Learning Unit 12 - Vapour Compression Cycle and Refrigeration Load Calculation
Learning Unit 12 - Vapour Compression Cycle and Refrigeration Load Calculation
STUDY UNIT 12
VAPOUR-COMPRESSION CYCLE
• analyse and perform cyclic calculations for the Carnot refrigeration cycle
• state the difficulties experienced with the Carnot refrigeration cycle
• analyse and perform cyclic calculations for vapour-compression refrigeration systems
• apply a pressure-enthalpy chart in the analysis of the performance of a vapour-
compression refrigeration system
• perform various cyclic calculations for different types of refrigerants
12.2 Introduction
In this section we also define some of the common terms used in industrial refrigeration
systems to help students to get a better understanding of the content:
• A heat pump (HP) is a refrigerating system used to transfer heat into a space or
substance. The term “heat pump” is used because energy is transferred against the
natural temperature gradient from a low temperature to a higher one.
• A heat engine is a system that converts heat or thermal energy to mechanical energy
that can be used to do mechanical work.
1
Applied Thermodynamics and Heat Transfer THT3701
The efficiency of the Carnot cycle cannot be exceeded when operating between two given
temperatures. The Carnot cycle operating as a heat engine is familiar from the study of
thermodynamics. The Carnot heat engine receives energy at a high level of temperature,
converts a portion of the energy into work and discharges the remainder to a heat sink at a low
level of temperature. The Carnot cycle for refrigeration performs the reverse effect of the heat
engine, because it transfers energy from a low level of temperature, requires the addition of
external work and discharges energy to a high level of temperature.
The performances of the refrigerator and the HP are defined by what is known as the
coefficient of performance (COP). The COP is an index of performance of a thermodynamic
cycle. Because the COP can be greater than 1, it is used instead of thermal efficiency.
While the Carnot cycle offers a high coefficient of performance, practical
considerations require certain revisions, which eventually transform it into the actual vapour
cycle.
Figure 12.1 shows a reversed heat engine cycle, where a quantity of heat, Q2, is
transferred from a cold source at temperature T2. The quantity of heat, Q2, is also called the
refrigerating effect.
2
Applied Thermodynamics and Heat Transfer THT3701
Q2 is the important quantity for a refrigerator; for a heat pump, it is Q1. The work input, W,
determines the running cost. The quantity of heat, Q1, is called the heating effect. It should be
noted that there is no difference in operation between a refrigerator and a heat pump.
Therefore,
and (12-2)
. (12-3)
The best COP will be given by a cycle that is a Carnot cycle. A Carnot cycle using a wet vapour
as the working substance is shown diagrammatically in figure 12.2(a). The most widely used
refrigerators and heat pumps are those that use a liquefiable vapour as the working substance
or refrigerant.
3
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.2 Reversed heat engine system operating on the Carnot cycle
The cycle is indicated on the T-s (temperature-entropy) diagram of figure 12.2(b). The cycle
events are as follows:
1–2. Wet vapour at state 1 enters the compressor and is compressed isentropically to state 2.
2–3. The vapour enters the condenser at state 2 and is condensed to constant pressure (isobaric)
and temperature (isothermal) to state 3, when it is completely liquid. Q1 is the heat rejected
during this process.
3–4. The liquid is expanded isentropically behind the piston doing work.
4–1. The refrigerant enters the evaporator where heat is extracted isothermally.
Then, from the T-s diagram (figure 2.2(b)) since the areas are proportional to the heat
quantities:
(12-4)
(12-5)
(12-6)
(12-7)
(12-8)
4
Applied Thermodynamics and Heat Transfer THT3701
It is important to note that the COPref and COPhp decrease with increased temperature difference
(T1 – T2).
Question 12.1
What is the important requirement of the Carnot cycle?
Question 12.2
Why is the Carnot cycle impractical?
Example 12.1
A refrigerator has working temperatures in the evaporator and condenser coils of –30 °C and
32 °C respectively. What is the maximum COP possible? If the actual refrigerator has a COP
of 0.75 of the maximum, calculate the required power input for a refrigerating effect of 5 kW.
Solution 12.1
T1 = 32+273 = 305 K and T2 = -30+273 = 243 K
Example 12.2
The pressure in the evaporator of an ammonia refrigerator is 1.902 bar and the pressure in the
condenser is 12.37 bar. Analyse the thermal performance if the Carnot cycle is used.
Solution 12.2
From the property table of ammonia, the evaporation temperature at the pressure of 1.902 bar
is –20 °C and the condensing temperature at 12.37 bar is 32 °C.
5
Applied Thermodynamics and Heat Transfer THT3701
Therefore:
6
Applied Thermodynamics and Heat Transfer THT3701
Cycle Reversed
Carnot cycle
Evaporating temperature (°C) –20
Condensing temperature (°C) 32
Refrigerating effect (kJ/kg) 941.4
Heat pumping effect (kJ/kg) 1134.86
Compression work input (kJ/kg) 217.32
COPref 4.87
COPhp 5.87
Mass flow rate/unit capacity (refrigeration) 1.0
(g/s)
Mass flow rate/unit capacity (heat pump) (g/s) 0.88
Discharge temperature (°C) 32.0
The evaporation and condensation processes take place when the refrigerant is receiving or
rejecting the specific enthalpy of vaporisation. These processes are constant temperature and
constant pressure processes. A vapour compression cycle is one in which these two processes
correspond to those of the reversed Carnot cycle for a vapour. This enables the temperature
range to be kept low. Certain practical considerations have led to modifications to the ideal
cycle discussed in section 2.3.
7
Applied Thermodynamics and Heat Transfer THT3701
• The refrigerating effect, Q2 = T2 (s1 – s4) = h1 – h4, is reduced by using a throttle valve
instead of the expansion cylinder.
Figure 12.4 T-s diagram for a reversed cycle with superheated vapour in the compressor
• Now the rejection of heat in the condenser cannot be carried out at a constant
temperature.
Question 12.3
The pressure in the evaporator of an ammonia refrigerator is 1.902 bar and the pressure in the
condenser is 12.37 bar. Analyse the thermal performance if the standard cycle is used.
(Hint: Use a similar method as in example 2.)
The summary of the comparison of performance of the two cycles is given in table 12.2.
8
Applied Thermodynamics and Heat Transfer THT3701
Table 12.2 Comparison of the thermal performance analysis between the reversed Carnot cycle and the standard
refrigeration cycle
Figure 12.5 T-s diagram for a reversed cycle with subcooling in the condenser
9
Applied Thermodynamics and Heat Transfer THT3701
• Furthermore, the volume flow rate ( is the parameter that determines the size of the
compressor and other cycle components, and it can be calculated from
.
Question 12.4
What are the benefits of subcooling and superheating in a refrigeration cycle?
Question 12.5
The pressure in the evaporator of an ammonia refrigerator is 1.902 bar and the pressure in the
condenser is 12.37 bar. Analyse the thermal performance if the refrigeration cycle with a
superheating degree of 5 °C and a subcooling degree of 3 °C is used.
Add the results of this analysis to those given in table1 2.2 and discuss.
Here refrigeration cycles are presented on a pressure-enthalpy (p-h) diagram instead of a T-s
diagram. The pressure-enthalpy diagram is more convenient for refrigeration cycles since the
enthalpies required for calculation can be read off directly. The essential features of the p-h
diagram are shown in figure 12.7. A typical refrigeration cycle is shown on a p-h diagram in
figure 2.8.
10
Applied Thermodynamics and Heat Transfer THT3701
11
Applied Thermodynamics and Heat Transfer THT3701
. (12-12)
An efficient refrigeration system has a low value of power per kilowatt of refrigeration,
but a high COP.
Figure 12.9 (a) The standard vapour-compression cycle on the pressure-enthalpy diagram, (b) flow diagram
12
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.10 shows how a standard cycle (red line) and subcooling and superheating (purple
line) can be represented on a p-h chart. (A refrigerant 134a or R134a chart is used.)
13
Applied Thermodynamics and Heat Transfer THT3701
Example 12.3
A vapour-compression plant using R134a operates with an evaporator pressure of 293 kPa and
a condenser saturation pressure of 1130 kPa. The vapour entering the compressor is saturated
at 293 kPa and the liquid leaving the condenser is saturated at 1130 kPa. The compressor
discharge temperature is 64 °C. Analyse the thermal performance of the refrigeration cycle.
Solution 12.3
State 1
Given:
pressure = 293 kPa
saturated vapour
Then from the chart:
temp = 0 °C
spec vol = 0,069 m³/kg
enthalpy = 396,5 kJ/kg
entropy = 1,72 kJ/kg.K
14
Applied Thermodynamics and Heat Transfer THT3701
State 2
Given:
pressure = 1130 kPa
dis temp = 64 °C
Then from the chart:
spec vol = 0,020 m³/kg
enthalpy = 443 kJ/kg
entropy = 1,78 kJ/kg.K
State 3
Given:
pressure = 1130 kPa
saturated liquid
Then from the chart:
cond temp = 44 °C
enthalpy = 261,8 kJ/kg
density = 1130 kg/m³ (spec vol = 0,000885 m³/kg)
State 4
Given:
pressure = 293 kPa
expansion: isentropic
h4 = h3 = 261,8 kJ/kg
The analysis
This fulfils the first law of thermodynamics, which states that in order to bring refrigerant back
to an expansion device in the same condition, all energy and heat input must be removed.
15
Applied Thermodynamics and Heat Transfer THT3701
Question 12.6
A cold storage plant is used to cool 5000 litres of milk per hour from 30 °C to 4 °C, and the
heat leakage into the plant is estimated to be 40 kW. The refrigerant used is ammonia and the
temperature required in the evaporator is –6 °C. The compressor delivery pressure is 10.34 bar
and the condenser liquid is undercooled to 24 °C before throttling. The plant has a brine
circulation system and the rise in temperature of the brine is 5 K. Assume that the vapour is
dry saturated on leaving the evaporator and that the compression process is isentropic.
Calculate:
(1) the power input required taking the mechanical efficiency of the compressor as 80%
(2) the rate at which the brine must be circulated in litres per second
For milk, specific heat is 3.77 kJ/kg K and density is 1030kg/m3.
For brine, specific heat is 2.93 kJ/kg K and density is 1190 kg/m3.
Compared with the standard cycle, the actual cycle suffers from insufficiencies. Some
comparisons are drawn by superimposing the actual cycle on the pressure-enthalpy diagram of
the standard cycle as in figure 12.11.
The essential differences appear in the pressure drops in the condenser and evaporator,
in the subcooling of liquid and in the superheating of the vapour.
16
Applied Thermodynamics and Heat Transfer THT3701
(1) The standard cycle assumes no pressure drop in the condenser and evaporator.
However, the pressure of the refrigerant drops due to friction. As a result, the
compression process 1–2 would require more work than in the standard cycle.
(2) Subcooling of the liquid is a normal occurrence in the actual cycle.
(3) Superheating often occurs in the actual cycle (but not always).
(4) Lastly, the compression is no longer isentropic in the actual cycle.
12.7 Summary
Of the three basic refrigeration methods (vapour compression, absorption and thermoelectric)
the most common method in the RAC industry is the vapour compression, with the absorption
method a distant second choice. The following parameters play an important role in the
analysis of a vapour-compression refrigeration cycle:
Refrigerating effect
This important quantity represents the amount of heat supplied to the system from the
surroundings or heat extracted at low temperature. It is given by
where
= specific enthalpy at compressor suction, and
= specific enthalpy at evaporator inlet.
Work input
The work input or work supplied is important because it is the quantity that represents the
amount of energy to be consumed. It is given by
where
= specific enthalpy at compressor exhaust.
Or, .
17
Applied Thermodynamics and Heat Transfer THT3701
The refrigeration capacity is the amount of heat that must be transferred per unit time from the
cold chamber. Hence, the mass flow rate of the refrigerant per kilowatt of refrigeration capacity
is given by
where
= the specific volume of the refrigerant at the compressor suction.
Discharge temperature
The discharge temperature of the compressor is represented by the temperature at the outlet of
the compressor.
12.8 Problems
Problem 12.1
18
Applied Thermodynamics and Heat Transfer THT3701
Problem 12.2
If in a standard vapour-compression cycle using refrigerant 22 the evaporating temperature is
–5 °C and the condensing temperature is 30 °C, sketch the cycle on pressure enthalpy
coordinates and calculate the following:
(i) the work of compression
(ii) the refrigerating effect
(iii) the heat rejected in the condenser in kJ/kg
(iv) COP
Answer: 6.47
Problem 12.3
An ideal refrigeration cycle operates with R134a as a working fluid. The temperature of the
refrigerant in the condenser and evaporator are 40 °C and –20 °C respectively. The mass flow
rate of the refrigerant is 0.1 kg/s. Determine the cooling capacity and the COP of the plant.
Problem 12.4
The pressure in the evaporator of an R134a refrigerator is 1.902 bar and the pressure in the
condenser is 12.37 bar. Analyse the thermal performance if the Carnot cycle is used.
Problem 12.5
The pressure in the evaporator of an R134a refrigerator is 1.902 bar and the pressure in the
condenser is 12.37 bar. Analyse the thermal performance if the standard cycle (see figure 12.4)
is used.
Problem 12.6
A refrigeration system using R22 is to have a refrigeration capacity of 80 kW. The cycle is a
standard vapour compression in which the evaporating temperature is –8 °C and the condensing
temperature 42 °C.
(i) Determine the volume flow rate of the refrigerant at the inlet to the compressor.
(ii) Calculate the power required by the compressor.
(iii) At the entrance of the evaporator, what is the fraction of vapour in the mixture expressed
both on a mass basis and volume basis?
Answers: 0.036 m3/s; 19.5 kW; 0.1558 kg/s; 0.0095 m3/s
Problem 12.7
A refrigeration R22 vapour-compression system includes a liquid to suction heat exchanger in
the system. The heat exchanger warms saturated vapour coming from the evaporator from –10
°C to 5 °C with liquid that comes from the condenser at 30 °C. The compressions are isentropic
in both cases listed below.
19
Applied Thermodynamics and Heat Transfer THT3701
(i) Calculate the coefficient of performance of the system without the heat exchanger, but
with the condensing temperature of 30 °C and an evaporating temperature of –10 °C.
(ii) Calculate the coefficient of performance of the system with the heat exchanger.
(iii) If the compressor is capable of pumping 12.0 ℓ/s measured at the compressor suction line,
what is the capacity of the system without the heat exchanger?
(iv) With the same compressor capacity as in (iii), what is the refrigeration capacity of the
system with the heat exchanger?
Answers: COPref = 5.43; COPhp = 6.43; COPref = 9.68; COPhp = 10.68; 30.25 kW;
50.68 kW
Problem 12.8
A standard vapour-compression cycle developing 50 kW of refrigeration using refrigerant 22
operates with a condensing temperature of 35 °C and an evaporating temperature of –10 °C.
Calculate:
(i) refrigerating effect in kJ/kg
(ii) circulation rate of refrigerant in kg/s
(iii) power required by the compressor in kW
(iv) coefficient of performance
(v) volume flow rate measured at the compressor suction
(vi) power per kW of refrigeration (i.e. kW/kW)
(vii) compressor discharge temperature
Answers: 158.5 kJ/kg; 0.315 kg/s; 10.6 kW; 4.72; 0.0206 m3/s; 0.212 kW/kW; 57 °C
20
Applied Thermodynamics and Heat Transfer THT3701
MULTIPRESSURE SYSTEMS
12.10 Introduction
A refrigeration system that has two or more low-side pressures is known as a multi-pressure
system or a compound vapour-compression system. The low-side pressure is the pressure of
the refrigerant between the expansion device and the compressor intake.
In situations where a high condensing temperature is required and/or a very low
evaporating temperature is needed, a single-stage compression system would bring about heavy
operating losses. To overcome the losses, it would be advantageous to employ compound or
multistage compression, which entails that compression is carried out in a series of cylinders.
First we discuss the two functions integral to multi-pressure systems, namely the removal of
flash gas and intercooling.
Question 12.7
What do you understand by compound or multistage vapour-compression systems?
Question 12.8
Discuss the limitations of single-stage vapour-compression refrigeration systems.
Flash gas is refrigerant in gas form that is produced naturally when the condensed liquid is
subjected to boiling. The presence of flash gas in the throttling process reduces the efficiency
of the refrigeration cycle. It can also lead to improper working of the expansion system, and it
can increase superheating at the evaporator.
A saving in the power requirement of a refrigeration system results if the flash gas that
develops is removed and compressed before complete expansion. When saturated liquid
expands through an expansion valve, flash gas gradually increases. The equipment used to
21
Applied Thermodynamics and Heat Transfer THT3701
achieve the separation of the liquid from the vapour is called a flash tank or flash chamber (see
figure 12.12).
In the flash tank, part of the expansion is performed, liquid is separated from the vapour,
expansion of the liquid is continued (line 4) and vapour is recompressed without further
expansion (line 6). The end-point of part expansion (which should have been point 2) is
interrupted at point 3 by the separation process.
Figure 12.12 Flash tank for removing flash gas during expansion process
12.12 Intercooling
During multistage compression, the gas is cooled at constant pressure before it enters the next
cylinder. This cooling process between the stages is called intercooling. Intercooling between
stages reduces the work of compression per kilogram of vapour. In two-stage compression, an
intercooling from point 2 to point 4 on the pressure-displacement diagram in figure 12.13 saves
work. If the processes are reversible, the saving is represented by the shaded area.
22
Applied Thermodynamics and Heat Transfer THT3701
Examining the equation for work in a reversible polytropic compression of a perfect gas is
another way of showing that the work of compression increases when the process moves out
farther into the superheat region:
(3-1)
where
23
Applied Thermodynamics and Heat Transfer THT3701
In figure 12.15(b), discharge gas from the low-stage compressor bubbles through the
cold liquid in the intercooler and leaves at point 4 as saturated vapour.
Figure 12.15 Intercooler with (a) a water-cooled heat exchanger and (b) liquid refrigerant
Example 12.4
Calculate the power needed to compress 1.2 kg/s of ammonia from saturated vapour at 80 kPa
to 1000 kPa by (a) single-stage compression and (b) two-stage compression with intercooling
by liquid refrigerant at 300 kPa.
Solution 12.4
24
Applied Thermodynamics and Heat Transfer THT3701
Table 12.3 shows a summary of the calculations with the subscripts referring to state points in
figure 12.14.
The high-stage compressor in the intercooled system must compress1.2 kg/s plus the flow rate
of refrigerant that evaporates to de-superheat the gas at point 2. The flow rate of ammonia
compressed in the high stage can be calculated by making a heat and a mass balance about the
intercooler, as shown in figure 12.16.
Heat balance:
Mass balance:
Solving gives
Intercooling the ammonia with liquid refrigerant reduces the power required from 468 to
453.2 kW.
25
Applied Thermodynamics and Heat Transfer THT3701
Example 12.5
Compare a compression of 3.5 kg/s of refrigerant 22 (with that of ammonia) from saturated
vapour at 100 kPa to a condensing pressure of 1000 kPa by (a) single-stage compression and
(b) two-stage compression with intercooling by liquid refrigerant at 300 kPa.
Solution 12.5
Table 3.2 shows a summary of the calculations with the subscripts referring to state points in
figure 3.3.
For refrigerant 22, intercooling with liquid refrigerant midway during the compression is
ineffective. In an ammonia system, there is an optimum pressure at which the intercooling
should take place. In the compression of air by cooling water or by rejecting heat to ambient,
the intermediate pressure for minimum total power is
where
The development of the equation provides an approximate guideline for the optimal
intermediate pressure.
26
Applied Thermodynamics and Heat Transfer THT3701
With one compressor and one evaporator, the flash chamber may function as shown in
figure 12.17.
Figure 12.17 System with one compressor and one evaporator using a flash tank
A pressure-reducing valve throttles the flash gas from the intermediate pressure to the
evaporator pressure because there is high suction pressure compressor available.
Question 12.9
Briefly explain why the system shown in figure 12.17 is not frequently used.
Figure 3.7 shows the schematic arrangement of the different components of a two-stage
compression with liquid intercooler, along with p-h diagram showing the processes involved.
The main components of the system are an evaporator, a low-pressure compressor, a liquid
intercooler, a high-pressure compressor, a condenser and an expansion valve.
27
Applied Thermodynamics and Heat Transfer THT3701
Question 12.10
Describe in your own words the sequence of operation (1–2; 2–3; 3–4; 4–5; 5–6–1) for the
system shown in figure 12.18.
The system which has two evaporators operating at different temperatures is common in
refrigeration. Low-temperature refrigeration may be required for a process and another may be
used to provide air conditioning for some offices. A dairy cooling milk and manufacturing ice
cream is another example of such a system. A frozen-food plant may require one evaporator at
–40 °C to quick-freeze the food and the other at –25 °C to hold the food after it is frozen. One
method of arrangement of this type of system is shown in figure 12.19(a). Figure 12.19(b)
shows the corresponding p-h diagram.
Figure 12.19
(a) One compressor and two evaporators with the air conditioning evaporator at –10 °C
(b) Pressure-enthalpy diagram for system of (a)
28
Applied Thermodynamics and Heat Transfer THT3701
Question 12.11
What are the drawbacks of the system in figure 12.19(a)?
To overcome the drawbacks of the system in figure 12.19(a), a revision may be made
as shown in figure 12.20(a). Figure 12.20(b) shows the corresponding p-h diagram. A pressure-
reducing valve installed after the high-temperature evaporator regulates the pressure and
maintains the temperature in the air conditioning evaporator.
Figure 12.20
(a) One compressor and two evaporators with a pressure-reducing valve to maintain a high temperature in the air
conditioning evaporator
(b) Pressure-enthalpy diagram for a system of (a)
12.16 Two compressors and one evaporator with intercooler and flash tank
This system is often the ideal way to serve one low-temperature evaporator. It requires less
power than a system with a single compressor.
Example 12.6
Calculate the power required by the two compressors in an ammonia system that serves a
250 kW evaporator at –25 °C. The system uses two-stage compression with intercooling and
removal of flash gas. The condensing temperature is 35 °C.
Solution 12.6
29
Applied Thermodynamics and Heat Transfer THT3701
First sketch the schematic diagram of the system (see figure 12.21(a)) and the corresponding
pressure-enthalpy diagram (see figure 12.21(b)). The functions of the intercooler and flash tank
are combined in one vessel.
The intermediate pressure for optimum economy can be calculated from
where
The enthalpies at all points are determined from the table of properties of liquid and
saturated vapour ammonia and the p-h diagram of superheated ammonia.
h1 = hg at –25 °C = 1430 kJ/kg
h2 = h at 453 kPa after isentropic compression = 1573
h3 = hg at 453 kPa = 1463
h4 = h at 1352 kPa after isentropic compression = 1620
h5 = hf at 35 °C = 366 h6 = h5 = 366
h7 = hf at 453 = 202 h8 = h7 = 202
The mass rates of flow through the compressors can be calculated by means of heat and
mass balances.
Heat balance about the evaporator:
30
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.21
(a) Two compressors and one evaporator in example 12.6
(b) Pressure-enthalpy diagram for system in (a)
and
Low-stage power:
High-stage power:
31
Applied Thermodynamics and Heat Transfer THT3701
Total power =
Power =
The two-stage compressor system requires 12% less power than the single-compressor
system.
Figure 12.22 Pressure-enthalpy diagram for single-compressor system for conditions in example 12.6
In refrigeration, liquid subcooler (see figure 12.23) is an application often used to decrease the
temperature of the liquid refrigerant to below its boiling temperature or condensing
temperature, hence it increases the performance of the evaporator. It is a device which gives
the same result as flash gas removal. It cools the liquid refrigerant by evaporating a small
fraction of the liquid.
32
Applied Thermodynamics and Heat Transfer THT3701
Question 12.12
Explain the differences in the thermal performance of flash gas removal and a liquid subcooler.
Figure 12.24 shows the schematic arrangement of the different components of a two-
stage compression with water intercooler and liquid subcooler, along with a p-h diagram of the
processes involved.
33
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.25 shows the schematic arrangement of the different components of a two-stage
compression with water intercooler, liquid subcooler and liquid flash chamber, along with a p-
h diagram of the processes involved.
34
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.25 Two-stage compression with intercooler, liquid subcooler and liquid flash chamber
Figure 12.26 shows the schematic arrangement of the different components of a two-stage
compression with water intercooler, liquid subcooler and flash intercooler, along with a p-h
diagram of the processes involved.
35
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.26 Two-stage compression with water intercooler, liquid subcooler and flash intercooler
Activity 12.1
Thoroughly study pages 202, 204, 206 and 208, as well as examples 6.1 to 6.7, in the prescribed
book (Kumar 2017). These relate to figures 12.18, 12.24, 12.25 and 12.26 in this study unit.
36
Applied Thermodynamics and Heat Transfer THT3701
12.20 Two compressors and two evaporators with intercooling and flash gas
removal
Process and chemical industries often require different temperatures of refrigeration in various
sections of the plant. Evaporators at two different temperatures can be handled efficiently by a
two-stage system which employs intercooling and the removal of flash gas.
Example 12.7
In an ammonia system, one evaporator is to provide 180 kW of refrigeration at –30 °C and
another evaporator is to provide 200 kW at 5 °C. The system uses two-stage compression with
intercooling and is arranged as in figure 12.27(a). The condensing temperature is 40 °C.
Calculate the power required for the compressors.
37
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.27
(a) Two compressors and two evaporators operating with intercooling and flash gas removal
(b) The pressure-enthalpy diagram corresponding to the system in (a)
Solution 12.7
Sketch the pressure-enthalpy diagram of the cycle in figure 12.27(b). The discharge pressure
of the low-stage compressor and the suction pressure of the high-stage compressor are the same
as the pressure in the 5 °C evaporator.
Next, determine the enthalpies at the state points.
The simplest way to calculate the mass rate of flow handled by the high-stage compressor is to
make a heat and mass balance about both the high-temperature evaporator and the intercooler,
as shown in figure 12.28.
38
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.28 Heat and mass balance about high-temperature evaporator and intercooler in example 4
Heat balance:
Mass balance:
Therefore
Combining gives
Solving leads to
39
Applied Thermodynamics and Heat Transfer THT3701
If one compressor served each evaporator in a single-stage compression, the power requirement
of the compressors would have been as follows:
Flow through low-temperature evaporator:
The combined power for the compressors serving the evaporators individually is greater than
for the combined system shown in figure 12.27. All of the saving is attributable to the flash gas
removal and intercooling of refrigerant serving the low-temperature evaporator.
In the systems where there are two stages of compression, the flow diagrams have shown two
separate compressors. However, there are single compressors available that accept both high
and low suction pressures; these can be used in place of the two compressors shown in figure
12.27.
40
Applied Thermodynamics and Heat Transfer THT3701
12.23 Summary
• The removal of and recompression of flash gas before complete expansion decreases
the power requirement by the compressor in multipressure systems.
• Intercooling decreases the power requirement when ammonia is the refrigerant.
• Intercooling decreases the discharge temperature of the refrigerant from the high-stage
compressor.
• A decision to use multiple-stage systems should essentially be based on an economic
analysis.
• The savings in the use of energy must be compared with the cost of additional
equipment.
• Other factors, such as type of refrigerant, the type of compressor and the system’s size,
also have an influence.
41
Applied Thermodynamics and Heat Transfer THT3701
PHASE 1: Identify the refrigeration cycle for the project (cycle and working conditions).
12.25 Problems
In the following problems, liquid leaves the condensers saturated, vapour leaves the
evaporators saturated and compressions are isentropic.
12.9 A liquid subcooler receives liquid ammonia at 30 °C and subcools 0.6 kg/s to 5 °C.
Saturated vapour leaves the subcooler for the high-stage compressor at –1 °C. Calculate
the flow rate of ammonia that evaporates to cool the liquid.
Answer: 0.0575 kg/s
42
Applied Thermodynamics and Heat Transfer THT3701
43
Applied Thermodynamics and Heat Transfer THT3701
12.12 A two-stage ammonia system using flash gas removal and intercooling operates on the
cycle shown in figure 12.27(a). The condensing temperature is 35 °C. The saturation
temperature of the intermediate-temperature evaporator is 0 °C and its capacity is 150 kW. The
saturation temperature of the low-temperature evaporator is –40 °C and its capacity is 250 kW.
What is the rate of refrigerant compressed by the high-stage compressor?
Answer: 0.411 kg/s
12.14 A two-stage refrigerant 22 system that uses flash gas removal and intercooling serves a
single low-temperature evaporator as shown in figure 12.21(a). The evaporating temperature
is –40 °C and the condensing temperature is 30 °C. The pumping capacity of the high- and
low-stage compressors is shown in figure 12.32. What is
(a) the refrigerating capacity of the system?
(b) the intermediate pressure?
Answers: (a) 318 kW; (b) 390 kPa
44
Applied Thermodynamics and Heat Transfer THT3701
Figure 12.32 Pumping capacity of low- and high-stage compressors of the system in problem 12.14
(The suction pressure of the low-stage compressor is 105 kPa [–40 °C] and the discharge pressure of the high-
stage compressor is 1192 kPa [30 °C].)
12.15 The following data refer to a compound refrigeration system employing water and flash
intercoolers. The system has a load of 20 tons of refrigeration in the evaporator and uses
ammonia as refrigerant. The saturation temperatures in the evaporator and condenser are –
40 °C and 32 °C respectively, and the intercooler pressure is adjusted for minimum power
consumption. Assuming no superheating, no subcooling, isentropic compression and 75%
volumetric efficiency at each stage of compression.
Calculate:
(a) mass circulation of ammonia through the condenser
(b) piston displacements for each cylinder
(c) power required to drive the unit
(d) coefficient of performance of the system
Answers: 0.74 kg/s; 9.52 and 4.25 m3/min; 28.2 kW; 2.48
45
Applied Thermodynamics and Heat Transfer THT3701
12.27 Introduction
Refrigeration loads result from two actions: (1) to cool something down (i.e., to reduce its
enthalpy) and (2) to keep something cool (i.e., to remove incoming and internally generated heat).
Total refrigeration load includes transmission load, product load, internal load, infiltration air and
equipment-related load. The first four types of loads constitute the net refrigeration load for which
a refrigeration system is provided. The sum of the net heat and the equipment-related refrigeration
load is the total heat used when selecting a compressor. It is important that indoor and outdoor
weather conditions be taken into consideration or identified prior to the calculation of the
refrigeration load.
Generally, the outdoor weather condition is taken as the worst local conditions based on the 2.5%
principle. Table 12.4 lists outdoor information for some of South African locations.
Open Rubric
Applied Thermodynamics and Heat Transfer THT3701
The indoor temperature of the refrigerated space is identified based on the processing and storage
requirement of different food products. For example, for fresh fruits and vegetables the cold room
temperature can be between –2 °C and 5 °C, and for meat about –18 °C.
• transmission load:
heat transferred into the refrigerated chamber through the surface of the chamber
• product load:
heat produced by the products stored in the refrigerated chamber
• internal load:
heat produced by internal sources such as lights, electric motors, and people working
in the space
• infiltration load:
heat gain associated with the entering of air in the refrigerated chamber
• equipment-related refrigeration load
where
is the heat gain, in W,
is the overall heat transfer coefficient in W/m2.K,
is the outside area of section, m2, and
is the difference between outside air temperature and air temperature of the refrigerated
chamber.
The overall coefficient of heat transfer of the walls, floor or ceiling can be calculated from
, (12-13)
where
2
Applied Thermodynamics and Heat Transfer THT3701
Usually, a value of 1.6 for and is used for still air. If the outer surface is exposed to
7 m/s wind speed, is increased to 6 W/m2.K.
Because walls are usually made of more than one material, the value of represents the composite
resistance of the materials.
The thermal conductivity values of cold storage insulation materials are given in table 12.5.
The thickness of the insulated panels can be between 50 mm and 150 mm. Table 12.6
provides a list of minimum insulation material thicknesses based on expanded polyurethane as
suggested by the US refrigeration industry.
The temperature difference ΔT is calculated based on the indoor and outdoor temperatures.
3
Applied Thermodynamics and Heat Transfer THT3701
, (12-14)
where
is the specific heat capacity above freezing in kJ/(kg.K),
is the specific heat capacity below freezing in kJ/(kg.K),
is the initial temperature decrease above freezing in °C,
is the initial temperature decrease below freezing in °C, and
is the latent heat of freezing in kJ/kg.
Some of the components will be zero if cooling does not take place through the range of
temperatures above and below the freezing point.
, (12-15)
where
is the heat removed in kJ,
is the mass of product in kg,
is the specific heat of product above freezing in kJ/(kg.K),
is the initial temperature of product above freezing in °C, and
is the freezing temperature of product in °C.
, (12-16)
where
is the latent heat of fusion of product in kJ/kg.
• Heat removed to cool from freezing point to final temperature below freezing point
(12-17)
where
is the specific heat of product below freezing in kJ/(kg.K) and
is the final temperature of product below freezing in °C.
4
Applied Thermodynamics and Heat Transfer THT3701
, (12-18)
where
is the average cooling load in kW, and
is the allotted time in h.
The specific heat values above or below freezing for a variety of products are provided in
table 12.7. A product’s latent heat of fusion may be estimated by multiplying the water content of
the product by the latent heat of fusion of water, which is 334 kJ/kg.
Since most food products freeze at temperatures –3 and –0.5 °C, it is reasonable to estimate –2 °C
when the actual freezing temperature is unknown.
Table 12.7 Unfrozen composition data, initial freezing point and specific heats of foods
5
Applied Thermodynamics and Heat Transfer THT3701
Celeriac 88.00 1.50 0.3 9.20 1.80 1.0 –0.9 3.9 1.89 294
0 0
Celery 94.64 0.75 0.1 3.65 1.70 0.8 -0.5 4.07 1.74 316
4 2
Collards 90.55 1.57 0.2 7.11 3.60 0.5 -0.8 4.01 1.86 302
2 5
Corn, sweet, 75.96 3.22 1.1 19.02 2.70 0.6 -0.6 3.62 1.98 254
yellow 8 2
Cucumbers 96.01 0.69 0.1 2076 0.80 0.4 -0.5 4.09 1.71 321
3 1
Eggplant 92.03 1.02 0.1 6.07 2.50 0.7 -0.8 4.02 1.83 307
8 1
Endive 93.79 1.25 0.2 3.10 3.10 1.4 -0.1 4.04 1.69 313
0 1
Garlic 58.58 6.36 0.5 2.10 2.10 1.5 -0.8 3.17 2.19 196
0 0
• Enthalpy method
The product’s refrigeration load can also be identified by its change in enthalpy
(12-19)
where
The enthalpy values for some frozen foods are given in table 12.8.
6
Applied Thermodynamics and Heat Transfer THT3701
Water Temperature, °C
content,
% by –
Food mass –40 –30 –20 –18 16 –14 –12 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0
Fruits and
Vegetables
Applesauce 82.8 Enthalpy, kJ/kg 0 23 51 58 65 73 84 95 102 110 120 132 152 175 210 286 339 343
% water unfrozen – 6 9 10 12 14 17 19 21 23 27 30 37 44 57 82 100 –
Asparagus, peeled 92.6 Enthalpy, kJ/kg 0 19 40 45 50 55 61 69 73 77 83 90 99 108 123 155 243 381
% water unfrozen – – – – – 55 61 69 73 77 83 90 99 108 123 155 243 381
Bilberries 85.1 Enthalpy, kJ/kg 0 21 45 50 57 64 73 82 87 94 101 110 125 140 167 218 348 352
% water unfrozen – – – 7 8 9 11 14 15 17 18 21 25 30 38 57 100 –
Carrots 87.5 Enthalpy, kJ/kg 0 21 46 51 57 64 72 81 87 94 102 111 124 139 166 218 357 361
% water unfrozen – – – 7 8 9 11 14 15 17 18 20 24 29 37 53 100 –
Cucumbers 95.4 Enthalpy, kJ/kg 0 18 39 43 47 51 57 64 67 70 74 79 85 93 104 125 184 390
% water unfrozen – – – – – – – – 5 – – – – 11 14 20 37 100
Onion 85.5 Enthalpy, kJ/kg 0 23 50 55 62 71 81 91 97 105 115 125 141 163 196 263 349 353
% water unfrozen – 5 8 10 12 14 16 18 19 20 23 26 31 38 49 71 100 –
Peaches, 85.1 Enthalpy, kJ/kg 0 23 50 57 64 72 82 93 100 108 118 129 146 170 202 274 348 352
without stones % water unfrozen – 5 8 9 11 13 16 18 20 22 25 28 33 40 51 75 100 –
Pears, Bartlett 83.8 Enthalpy, kJ/kg 0 23 51 57 64 73 83 95 101 109 120 132 150 173 207 282 343 347
% water unfrozen – 6 9 10 12 14 17 19 21 23 26 29 35 43 54 80 100 –
Plums, 80.3 Enthalpy, kJ/kg 0 25 57 65 74 84 97 111 119 129 142 159 182 214 262 326 329 333
without stones % water unfrozen – 8 14 16 18 20 23 27 29 33 37 42 50 61 78 100 – –
Raspberries 82.7 Enthalpy, kJ/kg 0 20 47 53 59 65 75 85 90 97 105 115 129 148 174 231 340 344
% water unfrozen – – 7 8 9 10 13 16 17 18 20 23 27 33 42 61 100 –
Spinach 90.2 Enthalpy, kJ/kg 0 19 40 44 49 54 60 66 70 74 79 86 94 103 117 145 224 371
% water unfrozen – – – – – – 6 7 – – 9 11 13 16 19 28 53 100
7
Applied Thermodynamics and Heat Transfer THT3701
• Heat of respiration
As they respire during storage, fresh fruits and vegetables release heat:
where
Table 12.9 Heat of respiration for fresh fruits and vegetables at various temperatures (ASHRAE 2010)
During curing, peanuts in the shell were dried to about 5-6% moisture, and in
roasting are dried further to about 2% moisture.
lRates are for 1 day after harvest.
8
Applied Thermodynamics and Heat Transfer THT3701
Example 12.8
100 kg of lean beef is to be cooled from 18 °C, then frozen and cooled to –18 °C in 24 hrs. The
moisture content is 69,5%. Estimate the refrigeration load.
Solution 12.8
Table 12.10 Heat gain from typical electric motors (Huan 2017)
9
Applied Thermodynamics and Heat Transfer THT3701
• People
The amounts of refrigeration load that can be added by people depend on factors such
as room temperature, type of work being done, type of clothing worn and the number
of people. A person’s refrigeration load may be estimated using
, (12-20)
Average load values of persons in a refrigerated space are provided in table 12.11.
• Lights
• People
• Equipment
10
Applied Thermodynamics and Heat Transfer THT3701
12.30.4 Infiltration
Infiltration is airflow at an open door caused by higher density cold air. It commonly occurs
due to difference in air density between rooms. Heat gain through doorways from air exchange
is as follows:
(12-24)
where
is the sensible and latent refrigeration load for fully established flow in kW,
Gosney and Olama (1975) have developed the following air exchange equation for fully
established flow:
, (12-25)
where
(12-26)
11
Applied Thermodynamics and Heat Transfer THT3701
Example 12.9
A catch of 1000 kg of bluefin tuna must be cooled from 10 °C and then frozen. After being
frozen, the catch must be cooled to –18 °C in 10 hours. Estimate the refrigeration load. Refer
to table 12.7 for the properties of foods. For latent heat, use the latent heat of fusion.
Solution 12.9
From table 5.4, the specific heat of Bluefin tuna before freezing is c1 = 3.43 kJ/kgK and Bluefin
tuna freezes at –2.2 °C. Therefore, the sensible heat that must be removed to freezing point is
The latent heat of fusion, which considers only the moisture content of the fish, is 227 kJ/kg.
The latent heat removed to freeze the fish is
From table 12.7, the specific heat of Bluefin tuna after freezing is c2 = 2.19 kJ/kgK. Therefore,
the sensible heat that must be removed to –18 °C is
12.31 Summary
Based on the second law of thermodynamics, heat flows from a body at a high temperature to
a body at a low temperature. If the temperature of a certain space is lower than that of its
surroundings, heat will flow into that space. The amount of heat gained by that space is the
amount which must be removed. When this amount of heat is expressed per unit time, it is the
rate at which heat must be removed, expressed in kW (kilowatts or kilojoules per second) and
is called the refrigeration load. This load can enter the space from different sources, such as the
heat transmitted by conduction through walls, ceiling and floor, and heat gain owing to the
release of energy in a space (lights, equipment, people, etc.)
Because of usually higher variations in the temperature of the incoming product, doors
left open, lights left on, storage procedure and so on, the actual refrigeration requirements may
vary from the calculated load. Hence the safety factor may be used to account for the above
12
Applied Thermodynamics and Heat Transfer THT3701
variations. General practice is to add a 10% safety factor to the calculated load. However, the
designer should carefully consider the safety factor to ensure that the most efficient and
economical system is provided.
12.32 Problems
Problem 12.17
Calculate the total refrigeration load for a freezer storage with design criteria as follows:
Design criteria:
• summer: 33 °C dry bulb (db), 27 °C wet bulb (wb)
• comments: 0.4% summer and winter conditions
• room dimensions: 40.5 x 68 x 9 m
• floor area: 2743 m2
• pallet positions: 4800
• turns per yr: 20
• use factor: 90%
• design room temperature: –23 °C
Insulation thickness:
m k, W/(m.k) U, W/(m.k) R, (m2.k)/W
Roof 0.152 2.048 3.414 7.441
Floor 0.152 2.711 4.518 5.620
Wall, East 0.102 1.745 4.363 5.822
North 0.102 1.745 4.363 5.822
Westa 0.102 1.745 4.363 5.822
Southb 0.102 1.745 4.363 5.822
k = thermal conductivity U = k/(m) thickness R = thermal resistance
13
Applied Thermodynamics and Heat Transfer THT3701
14