Data sheet

Accupack with charging controller: LDR2024


Technical data
General data
Type LDR2024
FEAS Order number 589920
Product description Accupack with electronic charging controller
Product function DC power supply

Input data
Min. input voltage UIn Min 18.0 VDC
Max. input voltage UIn Max 50.0 VDC
Charging current ca. 0.3 A
Charging time max. 6 h
Protective circuit -

Output data
Output voltage Unominal 20.0 - 27.0 VDC following the accu-voltage
Buffered voltage Ubuffer 20.0 - 27.0 VDC following the accu-voltage
Output current Inominal 1.0 A
Current limiting -
Residual ripple (20MHz) <50mVPP

Control data
Control deviation load -
Control deviation supply -
Control time -
- konform Operating data
Duty circle (ED) 100% (continuous operation)
Capacity C 2.6 Ah (20°C)
Buffering-time typ. 1.0A - 2.5h (see graph on the left)
Efficiency ca. 82% (grid operation)
Parallel connection No
Operating temperature range -20°C to +50°C
Derating from 40°C
Discharge current diagramm at 20°C Storage temperature range -20°C to +50°C
Load (A) è

Cooling selfcooling
2,0
recommended respective distance 15mm each
Installation altitude unlimited
MTBF > 380.000h
1,5

LDR2012
Safety devices
Fuse for input recommended, 2.5 A slow blow at 24 V UIN
1,0 Fuse for output not necessary - short circuit proof
Overload protection integrated into device

LDR2024
Safety data
0,5
Test voltage transformer -
High voltage resistance -
0
Degree of EMI suppresion according VDE0871B, EN55022/B
0 60 120 180 240 300 360 420 480 540 600 660 720 780 840 900 960 1020 1080 1140 1200 1260 1320 Protection class G
Class III
2h 4h 6h 8h 10h 12h 14h 16h 18h 20h 22h
Discharging period t (min) è Extra low safety potential PELV (EN60204), SELV (EN60950)
Ambient humidity 95% relative humidity, yearly average
dewing allowed for use in tropical ambient
Protective class enclosure IP44
Protective class terminals IP20 (BGV A3)
Vibration proof up to 5g at 33Hz in X, Y and Z
acc. IEC68 and DIN41640
Status & Signal
Status indicator LED - Operation, Charging, Buffer-mode
Signals Relais - Line-In, Accu-protection
Products of the series: Interfaces sleeping-mode

Applied construction regulations


Type LDR2012 LDR2024
according to VDE VDE0100, VDE0110, VDE0113, VDE0551,
VDE0806
Order number 589921 589920
IEC IEC60950-1, IEC61000-6-1-2-3-4, IEC60068-2-3,
IEC60068-2-11-52, IEC60529
Output voltage 10.0 - 14.0 VDC 20.0 - 27.0 VDC EN EN60950-1, EN61140, EN61000-6-1, EN61000-6-2,
EN61000-6-3, EN61000-6-4, EN55022, EN55011
EN61000-3-2, EN61000-3-3, EN60204
Output current 1.8 A 1.0 A
EN60529, EN61000-4-2-3-4-5-6-8-11, EN60068-1,
EN6068-2-1, EN61558-2-17
Capacity (20°) 5.2 Ah 2.6 Ah EN61010-1
CSA/UL CSA-C 22.2 / UL60950, UL508, UL1950
Charging-current 0.6 A 0.3 A Mechanical data
Mounting on Rails according to DIN 46277 or wall
2,5 h 2,5 h
Buffered time typ. 1.8 A typ. 1.0 A Dimensions (W x H x D) 100mm x 75mm x 110mm
Weight approx. 1.45kg

Postfach 1521 Phone: +49 4102 42082 E-Mail: [email protected]


D - 22905 Ahrensburg Fax: +49 4102 40930 Internet: www.feas.com