Manual
Manual
Manual
PREVENTATIVE MAINTENANCE
M A N U A L
COMPACT HIGH POWER OUTDOOR UNIT
0104700500r2
For Use With Model Numbers...
T07DO
T07CO
Manufacturing
East Coast Operations
45 River Drive
Georgetown, ON
Canada L7G 2J4
PROPRIETARY INFORMATION
The design and other information contained in this document are provided solely for the
installation, operation, and maintenance of CPI equipment. Except for rights expressly granted
by contract, all such information is the exclusive property of CPI, Satcom Division. This
document may not be duplicated, in whole or in part, or be used for manufacture without
written permission of CPI, Satcom Division.
Copyright © 2010 by Communications & Power Industries, Inc. All rights reserved.
TABLE OF CONTENTS
Operational Warnings 0103910900
Safety Section 0104002200
Chapter 1 0104720100 Rev.2
Introduction
Chapter 2 0104720200 Rev.2
Unpacking and Installation
Chapter 3 0104720300 Rev.2
Operation
Chapter 4 0104720400 Rev.1
Preventative Maintenance
Chapter 5 0104720500 Rev.2
Drawings
Appendix A 0104002500 Rev.2
Support Information 0103098900
Product Warranty SC4133
TWT Warranty PUB5370
Warranty Return Form MF-1024
Appendix B 0104002400 Rev.4
Optional L-Band BUC
Appendix C 0104682700 Rev.1
Messages
DOC.01047200 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED iii
TOC
1-1
Chapter 1
Introduction
Table of Contents
CHAPTER 1 INTRODUCTION ...........................................................................................................1-1
1.1 OVERVIEW.................................................................................................................................1-3
1.6 CONVENTIONS..........................................................................................................................1-8
1.6.1 NOTES AND CAUTIONS ......................................................................................................1-8
DOC.01047201 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 1-1
INTRODUCTION
List of Figures
Figure 1-1. Front View............................................................................................................................1-4
List of Tables
Table 1-1. Model, Frequency Range, and Rated Output Power ......................................................1-3
1.1 Overview
The CPI Compact High Power Outdoor Unit (Compact HPA ODU) is designed for satellite
communication earth stations, satellite newsgathering vehicles, and flyaway applications. The
key feature of these amplifiers permits direct mounting to antenna structures, thereby
eliminating transmission line losses encountered in conventional remotely mounted
arrangements. Table 1-1 shows the model numbers, frequency ranges, and power output of
these amplifiers. Figure 1-1 is a photograph of a standard Compact HPA ODU as all models are
similar in appearance.
By industry convention, amplifiers are classified by the rated power level of the internal
traveling wave tubes (TWT). In actuality, the TWT's rated power is attenuated by the output
component thus decreasing the overall rated power of the amplifier at the output flange. Refer
to the "Drawings" chapter for specifications and a detailed outline.
DOC.01047201 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 1-3
INTRODUCTION
All base models are equipped with an Ethernet jack and are TCP/IP enabled. This allows a
remote PC within the same network as the amplifier running a web browser application the
ability to control and monitor the amplifier.
An outline drawing can be found in the “Drawings” chapter. Detailed dimensions and the
interface connector locations can be found on the outline drawing.
DOC.01047201 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 1-5
INTRODUCTION
1.4.4 Linearizer
A linearizer is used to improve the AM/PM, third order intermodulation products, spectral
regrowth, and NPR performance. An amplifier with a linearizer operating at 4 dB total
output backoff and an amplifier without a linearizer operating at 7 dB total output backoff
would have similar performance. The linearizer is tuned at the factory to provide linear
power across the entire frequency band of the amplifier.
This option may include a built in SSIPA in addition to the linearizer. This feature is
referred to as a LIPA and functions both as a linearizer and SSIPA.
DOC.01047201 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 1-7
INTRODUCTION
1.6 Conventions
Symbols and conventions used throughout this manual are described in the sections that follow.
2-1
Chapter 2
Unpacking and Installation
Table of Contents
CHAPTER 2 UNPACKING AND INSTALLATION .........................................................................2-1
2.1 OVERVIEW.................................................................................................................................2-3
2.3 UNPACKING...............................................................................................................................2-3
DOC.01047202 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 2-1
UNPACKING AND INSTALLATION
List of Figures
Figure 2-1. External Interface Locations .............................................................................................2-4
Figure 2-2. J8, Tightening Sequence and Location ............................................................................2-7
Figure 2-3. Programmable Relay Schematic.......................................................................................2-8
Figure 2-4. J10, Serial Remote Pin Designation Diagram ...............................................................2-10
List of Tables
Table 2-1. Recommended Torque ........................................................................................................2-6
Table 2-2. J5 Pin Designations ..............................................................................................................2-8
2.1 Overview
This chapter contains instructions for unpacking and installing the amplifier. Read all
instructions to become familiar before proceeding. All external interfaces are detailed in this
chapter as well.
2.2 Pre-Inspection
Inspect the exterior of the shipping container(s) for evidence of damage in shipment. If damage
is evident, immediately contact the carrier that delivered the equipment and submit a damage
report. Failure to do so could invalidate future claims.
2.3 Unpacking
Carefully unpack and remove all items from the shipping container(s). Inspect the interior of
the container for damage. Save all packing material until all inspections are complete. It is
recommended that all packing material be saved for potential future use. Verify that all items
listed on the packing slips have been received.
Inspect all items for evidence of damage in shipment. If damage seems evident, immediately
contact the carrier that delivered the equipment and file a claim. Failure to do so could
invalidate future claims.
DOC.01047202 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 2-3
UNPACKING AND INSTALLATION
It is recommended that locations subject to electrical interference, such as that from motor
contactors, be avoided.
Heat produced during operation is conducted through heatsink fins which are cooled by a
central blower. The intake and exhaust areas must not be blocked. The air intake must be given
a minimum clearance of two inches and the air exhaust must be given a minimum clearance of
four inches. The hot air should be exhausted away from the air intake. For further information
see the outline drawing located in the "Drawings" chapter.
Prime power is applied to connector J1 (AC IN) located on the front panel. Prime power is 200 -
240VAC ± 10%, 47-63 Hz. The proper voltage is indicated on a label located on exhaust end of
unit. A prime power mating connector is supplied in the ship kit with the unit. The pins of the
prime power connector should be wired as follows:
Pin 1 - line (or Phase A) Pin 3 - Neutral (or Phase B)
Pin 2 - No connection Pin PE - Protective Earth
Prepare the prime power cable but do not connect the cable to the amplifier at this time.
2.4.2.2 Grounding
Proper grounding of the amplifier to the station protective earth bus is necessary for personnel
and equipment safety. The 6-32 UNC-2B threaded ground stud on the front panel is used for
grounding. #14AWG wire or larger is recommended for the grounding cable. The amplifier
should be protected against direct lightning strikes.
Note: The baud rate is fixed at 9600 and cannot be changed. This ensures
both Ethernet and serial communications can be established.
DOC.01047202 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 2-5
UNPACKING AND INSTALLATION
3. After alignment is verified in all planes, loosely attach the mating waveguide to the output
waveguide flange of the amplifier with the 6-32 inch bolts (WR-62/WR-75) or 10-32 inch
bolts (CPR-137), flat-washers, and lock-washers provided in the ship kit. Each bolt should
be dressed with a lock washer and then a flat washer before being used. Start all bolts by
hand and verify alignment.
4. A progressive tightening procedure is recommended. Tighten each bolt until the lock
washer starts to compress before proceeding to the next one. Repeat until all bolts have
been partially tightened.
5. Starting with the first bolt, fully tighten them to the recommended torque per table 2-1.
Over-tighten can strip threads or distort the mating flange. Refer to figure 2-2 for the
tightening sequence.
Frequency Band Waveguide Screw Qty. Screw Size Screw Torque (in/lbs)
Ku Band WR-75 4 6-32 in. 8.5
DBS Band WR-62 4 6-32 in. 8.5
C Band CPR-137 8 10-32 in. 32
DOC.01047202 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 2-7
UNPACKING AND INSTALLATION
DOC.01047202 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 2-9
UNPACKING AND INSTALLATION
3-1
Chapter 3
Operation
Table of Contents
CHAPTER 3 OPERATION...................................................................................................................3-1
3.1 OVERVIEW.................................................................................................................................3-4
3.3 PC INTERFACING.....................................................................................................................3-4
3.3.1 FINDING THE IP ADDRESS .................................................................................................3-5
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-1
OPERATION
List of Figures
Figure 3-1. Local Area Connection Properties ...................................................................................3-5
Figure 3-2. TCP/IP Properties Example .............................................................................................3-6
Figure 3-3. Login Screen......................................................................................................................3-10
Figure 3-4. Amp Status Screen and Menu ........................................................................................3-10
Figure 3-5. Amp Status Screen ...........................................................................................................3-14
Figure 3-6. Amp Info Screen...............................................................................................................3-16
Figure 3-7. Meter log screen ...............................................................................................................3-17
Figure 3-8. Log Setting Screen ............................................................................................................3-17
Figure 3-9. Setpoints screen ................................................................................................................3-18
Figure 3-10. Config Screen ..................................................................................................................3-19
Figure 3-11. Timers screen ..................................................................................................................3-20
Figure 3-12. IP settings screen ............................................................................................................3-20
Figure 3-13. Email screen ....................................................................................................................3-21
Figure 3-14. Set login screen ...............................................................................................................3-21
List of Tables
Table 3-1. User-configurable Preference Settings. ...........................................................................3-11
Table 3-2. Factory Settings ..................................................................................................................3-11
Table 3-2. Factory Settings (continued).............................................................................................3-12
Table 3-3. Temperature Limit Settings ..............................................................................................3-12
Table 3-4. Amp Status Button Definition..........................................................................................3-15
Table 3-5. Front Panel Controls and Indicators ...............................................................................3-24
Table 3-5. Front Panel Controls and Indicators (continued)..........................................................3-25
Table 3-6. Parameter and Manual Reset Default Setting................................................................3-25
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-3
OPERATION
3.1 Overview
The amplifier is operated remotely using a web browser application. Each amplifier is
configured and thoroughly tested at the factory. Once installed, the amplifier should be
monitored at initial power on to ascertain that it functions properly. The following sections
describe procedures for PC interfacing, pre-power on, navigating the control panel, initial
power on with checkout, browser screens, front panel controls, and shutdown.
3.3 PC Interfacing
The operator can use a PC, connected to the J2 on the amplifier, using an Ethernet cable. The
mating connector for J2 on the amplifier is provided in the ship kit and should already be
available for this step. The IP settings are set at the factory and should be changed. A
controlling PC should be used to setup the Ethernet address of the amplifier.
6. The Internet protocol properties screen should appear. See figure 3-2.
7. Fill in the subnet mask field with 255.255.255.0.
8. Fill in the default gateway field with the same default gateway as the amplifier.
9. Fill in the IP address with the address provided on the front panel label of the amplifier
changing only the last number in the IP address from 1-255 so it is different from the
amplifiers IP address. ***All devices on a network must have a unique IP address***
The controlling PC workstation is setup for connection with the amplifier.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-5
OPERATION
Note: When using a remote control unit (RCU), refer to the RCU installation
and operation manual for connection details and setup.
3.5.3.1 Standby
When the amplifier is in the standby state, it is indicated within the state box. When the
amplifier is in this state the TWT's heater is kept hot while helix voltage is removed.
Transmission is not possible during this state.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-7
OPERATION
3.5.3.2 Transmit
When the amplifier is in the transmit state, it is indicated within the state box. During this state
the TWT's helix voltage is applied allowing amplification of an RF input signal. This is
considered normal operation.
3.5.3.3 RF Inhibit
The RF inhibit state is indicated by a flashing blue background within the state box. The RF
inhibit can be enabled during in either the standby or transmit state. When RF inhibit is
enabled, power to the SSIPA is removed. The RF input signal is isolated from reaching the TWT
and RF becomes inhibited.
3.5.3.4 Fault
When the amplifier is in the fault state, it will be indicated by a flashing red background within
the state box. The type of fault and fault code is displayed below the state box. There are two
types of faults; non-latching, and latching. Faults which are not critical to the amplifiers
operation will be non-latching. The amplifier will attempt to recycle these faults three times
before becoming latched into the fault state. If the fault state is cleared during while recycling
the amplifier will resume normal operation and a log entry will be generated. If the fault
remains after three recycle attempts, the amplifier will become latched into the fault state and
operator intervention is required. All faults should be investigated before manually resetting as
they may indicate maintenance required or the end of life which can save in costly down time.
3.5.3.5 Alarm
When the amplifier is in the alarm state, it will be indicated by a flashing yellow background
within the state box and is usually an early indication a fault may occur. Some alarm settings
are operator settable within the 'Setpoints' screen and others have been setup at the factory.
Alarms should always be set lower then the fault trip limit.
Initial power on should not be performed unless all procedures in the “Unpacking and
Installation” chapter have been completed. Should maladjustments be discovered during initial
power on, proceed to the “Troubleshooting” chapter in the service manual or contact CPI
customer support. Refer to the “Customer Support and Warranty Information” appendix for
contact information.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-9
OPERATION
Note: The amplifier should be in the STANDBY mode at this time. If the amplifier
is not in standby mode click on the standby icon in the Amp Status screen and
confirm the selection.
3. Enter the default IP address found on the front panel label in the web browser application of
the controlling PC.
4. A login screen will appear as shown in the figure below.
5. Enter the default user name and password (lower case.) It is recommended that the default
user name and password are changed from the factory default.
User Name: cpi Password: cpi
6. The amp status screen will be shown. Refer to the figure below.
7. The first three minutes during turn on is the heater time delay (HTD). After the countdown
the amplifier will indicate the STANDBY state.
Setting Name Min. Setting Factory Setting Default Setting Max. Setting
Low RF Output Alarm 0W 0W 0W 750W
Low RF Output Fault 0W 0W 0W 750W
High RF Output Alarm 0W 700W 700W 800W
High RF Output Fault 0W 710W 710W 800W
High Reflected RF Alarm 0W 50W 35W 65W
(NOTE1)
High Reflected RF Fault 0W 60W 50W 75W
High RF Drive Alarm 1.0mW 3.0mW 10.0mW 50.0mW
High RF Drive Fault 1.0mW 8.0mW 31.6mW 100.0mW
ALC Disable RF 0W 5W 5W 10W
ALC Setpoint 0W 0W 0W 800W
Attenuation Setpoint 0dB 30dB 30dB 30dB
Helix Over Voltage Fault(NOTE2&3) 11.0kV NPV +300V 12.8kV 13.8kV
Helix Under Voltage Fault(NOTE2&3) 0.0kV NVP -300V 10.7kV 13.2kV
Helix Over Current Fault(NOTE3) 0.0mA 12.0mA 12.0mA 15.0mA
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-11
OPERATION
9. Click the STANDBY icon to end the initial check H.V. on.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-13
OPERATION
Button Definition
TRANSMIT Applies helix voltage to the TWT. This is the normal operating mode for the amplifier.
STANDBY Removes helix voltage from the TWT. Used to cool the TWT during shutdown.
RF INHIBIT Removes power to the SSIPA inhibiting the RF input signal from reaching the TWT.
RESET Recycles faults. The fault condition must be cleared before using the RESET button.
The amplifier will attempt to recover from most faults three times before becoming
latched in a fault state. A latched fault must be manually reset.
ALC(NOTE1) The amplifier will adjust the attenuator to sustain the automatic level control (ALC)
setpoint value. The attenuator will continually change to keep output power constant.
Adjusting the attenuator will disable ALC.
Manual(NOTE1) The amplifier will adjust the attenuator initially to the manual setpoint value. Manual
mode will not continually adjust the attenuator to keep power constant.
Table 3-4 Notes:
1. The range of power adjustment is relative to the range of the attenuator.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-15
OPERATION
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-17
OPERATION
The linearizer configuration will only be shown if a linearizer is installed. The three linearizer
settings gain, phase, and magnitude can be adjusted between the ranges of 0 to 255 for each
tube channel. Adjustments can only be made if the correct password has been entered. This
password will be provided by CPI if needed. The linearizer is tuned at the factory for the entire
frequency band of the amplifier to meet specification.
Tube channels can be changed using the “Tube Channel” field below the linearizer settings.
There can be a maximum of 8 tube channel presets.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-19
OPERATION
The CIF Protocol field is operator selectable between binary computer interface protocol (BCIP)
or ASCII computer interface protocol (ACIP). The address field sets the CIF address of the
amplifier. No two amplifiers in a system can have the same address. The BCIP the address
range is 17-255 and the ACIP address range is 48-111.
The ‘BUC Unlock Type’ field is operator selectable to FAULT or ALARM. If the reference signal
of the BUC either drifts or is removed either a fault or alarm will be generated by the amplifier.
The Legacy WGS I/F will only be shown if the legacy WGS I/F option is installed. The
‘Interlock Type’ field selects if the external interlock generates an ALARM or a FAULT and is
operator settable.
The ‘Relay Control’ is used to select the conditions which will activate the WGS I/F relay.
The ‘Remote Control Point’ is used to determine which interface the amplifier will be controlled
through. It can be set to either “Ethernet CIF”, “Serial CIF”, “WEB Browser” or ”Remote”. All
interfaces have the ability to control the amplifier.
3.7.6 Timers
The ‘Timers’ screen shows unit on time, heater on time, heater off time, transmit time, and HTD.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-21
OPERATION
The ‘Confirm Transmit Selection’ when enabled, will prompt the operator with an "Are You
Sure" message box in the browser whenever the TRANSMIT button is pushed from the “Amp
Status” screen.
The ‘Confirm Standby Selection’ when enabled, will prompt the operator with an "Are You
Sure" message box in the browser whenever the STANDBY button is pushed from the “Amp
Status” screen.
The ‘Confirm Inhibit Selection’ when enabled, will prompt the operator with an "Are You Sure"
message box in the browser whenever the RF INHIBIT button is pushed from the “Amp
Status” screen.
The ‘Save Transmit State’ when enabled, will allow an amplifier which was powered off in
transmit state to automatically return to the transmit state when powered on again.
The ‘Enable Fault Alarm Sound’ when enabled, will play an audible alarm in the web-browser
whenever the amplifier has faulted. When using this feature remember to check all sound
settings of the PC to ascertain they are working properly.
The ‘BIPA Installed’ shows whether a BIPA is installed (checkmark) or not (unchecked). This is
determined at the factory and cannot be disabled by the operator.
The ‘SEM Installed’ shows whether the switch expansion module (SEM) is installed
(checkmark) or not (unchecked). This field is operator selectable and should not be enabled if
the amplifier is not in a SIM switch system. A resulting “Switch Interlock Fault” will result
when this field is enabled and the amplifier is not used in a SIM switch system.
When the ‘SEM Installed’ is enabled, a “Switch Ctrl” screen will be available to the operator.
The “Switch Ctrl” screen is used to set parameters and provide control of the switch system.
Detailed operation of the “Switch Ctrl” screen is provided in the switch system manual.
The ‘Ext Interlock Enable’ selects of the external interlock is enabled (checked) or not
(unchecked). The external interlock pin must be connected to the common pin on the J5
connector when Legacy is installed as a standard feature. This interlock should not be enabled
when the SIM switch option is purchased.
The Save User Settings button will save all the current settings to non volatile (NV) amplifier
memory.
The Load User Settings button will load the saved setting in the NV amplifier memory.
The Load Factory Settings will load the factory configured settings.
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-23
OPERATION
DOC.01047203 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 3-25
OPERATION
4-1
Chapter 4
Preventative Maintenance
Table of Contents
CHAPTER 4 PREVENTATIVE MAINTENANCE............................................................................4-1
4.1 OVERVIEW.................................................................................................................................4-3
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-1
PREVENTATIVE MAINTENANCE
List of Figures
Figure 4-1. Performance Test Setup.....................................................................................................4-8
List of Tables
Table 4-1. Preventive Maintenance Performed by Operators..........................................................4-3
Table 4-2. Preventive Maintenance Performed by Technician ........................................................4-4
Table 4-3. Recommended Test Equipment.........................................................................................4-4
Table 4-4. Power and Gain Test Data Sheet........................................................................................4-9
4.1 Overview
This chapter provides instructions for routine maintenance of the amplifier. It includes
procedures and test equipment for scheduled maintenance tasks and amplifier performance
testing. Guidelines for protecting parts from electrostatic discharge are also included in this
chapter.
Caution: Improper maintenance of the amplifier may void the warranty. For
additional information, see Appendix A, “Warranty & Support Information”
The amplifier’s internal memory contains a an alarm or fault log which can be used to easily
understand the long term operating conditions that the amplifier has experienced. This log can
be downloaded, and e-mailed which can be helpful in identifying trends or potential problems.
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-3
PREVENTATIVE MAINTENANCE
Example
Item Description
(Equivalent may be substituted)
1 Analog Swept Signal generator, capable of CW and HP 8757D / E8257D
swept operation, compatible with Scalar Analyzer. Scalar
Network Analyzer, complete with dual detector probes.
2 Vector Network Analyzer HP E5071C; N5230C
3 Second CW signal source HP E8257D
4 CPI HV Test Set (includes HV Breakout Box, Heater CPI 0103531900
Load and adapter cables. Also contains a heater
breakout box.
5 RF pads, adapter, 10db coaxial coupler, Type N / SMA / HP / WINCHEL / Narda
2.9 / 2.4
6 RF Power Meter complete with power sensors, power HP E4418 meter HP 8481, ECP-
measurement range -30 to +20 dBm E18A sensor
7 High quality, low loss RF test cables as required for test
set ups
8 RF Radiation Detector Narda 8718 meter with 8621 probe
9 Calibrated Waveguide Directional Coupler, 50 dB APOLLO, MITEC, etc.
10 Dummy Load for rated power +20% APOLLO, MITEC etc.
11 Spectrum Analyzer HP N9010EXA ; E4446A PSA series
12 PC (Computer) with USB; ETHERNET; 232 SERIAL and HP / Dell
cables
Warning: before attempting any cleaning, remove all power. When using
solvents, provide adequate ventilation and avoid breathing fumes. When
cleaning with air, wear safety goggles and use clean, dry compressed air not
exceeding 25 psi (1.75 kg/cm).
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-5
PREVENTATIVE MAINTENANCE
Warning: When using compressed air wear proper eye protection. Do not use
pressure blowers to clean debris from your person.
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-7
PREVENTATIVE MAINTENANCE
Amplifier Model
Number:
Amplifier Serial Number:
Center-Low:
Center:
Center-High:
High:
Notes:
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-9
PREVENTATIVE MAINTENANCE
4.6.1 Precautions
ESD damage can be prevented for the most part by following these precautions:
1. Treat all electronic parts and assemblies as static sensitive.
2. Do not touch leads, pins, or traces while handling parts.
3. Keep parts in original containers until ready for use.
4. Discharge static before handling devices by touching a grounded metallic surface such as a
cabinet. For personal grounding, use a wrist strap grounded through a 1-megohm resistor.
5. Do not slide static-sensitive devices over any surface.
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-11
PREVENTATIVE MAINTENANCE
• Do not allow clothing to come in contact with components or assemblies. Sleeves should be
rolled high enough to keep them away from sensitive parts. Antistatic smocks should be
worn.
• Gloves, if used, should be made of cotton or antistatic materials only.
• Brushes, if needed, should have natural, not synthetic, bristles.
• If walking is necessary and wrist straps cannot be worn, use a conductive floor mat in
conjunction with conductive shoe heels.
• Transport and store electrostatic-sensitive devices only in static-protective containers. No
paper or cards should be placed inside the containers. A label attached to each container
should warn personnel to observe proper handling precautions.
• Transportation carts should have carrying surfaces covered by conductive mats and should
have at least two conductive wheels. Verify that carts, wheels, casters, frames, and shelves
are conductive. Do not transport sensitive electronic equipment on a rubber-wheeled cart
being pushed by a person wearing crepe- or heavy-rubber-soled shoes; this promotes very
high levels of electrostatic charge.
4.6.4 Packaging
Package parts properly for storage or transportation in the following manner:
Attach a static warning label on the outside of each applicable envelope and container. (A
JEDEC/EIA ESDS symbol is preferred.) Pack parts for storage or transportation in antistatic
packaging; pack the parts tightly to prevent motion that could generate static.
Note: The best protective enclosure is a Faraday cage, which shunts any
inductive charges around the part, providing complete protection. Metal,
metalized plastic, and carbon-loaded plastic bags are all examples of
Faraday cages. Metalized plastic has the advantage that it is
semitransparent and its contents can be seen without opening it. The often-
used “pink poly” bags afford less protection.
DOC.01047204 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 4-13
PREVENTATIVE MAINTENANCE
5-1
Chapter 5
Drawings
This chapter contains the drawings for the Compact HPA ODU.
DOC.01047205 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED 5-1
DRAWINGS
Appendix A
Customer Support and Warranty
Information
For details, refer to separate supplements included following this page.
APP.01040025 REV.2 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED A-1
CUSTOMER SUPPORT AND WARRANTY INFORMATION
B-1
Appendix B
L-Band BUC Option
B.1 Overview
The L-Band RF input signal is converted by the Block Up-Converter (BUC) to the frequency
band of the amplifier.
Each amplifier is provided with a label indicating the correct L-Band input frequencies accepted
by the BUC. This label is shown in figure B-1. The bandwidth of the L-Band input frequency is
typically the same bandwidth as the amplifier's output frequency bandwidth.
Warning: Ensure that the proper L-band frequency range is not exceeded
or damage may result. Damage due to an improper frequency input may
not be covered in the warranty of the amplifier.
This appendix provides information on BUC operation and explains the three types of
frequency references which can be used.
DOC.01040024 REV.4 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED B-1
L-BAND BUC OPTION
inhibit RF and shutdown HV to the TWT. A reset command will restore the amplifier to normal
operation once the fault has cleared.
The FLO reference can be supplied in one of the following three ways:
• Multiplexed - FLO reference is multiplexed with the L-Band input signal.
• Internal - FLO reference is generated internal to the BUC.
• External - FLO reference through a dedicated reference port.
Caution: For multiplexed and external FLO reference BUC's, the L-band
input signal must be free of the spurious signals that can cause poor
performance. Spurious signals may also cause the amplifier to fail.
C-1
Appendix C
Messages
Section Limit – Status Indicator Operator Settable Factory Setting Status Indicator
BIPA BUC LOCK X
EEPROM X
WGSIF INTERLOCK X
HIGH RF DRIVE X
RF HIGH POWER LIMIT X
LOW POWER LIMIT X
REFLECTED POWER LIMIT X
MAIN BBRAM X
BIPA COMM X
BIPA RESTARTED X
CAN BUS X
CAN LEVEL KEY X
EEPROM X
APP.01046827 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED C-1
MESSAGES
Section Limit – Status Indicator Operator Settable Factory Setting Status Indicator
MAIN PS COMM X
(con’t)
PS RESTARTED X
RF COMM X
RF RESTARTED X
SEM COMM X
SEM RESTARTED X
SYSTEM X
POWER CABINET TEMPERATURE
X
SUPPLY LIMIT
EEPROM X
HEATER CURRENT LIMIT X
HEATER OVER VOLTAGE X
HEATER UNDER VOLTAGE X
HELIX CURRENT LIMIT X
HELIX OVER VOLTAGE X
HELIX UNDER VOLTAGE X
HELIX VOLTAGE
X
DETECTED
TUBE BLOWER UNDER
X
SPEED
TUBE OVER TEMP X
TUBE OVER TEMP SWITCH X
Section Limit – Status Indicator Operator Settable Factory Setting Status Indicator
BIPA BUC LOCK X
I2C TIMEOUT
HIGH RF DRIVE X
POWER CABINET OVER
X
SUPPLY TEMPERATURE
I2C TIMEOUT X
TUBE BLOWER OVER
X
SPEED
TUBE OVER
X
TEMPERATURE
MAIN LOW BATTERY X
RTC FAILURE X
RF ALC LIMIT X
HIGH REFLECTED RF X
HIGH RF OUT X
LOW RF OUT X
SWITCH AMP IDENT CONFLICT X
SIM X X
APP.01046827 REV.1 THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED C-3
MESSAGES