
Excitation 40 °C cont. St.by St.by 40 °C cont. St.by St.by
TYPE SHUNT AREP+ PMG wires H : 125 K F : 105 K H : 150 K H : 163 K H : 125 K F : 105 K H : 150 K H : 163 K
TAL 040 B J6S/4 M6S/4 - 6/12 11.5 10.5 12 12.5 12.5 11.5 13.5 14
TAL 042 A J6S/4 M6S/4 Option 6/12 31.5 28.5 33.5 34.5 31.5 28.5 33.5 34.5
TAL 042 C J6S/4 M6S/4 Option 6/12 39 35.5 41.5 43 40 36.5 42.5 44
TAL 042 D J6S/4 M6S/4 Option 6/12 43 39 45.5 47.5 44 40 46.5 48.5
TAL 044 B * J6S/4 M6S/4 Option 6/12 92 84 98 101 100 91 106 110
TAL 044 C J6S/4 M6S/4 Option 6/12 103 94 109 113 113 103 120 124
TAL 044 D J6S/4 M6S/4 Option 6/12 115 105 122 127 125 114 133 138
TAL 044 E * J6S/4 M6S/4 Option 6/12 143 130 152 157 156 142 165 172
TAL 044 H * J6S/4 M6S/4 Option 6/12 155 141 164 171 169 154 179 186
TAL 044 J J6S/4 M6S/4 Option 6/12 172 157 182 189 188 171 199 207
TAL 044 K * J6S/4 M6S/4 Option 6/12 189 172 200 208 206 187 218 227
TAL 044 L J6S/4 M6S/4 Option 6/12 210 191 223 231 225 205 239 250
TAL 044 M J6S/4 M6S/4 Option 6/12 230 209 244 253 250 228 265 275
TAL 046 C * J6S/4 M6S/4 Option 6/12 262 238 278 288 288 262 305 316
TAL 046 D * J6S/4 M6S/4 Option 6/12 280 255 297 308 313 285 332 344
TAL 046 E * J6S/4 M6S/4 Option 6/12 315 287 334 347 344 313 365 378
TAL 046 F * J6S/4 M6S/4 Option 6/12 340 309 360 374 360 328 382 400
TAL 046 G J6S/4 M6S/4 Option 6/12 365 332 387 402 406 369 430 447
TAL 046 H J6S/4 M6S/4 Option 6/12 400 364 424 440 438 399 464 480
TAL 0473 A J6S/4 M6S/4 Option 6/12 500 455 530 550 510 465 540 560
TAL 0473 B J6S/4 M6S/4 Option 6/12 530 480 560 585 570 520 605 625
TAL 0473 C J6S/4 M6S/4 Option 6/12 590 535 625 650 625 570 665 690
TAL 0473 D J6S/4 M6S/4 Option 6/12 630 575 670 695 690 630 730 750
TAL 0473 E * J6S/4 M6S/4 Option 6/12 685 625 725 755 750 685 795 825
TAL 0473 F * J6S/4 M6S/4 Option 6/12 755 685 800 830 825 750 875 910
TAL 049 B J6S/4 M6S/4 Option 6/12 840 765 890 925 915 835 970 1005
TAL 049 C J6S/4 M6S/4 Option 6/12 940 855 995 1040 1025 935 1085 1130
TAL 049 D J6S/4 M6S/4 Option 6/12 1045 950 1110 1155 1140 1035 1210 1255
TAL 049 E J6S/4 M6S/4 Option 6/12 1146 1045 1215 1260 1250 1140 1325 1375
1800 R.P.M. - P.F. 0.8 380 - 416 V 190 - 208 V 220 - 240 V
9.3 - Winding 8S or 8 specific kVA @ 190V, 220V, 380V kVA @ 208V, 240V, 416V
40 °C 27 °C 40 °C 27 °C
Excitation 40 °C cont. St.by St.by 40 °C cont. St.by St.by
TYPE SHUNT AREP+ PMG wires H : 125 K F : 105 K H : 150 K H : 163 K H : 125 K F : 105 K H : 150 K H : 163 K
TAL 040 B J8S/4 M8S/4 - 6/12 11.5 10.5 12 12.5 12.5 11.5 13.5 14
TAL 042 A J8S/4 M8S/4 Option 6/12 29 26.5 30.5 32 31.5 28.5 33.5 34.5
TAL 042 C J8S/4 M8S/4 Option 6/12 36.5 33 38.5 40 40 36.5 42.5 44
TAL 042 D J8S/4 M8S/4 Option 6/12 40 36.5 42.5 44 44 40 46.5 48.5
TAL 044 B * J8S/4 M8S/4 Option 6/12 92 84 98 101 100 91 106 110
TAL 044 C * J8S/4 M8S/4 Option 6/12 103 94 109 113 113 103 120 124
TAL 044 D * J8S/4 M8S/4 Option 6/12 115 105 122 127 125 114 133 138
TAL 044 E J8S/4 M8S/4 Option 6/12 143 130 152 157 156 142 165 172
TAL 044 H J8S/4 M8S/4 Option 6/12 154 140 163 169 169 154 179 186
TAL 044 J * J8S/4 M8S/4 Option 6/12 170 155 180 187 186 169 197 205
TAL 044 K J8S/4 M8S/4 Option 6/12 189 172 200 208 206 187 218 227
TAL 044 L * J8S/4 M8S/4 Option 6/12 210 191 223 231 225 205 239 248
TAL 044 M * J8S/4 M8S/4 Option 6/12 228 207 242 251 245 223 260 270
TAL 046 C J8S/4 M8S/4 Option 6/12 262 238 278 288 288 262 305 317
TAL 046 D J8S/4 M8S/4 Option 6/12 268 244 284 295 295 268 313 325
TAL 046 E J8S/4 M8S/4 Option 6/12 315 287 334 347 344 313 365 378
TAL 046 F J8S/4 M8S/4 Option 6/12 340 309 360 374 354 322 375 389
TAL 046 G * J8TS/4 M8TS/4 Option 6/12 365 332 387 402 - - - -
TAL 046 H * J8TS/4 M8TS/4 Option 6/12 397 361 421 437 - - - -
TAL 0473 A J8S/4 M8S/4 Option 6 494 450 524 543 510 565 541 561
TAL 0473 E ** J8S/4 M8S/4 Option 6 685 623 726 754 690 628 731 759
TAL 0473 F ** J8S/4 M8S/4 Option 6 754 686 799 829 815 742 864 897
TAL 042 B J6/4 M6/4 Option 6/12 19.2 17.5 20.5 21.1
TAL 044 L J6/4 M6/4 Option 6/12 113 102 119 124
TAL 044 M J6/4 M6/4 Option 6/12 125 114 133 136
TAL 046 C J6/4 M6/4 Option 6/12 152 138 161 167
TAL 046 D J6/4 M6/4 Option 6/12 165 150 175 182
TAL 046 E J6/4 M6/4 Option 6/12 182 166 193 200
TAL 046 F J6/4 M6/4 Option 6/12 200 182 212 220
TAL 046 G J6/4 M6/4 Option 6/12 215 196 228 237
TAL 046 H J6/4 M6/4 Option 6/12 231 210 245 254
TAL 044 J - - - 4 - - - -
© 2024 Moteurs Leroy-Somer SAS. The information contained in this brochure is for guidance only and
does not form part of any contract. The accuracy cannot be guaranteed as Moteurs Leroy-Somer SAS
have an ongoing process of development and reserve the right to change the specification of their products
without notice.
Moteurs Leroy-Somer SAS. Headquarters: Bd Marcellin Leroy, CS 10015, 16915 Angoulême Cedex 9,
France. Share Capital: 32,239,235 €, RCS Angoulême 338 567 258.
5706 en - 2024.02 / p