TAA00002KY
TYPE APPROVAL CERTIFICATE
This is to certify:
That the SOx Exhaust Gas Cleaning Control System
Issued to
Wärtsilä Moss AS
Moss, Norway
Application :
Product(s) approved by this certificate is/are accepted for installation on all vessels classed
by DNV GL.
Location classes:
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
© DNV GL 2014. DNV GL and the Horizon Graphic are trademarks of DNV GL AS.
Job Id: 262.1-030408-1
Certificate No: TAA00002KY
Product description
This approval covers control cabinets used in Wärtsilä exhaust gas cleaning (scrubber) control &
monitoring system. Application SW is not covered by this type approval certificate (TAC). See table 1 for
control cabinets covered by this TAC. Table 2 relates the main components in these cabinets to DNV GL
TAC’s.
Table 2: C&M components used in the exhaust gas cleaning control system with cross reference to Type
Approval Certificate
Manufacturer Module type Type Approval Components used Description
Certificate1) in the following
cabinets
DEIF AL8-2 TAA00000ZU MCP & IO-Maxi & Alarm Unit
IO-Medi & IO-Mini
Phoenix Contact Quint4- TAA00000BV MCP & IO-Maxi & Power supply unit
PS/1AC/24DC/10 (rev.5) IO-Medi & IO-Mini
Phoenix Contact Quint4-Diode/12- TAA000011F MCP & IO-Maxi & Diode
24DC/2x20/1x40 (rev.1) IO-Medi & IO-Mini
Phoenix Contact QUINT- TAA0000265 MCP & IO-Maxi & Power Buffer
Buffer/24DC/24DC/40 (rev.1) IO-Medi & IO-Mini Module
Schneider STBACI…, STBACO…, TAA0000064 MCP & IO-Maxi & Modular
STBDDI…, STBDDO…, IO-Medi & IO-Mini distributed I/O
STBNIP…, STBPDT…, system
STBXBE…, STBXMP…
Schneider HMIDT732 14 591 - 15 HH MCP & TSP 15 Touch Smart
Display
Schneider HMIG3U 14 591 - 15 HH MCP & TSP Premium BOX for
Touch screen
Westermo L210-F2G TAA000000R MCP & TSP Ethernet Switch
(rev.1)
Westermo L206-S2 TAA000000R MCP Ethernet Switch /
(rev.1) Firewall
Schneider BMEH582040 TAA00000VJ MCP Redundant HSBY
(rev.1) processor module
M580
Schneider BMEXBP0400 TAA00000VJ MCP Rack X80 - 4 slots
(rev.1) - Ethernet
backplane
Weidmüller IE-XM-RJ45/IDC TAE00003EW IO-Maxi & IO-Medi & Outlets for RJ45
IO-Mini & TSP plug-in connectors
Nagasaki APPC-15629T TAA00000JE MCP Data Logger
(rev.1)
PR Electronic 3333 TAA00001RW MCP & IO-Maxi & Pt100 converter,
(rev.1) IO-Medi & IO-Mini loop-powered
PR Electronic 4116 TAA0000101 MCP & IO-Maxi & Universal
IO-Medi & IO-Mini transmitter
PR Electronic Series 3103-3333 TAA00001RW MCP & IO-Maxi & Isolators /
(rev.1) IO-Medi & IO-Mini convertors/
repeaters
Schneider Magelis Bos iPC, TAA000008M MCP Industrial
Magelis / Harmony (rev.3) computer
Modular PC
Rittal GmbH & AX enclosure TAE00003WA MCP & NSP & STP & Enclosure for
Co. KG IO-Maxi & IO-Medi & Electrical
IO-Mini Equipment
1) Currently valid DNV GL TAC / rev numbers.
Places of Manufacture
Moss Automation
Varnaveien 22
P.B 2084, Høyden
1521 Moss
Norway
Application/Limitations
1. This TAC covers hardware, system design principle and network setup.
2. This TAC is only valid for cabinets as listed in Table 1 when manufactured at the “Places of
Manufacture”.
3. HW-test of each individual cabinet shall be witnessed by DNV GL. The test reports for each
individual cabinet shall be signed and stamped by the attending DNV GL surveyor.
4. Installation of the cabinets covered by this TAC on-board may commence without informing DNV
GL on the condition of successful HW-test (ref. item 3 above).
6. Test of application software shall be performed at the premises of Moss Automation as described
under “Places of Manufacturer” or at the premise of Wärtsilä Moss and may commence only after
the system documents specified under “Approval Conditions” are approved.
7. Test of the application software shall be performed on an identical MCP connected to identical
NSP1, NSP2, TSP and emergency stop boxes as delivered on-board, connected to a test
simulator tool.
9. After successful testing, a DNV GL product certificate covering the entire EGC C&M system shall
be issued.
10. Potential changes in HW and SW from FAT to SAT shall be followed up as described in the
document SW & FW handling from FAT to SAT, doc. ID: DMTA00028576.
11. The SW and the SW configuration used during FAT shall be set accordingly in the installed
system. The installed SW shall be according to the project specific software revision document.
12. HW safety stop configuration/jumper shall be set according to project specific circuit diagrams.
13. The network setup between the control cabinets mentioned in Table 1 has been tested and
approved according to DNV GL Pt.4 Ch.9 Sec.4 [3.3] / Network test and verification. As long as
the setup is as described in sec.6.4 in the document WÄRTSILÄ EGC CONTROL SYSTEM –
TECHNICAL DESCRIPTION rev.2, network analyses and testing, including network storm, will not
be required in specific projects.
Approval conditions
The following documentation of the actual application shall be submitted for approval in each case:
- Reference to this type approval
- I020 Control system functional description
- I030 System block diagram (topology)
- I040 User interface documentation
- I050 Power supply arrangement
- I110 List of controlled and monitored points
- I150 Circuit diagrams
- Z252 Test procedure at Manufacturer.
- Confirmation that Application/Limitation point 13 is fulfilled
- List of panels with serial numbers used in a specific project, with test reports linked to the serial
numbers. It is accepted that the serial numbers are submitted to DNV GL at the certification test,
but then this shall be informed in the documentation submitted for approval.
Product certificate
Each delivery of the application system is to be certified according to Pt.4 Ch.9 Sec.1. The certification
test is to be performed at the manufacturer of the application system according to an approved test
program. After the certification the following clause for application software control will be put into force:
Marking of product
The cabinets will be marked with:
WÄRTSILÄ EGC
MANUFACTURER: As stated in place of manufacture
PANEL TYPE: As stated in table 1
ARTICLE NO.: As stated in table 1
SERIAL NO.:
Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the type are
complied with, and that no alterations are made to the product design or choice of systems, software
versions, components and/or materials. The main elements of the assessment are:
• Ensure that type approved documentation is available
• Inspection of factory samples, selected at random from the production line (where practicable)
• Review of production and inspection routines, including test records from product sample tests
and control routines
• Ensuring that systems, software versions, components and/or materials used comply with type
approved documents and/or referenced system, software, component and material specifications
• Review of possible changes in design of systems, software versions, components, materials
and/or performance, and make sure that such changes do not affect the type approval given
• Ensuring traceability between manufacturer’s product type marking and the type approval
certificate
Periodical assessment is to be performed at renewal of this certificate.
END OF CERTIFICATE