REPORT ON PLATE LOAD TEST

For

Construction of 2 Lane ROB (End to end including approaches) At KM 838/7-9


IN lieu of LC no.4 b/w BMU-MRE station in PRYJ-CNB section of PRYJ
division of NCR, Uttar Pradesh.

DATE OF TESTING:- 18.03.2024


TEST LOCATION :- W1 LHS

CLIENT
NORTH CENTRAL RAILWAY

Contractor

M/S PRAGATI CONSTRUCTION CONSULTANT

Submitted To
NORTH CENTRAL RAILWAY

By

BHARAT INFRA CONSTRUCTIONS


180B, MOHALLA MIRDHAN, FARIDPUR, BAREILLY, UTTAR PRADESH
Mob No. 8279524588, 9999166558, email us :[email protected]
BHARAT INFRA CONSTRUCTIONS

TABLE OF CONTENTS

TITLE SHEET NO

1.0 INTRODUCTION 1

1.1 Project Description 1

1.2 Purpose of Study 1

2.0 FIELD INVESTIGATION 1

2.1 Plate Load Test 2

3.0 BEARING CAPACITY OF SOIL 3

4.0 SUMMARY OF PRINCIPAL FINDINGS 3

5.0 CLOSURE 4

Field observations 5-6

Load settlement graph 7

Test arrangement 8

photographs 9
BHARAT INFRA CONSTRUCTIONS SHEET NO 1

1.0 INTRODUCTION

1.1 Project Description

North Central Railway are planning for Construction of 2 Lane ROB


(End to end including approaches) At KM 838/7-9 IN lieu of LC no.4 b/w
BMU-MRE station in PRYJ-CNB section of PRYJ division of NCR, Uttar
Pradesh. The work of plate load test has been awarded to

BHARAT INFRA CONSTRUCTIONS by M/S PRAGATI


CONSTRUCTION CONSULTANTS

The report Presented hereunder, deals with the test results and
their interpretation, estimation of safe allowable bearing capacity
and recommendation, regarding the type, size and shape of
foundation which may be provided for the proposed structure.

1.2 Purpose of Study

The purposes of this study were to evaluate the subsurface


stratigraphy so as to develop recommendations for foundation
design and construction. To accomplish these purposes, the
study was conducted in the following phase:

I Conducting one plate load test at given location and depth at


site.

II Preparing this technical report with foundation design and


recommendations.
BHARAT INFRA CONSTRUCTIONS SHEET NO 2

2.0 FIELD INVESTIGATION

2.1 Plate Load Test

The Plate Load Tests was conducted at given location in general


accordance with IS: 1888. The depth of test was about to ground
level. The test location was given by client as shown on site plan.
Square plate of 450mm x 450mm was used for testing. The dead
load was used to provide the reaction by kentledge.

The dead load was applied in the form of loaded hyva truck. The
loading arrangement is shown separately on figure. The test plate
was placed over a fine sand layer of maximum thickness of 5 mm,
so that the center of plate coincides with the center of reaction
girder/beam, with the help of plumb and bob and horizontally
leveled by a sprit level to avoid eccentric loading. The hydraulic
jack was was centrally placed over the test plate with the loading
column in between the jack and reaction beam so as to transfer
load to the plate. A minimum seating pressure of 70gm/cm2 was
applied and removed before starting the load test.

The plate was loaded by pushing a hydraulic jack against the


dead load. Dial gauges of 0.01mm least count were used to
measure the plate settlement with reference to a stable datum
bar. The load was applied in small increments of about 10.616 ton
on soil. The final load was applied till the settlement of plate
exceeds 25 mm. Each load was held until the time rate settlement
becomes negligible. The results are presented on plate verses
measured displacement of plate on figures.
BHARAT INFRA CONSTRUCTIONS SHEET NO 3

Two supports of reference beam or datum rod was placed over


form ground, fixed with two dial gauges resting on the plate. The
dial gauges were so arranged that settlement was measured that
settlement was measured continuously.

Settlements were observed for each increment of load after an


interval of 1, 2.25, 4, 6.25, 9, 16, 25 minute and thereafter an
hourly intervals to the nearest of 0.02mm

3.0 BEARING CAPACITY OF SOIL

Based on the plate load test conducted at site following test


result has been observed-
ground level: 99.380 MM
Test level: 98.130 MM
According to Graph the settlement did not exceed 25mm before
final load. Hence soil is safe for 21.57 t/m2
Net Safe bearing capacity of soil: 21.57 t/m2

4.0 SUMMARY OF PRINCIPALFINDINGS

BHARAT INFRA CONSTRUCTIONS Carried out one plate load test for
Construction of 2 Lane ROB (End to end including approaches) At KM
838/7-9 IN lieu of LC no.4 b/w BMU-MRE station in PRYJ-CNB section
of PRYJ division of NCR, Uttar Pradesh.
Following are the foundation recommendations.
ground level: 99.380
Test level: 98.130
Net Safe bearing capacity of soil: 21.57 t/m2
BHARAT INFRA CONSTRUCTIONS SHEET NO 4

5.0 CLOSURE

We appreciate the opportunity given to us to submit this report. Please


contact us if you need any clarification.

For BHARAT INFRA CONSTRUCTIONS


BHARAT INFRA CONSTRUCTIONS SHEET NO - 5
PLATE LOAD TEST OBSERVATION

Construction of 2 Lane ROB (End to end including approaches) At KM 838/7-9 IN lieu of


PROJECT LC no.4 b/w BMU-MRE station in PRYJ-CNB section of PRYJ division of NCR, UP.

LOCATION W1 LHS
PLATE SIZE 450 MM X 450 MM TEST LEVEL 98.13
REQUIRED SBC 21.57 MT GROUND LEVEL 99.38
AVG.
DATE TIME LOAD READING, mm
SETTLEMENT
(H:M:S) IN DIV. IN TON DIAL GAUGE I DIAL GAUGE II mm

18.03.2024 00:00:00 2.00 10.616 0.21 0.29 0.2500


00:01:00 2.00 10.616 0.23 0.32 0.2750
00:02:00 2.00 10.616 0.24 0.33 0.2850
02:25:00 2.00 21.232 0.24 0.34 0.2900

00:00:00 4.00 21.232 0.52 0.87 0.6950


00:01:00 4.00 21.232 0.54 0.90 0.7200
00:02:00 4.00 21.232 0.55 0.91 0.7300
02:25:00 4.00 21.232 0.55 0.92 0.7350

00:00:00 6.00 31.848 1.01 1.53 1.2700


00:01:00 6 00
6.00 31 848
31.848 1 05
1.05 1 57
1.57 1 3100
1.3100
00:02:00 6.00 31.848 1.06 1.59 1.3250
02:25:00 6.00 31.848 1.06 1.59 1.3250

00:00:00 8.00 42.464 1.58 2.11 1.8450


00:01:00 8.00 42.464 1.62 3.15 2.3850
00:02:00 8.00 42.464 1.64 3.17 2.4050
00:02:25 8.00 42.464 1.66 3.18 2.4200
00:04:00 8.00 42.464 1.67 3.19 2.4300
00:06:25 8.00 42.464 1.67 3.19 2.4300

00:00:00 10.50 55.690 2.80 3.11 2.9550


00:01:00 10.50 55.690 2.88 3.19 3.0350
00:02:00 10.50 55.690 2.85 3.24 3.0450
00:02:25 10.50 55.690 2.87 3.26 3.0650
00:04:00 10.50 55.690 3.00 3.29 3.1450
00:06:25 10.50 55.690 3.05 3.33 3.1900
00:09:00 10.50 55.690 3.08 3.86 3.4700
00:16:00 10.50 55.690 3.19 3.40 3.2950
BHARAT INFRA CONSTRUCTIONS SHEET NO - 6

SETTLEMENT
APPLIED LOAD IN METRIC TON
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.0

1.0

2.0
ETTLEMENT IN MM

3.0

4.0
SE

5.0

6.0

SETTLEMENT

TEST LOCATION:- W1 LHS

PLATE SIZE 450X450MM

TEST LEVEL 98.130

GROUND LEVEL 99.380

DATE OF TESTING 18.03.2024

SAFE BEARING CAPACITY 21.57 T/M²

PLATE LOAD TEST


BANSAL CALIBRATION SERVICES
Calibration Certificate C C-2438
■ .

Format No.:- BCSIQFll.8-01,Rev. No.-01, Rev. Date 03.11.2022 ULR No.:-CC243823000011807F


Certificate No. BCS/MN/24110108-005 No. of Page 1 OF 1
Customer Name S.R.F. No. & Date BCS/MN/24110108/19-11-2023
Address M/s, Bharat Infra Constructions
Calibration Date 19-11-2023
180 B, Mohalla Mirdhan, Faridpur,
Sugg. Calibration Due Date 18-11-2024
Bareilly, (UP)-243503
Certificate Issue Date 19-11-2023
A) Identification ON UUC (Unit Under Calibration)
Calibration Certificate of DIAL PRESSURE GAUGE Instrument Sr. No. /Id No. 9002UQBM
Make Wika Location .

Range /Size 0 - 600 kglcm2 Visual Inspection OK


Least Count 10kg/cm 2 Calibration Performed at Lab
B) Master Equipmenfused for Calibration
Name Range I Serial no. Calibration Agency Traceability Certificate No Calibration Date Valid Up-to
Digital Pressure Gauge 0 to 700 bar/ 017D2403 PV PV/2304/0482 27--04-2023 26--04-2024
° DKD-R6-1-
Temperature 23•c ±1.5 C Calibration Reference Standard
Environmental Condition 03/2014
Humidity 30 to 75%RH Calibration Procedure No. BCS/M/CP-77
Mechanical Calibration
Calibration Results
Displayed Pressure on UUC Measured Pressure on Master (bar)
Sr. No. Average Pressure in (bar) Error in (bar)
( ka/cm21 lbarl Increasing Decreasing
1 0 0.0 0.00 0.00 0.000 0.000
2 100 98.1 98.26 98.19 98.225 0.125
3 200 196.1 196.74 196.68 196.710 0.610
4 300 294.2 294.96 294.84 294.900 0.700
5 400 392.3 393.47 393.36 393.415 1.115
6 500 490.3 491.68 491.54 491.610 1.310
7 600 588.4 589.97 589.86 589.915 1.515

Uncertainty in Measurement=± 2.0 bar


The uncertainty st ated is the expanded uncertainty of measurement obtained by multiplying the standard uncertainty by the coverage factor k=2 correspond to
confidence level of 95%.
•.. End of Certificate'..
Note:- 1. The Calibration results reported in this certificate are val Id at the time of and the stated condition of measurement
2. This report should not be reproduced except in full without our prior permission in writing.
3.Calibration certificate without signature are not valid.

·��Yo/
4. All our certificates are Metrological Traceable.
-�-��
-

i
5. This Certificate relates to the item Calibrated.
Approved By

�.J-lr �,____
Calibrated By

Ghl� ,i>,�rl/E
DALIP KUMAR NOORDEEN DAJ
CALIBRATION ENGG. AUTHORIZED SIGNATORY ��

49/39, Site IV, lndl. Area Sahibabad, Ghaziabad-201010, U.P. INDIA


Mob.:08920907896,09313212192
E-mail : [email protected], [email protected], www.bcstestlab.com
BANSAL CALIBRATION SERVICES
Calibration Certificate
CC-2438

Format No. BCS /QF/7.8-01 ULR No.:-CC243823000001880F


Certificate No : BCS/MN/24110059-002 No. of Page 1 OF 1
Customer Name : S.R.F. No. & Date BCS/MN/24110059/10-11-2023
Address Mis. BHARAT INFRA CONSTRUCTIONS Calibration Date 10-11-2023
MOHMinihan, Nauda Baag WaliMasjid,
Faridpur, Bareilly. Sugg. Calibration Due Date 9-11-2024
Certificate Issue Date 10-11-2023
A) Identification ON UUC (Unit Under Calibration)
Calibration Certificate of PLUNGER TYPE DIAL GAUGE Instrument Sr./ Id. No. 2371548
Make/Model ASAHI Location -
Range/Size 0-25 mm Visual Inspection Ok
Least Count 0.01 mm Calibration Performed at Lab
B) Master Equipment used for Calibration
Name/make Range / Serial no. Calibration Agency Traceability Certificate No Certificate Date Valid Up-to
ULMM 0-100mm/BCS/M/ULM-01 BCS BCS/N/21040005-001 10-04-2021 09-04-2023
° °
Environmental Temperature 20 c ±2 C Calibration Reference Standard IS: 2092: 1983
Condition Humidity 40to60%RH Calibration Procedure BCS/M/CP-13
Mechanical Calibration
Calibration Results
Observed Value in mm Observed Value in mm
Sr. No. Nominal Value in mm Mean Value in (mm)
(Upward) (Downward)
1 0.00 0.0000 0.0000 0.0000
2 1.00 1.0007 1.0003 1.0005
3 2.00 2.0013 2.0012 2.0013
4 3.00 3.0019 3.0016 3.0018
5 4.00 4.0023 4.0021 4.0022
6 5.00 5.0035 5.0032 5.0034
7 8.00 8.0044 8.0043 8.0044
8 10.00 10.0053 10.0049 10.0051
9 15.00 15.0064 15.0063 15.0064
10 20.00 20.0071 20.0068 20.0070
11 25.00 25.0079 25.0074 25.0077
Uncertainty of Measurement ±6.0pm The uncertainty stated is the expanded uncertainty of measurement obtained by multiplying the standard
uncertainty by the coverage factor k=2 correspond to confidence level of 95%.
Note:• 1. The Calibration results reported in this certificate are valid at the time of and the stated condition of measurement.

I.'
2. This report should not be reproduced except in full without our prior permission in writing.

I
3. Calibration certificate without signature are not valid.
4. All our certificates are Metrological Traceable.
5. This Certificate relates to the item Calibrated. ,�
., :i7 ;'

I
.
Calibrated By Aooroved By \_! �HAZIABAD ' ' j

DALIP KUMAR
CALIBRATION ENGG.
ID oJJ P JL v1 )rV).-- V.S BANSAL
AUTHORIZED SIGNATORY I
l\
,
.. :l.·�·--:J.
.

-�
_.,.. -
J

49/39, Site IV, lndl. Area Sahibabad, Ghaziabad-201010, U.P. INDIA


Tele.: 00-91-120-4556377 & 79 Mob. : 08920907896
E-mail : [email protected], [email protected], www.bcstestlab.com
BANSAL CALIBRATION SERVICES
Calibration Certificate
CC-2438

Format No. BCS /QF/7.8-01 ULR No.:-CC243823000001879F


Certificate No : BCS/MN/241 1 0059-001 No. of Page 1 OF 1
Customer Name S.R.F. No. & Date BCS/MN/24110059/10-11-2023
Address M/s. BHARAT INFRA CONSTRUCTIONS Calibration Date 10-11-2023
MOHMirdhan, Nauda Baag WaliMasjid,
Faridpur, Bareilly. Sugg. Calibration Due Date 9-11-2024
Certificate Issue Date 10-11-2023
A) Identification ON UUC (Unit Under Calibration)
Calibration Certificate of PLUNGER TYPE DIAL GAUGE Instrument Sr./ Id. No. 2339932
Make/Model ASAHI Location -
Range/Size 0-25 mm Visual Inspection Ok
Least Count 0.01 mm Calibration Performed at Lab
B) Master Equipment used for Calibration
Name/make Range/ Serial no. Calibration Agency Traceability Certificate No Certificate Date Valid Up-to
ULMM 0-100mm/BCS/M/ULM-01 BCS BCS/N/21040005-001 10-04-2021 09-04-2023
Environmental Temperature 20 ° C ±2° C Calibration Reference Standard IS: 2092: 1983
Condition- Humidity 40to 60%RH Cai!l:ration Procedure BCS/M/CP-13
Mechanical Calibration -·
Calibration Results
Observed Value in mm Observed Value in mm
Sr. No. Nominal Value in mm Mean Value in (mm)
(Upward) (Downward)
1 0.00 0.0000 0.0000 0.0000
2 1.00 1.0003 1.0002 1.0003
3 2.00 2.0007 2.0006 2.0007
4 3.00 3.0013 3.0011 3.0012
5 4.00 4.0018 4.0013 4.0016
6 5.00 5.0026 5.0019 5.0023
7 8.00 8.0032 8.0024 8.0028
8 10.00 10.0045 10.0036 10.0041
9 15.00 15.0057 15.0047 15.0052
10 20.00 20.0065 20.0057 20.0061
11 ,,. 25.00 25.0075 25.0068 25.0072
• Uncertainty of Measurement. I ±6.0 µm The uncertainty stated is the expanded uncertainty of measurement obtair\l!d by multiplying the standard
uncertainty by the coverage factor k=2 correspond to confidence level of 95%.
Note:• 1. The Calibration results reported in this certificate are valid at the time of and the stated condition of measµrement.
2. This report should not be reprodu� except in full without our prior permission in writing.
3. Calibration certificate without sig1ature are not valid.
4. All our certificates are Melrological Traceable.
5. This Certificate relates to the item Calibrated. d,-. .tr �

.. i\ r'-lAZIAS 1
J
Calibrated Bv • Aooroved By
l)a,Gf.. {Lu�
�-;
It:..,._ ..,

_.,.-- ,,
DALIP KUMAR V.S BANSAL
CALIBRATION ENGG. AUTHORIZED SIGNATORY I
'

49/39, Site IV, lndl. Area Sahibabad, Ghaziabad-201010, U.P. INDIA


Tele.: 00-91-120-4556377 & 79 Mob.: 08920907896
E-mail : [email protected], [email protected], www.bcstestlab.com