Circuit Breaker Timing Test Procedure
Circuit Breaker Timing Test Procedure
This article explains the timing test of circuit breaker. Why it is necessary to perform breaker timing test.
What is the standard circuit breaker timing test procedure. Which equipment is used for CB timing test
Contents [hide]
5 Accepted Results
the backbone of electrical protection system. Because of their key importance, they must be checked
periodically. Circuit breaker timing test is among different maintenance tests which should be performed
regularly. It measures the mechanical operating time of the circuit breaker. This test is always important
because delay in operation of circuit breaker can have disastrous effects on the equipment when fault
occurs.
Operation time: Operation time of the circuit breaker is the closing and opening times of contacts.
Closing time: The time interval between energizing the coils of the breaker (when CB contacts are in open
position) and the instant when the contacts touch each other.
Check Also
Opening time: It is opposite to that of closing time. It is the time interval between energizing the trip coil
(CB contacts are in open position) and the instant when contacts separate from each other.
that they withstand high current (other abnormal condition) for very limited time. If the circuit breaker
failed to operate in that limited time, the equipment may be damaged or destroyed. Therefore it is very
important that circuit breaker must operate in specific minimuk time (operation time) in order to
minimize damage. This feature makes it very important to check the operation time of circuit breaker
periodically.
Relay coordination. Circuit breakers are installed at different positions to provide protection to power
system. It is recommended that only faulty part of power system should be detached while the other
should remain intact. It is only possible that breaker near to the fault should be tripped while breaker
away from load and near to source should remain intact. This is called relay coordination. The timing of
the relay are set in such a way that breaker near the fault should trip first. However if the breaker fails to
operate in its specific time, the breaker away from fault (near to source) will trip hence healthy part of
system will also be detached. So correct operation time is necessary for the relay coordination.
were based on oscillographic mode of record curves and currently are not used. Second generation testing
methods based on digital timers with time-pulse conversion e.g. Circuit-breaker timer.
The equipment which is widely used nowadays for performing timing test of circuit breaker is the Circuit
breaker (CB) analyzer. The major probes and connection points are shown in the following figure.
Check Also
Connection to the input & output of each phase of circuit breaker from circuit breaker analyzer.
DC supply to the tripping coil of the circuit breaker from external source. Circuit breaker specifications
http://www.help2educate.com/circuitbreakertimingtestprocedure/ 2/3
4/8/2017 Circuit breaker timing test Procedure |
connection to incoming of each phase of breaker is provided from CBA via red, yellow and blue wires
while outgoing is connected with black wire. Positive (+) and Negative (-) sign shows the connection of
external battery to the triggering circuit.
When the connections are done, note the state of the circuit breaker from breaker state indicator (on or
off). Press the ready button, the circuit breaker will be operated and the time will be displayed on the
screen. Results of the timing test of circuit breaker can be printed using thermal printer, downloaded
directly to USB via USB port and displayed on PC via USB interface. Repeat the process for closing and
Accepted Results
The exact correct operation time of circuit breaker is provided by the manufacturer. It can be mentioned
on the nameplate of circuit breaker. Click here to learn how to interpret name plate of circuit breaker.
However as a rule of thumb, operating time of circuit breaker should fall in the following ranges
These are just estimated values which can be regarded as acceptable operation time.