Firmware Upgrade Instructions RX 3 I CPEs
Firmware Upgrade Instructions RX 3 I CPEs
Version 1.0
Instructions for Firmware Upgrade
Introduction
The PACSystems RX3iTM CPU has operating firmware stored in FLASH memory. RX3i CPUs equipped with USB
ports are capable of updating the stored operating firmware from a USB flash drive through the USB port with no
other outside software.
NOTE: The instructions provided outline a specific procedure that MUST be followed in sequence. If the
procedure for some reason is not followed, please contact the GE Intelligent Platforms Hotline for help in
upgrading the PLC CPU.
PLEASE READ ALL INSTRUCTIONS COMPLETELY PRIOR TO STARTING THE UPDATE PROCEDURE.
such as 7-Zip or FreeZip. Configure your ZIP utility to create folders/directories on extraction.
Proficy Machine Edition PLC Programming Software is required to back up the PLC application before
the upgrade and to restore the application afterward unless application logic, hardware configuration,
initial/forced values, and controller supplemental files are written to flash before starting the upgrade.
Microsoft and Windows are registered trademarks of Microsoft Corporation.
WinZip and PKZIP are registered trademarks of their respective owners.
Page 1 of 3
Instructions for Firmware Upgrade
Page 2 of 3
Instructions for Firmware Upgrade
4. Insert the prepared USB flash drive in the port labeled USB-A RDSD. Press and release the START
button. The RDSD LED will blink green while the image is being copied to the CPU (15-20 seconds).
When the copy has completed, the RDSD LED will stop blinking, and turn off. NOTE: It is imperative
that power not be disrupted and the USB flash drive not be removed while the image copy is in
progress… irreparable damage could occur to the CPU.
COM 1
ETHERNET
USB-A RDSD !
COM 2
Page 3 of 3