Opearion Manual For Co Gas Boosting Station (Tata Kpo)
Opearion Manual For Co Gas Boosting Station (Tata Kpo)
Opearion Manual For Co Gas Boosting Station (Tata Kpo)
CONTENTS
SECTION 1 - CO GAS BOOSTER
1.1. Introduction
1.2. General Instruction
1.3. Data Sheet of Booster
1.4. Performance Curve of Booster
1.5. Motor
1.6. Data Sheet of Motor
1.7. Performance Curve of Motor
1.8. Startup Curve
1.9. HCV
1.10. Booster Erection Procedure
1.11. Fan Description
1.12. Shaft Description
1.13. Impeller Locking Arrangement
1.14. Impeller Description
1.15. Impeller Seal Description
1.16. Booster Casing Description
1.17. Bearing & Motor Pedestal Description
1.18. Fan Operation
1.19. Bearing Storage & Handling
1.20. Oil Lubricating Bearing
1.20.1. Description
1.20.2. Erection
1.20.3. Maintenance
1.21. Fluid Coupling
1.22. Resilient Coupling
1.23. Coupling Alignment
1.24. Shaft Axial Alignment
1.25. Shaft Radial Alignment
1.26. Maintenance
1.27. Troubleshooting
1.28. Assessment of vibration Behavior
1.29. Vibration Chart
1.30. Nitrogen Purging Procedure
1.31. Boosting Station Start-up Procedure
1.32. Piping and Instrumentation Diagram
1.33. Do’s & Don’ts
1.34. Control Philosophy
1.35. List of Instruments
1.36. Contacts
1.1 INTRODUCTION
The fans are dispatched in dismantled condition with proper packing. The entire fan parts
to be handled with care. Lifting Lugs to be used and never pass slings and timber through
casing and impeller in order to assist in rigging. Proper care to be taken particularly to the
impeller, hub, shaft, bearing housings and bearings during the transportation. Always
avoid any shocks to the fan parts that could damage the fan parts. If impeller is damaged
slightly, it should be repaired and to be balanced again.
When packages are received at site, check all the parts with the help of the packing list
and drawing. If necessary make a list of missing parts (in case of short supply) and
initiate action for replacement. Check the condition of the parts that may have been
damaged during transport. In case of damages, take steps to repair the damage in
consultation with manufacturer.
Storage for a period of more than couple months must be ensured in the best possible
condition basically protected from dampness so as to avoid oxidization of the different
parts of the fan unit.
The mechanical parts with machined surfaces are coated with anti-corrosion varnish. In
case of prolonged storage, before putting in to service, the equipment will be inspected
periodically and the machined parts will be protected from time to time using protective
coating in case of need. The equipment’s should be kept sufficiently large premises, thus
providing space for inspection and easy maintenance. Moreover, the storage premises will
protect the equipment from sudden changes in temperature, dust, foreign matter, etc.
Always keep the rotor on temporary pedestal at the site prior erection.
Type 1MJ7, Flame proof squirrel cage introduction motors are designed to operate
satisfactory in hazardous locations such as mines, petrochemical plant, boosting stations
etc. classified as division 1 areas. The motors are designed to meet IS/IEC60079-1 for gas
groups IIA,IIB & IIC and are certified by statutory bodies like CIMFR, Dhanbad etc. and
approved by PESO (formerly CCOE)
Even through motors are designed to operate satisfactory in most arduous conditions,
best result are obtained only by carefully planned maintenance as outlined in this
instruction manual. The help may be taken from IS/IEC 60079-17 for installation
inspection and maintenance and IS/IEC 60079-19 for repair, Overhaul and reclamation.
The construction features of flameproof motors type 1MJ7 are similar to 1LA7 series
motors which are elaborated in this manual.
The stator frame id of welded construction. The stator core pack is fitted centrally in the
stator frame and secured against rotation and displacement.
The stator winding of the HV machines is a double layer coil winding and is provided with
MICALASTIC insulation complying with class F insulation requirements. This insulation
system is based on integrated mica and is made by a special synthetic resin impregnation
process. The insulation possesses high electric strength, high resistance to moisture and
aggressive gases and vapors, excellent mechanical stability and long life.
The shafts have two bearings (drive end & non-drive end) and a cylindrical shaft extension
at the drive end. A second shaft extension may be provided at the non-drive end. The
laminated rotor core is pressed on to the shaft, clamped and secured against axial
displacement, and carries the rotor winding.
The rotor winding consists of copper or copper alloy single or double cage as reqd.
consisting of conducting bars inserted in the slot & short circuited with copper ring at
both through brazing.
END SHIELDS
TLT ENGINEERING INDIA PVT. LTD. Page 5 of 68
The end shield at the drive and non-drive ends are disk shaped and arranged for taking
the bearing assembly which is appreciate for the type variant of the machine.
BEARINGS
Depending on the design and the operating conditions specified in the order, the
machines are fitted with grease-lubricated rolling-contact bearings or with sleeve bearings
with or without force-oil lubrication.
Sleeve bearing of machines are of the floating type without axial restraint. Axial restraint
for the rotors of such machines must be provided from the locating bearing of the driven
machine via a suitable coupling having limited play.
For a full description and special instruction, reference should be made to the relevant GA
drawings and data sheets of motors.
Connection from stator winding are brought into flame proof terminal box which houses
bushing type terminal studs front cover is bolted type with allen screws. Clearance and
flame path length are maintained as per IS/IEC 60079-1 (Group IIC). Complete box with
front cover is of robust construction to contain explosing pressure. It is suitable up to a
cable size 1 x 3 core x 185 mm² XLPE cables. Suitable flame proof cable glands are also
provided.
The auxiliary terminal boxes for flame proof motors are made of special grade cast iron
and house ‘KLIP ON’ type terminals. Here also front cover is bolted type with allen screws.
Clearance and flame path lengths are maintained as per IS/IEC 60079-1 (Gas groups IIC)
suitable flame proof cable glands are provided at bottom. Separate boxes are provided for
space heaters, ETD, BTDs.
BEARINGS RTDs
Bearing are also provided with resistance temperature detector to allow for monitoring of
bearing temperatures. They can be connected to temperature scanner/transmitter to
monitor the bearing temperature. If bearing temperature reaches or exceed to permissible
limit value, the same can be use generate a alarm/trip of the motor.
DISMANTLING AND RE-ASSEMBLY PROCEDURE
TLT ENGINEERING INDIA PVT. LTD. Page 8 of 68
To maintain the flame proof features, ensure the components are marked with motor s.no.
from which they are dismantled, in case several identical machines are dismantled at a
time. Those parts which from proof enclosure should not be interchanged. No clearance
should be altered, not any bores modified without manufactures consent. Parts such as
bearing caps, DE & NDE, should not be interchanged.
NOTE :
It is recommended to dismantle flame proof motors at site in consultation
with BHEL.
MOTOR DISMANTLING
SEQUENCE OF DISMANTLING
REASSEMBLY
Reassembly of the motor is reverse of the above procedure. It is recommended that new
rolling bearings be installed as follows: Heat the bearings of the inner ring of the roller
bearings in oil or air to a temperature of approx. 110°C-120°C and slip them onto the
shaft. Heavy blows may damage the bearing and must be avoided.
1.6. DATA SHEET OF MOTOR
PERFORMANCE
Method of starting DOL
Torque at rated voltage (%of FLT)
a) Breakaway starting torque 92%
b) Pull-up torque 60%
c) Pull-out torque 250%
Starting time at 80% RV 100% RV 110% RV
a) Load coupled (sec) 16.0 7.0 5.8
b) Load un-coupled (sec) 8.5 3.7 3.1
Locked rotor withstands time (hot) in sec. 31 20 16
Locked rotor withstands time (cold) in sec. 41 26 21
Starting requirement
a) No. of equally spread starts per hour 3
b) No. of cold starts 3
c) No. of hot starts 2
Thermal time constant (Heating/cooling) (Min) 30 / 120 minutes
Whether motor suitable for bus transfer Yes
Noise Level As per IS: 12065
Vibration Level As per IS: 12065
BEARING
Make SKF / FAG
Type Antifriction
Recommended lubricant Grease (IOC-SERVOGEM-3/EQV)
Catalogue No. (DE/NDE) NU218M + 6218C3 / NU216M
Life 40000 Hrs.
For FOL system
a) Oil flow (LPM) per bearing NA
b) Max / Min. oil pressure (kg-m2) NA
MISCELLANEOUS
Type of mounting Horizontal
Moment of inertia (GD2) KG-M²
a) Load (referred) to motor speed 600 Kg-m² but the motor shall be coupled with
fluid coupling having MI=4.95 Kg-m² for
primary part
Motor 22.8
OGA Drawing no. 34020046203
Surge Withstand Voltage (Stator winding/coil) As per IEC: 60034-15
a) 0.3/ 3 Microsecond Surge (kVp) 20.41 (For inter turn insulation)
b) 1.2/ 50 Microsecond Surge (kVp) 31.40 (For main insulation)
WEIGHTS (APPROX)
Stator (KG) 4010
Rotor (KG) 490
Total (KG) 4900
Motor is suitable for operation at 6.3KV and shall deliver full power.
SMART POSITIONER
YT-3400/3450 series Smart Valve Positioner accurately controls valve stroke in response
to an input signal of 4-20mA from the controller. Built-in micro-processor optimizes the
positioner’s performance and provides unique functions such as Auto-Calibration, PID
Control, Alarms, and HART Protocol Communications.
LABEL DESCRIPTION
INSTALLATION
SAFETY
When installing a positioner, please ensure to read and follow safety instructions.
1. Any input or supply pressures to valve, actuator, and / or to other related devices
must be turned off.
2. Use bypass valve or other supportive equipment to avoid entire system “shut
down”.
3. Ensure there is no remaining pressure in the actuator.
YT-3400/3450R INSTALLATION
YT-3400/3450R should be installed on rotary motion valve such as ball or butterfly type
which uses rack and pinion, scotch yoke or other type of actuators which stem rotates 90
degrees. Before proceeding with the installation, ensure following components are
available.
1. Positioner unit
TLT ENGINEERING INDIA PVT. LTD. Page 16 of 68
2. Fork lever and lever spring
3. Standard rotary bracket (included with the positioner)
4. 4 pcs x hexagonal headed bolts (M8 x 1.25P)
5. 4 pcs x M8 plate washer
INSTALLATION STEPS
Safety
Supply pressure should be clean and dry air – avoiding moisture, oil or dust.
Always recommended to use air filter regulator (i.e. YT-200 series).
Young Tech Co., Ltd has not tested positioner’s operation with any other gases
other than clean air. Please contact Young Tech Co., Ltd for any questions.
TLT ENGINEERING INDIA PVT. LTD. Page 17 of 68
Supply Pressure Condition
Piping Condition
Connection – Actuator
Double acting type positioner is set to use OUT1 and OUT2 port. As input signal
increases, the supply pressure will be supplied through OUT1 port.
NOTE :
Make sure that non-shrinkage type grout materials are used.
NOTE :
Top surface level of bearing pedestal should be check by master level.
Permissible deviation is 2 division of master level having accuracy
0.05mm/meter. This level should be obtained by adjusting steel packers in
between base frame and foundation.
15. Installed bottom half of the casing on the packer plates and bolt it.
16. Check the casing Centerline, level and center height with respect of bearing
TLT ENGINEERING INDIA PVT. LTD. Page 19 of 68
pedestal.
ROTOR ASSEMBLY
17. Sling the booster rotor assembly consisting of impeller, hub, shaft, bearing and
bearing housings.
NOTE :
Do not use metal sling directly on the shaft during the installation.
18.Position the booster rotor assembly on the bearing pedestal and bolt it.
19.Check shaft alignment in respect of bearing pedestal Centre line by shifting bearing
housing.
20.Check bearing skews on both sides bearing housing with filler gauge.
21.Tight all housing fixing bolts.
22.Check shaft levels on coupling seating area by using master level. This level should be
within 0.05mm/meter. For adjust the level brass shims or SS shims to be used in
between bearing pedestal and bearing housing.
23.Tight all housing fixing bolts. Booster shaft should not be disturbed throughout the
installation hence after.
24.Check pedestal level once again.
25.Apply a thick layer of rubber solution (Pedilite 998) on the parting flanges of casing
and inlet cone and use neoprene rubber gaskets for sealing purpose.
26.Install top half of casing with inlet cone and bolt it.
27.Tighten the parting flange bolts.
28.Position the inlet cone and check the cone gap and overlap.
NOTE :
If desired gap & overlap between inlet cone & impeller is not achieved then
casing can be adjusted in order to achieve the same.
29. Check the distance between the shaft and the PCD of the flange welded on the
casing for labyrinth seal. Equidistance to be achieved all around by adjusting the
casing. Maximum deviation of 2mm is permissible.
30. Insert the coupling half on the fan shaft by heating the coupling hub in hot oil
bath up to 130~135°C and insert the other half of coupling on motor shaft.
31. Place the motor on base frame and align motor shaft with respect to booster shaft.
Brass shims or SS shim to be used for alignment. Align of coupling should be
done using two axial dial gauge and one dial gauge for radial. Coupling gap must
be as per drawing.
Allowable radial misalignment max. 0.05mm
Allowable axial misalignment max. 0.05mm
32. Arrange for final grouting of fan and motor base frame & pockets for casing by
using non-shrink type grout material.
33. Allow the grout to dry long. (Min. 72Hrs). Proper curing of the grouting should be
ACCESSORIES
35.Fix the inlet damper with the inlet cone.
36.Fix the inlet & outlet flexible connection.
37.Fix the Labyrinth shaft sealing arrangement.
NOTE :
Ceramic Rope Gasket with sealant should be on the flanges of above.
NOTE :
Whenever welding is carried out on the fan parts during erection at site
condition, direct earthing to be given, to avoid current passes through the
bearings.
The stator section consists of the following components: Inlet cone (8.1) & Casing (8).
Control is by inlet butterfly damper.
All stator parts are spilt so that an impeller change is possible without any difficulty.
The housing rests on a separate support, which ensures a sufficiently constant position of
the shaft penetration points even in case of large expansion by temperature (centerline
support).
The rotor consists substantially of the following parts: Shaft (2), Impeller (1) with hub
attachment & Fluid Coupling (5).
At each end the shaft is provided with a center hole. The threaded center bore holes are
used for mounting the bearing, the coupling and the impeller. They must in no case be
used for transport purpose.
4
3
It consists of the back plate (1) with hub (5) and support cone (4), the shroud (2) and the
interposed blade (3). Impeller and shaft are dynamically balanced in the assembled
condition.
A
VIEW AT A-A
(CLOCKWISE)
5
TLT ENGINEERING INDIA PVT. LTD. Page 23 of 68
1.15. IMPELLER SEAL DESCRIPTION
The fan impeller sealing consists of a sealing tape which is stretched around the inlet cone
by means of two clamping angles and hexagonal bolts.
The sealing tape end projecting beyond the inlet cone engages into the groove of the fan
impeller and inlet ring.
GENERAL
The ready-to-operate condition of the booster fans is established only when the work and
tests described under. “MAINTENANCE” is completed and has been entered into protocols.
The work to be performed under point 1 until start-up of the machines has to be done in a
chronological order which is not interrupted. When interruption is absolutely necessary,
the checks and tests have to be repeated.
The “CHECKS” under points 1, 2 and 3 have to be made and entered into protocols upon
each and every start-up. Confirmations to this effect have to be entered into the checklist.
The installation dimensions of the fan rotor, the coupling half distance and the position of
the impeller sealing means, if any, have to be checked on the basis of the instructions for
installation.
The sense of impeller rotation and the position of the blades with respect to the volute
have to be checked on the basis of the accompanying sketch. Casing and inlet box, if any,
shall be free from foreign matter and water. Inspection doors shall be closed tightly. The
sense of motor rotation shall agree with the sense-of-rotation arrow on the design.
All bolts on motor, bearings, and casing as applicable, shall be tightened up firmly.
The protective hood for the coupling/belt drive shall be mounted. The bearings shall be
checked with correct quantity of lubricant.
The dampers in the line upstream and/or downstream of the fan shall be closed
CONTINUES OPEARTION
Fan running shall be steady and free from trouble; steady running and noise produced by
running shall carefully be observed during the initial operating hours.
The bearing temps shall be supervised until constant temp has been established after
some hours.
When unsteady running is observed or the bearing temps. are raising permanently or
exceed 100ºC., the fan shall be shut down for finding and eliminating the cause.
The fan shall be started with closed damper flaps / vanes in order to avoid over loading of
the driving motor. For safety reasons no persons should stay in the coupling / pulley and
rotor zone during start – up procedures.
The damper flaps / vanes shall be opened after operating speed has been reached.
Operation with closed damper should not be continued for too long time, because the fan
would be heated to an excessive extent.
The conditions for carrying out the trial run are given when erection of the fan is
completed, the work described under 2.2 “checks prior to starting have been performed
and the concrete grout has fully set.
Driving motor to be switched on slowly open the damper flaps/vanes after the motor has
run up-to the speed.
The bearing assembly has to be supervised during the initial running hours.
The checks are to be based on the instruction for installation, operation and maintenance
of the bearings.
BEARING TEMPEARTURE
During the initial hours, the bearing temperature shall raise evenly up to 95ºC with
ambient temperature around 40 – 45 ºC.
When the bearing temperature is raising beyond 120ºC, immediately switch off the driving
motor and determine the causes of high temperature.
Permanently supervise the noise and vibrations produced during the initial running
hours.
Rolling bearings should be stored in a cool, clean, low humidity environment free of dust,
shocks and vibrations. Storing bearings directly on the floor should therefore be avoided.
If stocks of bearings are kept, it is important to impose the practice of stock rotation.
Bearings are preserved and packaged to ensure that when complying to these storage
circumstances the storage life will be several years.
The simplest and most effective bearing maintenance is to keep the bearing clean.
Contamination will shorten the life of any bearing and the importance of cleanliness
cannot be overstressed.
1. Make sure that housing and shaft are clean and not damaged.
2. Make sure that the new bearing is identical to the one being replaced
3. Ensure that the lubricant to be used is clean and of the correct specification.
4. Make sure the necessary tools and equipment are at hand.
5. Keep the work area clean.
1. Do not try to wash the bearing. The preservative used is compatible with mineral
based oils and greases and should only be removed from the bore and the outside
diameter of the bearing's outer ring. A lint-free cloth dampened with a cleaning
agent is suitable for this purpose.
2. Ensure that the mounting forces are only applied to the bearing ring with the
interference fit.
3. Use a minimum force with maximum control method.
4. Lightly coat the mating surfaces with oil.
1.20.1. DESCRIPTION
Oil Lubricated anti-friction bearings are installed into the horizontally split housings. The
Bearings are seated with their cylindrical bore directly on the shaft.
LOE bearing housings are specially designed for fixed and free bearings so that it is not
necessary to install fixing rings. The total axial displacement of the free bearing amounts
approx. 20mm.In the LOE housing the upper part is connected with the lower part by four
bolts. Two tapered centering pins prevent incorrect assembly of the housing part. The
housing lids are undivided. The oblong holes in the housing feet for attachment enable
subsequent alignment on the sub base. Pinholes are provided for avoiding re-alignment of
the housing upon erection after a plant revision, if any.
For bearing applications where speeds and operating temperature are such that oil
lubrication is necessary and high reliability is required the oil slinger ring lubrication
method is recommended. The slinger ring serves to bring about oil circulation. The ring
hangs loosely on labyrinth ring on the shaft at one side of the bearing and dips into the oil
in the lower half of the housing. A bolt keeps in the lower part of the housing so that it
may not leave the groove of the labyrinth ring during operation. As the shaft rotates, the
ring follows and transports oil from the bottom to a collecting trough. The oil then flows
through the bearing back into the oil sump at the bottom.
LUBRICATION
The frequency with which it is necessary to change the oil depends mainly on the
operating conditions and the quantity of oil. The lube oil may be introduced through the
breather existing in the upper part of the housing. The oil level may be checked by means
of oil level indicator threaded into a lug, which is integrated cast to the lid. After the initial
300 to 500 operating hours it is advisable to drain the oil and to check the lubricity. The
result of this check constitutes a reference point for determining the oil change intervals.
TLT ENGINEERING INDIA PVT. LTD. Page 28 of 68
In the case of hot gas fans it is advisable to carry out a further oil change after
(approximately) 1,000 operating hours. The further oil changes shall be established
according to the results of the oil investigations. The following course guidance value may
be given: approximately 2,000 hours in the case of hot gas fans. In order to prevent
impurities from penetrating into the housing a grease chamber with re-lubricating
capability is located by the side of the labyrinth rings.
1.20.2. ERECTION
Prior to fitting the anti-friction bearing (1) the housing lid (7 or 8, respectively),one sealing
disc.(15) as well as the labyrinth ring (11) will be pushed on to the shaft, while the oil
feeding ring (13) is placed in the groove of the labyrinth ring. The anti-friction bearings (1)
shall be heated to a temperature of approximately 80 to 90ºC different methods may be
chosen for heating e.g. SKF heaters, oil bath, heating cabinet. Be sure that the bearing
The anti-friction bearing (1) will now be pushed onto the shaft. Immediately thereafter
screw on the shaft nut (2) with the securing plate (3) and tighten it up to an extent
ensuring that the bearing inner race, with the labyrinth ring (11), fully rests on the shaft
collar during cool down.
Nut (2) has to be re-tightened and secured after cool down of the bearing (1), with one lug
of the securing plate (3) being into one groove of the shaft nut (2). The labyrinth ring (12)
will be pushed on as far as the shaft nut (2) and will be secured by means of the threaded
pin (20)
The maximum possible shifting of the outside bearing ring in axial sense in the casing
ranges between 0 to 0.9 mm.
On the one hand the allowance is required for manufacturing reasons and on the other
hand it safeguards that the seals rest perfectly between the casing body and the casing
covers.
Shaft with the mounted bearings to be placed into the housing bottom (4) , fixing bolts to
be un-tightened (in order to prevent warping of the bearing assembly),housing to be
aligned and to be bolted again tightly to the foundation.
Securing pin (18) , provided for preventing the oil slinger ring (13) from jumping out of the
labyrinth ring groove, to be slipped into the housing bottom (4)
The housing top (4a) to be mounted both tapered pins (19) for centering the housing parts
(4 and 4a) to be driven home, the pull-off nuts (23), with the washers (26) to be screwed
on. They will be tightened slightly so as to prevent the tapered pins from loosening.
Housing top and bottom to be screwed up with hex bolts (16) and lock washers (24)
Sealing faces of the housing body (4 and 4a) as well as of the housing lids (7 to10) to be
coated with a non-hardening sealing compound, e.g. Wpple 39 of Hylomar SQ 32/M.
After the venting time prescribed by the producers of the sealing compound, firmly screw
the housing lids (7 to 10) with the sealing disc (15) and the housing body (4 and 4a). The
hex screw (17) with the lock washers (25) are provided screw in and tighten screw plug
(14) with sealing ring.
The angular oil level indictor (30) , the plug screws (22) and one angular thermometer, to
be fitted into one plug screw drill hole with one sealing ring each.
In order to ensure that the bearing housing will occupy the same position when being
fitted again in future, the foundation will be drilled through the pre-drilled pinholes in the
housing feet and the housing will be fixed by means of pins.
DISMANTLING
Screws (16 and 17) to be un-tightened and tapered pins (19,23 and 26) to be removed:
Removing the securing pin (18) shall not be overlooked, because otherwise the oil slinger
ring (13) will be damaged.
Shaft to be removed:
Lug of securing plate (3) to be bent up, shaft nut (2) to be loosened and to be removed
with the securing plate:
START-UP
After the vent top (31) has been screwed off prior to start-up, oil shall be introduced into
the pedestal bearing housing until the oil level prescribed has been reached. It is
advisable to mark this oil level on the oil level indicator (30). The oil level shall be checked
during downtime, because in operation it will fall by some millimeters.
The bearing assembly shall be checked every day for quiet running (by listening) and for
normal temperature (by touching or by means of a thermometer). Irregular noise and
temperatures rising beyond the normally measured value indicate troubles the cause of
which shall be eliminated immediately (e.g. unbalance). Also the oil level shall be
supervised every day on the sight glass (30), preferably during downtime.
After the initial 300 to 500 operating hours it is advisable to drain the oil and to check the
lubricity. The result of this check constitutes a reference point for determining the oil
change intervals. In the case of hot gas fans it is advisable to carry out a further oil
change after (approx) 1,000 operating hours. The further oil changes shall be established
according to the results of oil investigations. The following course guidance value may be
given: approx 2,000 hours in the case of hot gas fan.
The oil slinger rings (13) are subjected to wear and tear. This is the reason why they shall
be checked for their condition at certain intervals of time. This may be done in
combination with usual checks, e.g. upon an oil change, by taking off the housing top.
In order to prevent impurities from penetrating into housing, the side of the labyrinth
rings locates a grease chamber with re-lubricating capability.
After the first fill, introduce sealing grease through grease fittings (29) only upon
requirement and in quantities, which are not too large in order to prevent the penetration
of grease into the inner oil space.
The intervals for re-lubrication shall be established on the basis of the operating
experience and the danger of contamination. Upon so doing, the shaft should slowly be
turned by hand so as to achieve better distribution of the grease.
SCHEDULE OF LUBRICATION
OIL
OIL LEVEL
LEVEL QTY.
(MM) QTY.
HOUSING HOUSING (MM) (LTR
(LTRS)
Ma S)
Min Max Min
x
LOE 214 50 65 1.3 LOE 226 55 75 2.3
LOE 217 50 65 1.4 LOE 228 55 75 3.7
LOE 218 50 65 1.5 LOE 230 65 90 4.2
LOE 220 50 65 1.7 LOE 232 65 90 4.7
LOE 222 50 70 2.1 LOE 234 90 105 6.0
LOE 224 50 70 2.3 LOE 236 90 110 6.0
SCHEDULE OF LUBRICATION
The PREMIUM FLUID COUPLING type “PST” is an adjustable speed fluid coupling designed for
mounting between an electric motor and a driven machine (such as a pump or a fan), to enable
the speed of the driven machine to be varied over a wide & stepless range while the motor runs
at constant speed. The power of the motor is transmitted smoothly & shocklessly by the kinetic
energy in the oil flowing between the input and output elements of the coupling.
The “PST” type of fluid coupling provides the ability to control continuously while the set is
running, the quantity of oil circulating between the input & output elements, thus enabling the
torque transmitted and/or the output speed to be controlled. With a constant speed electric
motor therefore, the speed of the driven machine can be varied infinitely over a speed range of as
much as 5 to 1 by the operation of the scoop control of the “PST” fluid coupling. With constant
torque drives, the speed range available could be upto 3 to 1. Automatic control can be easily be
arranged to enable the correct output of the pump of fan (or other machine) to be maintained at
all times according to the demands of the system.
The efficiency of drive is high - full load is carried with a very small speed loss.
For other applications, the PST type fluid coupling can be used as a reliable, non-wearing
alternative to clutch, with smooth pick-up and release of the load, while the motor runs
continuously.
The bearings supporting the rotating parts are carried in housings which are detachable
from the coupling box. For maintenance, therefore, the rotating parts and bearings can be
lifted out without disturbing the motor, coupling box or driven machine.
As the input and output shafts of the type PST fluid coupling are fully supported within
the box, the connections between the fluid coupling and the driving motor and the driven
machine must be made by fully flexible couplings.
The oil circulating pump is provided for circulating oil in to the working circuit.
o OIL FILTER
OIL COOLER
Flanged connections are provided on the coupling box for pipework to the external oil
cooler (oil coolers).
OIL LEVEL
The fluid coupling has site window in the side of the box, to indicate oil level.
SCREW THREADS
The threads used on this fluid coupling are of Grade 8.8/10.9 asper IS - 1367.
Tip of the scoop tube extended to a Radius slightly Greater than that of the working
circuit scoop 'Trims' All the oil from rotating members and returns it to the sump for
recirculation, Output shaft stationary.
INTERMEDIATE SPEED
Scoop tip withdrawn to intermediate radius. Working circuit and scoop casing partially
filled to level determined by scoop tip. Output shaft and driven machine running at
reduced speed.
FULL SPEED
Scoop tip retracted to inner radius of scoop casing. Working circuit full of oil and full
power is transmitted to the output shaft at maximum speed.
OPERATION
The impeller, driven by the motor, and the runner, which is connected to the driven
machine, both have a large number of straight radial vanes. When running, the working
circuit of the fluid coupling is filled with oil and the impeller behaves like a centrifugal
pump, creating an outwardly flowing stream of oil, which crosses the gap to the runner,
which acts as a turbine. The oil stream given up power as it returns to the impeller again,
the cycle is repeated.
Thus, when running, power is transmitted from the motor to the Driven machine through
the rotating vortex of oil.
When the fluid coupling is at rest, the oil is well below the openings in the box through
which the shafts pass. Before starting up the set, the main oil pump driven by the electric
motor should be started, - on starting up the set, the main oil pump of the fluid coupling
raises the oil from the coupling sump and delivers it through the heat exchanger. The oil
then flows through scoop housing into the working circuit via drilled ports of the impeller.
A 100% oil filter is provided between the fluid coupling and the heat exchanger.
All the time the coupling is running, oil is escaping from the working circuit through ports
in the impeller into the scoop chamber. The tip of the adjustable scoop, sliding radially in
the scoop housing, has its open tip projecting into the scoop chamber. The movement of
this scoop is controlled externally and the radial position of the tip determines the depth
of oil permitted to remain in the scoop chamber, and hence in the working circuit. The oil
trimmed out of the scoop chamber by the scoop tube returned to the sump (tank) for re-
circulation.
The speed of the output shaft is determined by the volume of oil in the working circuit and
it may be seen that this, is controlled by the depth of the ring of oil in the scoop chamber
and regulated by the position of the tip of the scoop tube.
Moving the scoop tube into the rotating ring of oil, progressively removes the oil from the
scoop chamber and from the working circuit and discharges it into the sump (tank).
Before the set is started up, the sump tank of the fluid coupling must be correctly filled
with oil. Approved oils for use in PREMIUM FLUID COUPLING are as below:
MAKE GRADE
Indian Oil Company Servo System-46
Hindustan Petroleum Enklo-46
Bharat Petroleum Tellus-46
If climatic or operational conditions or local requirements dictate any variance from the
recommended oil please contact PREMIUM or their local representative.
Absolute cleanliness of all containers used for handling the oil is essential, especially
freedom from fluffy and gritty particles.
The approximate quantity of oil required to fill the fluid coupling and oil cooler is shown in
DATA SHEET. Oil for the cooler is additional.
Open the inspection plate of the coupling box and pour oil in until the oil level shows
MAXIMUM STATIC (cold oil).
Start up the set (see Section 6) with the scoop in the MINIMUM SPEED position, and run
it for a short while, to circulate the oil through the pipes and cooler and to oil-wet the
system. Shut down and add more oil until the level again shows MAXIMUM STATIC.
The level of oil in the sump of the fluid coupling box should be checked periodically. There
are two level in the sump of the fluid coupling box which indicate (by observation) the
following conditions:-
With the fluid coupling stationary and the oil cold, the oil level should read MAXIMUM
STATIC
With the fluid coupling running at operational speed the oil level should not show less
than MINIMUM RUNNING
OPERATING / INSTRUCTION
STARTING UP
o The oil level in the top window which should read MAXIMUM STATIC when the oil
is cold.
o The coolers; water or air, are functional
The motor can be started with the scoop control set in any position. We suggest during
commissioning that the scoop is set to 'Min. Speed' position for starts, allowing the
drive motor to run upto speed under no-load with the fluid coupling transmitting very
low torque.
RUNNING
When the set is running, the speed of the driven machine is adjusted by operation of
the scoop by the external control. Automatic control can be provided, coupled to the
scoop connection, by means of which the speed of the driven machine is automatically
maintained at the required value.
NOTE :
When running at very low speeds of the output shaft i.e. with the control
near the MINIMUM SPEED position it is possible that a noise may be heard
which does not occur in the normal speed range. This noise is a 'siren' effect
caused by the passage past the scoop tip of the communicating holes
between the working circuit and the scoop chamber, at this particular
position of the scoop. The presence of this sound is normal and does not
indicate any malfunctioning of the fluid coupling.
OIL LEVEL
The level of the oil in the sump tank of the fluid coupling should be checked
periodically by referring to the level. This check should, if possible, be made with the
set shut down, and preferably with the oil cold.
Oil of the correct grade - TELLUS 46 oil is recommended (See Section 5) - should be
added, when necessary, to bring the oil level to the MAXIMUM STATIC position.
The most favorable characteristics for the fluid coupling are obtained when the
temperature of the oil leaving the fluid coupling to the cooler is within the limits
quoted below :
° °
Minimum temperature for most favorable operating characteristic 50 C (122 F)
° °
Maximum normal permissible continuous operating temperature 85 C (185 F)
When a fluid coupling is used for clutching duties rather than speed control, these
observations on minimum temperature are of less significance.
The oil level in the coupling box must be checked by inspecting the appropriate level
every 150 operating hours.
OIL CONDITION
Every 3,000 hours or 6 months, it is recommended that the oil condition is checked.
OIL FILTER
The filter fitted in the oil flow line. It is recommended that the filter element is to be
cleaned or changed when the differential pressure between inlet and outlet reaches 12
p.s.i. (0.80 kg/cm2) or every 1,000 operating hours whichever is sooner.
SCOOP ACTUATOR
Before working on the fluid coupling, ensure that the motor is isolated and the set
immobilized.
During maintenance / service, protect the open coupling to prevent entry of dust and
dirt.
First disconnect the actuator from the scoop operating shaft by removing the
Linkage and Fork. Open the inspection plate (170) by removing the screws (291).
Disconnect the scoop operating shaft (130) from the rod end bearing male (111) by
removing nut (113) and bolt (112) . Remove the coupling box/cover mounting
hexagonal screws (155).
Carefully lift away the coupling cover, using the two lifting holes provided. Store on
wooden blocks to avoid damage to joint face.
Before remounting, clean the sealing surfaces and coat with new sealing
compound, lower cover onto coupling box. Follow the above procedure in the
reverse order to complete the remounting of the coupling cover.
Before remounting the scoop housing assembly, clean the sealing surfaces and coat
with new sealing compound.
Check scoop tip clearance, if necessary adjust clearance with the fork and lock nut
(202,115).
Connect the scoop operating shaft and check that scoop tube assembly moves
freely.
Remove the input half and output half coupling as specified by the manufacturer.
Remove the coupling cover and scoop assembly. Disconnect the Internal pipe (142)
and lubrication pipe of Input bearing.
Note : Hold the Rotating assembly by using crane, before disconnecting Rotating
assembly mounting screws (81).
Remove the Bolts (81) and disconnect Input housing (48) and Scoop Housing
Mounting Plate (91) from the Box both input and output side respectively and
remove Cylindrical Pins (77).
Lift the complete rotating assembly out of the coupling box and lower onto a
wooden cradle or floor.
The assembly now needs to be maintained in vertical position resting on the scoop
casing with the input shaft upwards.
Now take out the Input housing(48) with Roller Bearing outer track (12) located in
it. When the circlip (28) have been removed, jack off the bearing inner track.
The remaining assembly should now be lifted and turned over to rest on the Back
Casing (2) with the output shaft (29) up in the vertical position.
Remove the hex head screw (81) between Housing/Mounting Plate. Remove the hex
head screws (101) of the end cover. Disconnect the External Circlip (40) of the
output Ball Bearing (46).
Now take out the Input housing (48) with Roller Bearing outer track (12) located in
it. When the circlip (28) have been removed, jack off the bearing inner track.
The remaining assembly should now be lifted and turned over to rest on the Back
Casing (2) with the Output shaft (29) up in the vertical position.
Remove the hex head screw (81) between Housing/Mounting Plate. Remove the hex
head screws (101) of the end cover. Disconnect the External Circlip (40) of the
output Ball Bearing (46).
Special jacking arrangement is required to take out the scoop housing (90).
Withdraw the hexagonal bolts (18) and Cylindrical pins (16) between Impeller (4)
and Scoop Casing (3) and lift off Scoop Casing (3). Jack off the Impeller Ball
Bearing (11). Withdraw the bolts (20) and lift off Impeller Bearing Sleeve (5).
Now the Impeller (4) can be made free and taken out by removing the Cylindrical
pins (16) between the Impeller and Back Casing. Now the input shaft
Output Shaft (29) (with Runner (30)) is removed from the Back Casing(2).
Disconnect Output Shaft (29), Runner (30) and Baffle (31) by removing the fitted
Bolts (37) and Nuts (41).
Remove the Ball bearings (38) and (46) from Back Casing (2) and Scoop Housing
(90).
Thoroughly clean all components removing any deposits of sludge, loctite or old
sealing compound.
During the assembly of bearings, we suggest the use of oil bath or induction heater
as follows.
Replace all joints, seals, washers etc. by new ones. All bolts and screws must have
the same number and type of washers etc. as used originally.
o Re-assembly
Fit the bearings (38 & 40) in Back Casing (2) and scoop hsg. (90) respectively.
Connect the baffle (31) and Runner (30) to the output shaft (29) by tightening the
bolts (37) and Nuts (41).
Place the Back Casing with Bearing (38) pointing in the downward direction. Lower
the Output Shaft (29) and attached with the Runner (30) into the Back Casing. Fit
the External Circlip (39) after proper positioning of the Output Shaft in the Ball
Bearing (38).
Invert the present assembly with Output Shaft (29) in vertical position pointing
downwards. Lower the Input Shaft and position on the Back Casing (2). Position
the Cylindrical pins (17) and tighten the Socket head screws (19).
Reposition the current assembly with output shaft in vertical position pointing
upwards. Lower the Impeller (4) and position the dowels between the impeller and
back casing. Now lower the scoop casing and position to fit the cylindrical pins (16)
between scoop casing and impeller. Now lower the Scoop Casing (3) and Impeller
(4). Tighten the bolts by applying the loctite use the washers for locking purpose.
After fitting the Ball Bearing (11) on the Impeller Bearing Sleeve (5) position the
sleeve on to the Impeller (4). Tighten all Screw (20).
Great care is required to mount the Scoop Housing (90) since it is located on the
two ball bearings. After positioning the scoop housing on the Impeller Bearing
Sleeve (5). Fit external circlip to lock the Output Bearing (40) in the position.
Attach the End Cover (92) with Joints (92F & 92G) by tightening the Set Screws
(101). Fit the Seal (92A) with Cover Plate (92D) and Hex Head Screw (92E) in the
End Cover (92). Lower the Scoop Housing Mounting Plate (91) with Joint (91A) and
attach it to the Scoop Housing (90) by tightening the Bolts (81) with washer (82).
This completes the assembly of the output side parts. Now turn the assembly and
place it to rest on the scoop casing with input shaft in vertical and
upward direction.
Position the Bearing abutment ring (1A). Fit the Inner Race of Roller Bearing (12)
and Circlip (28).
Input Housing (48) fitted with Joint (48A) and Roller bearing outer track arrested
by Internal Circlip (89), lower it on Input Shaft (1). Fit the Felt Seal (92A) with
Cover Plate (92D) and Hex Screw (92E) to Input Housing (48).
ASSEMBLY
The sequence of assembly of resilient coupling at site has been illustrated in the pictures.
Method of assembly is the same for both standard type and split-cover type couplings,
except for the fitment of the covers.
Both the hubs of coupling must be fitted on respective shafts in perfect parallel and
angular alignment and simultaneously positioned with correct gap between the inner
faces of the two hubs.
Grooves of both the hubs are to be fully packed with recommended grease before insertion
of the grid spring and also after its insertion in the grooves, liberal quantity of grease
should be applied on the spring along the entire periphery of the hubs. Further maximum
when these are placed in position, through grease nipple provided.
After an initial run at full speed for about an hour, the coupling assembly should be
topped up with further quantity of grease regular run.
MAINTENANCE
Whenever it is necessary to disconnect the coupling for carrying out repair on the driven
machines, the two cover halves to be first unbolted followed by removal of the grid spring.
A round rod or screwdriver of convenient size is inserted into the loop end of the spring
next to one of its free ends and the spring be pried out radially in even, gradual stages.
The same procedure be followed alternatively from side to side until the full spring is
cleared off the grooves. The coupling hubs are now free from each other.
LUBRICATION
INTRODUCTION
Shaft misalignment is the deviation of relative shaft position from a collinear axis of
rotation measured at the points of power transmission when equipment is running at
normal operating conditions. The deviation of relative shaft position accounts for the
measured difference between the actual centerline of rotation of one shaft and the
projected centerline of rotation of the other shaft.
Simply stated, the objective of shaft alignment is to increase the operating lifespan of
rotating machinery. To achieve this goal, machinery components that are most likely to
fail must operate within their design limits.
Since the components that are most likely to fail are the bearings, seals, coupling, and
shafts, accurately aligned machinery will achieve the following results...
1. Reduction excessive axial and radial forces on the bearings to insure longer
bearing life and rotor stability under dynamic operating conditions.
2. Minimize the amount of shaft bending from the point of power transmission in
the coupling to the coupling end bearing.
3. Minimize the amount of wear in the coupling components
4. Eliminate the possibility of shaft failure from cyclic fatigue
5. Lower vibration levels in machine casings, bearing housings, and rotor
Check alignment in one plane at a time. One dial gauge is mounted at the top and the
other indicator at the bottom 180º position. Both the dial gauges are to be set in zero,
and the shafts are rotated together through 180º and the readings a and b taken. The
magnitude of misalignment is (a-b)/2. On further rotation of the shafts back to their
original position, the dial gauges must read zero; otherwise the checks are not valid.
This process is repeated until the face misalignment is less than 0.05mm. Note that the
distance F1 & F2 in the vertical plane as shown in the figure are related to a & b thus:
F2=F1(a-b)/2
Mount the dial gauge as shown in the figure and adjust to zero i.e a=0
Rotate the shafts together in the same direction say to the left by 90º and take the reading
C. rotate the shafts together by another shaft 90º in the same direction, so that the dial
gauge is at the bottom and the reading B is taken. 90º further turn the shafts in the same
direction (total 270º) and the reading D is taken: The two shafts are turned again 90º(total
360º) and the second top dial gauge reading should again be zero. If not, alignment check
is not valid.
1. If b is greater than a, center line of driven shaft is lower than that of motor shaft
by (b-a)/a
2. If a is greater than b, center line of driven shaft is higher than that of motor
shaft by (a-b)/2
3. If d is greater than c, center line of driven shaft is to the right of that of motor
shaft by (d-c)/2
4. If c is greater than d, center line of driven shaft is to the left of that of motor
shaft by (c-d)/2
Shift the center line of motor shaft or that of driven shaft properly, so as to obtain the
correct alignment.
1.26. MAINTENANCE
RUNNING MAINTENANCE
1. Open the inspection door of the casing and clean the impeller blades.
2. Check the erosion of the blades.
3. Check the overlap and radial clearance between impeller shroud and inlet cone. If
found disturbed, adjust the same.
4. Remove used bearing lubricant from the housing and refill with fresh lubricant.
5. Check the bearing condition like roller clearance and the rolling surfaces of races.
6. Check the alignment of the fan & motor coupling. If found disturbed, align the
same
7. Check the Inlet damper flaps movement.
8. Check the tightness of all fixing bolts.
9. Check all electrical connections.
10.Check the condition of inlet & outlet expansion joints. If found damaged, replace
the same.
11.Replace all the used gaskets by new ones of casing parting flanges, inlet & outlet
expansion joints, inlet cone etc.
12.Apply grease after cleaning to the link rods and vane bearings.
In each fan, the impeller represents a source of danger as high-energy body of rotation.
Further dangers also result from hot, corrosive or toxic media conveyed in the
corresponding fans. It is therefore absolutely necessary to fulfill the following
requirements prior to work on the impeller or within the fan casing:
1.27. TROUBLESHOOTING
VIBRATION
BEARING FAILURE
FAN PERFORMANCE
The values according to VDI2056/ISO2372 are guide values, which do not at all take into
consideration the type of the machines, whereas the size and the elasticity are only
conditionally allowed for.
4. All vent valves to be kept open (including booster vent valves) in between the
booster inlet U-Seal (Mkd. 3/5/7) & outlet u-seal (Mkd. 4/6/8)
5. Booster drain valves to be kept open and be sure that the booster drain line to be
terminated at drain pit.
6. Then purging to be done via purging valves and continuous monitoring the
pressure in the pressure transmitter (PT 301,303 / PT 401,403 / PT 501,503) and
the range of purging pressure to be kept at around 2000 mmWC – 3000 mmWC.
7. Purging to be continued till the time O2 level and CO level are at accepted limit.
1. First complete the Nitrogen purging procedure as clause 1.30 mentioned above.
2. All manual valves for purging, venting, sampling line, water line are fully closed.
3. Check Nitrogen pressure for line purging (at field PT 905) 2Kg/cm².
4. Check & ensure nitrogen pressure at shaft seal (Pressure should be more than
0.2Kg/cm² (2000mmWC) but not exceeding 0.3Kg/cm² (3000mmWC)
5. Selected booster drain line’s manual gate valve to be kept open and be sure that
the booster drain line to be terminated at bottom of drain pit (as per document).
7. Inlet & outlet water seal need to be broken for selected booster.
9. Check gas inlet pressure 350 – 500 mmWC (At HMI, check value indicate at
Engineering Station)
10. Check incoming power supply at HT MCC, LT MCC, Lighting Transformer, UPS,
SLDB, LDB, HT Transformer, RCP, ACDB, PLC.
11. Before start the booster check LOCAL/REMOTE selection for booster & all isolation
valves. To start the system from Engineering station, all selector switch to be kept
at REMOTE mode.
2. At Engineering Station, go to the damper (HCV) control page for selected booster. In
this page given all safety interlock & start interlock.
SAFETY INTERLOCK
START INTERLOCK
3. Check all safety and start interlock and ensure GREEN right mark. Green right
mark means OK, booster is ready to start.
TLT ENGINEERING INDIA PVT. LTD. Page 56 of 68
4. AUTO / MANUAL selection has given. Select AUTO / MANUAL mode.
5. Select booster page, check all the condition to start the booster. Motor should be
started only manually and from boosting station only.
6. At Engineering station select motor manual start button and then motor will start.
7. After start the selected booster, POV 306/406/506 will open automatically after
selected time delay.
8. Inlet HCV 302/402/502 open to minimum lockable position (say 25%) to reach
outlet pressure.
9. PCV 203 of Bypass line will work automatically, when process value is lower then
set pressure, then PCV 203 will close automatically and when process value is
higher than set pressure then PCV will open to maintain the set pressure. Under
normal operating condition of PCV 203, POV 202 & POV 204 will be in full open
condition. These two POVs are provided with “Stay Put” logic.
1. Emergency Push Button has given at Local Push Button inside booster house. Any
emergency condition press emergency push button to stop the booster then motor
will go dead stop condition after pressed the emergency push button.
3. With a delay (180 second) outlet POV 306/406/506 and inlet HCV 302/402/502
and PCV 203 (at bypass line) close automatically. Even all gas boosting station
valve will close automatically.
4. When Emergency Stop pressed, other Booster should not be started till the time
Operator investigates all probable causes and satisfies himself – reset Emergency
Button – then go for startup of other Booster.
DON’TS
1. Don’t remove the inspection door when the booster is in running condition
2. While shutting down the booster, it has to be ensured that the motor power connection
is removed before anybody enters in to the fan for any verification/inspection.
3. Do not start the booster before ensuring the damper is in full closed condition.
4. In case of in-situ balancing of the fan, welding should not be carried out on the
impeller by providing direct earthing to the impeller.
5. Do not stop N2 purging to Lab seal while booster in operation.
6. Never charge CO gas to the line without N2 purging and O2 level below 1%.
7. Do not dead stop the booster before complete N2 purge out.
8. Do not enter into the boosting station area without CO detector. Stop all the jobs if CO
leakage goes beyond 50ppm.
9. Do not do any hot job near CO boosting area without checking the gas leakages by CO
detector and without proper fire fighting arrangements.
10.Do not operate any equipment in DE-COUPLING mode without detaching the motors
from driven equipment.
11.Do not isolate the drip pots from the main gas line header while gas is charged in the
line.
PLC Panel shall be installed in the Control Room located in the CO Gas Boosting Station.
All DI/DO/AI/RTD/AO signals of the Gas Boosting Station will be hardwired from the
equipment/instruments upto the field JBs and subsequently from Field JBs to PLC Panel.
There should be one PC based Engineering Cum Operator Station and one PC based
Operator Station with appropriate HMI and Programming software. These PCs will be
located in the Control Room. The function of this PLC system should be as follows :
i. Control of the entire Gas Boosting Station through user interfaced graphics.
ii. ‘Remote / Local’ Selection for all Electrical Drives (Motors & Electrical Actuators)
will be made from local Push Button Station by a Selector Switch provided in the
field and Permission of ‘Local’ needs to come from HMI to enable the person in field
to operate in Local Mode. The detailed Write-up of Auto / Manual and Local /
Remote is attached in Annexure – I.
iii. The Auto/ Manual Selection will be provided on HMI at Operator Console. Under
the Remote Manual Mode, the individual Booster Motors, POVs, MOVs, PCV and
HCVs can be operated from Operator Console of HMI manually.
iv. Real-Time Trending of important parameters.
v. Historical Logging of critical parameters.
vi. Real-Time Alarm Generation and Alarm Logging.
vii. On-Line parameter value and status display on the HMI graphics.
viii. Facility of editing of Ladder Logic and HMI pages, if any changes are required.
a) CO gas shall be available at the Boosting Station Inlet Header from the network at
a Pressure of 350 - 500 mm. Wg. through 1 No. Motorised Valve
b) For Pressure & Temperature measurement at common suction, a PT and RTD is
provided on the main suction Header.
c) For Individual Booster, PT is provided at Inlet of each Booster. An alarm will raise
in the event of pressure falling below 200 mm. Wg. This alarm will call for
corrective action at client’s end to look into the reason for pressure fall.
d) Booster Motor Start / Stop / Trip conditions will be as follows :-
e) Each Booster will have Pneumatically operated Butterfly type Suction Control
Damper (HCV 302, HCV 402, HCV 502). In the event of Booster Motor ‘STOP’ or
‘TRIP’ or ‘Emergency Stop’, corresponding Booster Suction Control Damper will
close automatically and thereby isolate the Booster Inlet to large extent. There is
logic fed to the PLC that the Booster Motor will start if the Booster Suction Control
Damper for respective Booster is close. The HCVs will have “STAY-PUT” logic
f) In the event of Booster Motor STOP or TRIP, after the Suction Control Damper is
automatically closed, positive Isolation is done subsequently by filling the Water
Seal with water by manually operating the water line valves.
g) Each Booster will have 1 No. PT, 1 No. RTD and 1 No. Venturi with Flow
Transmitter at outlet for flow measurement through Individual Booster
iv. When the pressure falls below the set value, it indicates that downstream
flow requirement increases. It will first check the position of Bypass Line
PCV (PCV 203) – if PCV is open, it will start closing till the set value is
achieved in Export Gas Line Pressure. If set value is not achieved by fully
closing the PCV also, the control will be transferred automatically to Booster
Inlet HCV ( HCV for all working Boosters will be getting same signal
simultaneously) which will start opening till the set value is achieved. If set
value is not achieved by fully opening of HCV also, then “Export Header
Pressure Low” alarm will be generated.
v. When the pressure increases in the Export Header (more than set value), it
indicates that downstream flow requirement is decreased. The PLC will first
j) The individual Booster will have Discharge Pneumatically operated Butterfly type
ON-Off Valve (POV 306 or POV 406 or POV 506). Motor will not start if the Valve for
corresponding Booster is not closed. When the Motor trips or stops including
emergency stop, this valve will be automatically closed. Subsequently, positive
sealing will be done by filling the Water Seal with water by operating the valves
manually. This Discharge Isolation Valve of Booster Outlet will also have “STAY
PUT” logic.
k) We have provided RTD type Temperature Element for each Booster Bearing
Housing (Both Fixed & Free Bearing) to sense the temperature of the bearings and
also to get alarm and trip signal through PLC, in case the temperature exceeds the
set limits. Interlocking will be there with the main motor.
l) We have also provided Vibration Transmitter with probe for both Fixed & Free
Bearing Housing for each Booster in order to obtain the vibration measurement in
‘X’ & ‘Y’ Direction for Booster Bearings. The alarm and trip signal will be generated
in PLC and the main motor will be tripped if the vibration exceeds the set point.
Vibration Level Indication will be available in HMI for continuous monitoring.
m) Each Motor will have 12 Nos. Simplex Winding RTDs & 2 Nos. Duplex Bearing
RTDs which will be fed to a Multi-Channel Scanner (fitted in the HT Board inside
Electrical Room). Grouping will be done in the Scanner in such a way that 1 no.
Alarm and 1 No. Trip will be generated for each of the winding and bearing ( Total 3
Nos. for winding and 2 nos. for Bearing of each Motor). These Alarm and Trip
contacts will be connected to PLC panel.
o) In the event of any problem cropped up in the Control Valve PCV 203, 2 Nos.
POVs (POV 202 & POV 204) are provided across the PCV 203 to enable Client to
attend short time maintenance of the PCV 203. However, during the maintenance,
it should be ensured that Boosters are run at optimum level only through the HCVs
Remote Manually from PLC HMI. This means during this time, Boosting Station is
put on Manual Mode. Under normal operating condition of PCV 203, POV 202 &
POV 204 will be in full open condition. These two POVs are provided with “Stay
Put” logic
p) RTD is provided on the Booster Casing Scroll location to monitor the casing
temperature which is likely to rise and then stabilize due to excessive re-circulation
of gas through Bypass line for longer time. Alarm will be generated in case it
exceeds set value.
Purging the Labyrinth Seal of each Booster through manual valve with
standard Filter Regulator Set.
Purging the Booster after shut down and isolating it, if necessary through
separate manual valve.
Purging the water Seals as will be detailed in water Seal Drawings being
submitted separately.
s) Instrument Quality Air will be provided by Tata Steel at Take Over Point at 6
Kg/Cm2(g). Manual Globe Valve will be provided by us at the Inlet main Header. PT
and FT with Orifice are provided at downstream of Globe Valve
t) Venting arrangement will be as shown in the P&I Diagram through Manual valves.
During Nitrogen purging in the Pipe line, the Manual Vent valve must be kept
opened. The Vent Pipe should be installed at certain height above Booster Station.
After the purging is over and before starting the Booster, Vent Valves must be
properly closed to avoid ingress of air.
v) When the Booster is running at low RPM, the steam cleaning operation may be
started (if required) by manually opening the Solenoid Operated Steam Line Valve
from HMI. Once the steam cleaning operation is put on, through a time delay set in
PLC, the Solenoid Operated Steam Valve will be closed automatically. There will be
also an interlock so that during the steam cleaning valve “ON”, the Main Booster
Motor cannot be switched ‘ON’.
Starting of Booster
o The Water Seals at inlet of selected Booster should be drained completely
from Seal and related valves are closed.
o The Nitrogen Purging should be carried out to drive out the trapped air, if
any accumulated during the shut down maintenance etc. Close the Nitrogen
purging valve and close the Manual Vent Valve after purging
o Outlet isolation Valve, Inlet HCV to be manually kept open and closed from
HMI to allow flooding of CO gas in the system.
o The Water Seals at outlet of selected Booster should be drained completely
from Seal and related valves are closed.
o Start the Booster and take the control in PLC.
x) The water at Take Over Point will be taken through a Manually Operated Isolation
Valve and a Pressure Switch will be provided at downstream of manually operated
Valve
y) Steam will be also taken through a manually operated Valve (IBR) and downstream
of this Manual Valve, the Pressure Reducing Valve will be installed to bring down
the steam pressure at 2.5 Kg/Cm2. The IBR Certified valves will be installed
suitably at a location very close to Take Over Point of steam so that downstream of
PRV becomes Non-IBR Steam Line. Pressure Gauge with Steam Trap will be at the
downstream of IBR Valve.
z) For the Booster Drain Line, we shall provide 2 nos. manual gate type Isolation
Valves in parallel and Drain Line will be finally terminated to Drip Pot or Drain Pit
outside the Booster House as shown in the P&ID.
Booster
AT 601,602,603,604,605 Industrial
CO Monitor Station TLT
Scientific
Building
New Boosting
----
PLC Panel Station Rockwell TLT
Control Room
1 No.
Operator
HMIs For 1 No. Station in
---- Real Time TLT
Operator Station Booster
Station
Control Room.