Technical Data R1272: Ramcro - BMS-HFFR-TC Cable Single Pair, LSZH/FRNC-Insulation, Collective Screened, LSZH/FRNC-Sheath

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Technical Data

Document Reference R1272


Data Sheet

RAMCRO - BMS-HFFR-TC Cable


For standard applications, flame retardant.

Single pair, LSZH/FRNC-Insulation, Collective Screened, LSZH/FRNC-Sheath

MAS0105HXEDN-T-RB
Application
LSZH - FRNC sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio, Security, Safety, Control and Instrumentation.

Construction
Nominal
Formation 1 Pair Unit Value
Section 18 AWG
Conductor Tinned copper wire, 7 strand mm 1,1
Insulation Thermoplastic Low Smoke, Halogen Free - LSZH (FRNC) mm 2,2
Colour Code Black, White

Individual Screen N.A.


Wrapping at least 1 layer of plastic tape 0,023 mm
Collective Screen 0,026 mm Aluminium / PETP tape over tinned copper drain wire

Inner Sheath N.A.


Armour N.A.
Outer Sheath Thermoplastic Low Smoke, Halogen Free - LSZH (FRNC) - Purple RAL 4005 mm 6
RAMCRO ITALY R1272 DATA LAN CABLE - M-BUS - 1PR 18 AWG
Cable Printing
SCREENED LSZH (FRNC) 300 V 75 C IEC 60332-3-24 -MAS0105HXEDN-T-RB -
'PROD.WEEK/18' + BATCH + METER MARKING

Technical Data & Standard References


Fire Propagation:
- Test on single cable IEC 60332-1
- Test on bunched cables IEC 60332-3
Type of Cable: BMS-HFFR-TC Cable
Low Voltage Directive 2014/35/UE
Other References:
Smoke Density IEC 61034
Amount of halogen acid gas ZERO
Acidity (ph value) and conductivity IEC 60754-2
Sunlight resistance UL 1581 section 1200
Notes

Electrical & Mechanical Data

Conductor Cross-section Nom. 18 AWG Temperature Range:


DC Resistance per core at 20° C max Ω/km 23,2 During Operation °C -30°C up to 80°C
Insulation Resistance at 20° C min MΩ*km 25 During Installation °C -30°C up to 80°C
Nominal Mutual Capacitance max pF/m 125
Inductance max mH/km 1 Min. Bending Radius mm 8 x cable diameter
Test Voltage - Core/Core V 2000 Max Pulling Tension N/mm2 78
Test Voltage - Core/Screen V 2000 Weight Approx kg/km 49

Operating Voltage V 300 Put up length mt 305

Issued by: Davide Date of issue:


Prepared by RAMCRO Tech Via Marzorati, 15 - 20014 Nerviano - Milan - Italy / www.ramcro.it 17/01/2019 00:00