ExReg-V en

The document describes an explosion proof volume flow controller that can be used in hazardous areas. It has inputs for sensors and actuators, outputs alarms and data communication. It is compact and robust with IP66 protection for harsh environments.

Uploaded by

cweiliet
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views8 pages

ExReg-V en

The document describes an explosion proof volume flow controller that can be used in hazardous areas. It has inputs for sensors and actuators, outputs alarms and data communication. It is compact and robust with IP66 protection for harsh environments.

Uploaded by

cweiliet
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

E X P L O S I O N P R O O F

ExReg-V Volume flow controller 0...300 Pa ExReg - V-...


ExReg - V-... - A
ExReg - V-... - B
Electrical, explosion-proof volume flow controller (CAV / VAV)
ExReg - V- ... - CT
in conjunction with ExMax-...-CY... actuators only
ExReg - V- ... - OCT
24 VAC / DC supply, adaptive PID controller, alarm contact ExReg - V- ... - VA
EC type-approved in acc. with ATEX directive 2014 /34 /EU for zone 1, 2, 21, 22 ExReg - V- ... - OVA
Subject to change!

Compact. Easy installation. Universal. Cost effective. Safe.


Type Sensor Supply Range Connection / Interface (analogue) Alarm contact Wiring diagram
ExReg- V-300 Diff. pressure 24 VAC/DC 0...300 Pa 1 × actuator, 1 × set point Relay contact 30 V / 0.1 A SB 1.0
ExReg- V-300 - A Diff. pressure 24 VAC/DC 0...300 Pa 1 × actuator, 1 × set point, 1 × actual value, 1 × position actuator Relay contact 30 V / 0.1 A SB 1.1
ExReg- V-300 - B Diff. pressure 24 VAC/DC 0...300 Pa 1 × actuator, RS485 communication Relay contact 30 V / 0.1 A SB 1.2
ExReg- V- ... - CT Types as above with aluminium housing and seawater resistant coating (cable glands M16 brass nickel-plated, screws in stainless steel)
ExReg- V- ... - OCT Types as above, offshore version with aluminium housing and seawater resistant coating (stainless steel tubes for clamping ring connection,
cable glands M20 brass nickel-plated, screws in stainless steel)
ExReg- V- ... - VA Types as above with stainless steel housing for aggressive ambient (cable glands M20 brass nickel-plated, screws in stainless steel)
ExReg- V- ... - OVA Types as above, offshore version with stainless steel housing for aggressive ambient (tubes for clamping ring connection and screws in stainless steel,
cable glands M20 brass nickel-plated)

Product views and applications


Volume flow controller ...Reg-V...-CT ...Reg-V...-VA Offshore ...-OVA ExReg-V + ExMax-...-CY

Description Highlights
The ExReg-V... flow controller is an indispensable integrant in Building ►For all type of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22
Management Control Equipment for Chemical, Pharmaceutical, Industrial
►Power supply 24 VAC/DC
and Offshore plants for use in hazardous areas of zones 1, 2 (gas) and
21, 22 (dust). ►Sensor and controller in one housing
Highest protection class (ATEX) and IP66 protection, small dimensions, ►Direct connection of actuator to the controller’s integrated Ex-e terminal box
universal functions and technical data as well as an optional stainless ►No addional Ex-i module in panel required
steel housing guarantee safe operation even in harsh environments.
►No intrinsically safe wiring/installation between sensor and panel required
ExReg-V... is used directly in hazardous areas for control of air flows in
ventilation systems. To complete the technical solution an additional ►No intrinsically safe wiring/installation and no space in the panel required
damper actuator type ExMax-...-CY or ExMax-...-CYF (with Fail Safe ►Relay output with adjustable alarm monitoring
spring return) is required and also a ventilation damper with orifice plate ►Scalable analogue input and output (selectable für setpoint, actual value, et al.)
and a known shield factor (called k-factor).
►Optional analogue output for controller feedback
All controllers are programmable on site with menu guide. The internal
PID control structure is simple to use and automatically configured for ►Adjustable k-factor, universially applicable for any dampers
standard applications. The display shows the current status during ►Display with backlight, can be switched off
operation for the actual value, setpoint and actuator position (can be ►Password locking
disabled if required).
►Down to −20 °C ambient temperature applicable
...Reg-V...-OCT and ...-OVA offshore versions are equipped with stain-
less steel tubing Ø 6 mm. ►Compact design and small dimension
►Robust aluminium housing (optional with seawater resistant coating) or in stainless steel
►IP66 protection
►Offshore versions with pressure tube connection for clamping ring Ø 6 mm
ExMax-...-CY... – see additional data sheet
ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 1/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Technical data
Supply voltage / frequency 24 VAC /DC ± 15 % (20,4...27,6 VAC /DC), frequency 50...60 Hz
Current, power consumption 150 mA, ~ 3 W, internal fuse 500 mAT, without bracket, not removable
Galvanic isolation Supply for analogue in- and outputs min. 1,5 kV, supply for relay output min. 1,5 kV
Electrical connection Terminals 0,14...2,5 mm² at integrated Ex-e terminal box, stripping length 9 mm, torque 0,4…0,5 Nm, equipotential bonding 4 mm²
Cable glands 2 × M16 × 1,5 mm, Ex-e approved, for cable diameter ~ Ø 4...10 mm
Cable glands ...-CT 2 × M16 × 1,5 mm, Ex-e approved, brass nickel-plated, for cable diameter ~ Ø 6...10 mm
...-VA, ...-OCT, ...-OVA
2 × M20 × 1,5 mm, Ex-e approved, brass nickel-plated, for cable diameter ~ Ø 6...13 mm
Protection class Class I (grounded)
Display LCD matrix display with backlight, display for configuration, user guidance, parameter and actual value indication
Control elements 3 buttons for configuration
Housing material Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CT/...-OCT) or stainless steel housing,
№ 1.4581 / UNS-J92900 / similar AISI 316Nb (...-VA /...-OVA)
Dimensions (L × W × H) Aluminium housing ~ 180 × 107 × 66 mm, stainless steel housing ~ 195 × 127 × 70 mm (each without connectors)
Weight ~ 950 g aluminium housing, stainless steel version ~ 2,5 kg
Ambient temperature −20...+50 °C, storage temperature −35...+70 °C
Ambient humidity 0...95 % rH, non condensing
Sensor circuit Internal intrinsically safe circuit
Sensor Piezo pressure transmitter
Pressure connection P+ / P− sleeves Ø 4...6 mm. OCT and OVA versions have 2 stainless steel (316L) tube connections for clamp ring fittings Ø 6 mm
Measuring range 0…300 Pa, minimum measuring range is 2 % of full scale
Sensor damping (filter) 1...50 seconds, adjustable
Accuracy of pressure ± 2,5 % full scale ± 1 Pa
Setting zero point Via menu. Short-circuit mechanically both tube connectors P+ / P− for the moment of zero point setting
Air flow Calculation via k-factor (”shield factor”); adjustable parameters: V max, V min, V rated, k-factor
Regulation Adaptive PID controller (automatic or manual mode selectable)
Control tolerance 1...5 % adjustable
Delay time 3s
Alarm monitoring Monitoring the volume flow; adjustable functions: tolerance limit (fixed and variable value), alarm delay
Alarm contact (terminal 3) Relay; max. values: 0.1 A (30 VAC/DC), min. values: 10 mW / 0.1 V / 1 mA
Life time mechanically 10 × 106
electrically (rated) 100 × 103
Current output (terminal 6) Range 4...20 mA, invertible, basic accuracy ± 1.0 % of full scale, load < 500 Ω, influence < 0.1 %, open circuit voltage 24 V
Voltage input (terminal 8) Range 0...10 V, invertible, basic accuracy ± 1.0 % of full scale, over-voltage up to 30 V
Voltage input (terminal 9) Range 0...10 V, adjustable, basic accuracy ± 1.0 % of full scale, over-voltage up to 30 V
Voltage output (terminal 11) Range 0...10 V, adjustable, basic accuracy ± 1.0 % of full scale, load > 10 kΩ, influence < 0.1 %, short circuit proof (type ...Reg-V300-A)
Voltage input (terminal 13) Range 0...10 V, adjustable, basic accuracy ± 1.0 % of full scale, over-voltage up to 30 V (type ...Reg-V300-A)
Wiring diagram SB 1.0 / 1.1 / 1.2
Scope of delivery Sensor, 3 self-tapping screws 4,2 × 13 mm resp. in stainless steel (with ...CT and ...VA versions), short circuit tube

Approbations Special solutions and accessories


ATEX directive 2014 /34/EU ...-CT Types in aluminium housing with seawater resistant coating,
EC type-approved EPS 11 ATEX 1 380 parts nickel-plated
IECEx certified IECEx EPS 12.0028 ...-OCT Offshore version in aluminium housing with seawater resistant coating,
Approval for gas II 2 (1) G Ex e mb ib [ia Ga] IIC T6 Gb parts nickel-plated
Types ...-CT, ...-OCT II 2 (1) G Ex e mb ib [ia Ga] IIB T6 Gb ...-VA Types in stainless steel housing, parts nickel-plated
Approval for dust II 2 (1) D Ex tb ib [ia Da] IIIC T80°C Db IP66 ...-OVA Offshore version in stainless steel housing, parts nickel-plated
ExMax-...-CY Control actuator, 4...20 mA Input, 0...10 V output
CE identification CE № 0158 ExMax-...-CYF Control actuator, 4...20 mA Input, 0...10 V output with spring return
EMC directive 2014 /34 /EU ExBox-Y/S Ex-e terminal box, 4 × M20 × 1.5 mm cable glands Ø 6 .. 13 mm
Enclosure protection IP66 in acc. with EN 60529 MKR Mounting bracket for round ducts up to Ø 600 mm
Kit-S8-CBR 2 cable glands M16 × 1,5 mm, Ex-e, brass nickel-plated, for cable Ø 5...10 mm
Kit 2 Flexible pressure tube, 2 m, inner Ø 6 mm, 2 connection nipples
Kit-PTC-CBR 2 connecting tubes for tube fittings Ø 6 mm, stainless steel 316 L
ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 2/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Electrical Connection
The controller requires a 24 VAC/DC power supply on terminal 1(−/~) and 2 (+/~). Terminals distance between the controller and the actuator, the actuator may be connected directly
1 and 2 are internally connected to terminals 4 and 5 and supplies the control actuator. without the use of an additional terminal box. Otherwise please order terminal box (see ac-
(Note the actuator needs to initialize about 2 A starting current for max. 1 s). The actuator cessories).
is connected directly to the controller over terminals 4 – 8. If there is less than 1 meter Attention: Before opening the terminal box cover, the supply voltage must be shut off !

ExReg-V300 SB 1.0

ND / 2. V
The ExReg-V300 is the basic version and can be used for the control of constant volumetric

0V
0
mA

d Y lle ...1
24 VAC/DC

..1
flow rates (CAV) and variable flow rates of (VAV). The alarm contact (terminal 3) is used
tor

un ntro or 0
ND 20
− + tua

ctu , G 4...
as a feedback for normal operation, an analog feedback signal is not provided for these

,G r0
t
: G nt c tua
ac
~ ~
o r
devices.
tpo pply

Ga tpoi e ac
t
tua
ct
nta

o
Se valu
ac

The setpoint is adjusted via terminal 9. The voltage range for the minimum and maximum
:S

:a dY
co

int
DC

al
Uu un

flow rate is defined by a 2...10 V signal. A voltage value of about 12 V opens the damper
m

C/
lar

ro

ro
PE
Se

:G
VA

below 0.2 V the damper closes completely. During these forced control functions (damper
:A

S:
Yi:
AK

Ga
24

open / close) the controller is without function.


The CAV mode is configured in menu 2 by setting “CAV”. The CAV mode is activated
Actuator when the input voltage is not connected to terminal 9. In this case, the menu 7.2 “default”
set value is used as a flow. The force control functions (damper open / close) can be
PA applied by 0 V (close) and +24 V (open) to terminal 9. This can be done by connecting
1 2 3 4 5 6 7 8 9 10 the supply voltage level 0 V and 24 V with two relays.
The simple VAV operation in menu 2 configured via the setting “VAV”. This configuration
allows a modulation operation in a 2...10 V signal range. In the case of 2 V it is regulated
on the minimum value set in menu 5 “flow rate” and at 10 V to the maximum value. The
intermediate values are according to the voltage level (2...10 V) linearly as setpoints
available.
Galvanic Isolation 1,5 kV

ExReg-V300-A SB 1.1
ExReg-V300-A is the standard version for the control of variable volume flow (VAV). The
Gr val GND 0... V

0V
V
tor 10
mA

24 VAC/DC
...1
10

alarm contact (terminal 3) is used as feedback for normal operation and, in addition, the
ctu nd ctua r 0..
tor

2.. t co ntro 0 / 2
U tual GND ..20

− +
tua

U Gro ck a uato

device has an analog output (terminal 11), which outputs the actual value as a continuous
ac

ac d Y, r 4.

~ ~
lle

r
t

lle
c

signal, and an analog feedback of the actuator position (terminal 9). This feature is primarily
ly

Se und ntro
ato

Ga edb e a
pp
ct

r
V olle
nta

u
Su

Fe valu

U Gro e co

used for energy efficiency.


c t

o
al Y,
co

: G nt a

r
tpo c

t
C:

.10 n
u

The setpoint is adjusted via terminal 13. The voltage range for the minimum and maximum
m

U un
/D

u
tpo
lar

ro

0 / in

PE
VA
:A

flow rate is defined as either of 0...10 V or 2...10 V.


Se

U:

U:

:
AK

:
24

Ga
Y:

i:a
i

In addition, the positive control function can be used depending on the setting in menu
S:

6 “set point”. When the voltage value of about 12 V is exceeded the damper opens, when
Actuator it drops below 0.2 V the damper is completely closed. When utilising these force control
(damper open / close) the controller is without function. If the input is not connected, the
PA flow control defaults to the set value in menu 7.2.
1 2 3 4 5 6 7 8 9 10 11 12 13

Galvanic Isolation 1,5 kV

ExReg-V300-B SB 1.2
V
.10
mA

24 VAC/DC
tor

0..
al ND 20
tua

− +
tor
ctu , G ...

Bus-Topologie
ac

tua
:a dY r4

~ ~
ply

ac
ato
t c

up

lue
nta

ro ctu
:S

va
co

:G ta
DC

Ga oin
m

Uu un
C/
ar

etp

Bu 1
2
1

PE
Al

VA

sA

sB

sB
sA
S
:
AK

24

Bu
Yi:

Bu

Bu

Actuator

PA ▪ There must be connected to a bus only point-to-point connections


▪ Star wiring is not permitted
1 2 3 4 5 6 7 8 10 11 12 13 ▪ Each device works automatically as a repeater

Galvanic Isolation 1,5 kV


ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 3/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Important information for installation and operation Display, buttons and parameters
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with.
For electrical installations design, selection and erection, EN /IEC 60079-14 can be Display for
used. programming
and indication
Attention: Apply all Ex rules and regulation before opening the internal terminal
! box. Do not open cover when circuits are live! Push button
ENTER
Draw the wiring cables through the cable glands. For connection use the internal Ex-e
approved terminal box and connect equipotential bonding. Push button for
After connection install the cables in a fixed position and protect them against mechanical level selection
and thermical damage. Close all openings and ensure IP protection (min. IP66).
Avoid temperature transfer and ensure not to exceed max. ambient temperature! For
Change operation – parametrisation mode
outdoor installation a protective shield against sun, rain and snow should be applied.
To change from operation to parametrisation mode and vice versa, push ENTER
After mounting and installation a zero point compensation must be done to ensure
button for minimum of 3 seconds. Back over the menu “Save” and exit.
correct measurement results (see description).
Sensors are maintenance free. An annual inspection is recommended. For electrical Display in operating mode
installations inspection and maintenance, EN /IEC 60079-17 can be used. In operating mode the current set value, the actual value and the set value are dis-
Clean with damp cloth only. played. The red and the green LED indicate the current operating status.
Ex sensors must not be opened and repaired by the end user. When the green LED is illuminated continuously, the system is in a stable state and
indicates correct operation. If the limits of the actuator’s position are reached or an
B. Long cabling internal fault is detected, the red LED lights up.
We recommend using shielded signal wires and to connect one end of the shield to the A flashing red LED indicates that the set point can not be achieved. The alarm func-
...Reg-... terminal box. tion is active in this case. The yellow LEDs indicate during adjusting phase the direc-
C. Separate ground wires tion of movement of the actuator. The upper LED denotes the actuator opens, the
lower LED indicates the actuator closes. The yellow LED does not flash when the
For supply and signal wires use separate grounds. system is within the defined tolerance field (menu 12 “Controller / tolerance”).

Installation Password input


Hazardous area – The default / delivery setup is 0000. In this configuration the password input is not
Safe area
Zone 1, 2, 21, 22 activated. To activate the password protection (menu 12) change the 4 digits into your
choosen numbers (e. g. 1234) and press ENTER.
Please keep your password in mind for next parameter change ! Due to a new parameter
Actuator setup the password is requested.
P− P+

Power supply / Zero point compensation


signal wires
...Reg-V-... controller are equipped with a zero point compensation to adjust the module to
the installation position. The pressure nipples P+ / P− must be connected with a short circuit
tube and the zero point compensation performed by following the menu for parametrization
(menu 3.2).
P− P+ Before starting the zero point compensation, the device should be connected to power
>1m supply for a minimum of 15 minutes to reach the uniform working temperature!
Actuator

Control configuration
Power supply / ...Reg-V300 and ...-V300-A are designed for the control of volume flows. The control mode
signal wires can be set in menu 8 “Controller”. Normally, the fully automatic determination of the control
ExBox parameters (select “Auto”) is sufficient. In addition, an adaptive PID (proportional component
is calculated automatically) and a standard PID controller can be selected. These settings
should only be used by trained personnel.
In certain cases – especially in severe pressure fluctuations in the air duct – the gain of the
control loop (menu 8.2) and the control tolerance (menu 8.6) should be adjusted.

Control speed
The control speed can be determined directly over the motor running time of the actuator.
The control parameters in this case must not be changed. The controller recognizes the
change automatically via the feedback signal of the actuator (terminal 7). This applies to
all controller settings. The control speed depends only on the used motor running time.

For more information see data sheet of the actuator.

ExMax-...-CY... – see additional data sheet


ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 4/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Parametrisation and commissioning

To change from operation to parametrisation mode push “ENTER”


button for minimum 6 seconds. Operation → Parametrisation
If password protected: type password and push . push for 6 s
Back over to menu “Save” and exit.

Menu Function ENTER Indication Select ENTER Description


Menu 1 Language 1: Language
Select the language English
Deutsch, English, Français, Italiano, Espanol, back
Menu 2 Application 2: Application
Selection of application VAV
VAV, back
2.1 VAV Device’ll be recon-
Selecting standard VAV application figurated. Continue?
(factory setting) no yes
Menu 3 Sensor 3: Sensor
Configuration menu for sensor settings Filter
Filter, 0-point comp., status, back
3.1 Filter 3.1: Filter
Selection filter/damping of sensor 20 s
measurement select filter time
3.2 Zero point compensation Start 0-point
Short circuit P+ and P− compensation?
in final position no yes
3.3 Status 3.3: Status
Indication measurement value in Pa 87 Pa
5 ... 300 Pa
Menu 4 Actuator 4: Antrieb
Config menu actuator Invers
Invers, test, status, back
4.1 Invers 4.1: Invers
Select inverse mode off
off, on, back
4.2 Test 4.2: Test
Test actuator position manually 20 %
position actuator 0 ... 100 %
4.3 Status 4.3: Status
Indication of position actuator 20 %
position actuator 0 ... 100 %
Menu 5 Air volume 5: Air volume
Configuration menu for air volume k-factor
k-factor, V nominal, V maximal, V minimum, back
5.2 k-Factor 5.2: k-factor
Input k-factor 50
adjust k-factor
5.3 V nominal 5.3: Vnom
Input nominal air volume 1000 m³/h
adjust nominal value
5.4 V maximum 5.4: Vmax
Input maximum air volume 800 m³/h
adjust max. Value
5.5 V minimum 5.5: Vmin
Input minimum air volume 200 m³/h
adjust min. value
Menu 6 Actual value 6: actual value
Configuration menu for actual value
Range, status, back
6.1 Range 6.1: Range
Select output value 0...10 V
0...10 V, 2...10 V, 0/ 2...10 V, back
6.2 Status 6.2: Status
Indication actual value in m³ /h 100 m³/h

ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 5/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Parametrisation and commissioning


Menu Function ENTER Anzeige Select ENTER Description
Menu 7 Nominal value 7: Nominal value
Configuration menu for nominal value
Range, status, back
7.1 Range 7.1: Range
Select output value 0...10 V
0...10 V, 2...10 V, 0/2...10/12+ V, back
7.2 Value 7.2: Value CAV modus is automatically activ if no input signal
Adjust setpoint for CAV modus 500 m³/h connected terminal 9 resp. 13 (...-A version)
adjust CAV value
7.3 Status 7.3: Status
Indication of setpoint m³/h 100 m³/h

Menu 8 Controller 8: Controller


Configuration menu for the controller
Type, gain, P-, I-, D, tolerance
8.1 Type 8.1: Type
Select controller type Auto
Auto, PID adaptive, PID norm
8.2 Gain 8.2: Gain
Adjust gain of control loop 100 %
gain 1 ... 100 %
8.3 P-ratio 8.3: P-ratio
Adjust P-ratio 10
P-ratio 1 ... 100
8.4 I-ratio 8.4: I-ratio
Adjust I-ratio 2.0 s
I-ratio 1 ... 10 s
8.5 D-ratio 8.5: D-ratio
Adjust D-ratio 1.0 s
D-ratio 0 ... 10 s
8.6 Tolerance 8.6: Tolerance
Adjust contoller tolerance 2.0 %
Tolerance 1 ... 5 %
Menu 9 Switch 9: Switch contact
Configuration menu for the alarm relay
Alarm function, limit %, limit abs, delay time
9.1 Alarm function 9.1: Alarm function
Adjust alarm function on
On, off, back
9.2 Limit (%) 9.2: Limit (%)
Set alarm limit in % 2.0 %
Limit 0 ... 10 %
9.3 Limit (abs) 9.3: Limit (abs)
Set alarm limit in m³/h 20 m³/h
Limit 0 ... 240 m³/h
9.4 Delay time 9.4: Delay time
Set delay for alarm relay 20.0 s
Delay time 10 ... 200 s
Menu 10 No function
(Menu will be skipped)

Menu 11 Diagnostics 11: Diagnostics


Electrical test of all in- and outputs
Input 1, input 2, input 3, output 1, output 2, switch, back
11.1 Input 1 11.1: Input 1
Indication of status terminal 8 10.0 V

11.2 Input 2 11.2: Input 2


Indication of status terminal 9 10.0 V

11.3 Input 3 11.3: Input 3


Indication of status terminal 13 10.0 V

11.4 Output 1 11.4: Output 1


Test output value terminal 6 20.0 mA
Set 4 ... 20 mA
11.5 Output 2 11.5: Output 2
Test output value terminal 11 10.0 V
Set 0 ... 10 V
ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 6/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Parametrisation and commissioning


Menu Function ENTER Indication Select ENTER Description
Menu 11.6 Switch 11.6: Switch
Test relay function terminal 3 Function: open
Function open / close status open / close
Menu 12 Password 12: Password
Configuration menu for the passwords
Level 1, level 2, level 3, back
12.1 Level 1 12.1: Level1
Level 1 password 0000
User level Password
12.2 Level 2 12.2: Level 2
Level 2 password 0000
Installation level Password
12.3 Level 3 12.3:Level 3
Level 3 password 0000
Manufacturer level Password
Menu 13 Indication 13: Indication Short menu „on“ reduces the parameterization to a minimum.
Configuration menu for the indication Detail settings are not possible.
Display, contrast, brightness, short menu, back
13.1 Display 13.1: Display
Set display function on, lighted
On lighted, on, off, back
13.2 Contrast 13.2: Contrast
Set display contrast 60.0 %
0 ... 100 %
13.3 Brightness 13.3: Brightness
Set brightness for backlight 100 %
0 ... 100 %
13.4 Short menu 13.4: Short menu
Use short menu off
On, off, back
Menu 14 Parameter 14: Parameter
Menu for parameter administration
Save, use, activate, erase, back
14.1 Save 14.1: Save Save up to 3 different parameters to test the controller.
Save parameter P1 (active)
P1, P2, P3, back
14.2 Use 14.2: Use
Edit parameter P1 (active)
P1, P2, P3, back
14.3 Activate 14.3: Activate
Define active parameter P1 (occupied)
P1, P2, P3, back
14.4 Erase 14.4: Erase
Delete parameter P1 (occupied)
P1, P2, P3, back
Menu 15 Leave menu 15: Leave menu
Leave menu and save
Back, yes

ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 7/8
ExReg-V...
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F

Dimensions [mm ]
Aluminium housing ...Reg-V...-OCT
Ø 4,5
117

138
157,5

166

170
~ 180

213
Ø 4,5 68 Ø 4,5
55
80
107 66

Stainless steel housing ...Reg-V...-OVA


4.5
Ø 4.5
2

123.3
181.7

182.7

~ 194

~ 226
21.5

59

102

69 ~ 61

81.3 70
126.3

ExReg-V_en
V02 – 23-Sep-2016
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com 8/8