VAM-J Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

VAM-J

Heat Recovery Ventilation

VAM-J
Fully ErP compliant Heat Recovery Ventilation
systems for recovering waste energy from internal
spaces to reduce the load on air conditioning and
heating systems. VAM-J

The VAM-J series heat recovery ventilation systems are very high Features:
efficiency heat recovery ventilation systems designed to deliver
fresh air into occupied spaces whilst reducing the load on the > Energy saving ventilation using indoor heating, cooling and
heating and cooling systems by up to 73%. moisture recovery
> Ideal solution for shops, restaurants or offices requiring maximum
Suitable for most commercial applications with fresh air
floor space for furniture, decorations and fittings
requirements up to 2000m3/h, the VAM-J series is fully compliant
with the 2018 ErP lot 6 legislation and incorporates DC fan motors > Free cooling possible when outdoor temperature is below indoor
and a specially developed heat exchange element without the temperature (e.g. during night time)
need for any condensate drainage.
> Reduced energy consumption thanks to specially developed
A full range of optional accessories are available including CO2 DC fan motor
sensors to maintain indoor air quality whilst decreasing energy
> Prevent energy losses from over-ventilation while improving
consumption and a range of filters from M6 (medium) to F7 (fine)
indoor air quality with optional CO2 sensor
can be used to allow flexibility of design. Heater batteries are also
available which aid the hat exchange efficiency at low ambient > Can be used as standalone or integrated in the Sky Air or
conditions. Weatherproof enclosures can also be purchased for VRV system
when there is a need to install the VAM units outside. > Optional medium and fine dust filters M6, F7, F8 to meet
For applications with high humidity or where odours might be customer request or legislation
present, please see our Modular Light series which use aluminium > Shorter installation time thanks to easy adjustment of nominal air
heat exchangers for high efficiency sensible energy recovery. flow rate through the remote controller, so less need for dampers
For smaller projects with airflows from 150 to 250m3/h see our compared with traditional installation
VAM FC range.
> No drain piping needed
> Positive and negative pressure settings are available
VAM-J Heat Recovery Ventilation
VAM150FC VAM250FC VAM350J VAM500J VAM650J VAM800J VAM1000J VAM1500J VAM2000J
Dimensions Height mm 285 301 368 731
Width mm 776 1120 1350
Depth mm 525 868 917 1170
Weight kg 24 39 39 58 70 70 145 145
Duct Connection Diameter mm 100 150 200 200 250 250 250 2 x 250 2 x 250
Air Flow Rate Ultra-High m3/hr 150 250 350 500 650 800 1000 1500 2000
High m3/hr 140 230 300 425 550 680 850 1275 1700
Low m3/hr 105 155 200 275 350 440 550 825 1100
Ultra-High m3/sec 0.042 0.069 0.10 0.14 0.18 0.22 0.28 0.42 0.56
High m3/sec 0.039 0.064 0.08 0.12 0.15 0.19 0.24 0.35 0.47
Low m3/sec 0.029 0.043 0.06 0.08 0.10 0.12 0.15 0.23 0.31
External Static Ultra-High Pa 90 70 90 90 90 90 90 90 90
Pressure High Pa 87 63 70 70 70 70 70 70 70
Low Pa 40 25 50 50 50 50 50 50 50
Sound Pressure Ultra-High dBA 27.0 28.0 34.5 37.5 39.0 39.0 42.0 42.0 45.0
Level (Heat High dBA 26.0 26.0 32.0 35.0 36.0 36.0 38.5 39.0 41.5
Exchange Mode) Low dBA 20.5 21.0 29.0 30.5 31.0 30.5 32.5 33.5 36.0
Electrical Details Power Supply V / Hz / Phase 230 / 50 / 1
Running Current A 0.9 0.9 1.6 2.1 2.8 4.4 4.9 8.8 9.8
Max Fuse Size A 6 6 6 6 6 6 6 2 x 6* 2 x 6*

* For full details of specifications relating to EN308 please see the technical data book. * 2 power supplies required as 2 units bolted together.

Optional Accessory Compatibility VAM150FA VAM250FA VAM350J VAM500J VAM650J VAM800J VAM1000J VAM1500J VAM2000J
Inlet Heater Battery+ VH1B VH2B VH3B VH4B or VH4/AB VH5B

=+ Heater battery does NOT require PCB adaptor to connect to VAM


* available in Medium M6, Fine F7 and Fine F8. Only one filter is required to cover the whole of one side of the heat exchanger, even if the heat exchanger has two sections.

Optional Inlet Heater Battery VH1B VH2B VH3B VH4B VH4/AB VH5B
Capacity kW 1 1 1 1.5 2.5 2.5
Duct Diameter mm 100 150 200 250 250 350

Accessory Ref Description


BRC1H519W7 Wired touch screen remote controller - White
BRC1H519S7 Wired touch screen remote controller - Silver
BRC1H519K7 Wired touch screen remote controller - Black
KRP2A52 and UK.FB2 System adaptor PCB for remote on/off, status indication and temperature setting
RTD-Net and UK.FB2 Modbus Interface PCB for Sky Air and VRV
RTD-20 and UK.FB2 Energy control PCB for Sky Air and VRV
BRP4A50 PCB Adaptor for VAM-A series connection to 3rd party heater
KRP50-2 PCB Adaptor for VAM-A series connection to humidifier
BRP4A50A PCB Adaptor for VAM-B Series connection to 3rd party heater or humidifier
EKAFVJ50F6 Air filter for VAM350 / 500 J : Medium M6
EKAFVJ50F7 Air filter for VAM350 / 500 J : Fine F7
EKAFVJ50F8 Air filter for VAM350 / 500 J : Fine F8
EKAFVJ65F6 Air filter for VAM650 / 800 J : Medium M6
EKAFVJ65F7 Air filter for VAM650 / 800 J : Fine F8
EKAFVJ65F8 Air filter for VAM650 / 800 J : Fine F7
EKAFVJ100F6 Air filter for VAM1000 / 2000 J : Medium M6
EKAFVJ100F7 Air filter for VAM1000 / 2000 J : Fine F7
EKAFVJ100F8 Air filter for VAM1000 / 2000 J : Fine F8
BRYMA65 CO2 Sensor for VAM350 / 500 / 650
BRYMA100 CO2 Sensor for VAM800 / 1000
BRYMA200 CO2 Sensor for VAM1500 / 2000
EKPLEN200 Plenum for VAM1500 & 2000 (4 required per VAM) 350mm duct
UKEPLEN19-1072 / 07.19 / DesignHQ / Copyright 2019 Daikin

The present leaflet is drawn up by way of information only and


does not constitute an offer binding upon Daikin UK. Daikin UK has
compiled the content of this leaflet to the best of its knowledge.
No express or implied warranty is given for the completeness,
accuracy, reliability or fitness for particular purpose of its content FSC
and the products and services presented therein. Specifications are
subject to change without prior notice. Daikin UK explicitly rejects
any liability for any direct or indirect damage, in the broadest sense, Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC),
arising from or related to the use and/or interpretation of this leaflet. Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing
All content is copyrighted by Daikin UK. validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com

Daikin Airconditioning UK Limited The Heights Brooklands Weybridge Surrey KT13 0NY Tel 0845 6419000 Fax 0845 6419009 daikin.co.uk