SG With Answers - 21.2.2023
SG With Answers - 21.2.2023
SG With Answers - 21.2.2023
2. How many cycles will an AC signal make in 2 seconds if its frequency is 100
Hz?
a) 50 b) 100 c) 150 d) 200
Answer: d
Explanation: In electrical engineering, the frequency represents the ratio of the
number of cycles to the total time. Since frequency is given as 100 Hz and
an the
time is 2 sec thus a total of 200 cycles will be made.
5. If there are two bulbs connected in series and one blows out, what happens to
the other bulb?
a) The other bulb continues to glow with the same
sam brightness
b) The other bulb stops glowing
c) The other bulb glows with increased brightness
d) The other bulb also burns out
Answer: b
Explanation: Since the two bulbs are connected in series, if the first bulb burns
out there is a break in the circuit and hence the second bulb does not glow.
6. If two bulbs are connected in parallel and one bulb blows out, what happens
to the other bulb?
a) The other bulb blows out as well
b) The other bulb continues to glow with the same brightness
c) The other bulb glows
ows with increased brightness
d) The other bulb stops glowing
Answer: b
Explanation: If one bulb blows out, it acts as an open circuit. Current does not
flow in that branch but it continues to flow in the other branch of the parallel
circuit. Hence the other
er bulb continues to glow. Also the voltage across other
bulb remains the same due to which power delivered to it remains the same so it
continues to glow with the same brightness.
9. 1 kWh = ___________
a) 3.6 × 106 J b) 3.6 × 105 J c) 0.36 × 106 J d) 0.36 × 105 J
Answer: a
Explanation: The commercial unit of electric energy is kilowatt-hour (kWh).
1 kWh = 1000 Wh = 3.6 × 106J = one unit of electricity consumed. The
electric energy used in factories, industries and houses are measured in kWh.
10. Calculate the number of units of electricity used if a bulb of 100 W is kept
on for 5 hours.
a) 1 unit b) 0.1 unit c) 5 unit d) 0.5 unit
Answer: d
Explanation: The number of units of electricity consumed is
n = (total wattage × time in hour)/1000
Total wattage = 100 W; Time in hour = 5 hours
Therefore, n = (100×5)/1000 = 0.5 units
So, the number of units of electricity consumed is 0.5 units.
11. You bought 5 new light bulbs of 50 W each; in addition to the 7 bulbs you
already had in your house which is 50 W each. Calculate your electricity bill, if
you keep the new bulbs on for 5 hours and the older bulbs on only for 3 hours,
and the cost of one unit of electricity is Rs. 10.
a) Rs. 36 b) Rs. 35 c) Rs. 23 d) Rs. 39
Answer: c
Explanation: New bulbs = 5; Old bulbs = 7; Total wattage of new bulbs = 5 ×
50;
Total wattage of old bulbs = 7 × 50; Time the new bulbs are kept on = 5 hours;
Time the old bulbs are kept on = 3 hours
The number of units of electricity consumed by new bulbs (n1) = (total wattage
× time in hours)/1000
= (50×5×5)/1000 = 1.25
191EE546 - INTRODUCTION TO SMART GRID CAT – I (Materials) S.T. Subha Page 3
The number of units of electricity consumed by old bulbs (n2)
= (50×7×3)/1000 = 1.05
14. A power system will have greater flexibility of operation if they have
__________
a) Only Base load plants operating in combination
b) Various types of power plants operating in combination
c) Only Peak load plants operating in combination
d) Only thermal power plants operating in combination
Answer: b
Explanation: If various types of power plants are operated in combination, the
system will become more flexible i.e Steam and Nuclear power plants will
supply base loads, Hydroelectric power plants will supply base or peak loads
depending upon the availability of water, Gas turbine power plant will meet
15. Which of the following power plants can be profitably employed for
supplying base loads as well as peak loads?
a) Diesel power plant b) Hydroelectric power plant
c) Thermal power plant d) Nuclear power plant
Answer: b
Explanation: Seam and Nuclear power plants are only used to supply base load.
Diesel power plants are suitable for only peak load. Only hydroelectric power
plant can supply both peak load as well as base load because of its flexibility in
operation and low operating cost.
16. Which of the following is an essential requirement for a peak load plant?
a) Economical and speedy repair b) Capability of working continuously
c) Low operating cost d) Capability of quick start
Answer: d
Explanation: The power plants to be employed as peak load plant should only
have the capability of quick start, synchronization and taking up of system load
and quick response to load variations.
20. A system that integrates several types of power sources (wind turbines,
hydro, photovoltaics, and batteries) to give a reliable overall power supply is
termed as
Ans: d
Ans: c
22. Smart meter is an important element in building the smart grid. These
advanced meters
b. can send data and from electric companies and their customers
Ans: d
Ans: C
Ans: d
Ans: C
Ans: a
Ans: C
Ans: b
Answer: D
30. What is not true for smart grid in comparison with conventional power grid?
Ans: d
32. While designing the distribution to locality of one lac population with
medium dense load requirement, we can employ ___________
a) radial system b) parallel system c) ring main system d) any of
the mentioned
Answer: a
Explanation: A radial system is used for the medium requirement of loading and
a medium dense population as it becomes easier to install and operate.
Demand factor is the ratio of actual maximum demand on the system to the total
load connected to the system. The idea of demand factor was introduced due to
the fact that all the equipments connected to the system does not work at a time
in practice.
Ans: a
Ans: b
Ans: a
Ans: b
Ans: b
Ans: a
a. 66 KV b. 11 KV c. 400 KV d. 110KV
Ans: b
50.. Which of the following is not the characteristic of the existing Grid:
c. Self-healing
healing d. One way Communication
Ans: c
51. In which of the following methods, the data and power both are transferred
with the same conductor:
52. Which of the following may not be a barrier in the smart grid technologies?
c. Lack of regulator
a. 0.5 µs b. 1 µs c. 2 µs d. 0.1 µs
Ans: b
54. The boundaries of the customer domain typically consider which type of
meters
Ans: b
Ans: c
c. Transmission d. Customer
Ans: d
57. Energy Services Interfaces (ESI) communicates with other domain via:
Ans: a
Ans: d
*****************************************************************
UNIT – I
PART - B
1. Interpret the system having constant voltage and constant frequency regardless of
the load.
Normally, in a power system, more than one synchronous generators or alternators operate in
parallel. The alternators may be located at different places.
• Also, the alternators connected to the same busbar but separated by transmission lines
of low reactance may be considered as a single large machine.
The capacity of this power system is so large that its terminal voltage and frequency may be
taken constant. The connection or disconnection of a single alternator or a single small load
would not affect the magnitude and phase of the voltage and frequency. Therefore, the power
system behaves like a large alternator having virtually zero internal impedance and infinite
rotational inertia. Such kind of system having constant voltage and constant frequency
regardless of the load is known as infinite busbar system or infinite bus. An infinite bus can
be defined as follows −
An infinite bus is a power system so large that its voltage and frequency remain constant
regardless of how much real power and reactive power is drawn from or supplied to it.
When an alternator is operating in parallel with an infinite bus and its excitation voltage is
changed, the power factor of the machine changes. However, the change in excitation does
not change the terminal voltage which held constant in the system.
• The frequency of the infinite bus remains constant since the rotational inertia is too
large to enable the incoming machine to alter the speed of the system.
191EE546 - INTRODUCTION TO SMART GRID CAT – I (Materials) S.T. Subha Page 15
• The terminal voltage of the infinite bus remains constant, because the incoming
machine is very small to increase or decrease it.
• The synchronous impedance of an infinite bus is very small because the system
consists
nsists of a large number of alternators connected in parallel.
• The excitation of the alternator controls the reactive power supplied by the alternator
to the infinite bus. The increase in the excitation of the alternator increases the
reactive
active power output of the alternator.
The real power supplied by the alternator to the infinite bus is controlled by the governor
set points of the alternator.
• The terminal voltage and frequency of the alternator are controlled by the power
system to which it is connected.
nnected.
• The excitation of the alternator controls the reactive power supplied by the alternator
to the infinite bus. The increase in the excitation of the alternator increases the
reactive power output of the alternator.
V = E − IZs (eq)…(1)
Where,
Zs(eq) = Zs/n…(2)
∴V = E (Constant)…(3)
Hence, the speed of the machine is constant. Consequently, the frequency is constant.
Therefore, in order to obtain a constant voltage and constant frequency of a practical busbar
system, i.e., an infinite busbar, the number of alternators connected in parallel should be as
large as possible.
Voltage control in an electrical power system is important for operation for electrical power
equipment to prevent damage such as overheating of Generators and motors, to reduce transmission
losses and to maintain the ability of the system to withstand and prevent voltage collapse. In general
When reactive power supply lowers the voltage, as voltage drops current must increase to
maintain power supplied, causing system to consume more reactive power and the voltage drops
further. If the current increase too much, transmission lines go Offline, overloading other lines and
potentially causing cascading failures.
If the voltage drops too low, some generators will disconnect automatically to protect
themselves. Voltage collapse occurs when an increase in load or less generation or transmission
facilities causes dropping voltage, which causes a further reduction in reactive power from capacitor
and line charging, and still there further voltage reductions. If voltage reduction continues, these will
cause additional elements to trip, leading further reduction in voltage and loss of the load. The result
in these entire progressive and uncontrollable declines in voltage is that the system unable to provide
the reactive power required supplying the reactive power demands.
1. While active power is the energy supplied to run a motor, or illuminate an electric bulb, reactive
power provides the important function of regulating voltage.
2. If voltage on the system is not high enough, active power cannot be supplied.
3. Reactive power is used to provide the voltage levels necessary for active power to do useful work.
4. Reactive power is essential to move active power through the transmission and distribution system
to the customer.
Electrical grid or power grid is defined as the network which interconnects the generation,
transmission and distribution unit. It supplies the electrical power from generating unit to the
distribution unit. A large amount of power is transmitted from the generating station to load
centre at 220kV or higher. The network form by these high voltage lines is called the super
grid. The super grid feeds the sub-transmission network operating at 132kV or less.
The power station of the grid is located near the fuel source which reduces the transportation
cost of the system. But it is located far away from the populated areas. The power which is
generated at high voltage is stepped down by the help of step-down transformer in the
substation and then supply to the consumers. The electrical grid is mainly classified into two
types. They are:
In HVAC link the two AC systems are interconnected by an AC link. For interconnecting the
AC system, it is necessary that there should be sufficiently close frequency control on each of
the two systems.
For the 50Hz system, the frequency should lie between 48.5 Hz and 51.5 Hz. Such an
interconnection is known as synchronous interconnection or synchronous tie. The AC link
provides a rigid connection between two AC systems to be interconnected. But the AC
interconnection has certain limitations.
1. The interconnection of the two AC networks is the synchronous tie. The frequency
disturbances in one system are transferred to the other system.
2. The power swings in one system affects the other system. Large power swing in one
system may result in frequent tripping due to which major fault occurs in the system.
This fault causes complete failure of the whole interconnected system.
3. There is an increase in the fault level if an existing AC system is connected with the
other AC system with an AC tie line. This is because the additional parallel line
reduces the equivalent reactance of the interconnected system. If the two AC systems
are connected to the fault line, then the fault level of an each AC system remains
unchanged.
Unit - I
Part – C
(b). State the need of control of voltage and frequency in Electrical grid.
(a). The main difference between active and reactive power is that Active Power is actual or
real power which is used in the circuit while Reactive power bounce back and forth between
load and source which is theoretically useless.
The following power triangle shows the relation between Active, Reactive and Apparent
Power. These all powers only induced in AC circuits when current is leading or lagging
behind the voltage i.e. there is a phase difference (phase angle (Φ) between voltage and
current.
The Power which is really utilized and consumed for useful works in AC or DC circuit is
known as Active Power. It is also called True Power, Real Power, Useful Power or Watt-full
Power. It is denoted by “P” and measured in Watts, kW or MW. The average value of active
power can be calculated by the following formulas.
The power which moves and back (bounces back and forth) between source and load in the
circuit is known as Reactive Power. It is also called, Useless Power or Watt-less Power.
Reactive Power is denoted by “Q” and measured in VAR (Volt Ampere Reactive), kVAR or
MVARs.
Reactive Power is useful too i.e. it helps to produce magnetic and electric field and stores in
the circuits and discharge by transformers, solenoid, and induction motors etc.
The following table shows the main differences between Active and Reactive Powers.
Represented by P Q
• P = √ (S2 – Q2)
Measuring
Watt meter VAr meter
Instrument
We always in practice try to reduce reactive power to improve system efficiency. This is
acceptable at some level, if system is purely resistively or capacitance it make cause some
problem in Electrical system. AC systems supply or consume two kind of power: real power
and reactive power.
Assuming that load is constant, the voltage at the terminals of a rotating generator depends on
the changing magnetic flux through the generator’s stator windings as the generator’s rotor
spins. The amount of magnetic flux depends on the intensity of the rotor’s magnetic field; the
rate of change in flux is dependent on how fast the rotor is spinning.
Typically an off-grid generator’s AVR is set in a mode that attempts to keep voltage constant.
That is, as loads change, it increases or decreases field strength in response. Likewise, in an
inverter-based system, the inverter’s power electronic controls are designed to keep voltage
constant. As discussed below, AVRs are also used in grid-connected generators.
Control of Frequency
For a synchronous generator, frequency is determined by the rotational speed of the
generator shaft; faster rotation generates a higher frequency. A generator’s frequency depends
on the balance between the pressure and flow rate of water flowing through the turbine and
the amount of electrical load. (Similarly, a car’s motor speed depends on both the rate of fuel
flow to the motor and the load on the engine.) With no load, the generator will “freewheel”
and run at a very high rpm, just as a car’s engine will spin quickly if revved with the
transmission in neutral. If load is excessive, the generator bogs down (spins slower than
normal) and the frequency drops below the standard, just as a car slows down while going up
a steep hill.
In the case of an isolated mini-grid, the renewable electricity generator must maintain
frequency control because there is no option of frequency control by any other means. In an
isolated micro-hydropower context, commonly occurring large and sudden changes in load or
generation resources on the system can drive frequency up or down. In these systems, control
of frequency is accomplished one of two ways. One method uses a mechanical controller that
incrementally opens the water supply valve to increase water flow the moment that it detects
a drop in frequency and incrementally closes the valve when it detects excessive frequency.
This negative feedback loop keeps frequency fairly constant under most conditions.
Similarly, generators with internal combustion engines modulate the engine throttle in
All types of frequency control can do little to help in the situation in which load exceeds the
generating capacity of the source – unfortunately a common occurrence in many mini-grids
in developing countries. If loads exceed the generating capacity, the generator bogs down,
frequency drops, and a brownout typically ensues. More advanced utility systems employ
automatic relays that drop load when frequency begins to sag (known as under frequency
load-shedding schemes).
Definition: Electrical grid or power grid is defined as the network which interconnects the
generation, transmission and distribution unit. It supplies the electrical power from generating
unit to the distribution unit. A large amount of power is transmitted from the generating
station to load centre at 220kV or higher. The network form by these high voltage lines is
called the super grid. The super grid feeds the sub-transmission network operating at 132kV
or less.
The power station of the grid is located near the fuel source which reduces the transportation
cost of the system. But it is located far away from the populated areas. The power which is
generated at high voltage is stepped down by the help of step-down transformer in the
substation and then supply to the consumers. The electrical grid is mainly classified into two
types. They are:
Interconnection
The interconnection of the grid provides the best use of power resource and ensures great
security to supply. It makes the system economical and reliable. The generating stations are
interconnected for reducing the reserve generation capacity in each area.
Types of Interconnections
The interconnection between networks is mainly classified into two types, i.e., the HVAC
link and HVDC link.
In HVAC link the two AC systems are interconnected by an AC link. For interconnecting the
AC system, it is necessary that there should be sufficiently close frequency control on each of
the two systems.
For the 50Hz system, the frequency should lie between 48.5 Hz and 51.5 Hz. Such an
interconnection is known as synchronous interconnection or synchronous tie. The AC link
provides a rigid connection between two AC systems to be interconnected. But the AC
interconnection has certain limitations.
4. The interconnection of the two AC networks is the synchronous tie. The frequency
disturbances in one system are transferred to the other system.
5. The power swings in one system affects the other system. Large power swing in one
system may result in frequent tripping due to which major fault occurs in the system.
This fault causes complete failure of the whole interconnected system.
6. There is an increase in the fault level if an existing AC system is connected with the
other AC system with an AC tie line. This is because the additional parallel line
reduces the equivalent reactance of the interconnected system. If the two AC systems
are connected to the fault line, then the fault level of an each AC system remains
unchanged.
The DC interconnection or DC tie provides a loose coupling between the two AC system to
be interconnected. The DC tie between two AC systems is non-synchronous (Asynchronous).
The DC interconnection has the certain advantages. They are as follows:
Nowadays, the customary grids are replaced by the smart grids. The smart grid uses the smart
meter and appliances which improves the efficiency of the system.
• Power stations:: often located near energy and away from heavily populated areas.
Components:
1. Generation
Electricity generation is the process of generating electric power from sources of primary
energy typically at power stations
stations.. Usually this is done
with electromechanical generators driven by heat engines or the kinetic energy of water or
wind. Other energy sources include solar photovoltaics and geothermal power.
The sum of the power outputs of generators on the grid is the production of the grid, typically
measured in gigawatts (GW).
2. Transmission
Because the power is often generated far from where it is consumed, the transmission system
can cover great distances. For a given amount of power, transmission efficiency is greater at
higher voltages and lower currents. Therefore, voltages are stepped up at the generating
station, and stepped down at local substations for distribution to customers.
Most transmission is three-phase. Three phase, compared to single phase, can deliver much
more power for a given amount of wire, since the neutral and ground wires are
shared. Further, three-phase generators and motors are more efficient than their single-phase
counterparts.
However, for conventional conductors one of the main losses are resistive losses which are a
square law on current, and depend on distance. High voltage AC transmission lines can lose
1-4% per hundred miles. However, high-voltage direct current can have half the losses of
AC. Over very long distances, these efficiencies can offset the additional cost of the required
AC/DC converter stations at each end.
Transmission networks are complex with redundant pathways. The physical layout is often
forced by what land is available and its geology. Most transmission grids offer the reliability
that more complex mesh networks provide. Redundancy allows line failures to occur and
power is simply rerouted while repairs are done.
Substations
Substations may perform many different functions but usually transform voltage from low to
high (step up) and from high to low (step down). Between the generator and the final
consumer, the voltage may be transformed several times.
• Step-up substation: these use transformers to raise the voltage coming from the
generators and power plants so that power can be transmitted long distances more
efficiently, with smaller currents.
• Step-down substation: these transformers lower the voltage coming from the
transmission lines which can be used in industry or sent to a distribution substation.
• Distribution substation: these transform the voltage lower again for the distribution to
end users.
• Circuit breakers: used to automatically break a circuit and isolate a fault in the system.
• The substation busbar: typically, a set of three conductors, one for each phase of
current. The substation is orgranized around the buses, and they are connected to
incoming lines, transformers, protection equipment, switches, and the outgoing lines.
• Lightning arresters
Distribution is the final stage in the delivery of power; it carries electricity from the
transmission system to individual consumers. Substations connect to the transmission system
and lower the transmission voltage to medium voltage ranging between 2 kV and 35 kV.
Primary distribution lines carry this medium voltage power to distribution transformers
located near the customer's premises. Distribution transformers again lower the voltage to the
utilization voltage. Customers demanding a much larger amount of power may be connected
directly to the primary distribution level or the sub transmission level.
A radial system is arranged like a tree where each customer has one source of supply. A
network system has multiple sources of supply operating in parallel. Spot networks are used
for concentrated loads. Radial systems are commonly used in rural or suburban areas.
Radial systems usually include emergency connections where the system can be reconfigured
in case of problems, such as a fault or planned maintenance. This can be done by opening and
closing switches to isolate a certain section from the grid.
Long feeders experience voltage drop(power factor distortion) requiring capacitors or voltage
regulators to be installed.
Reconfiguration, by exchanging the functional links between the elements of the system,
represents one of the most important measures which can improve the operational
performance of a distribution system.
A substation receives its power from the transmission network, the power is stepped down
with a transformer and sent to a bus from which feeders fan out in all directions across the
countryside. These feeders carry three-phase power, and tend to follow the major streets near
the substation. As the distance from the substation grows, the fan out continues as smaller
laterals spread out to cover areas missed by the feeders. This tree-like structure grows
outward from the substation, but for reliability reasons, usually contains at least one unused
backup connection to a nearby substation. This connection can be enabled in case of an
emergency, so that a portion of a substation's service territory can be alternatively fed by
another substation.
Conventional electrical supply networks normally have vertical structure whereby the electric
power generated by the generation system is passed to transmission system which is then
transferred to distribution network for feeding it to connected loads. Figure 2.1 shows the
principle of vertical structure of electrical supply networks whereby electricity flows in one
direction, starting from generation system, through transmission system to distribution
networks and finally to loads.
Components:
1. Generation
Electricity generation is the process of generating electric power from sources of primary
energy typically at power stations
stations.. Usually this is done
The sum of the power outputs of generators on the grid is the production of the grid, typically
measured in gigawatts (GW).
2. Transmission
Electric power transmission is the bulk movement of electrical energy from a generating site,
via a web of interconnected lines, to an electrical substation, from which is connected to the
distribution system. This networked system of connections is distinct from the local wiring
between high-voltage substations and customers.
Because the power is often generated far from where it is consumed, the transmission system
can cover great distances. For a given amount of power, transmission efficiency is greater at
higher voltages and lower currents. Therefore, voltages are stepped up at the generating
station, and stepped down at local substations for distribution to customers.
Most transmission is three-phase. Three phase, compared to single phase, can deliver much
more power for a given amount of wire, since the neutral and ground wires are
shared. Further, three-phase generators and motors are more efficient than their single-phase
counterparts.
However, for conventional conductors one of the main losses are resistive losses which are a
square law on current, and depend on distance. High voltage AC transmission lines can lose
1-4% per hundred miles. However, high-voltage direct current can have half the losses of
AC. Over very long distances, these efficiencies can offset the additional cost of the required
AC/DC converter stations at each end.
Transmission networks are complex with redundant pathways. The physical layout is often
forced by what land is available and its geology. Most transmission grids offer the reliability
that more complex mesh networks provide. Redundancy allows line failures to occur and
power is simply rerouted while repairs are done.
Substations
Substations may perform many different functions but usually transform voltage from low to
high (step up) and from high to low (step down). Between the generator and the final
consumer, the voltage may be transformed several times.
• Step-up substation: these use transformers to raise the voltage coming from the
generators and power plants so that power can be transmitted long distances more
efficiently, with smaller currents.
• Step-down substation: these transformers lower the voltage coming from the
transmission lines which can be used in industry or sent to a distribution substation.
• Circuit breakers: used to automatically break a circuit and isolate a fault in the system.
• The substation busbar: typically, a set of three conductors, one for each phase of
current. The substation is orgranized around the buses, and they are connected to
incoming lines, transformers, protection equipment, switches, and the outgoing lines.
• Lightning arresters
Distribution is the final stage in the delivery of power; it carries electricity from the
transmission system to individual consumers. Substations connect to the transmission system
and lower the transmission voltage to medium voltage ranging between 2 kV and 35 kV.
Primary distribution lines carry this medium voltage power to distribution transformers
located near the customer's premises. Distribution transformers again lower the voltage to the
utilization voltage. Customers demanding a much larger amount of power may be connected
directly to the primary distribution level or the sub transmission level.
A radial system is arranged like a tree where each customer has one source of supply. A
network system has multiple sources of supply operating in parallel. Spot networks are used
for concentrated loads. Radial systems are commonly used in rural or suburban areas.
Radial systems usually include emergency connections where the system can be reconfigured
in case of problems, such as a fault or planned maintenance. This can be done by opening and
closing switches to isolate a certain section from the grid.
Long feeders experience voltage drop(power factor distortion) requiring capacitors or voltage
regulators to be installed.
Reconfiguration, by exchanging the functional links between the elements of the system,
represents one of the most important measures which can improve the operational
performance of a distribution system.
A substation receives its power from the transmission network, the power is stepped down
with a transformer and sent to a bus from which feeders fan out in all directions across the
countryside. These feeders carry three-phase power, and tend to follow the major streets near
Conventional electrical supply networks normally have vertical structure whereby the electric
power generated by the generation system is passed to transmission system which is then
transferred to distribution network for feeding it to connected loads.
1. Technology:
2. Distribution:
One-Way Distribution: Power can only be distributed from the main plant using traditional
energy infrastructure.
3. Generation:
Centralized: With traditional energy infrastructure, all power must be generated from a
central location. This eliminates the possibility of easily incorporating alternative energy
sources into the grid.
4. Sensors:
5. Monitoring:
6. Restoration:
7. Equipment:
Failure & Blackout: As a result of aging and limitations, traditional energy infrastructure is
prone to failures. Failure of infrastructure can lead to blackouts, a condition where the end
customer is receiving no power to their unit causing downtime.
8. Control:
Limited: Using traditional power infrastructure, energy is very difficult to control. After
leaving the power plant or substation, companies have no control over the energy
distribution.
9. Customer Choices:
Fewer: The traditional power grid system infrastructure is not properly equipped to give
customers a choice in the way they receive their electricity. Alternative energy sources, for
example, have to be separated from power plants and traditional grid infrastructure. This is
also part of the reasoning behind the establishment of electric companies as a public utility.
The price of electricity is dictated by the utility to which the consumer is connected. In other
words, consumers have no choice of opting from where they buy their electricity, that is,
consumers are considered passive.
5. List out the drawbacks and challenges faced in conventional electrical networks.
Challenges Faced:
Handling failure
Failures are usually associated with generators or power transmission lines tripping circuit
breakers due to faults leading to a loss of generation capacity for customers, or excess
demand. This will often cause the frequency to reduce, and the remaining generators will
react and together attempt to stabilize above the minimum. If that is not possible then a
number of scenarios can occur.
191EE546 - INTRODUCTION TO SMART GRID CAT – I (Materials) S.T. Subha Page 32
A large failure in one part of the grid — unless quickly compensated for — can cause current
to re-route itself to flow from the remaining generators to consumers over transmission lines
of insufficient capacity, causing further failures. One downside to a widely connected grid is
thus the possibility of cascading failure and widespread power outage. A central authority is
usually designated to facilitate communication and develop protocols to maintain a stable
grid.
Brownout
Blackout
A power outage (also called a power cut, a power out, a power blackout, power failure or
a blackout) is a loss of the electric power to a particular area.
Power failures can be caused by faults at power stations, damage to electric transmission
lines, substations or other parts of the distribution system, a short circuit, cascading
failure, fuse or circuit breaker operation, and human error.
Power failures are particularly critical at sites where the environment and public safety are at
risk. Institutions such as hospitals, sewage treatment plants, mines, shelters and the like will
usually have backup power sources such as standby generators, which will automatically start
up when electrical power is lost. Other critical systems, such as telecommunication, are also
required to have emergency power. The battery room of a telephone exchange usually has
arrays of lead–acid batteries for backup and also a socket for connecting a generator during
extended periods of outage.
Load shedding:
Electrical generation and transmission systems may not always meet peak demand
requirements— the greatest amount of electricity required by all utility customers within a
given region. In these situations, overall demand must be lowered, either by turning off
service to some devices or cutting back the supply voltage (brownouts), in order to prevent
uncontrolled service disruptions such as power outages (widespread blackouts) or equipment
damage. Utilities may impose load shedding on service areas via targeted blackouts, rolling
blackouts or by agreements with specific high-use industrial consumers to turn off equipment
at times of system-wide peak demand.
Normally, the electric power used within the plant is provided from the station's own
generators. If all of the plant's main generators are shut down, station service power is
provided by drawing power from the grid through the plant's transmission line. However,
during a wide-area outage, off-site power from the grid is not available. In the absence of grid
power, a so-called black start needs to be performed to bootstrap the power grid into
operation.
Aging infrastructure:
Despite the novel institutional arrangements and network designs of the electrical grid, its
power delivery infrastructures suffer aging across the developed world. Contributing factors
to the current state of the electric grid and its consequences include:
• Aging equipment – older equipment has higher failure rates, leading to customer
interruption rates affecting the economy and society; also, older assets and facilities
lead to higher inspection maintenance costs and further repair and restoration costs.
• Obsolete system layout – older areas require serious additional substation sites
and rights-of-way that cannot be obtained in the current area and are forced to use
existing, insufficient facilities.
• Outdated engineering – traditional tools for power delivery planning and engineering
are ineffective in addressing current problems of aged equipment, obsolete system
layouts, and modern deregulated loading levels.
Old cultural value – planning, engineering, operating of system using concepts and
procedures that worked in vertically integrated industry exacerbate the problem under a
deregulated industry.
Apart from being old and out-of-date, conventional electrical networks have recently
been subjected to many changes. The most important of these that proved to be difficult for
the networks to accommodate include:
(i). The integration of distributed energy resources (DERs) based-generators, including RESs
based-generators and storage systems into electrical networks, particularly at distribution
voltage levels.
(ii). Accommodating the recent new development in transport industry in terms of EVs will
be presented as a new type of load which puts further stress on the network.
(iii). Dealing with the dynamic situation between electricity market stakeholders and
electrical utilities due to liberalization of electricity market in recent years that require the
implementation of new tools and methodologies with the help of new and advanced
technologies.
UNIT – II
PART - B
2. Identify the areas of applications of Smart Grids and write some of the definitions of
Smart Grid.
A Smart Grid is an electricity Network based on Digital Technology that is used to
supply electricity to consumers via Two-Way Digital Communication. This system allows
for monitoring, analysis, control and communication within the supply chain to help
improve efficiency, reduce the energy consumption and cost and maximise the
transparency and reliability of the energy supply chain. The term “Smart Grid” was coined
by Andres E. Carvallo on April 24, 2007 at an IDC energy conference in Chicago.
Definition: Smart grid is integration of an electric power system, communication network,
advanced Sensing, metering, measurement infrastructure, complete decision support and
human interfaces software and hardware to monitor, control and manage the creation,
distribution, storage and consumption of energy. The areas of application of smart grids
include: smart meters integration, demand management, smart integration of generated
energy, administration of storage and renewable resources, using systems that
continuously provide and use data from an energy network. A Smart Grid is an electricity
network that can intelligently integrate the actions of all users connected to it – generators,
consumers and those that do both – in order to efficiently deliver sustainable, economic
and secure electricity supplies.
System (Generation, Transmission, Distribution) with an advanced two- way
communications system.
Enables real-time monitoring and control.
Provide greater visibility and transparency.
Consequently, enables cost reduction and efficiency improvement.
Smart Grid is based on Digital Technology that is used to supply electricity to consumers
via Two-Way Digital Communication. This system allows for monitoring, analysis,
control and communication within the supply chain to help improve efficiency, reduce the
A smart grid automatically detects and responds to routine problems and quickly recover if
they occur, minimizing downtime and financial loss. Self-healing concept important to the
Energy Infrastructure A secure ―architected sensing, communications, automation (control),
and energy overlaid infrastructure as an integrated, reconfigurable, and electronically
controlled system that will offer unprecedented flexibility and functionality, and improve
system availability, security, quality, resilience and robustness.
The Self-Healing Grid is a system comprised of sensors, automated controls, and advanced
software that utilizes real-time distribution data to detect and isolate faults and to
reconfigure the distribution network to minimize the customers impacted.
One of the main goals of a Self-Healing Grid is to improve system reliability.
This can be accomplished by reconfiguring the switches and reclosers installed on the
distribution feeder to quickly isolate the faulted section of the feeder and re-establish service
to as many customers as possible from alternate sources/feeders.
Unit - II
Part – C
2. The second generation is based on the automatic telephone switchboard equipment of the
1950s. It may be considered as one of the first uses of communication equipment in a grid
substation. Using this equipment, the operator at a remote location could read and have
control of the local substation. This equipment was called supervisory control equipment.
3. In the late 1960s the supervisory control and data acquisition system (SCADA) was
introduced to replace supervisory control equipment.
4. The SCADA system slowly expanded in the 1970s and 1980s whereby a minimum
monitoring of the majority of the transmission systems operating at voltages of 220 kV or
higher and some distribution substations were included. This system was also used to
centrally support control rooms and Remote Terminal Units (RTUs) for data collection and
control in the substations.
6. As technology progressed, communication links took the place of the hardwired inputs.
The RTU/PLC configuration was then replaced with different network architecture in the
mid-1990s. This network architecture consists of protection relays/intelligent electronic
devices (IEDs), PLCs, and other devices talking to each other over a network and
coordinating operations. Number of utilities has already moved to the second generation of
7. Since about 2005, there has been increasing interest in the Smart Grid. The recognition that
ICT offers significant opportunities to modernise the operation of the electrical networks has
coincided with an understanding that the power sector can only be de-carbonised at a realistic
cost if it is monitored and controlled effectively.
In the context of Smart Grid, historically distribution networks are usually controlled
manually. However, manually operated switches and fuses do not lend themselves easily to
the Smart Grid concept. For this reason, many utilities embarked on developing programs
aiming at deployment of intelligence, primarily to enhance the voltage profiles of distribution
networks and to speed up isolation of faults.
Apart from being old and out-of-date, conventional electrical networks have recently been
subjected to many changes. The most important of these that proved to be difficult for the
networks to accommodate include:
(i). The integration of distributed energy resources (DERs) based-generators, including RESs
based-generators and storage systems into electrical networks, particularly at distribution
voltage levels.
(ii). Accommodating the recent new development in transport industry in terms of EVs will
be presented as a new type of load which puts further stress on the network.
(iii). Dealing with the dynamic situation between electricity market stakeholders and
electrical utilities due to liberalization of electricity market in recent years that require the
implementation of new tools and methodologies with the help of new and advanced
technologies.
These changes have adversely affected the operation, management, and protection of
networks in a number of ways. Additionally the advancement in digital, communication,
automatic control, and other technologies has opened new windows and opportunities to find
solutions and tackle network’s problems. This in turn has led to initially contemplate on
modernizing conventional electrical networks and eventually to the development of the Smart
Grid concept.
2. Brief out the motives behind developing the Smart Grid Network.
It has been recognized that the changes to which electrical networks are subjected in recent
years have made the grid of today unable to meet the challenges of the future. This has led to
urgent need to modernizing electrical networks, which in turn has evolved into the
development of the Smart Grid concept. The Smart Grid concept is widely perceived as way
forward to solve problems related to growing energy consumption, integration of distributed
generation, energy efficiency, power supply reliability, and power quality. The factors that
led to the development of the Smart Grid concept may be summarized as follows:
● Sourcing 20% of the EU’s total energy, including transport, heating and lighting, and
electricity from renewable sources
All targets must be completed by 2020. This represents a considerable challenge for the
energy sector of today. As far as the electricity grid, the triple commitment is even more
challenging as this means that approximately 35% of all electricity must be generated from
renewable energy sources (RESs).
Sharp increase in oil prices following the Arab–Israeli conflict in October 1973
has led the industrial nations to multiply their efforts to harness RESs, including
wind, solar, hydro, etc. Subsequent years have witnessed the development of
mature technologies to generate electricity from RESs such as solar energy, using
photovoltaic (PV), and wind power, which are perceived as environment friendly
and they do not emit the greenhouse gas, CO2, associated with generation of
electricity using fossil fuels. It is claimed that the electricity generated from
fossil fuels causes approximately 25% of global greenhouse gas emissions [3]
which prompted utilities to redefine the electricity system of the future in terms
of how it should look like. However, the majority of electrical generators powered by RES
Liberalization of electricity market in the USA, Europe [4], and elsewhere has
made it necessary that the reliability and quality of energy supply must be ensured
while adapting the structure and processes to take on board the new market
approach and new legal obligations, integrating RESs into the system and
increasing the efficiency of both transmission and distribution networks in order to
limit the grid tariffs.
It is anticipated that implementing the Smart Grid concept will greatly improve the operation
of power system as a result of improving load factors, reducing system losses, and the
expected dramatic improvement in the outage management performance. It is also anticipated
that as a consequence of fully implementing the Smart Grid concept the grid will be equipped
with additional intelligence. This in turn will provide planners and engineers with extra
knowledge to build ‘‘what is needed when it is needed,’’ extend the life of assets, repair
equipment before it fails unexpectedly, and more importantly manage the work force
responsible for maintaining the grid. This will result in reducing the operation, maintenance,
and capital costs and thereby reducing the pressure on electricity prices.
Under the Smart Grid environment it will be much easier to integrate all types and sizes of
electrical generation and storage systems using simplified interconnection processes and
universal interoperability standards to support what is called a ‘‘plug and-play’’ approach. It
is expected that large central generation plants, including advanced nuclear plants and RESs,
such as wind and solar farms which are considered environment friendly, will continue to
play a major role despite the expected deployment of large number of smaller distributed
resources, including plug-in EVs. It will also be possible to interconnect generators with
capacities ranging from small to large at essentially all voltage levels. This will include DERs
such as photovoltaic, wind, advanced batteries, plug-in hybrid vehicles, and fuel cells.
Commercial users will find it much easier and more profitable to install their own generation
such as highly efficient combined heat and power installations and electric storage facilities.
It is expected that implementing the Smart Grid concept will help in monitoring, diagnosing,
and responding to power quality deficiencies. This in turn will lead to a substantial reduction
in the business losses currently experienced by consumers due to low power quality.
Adapting new power quality standards will balance load sensitivity with delivered power
quality. The Smart Grid will facilitate the supply of varying grades of power quality at
different pricing levels. Additionally, power quality events that originate in the transmission
and distribution elements of the electrical power system can be minimized. The irregularities
caused by certain consumer loads can also be isolated and consequently preventing the
adverse effect on the electrical system and other consumers.
A system-wide solution that ensures the reduction of physical and cyber vulnerabilities and
enables a rapid recovery from disruptions will be incorporated under the Smart Grid
environment. This will result in the Smart Grid being resilience which will deter any attack
that would be committed from even those who are determined and well equipped. However,
its decentralized operating model and self-healing features will also make it less vulnerable to
natural disasters than today’s grid. Additionally, security protocols will be designed such that
they will contain elements of deterrence, detection, response, and mitigation to ensure
minimizing the impact on the grid and the economy. This particular characteristic of the
Smart Grid makes it less susceptible and more resilient, which will in turn make it a more
difficult target for terrorists.
It is expected that active participation of consumers in electricity markets would bring several
benefits to the grid as well as the environment. By fully implementing the Smart Grid
concept, consumers will get access to the necessary information, control, and options that
allow them to engage in ‘‘electricity markets.’’ However, grid operators will consider willing
consumers as resources in the day-to-day operation of the grid as will be discussed later on in
the following chapters. Additionally well informed consumers will have the ability to modify
their consumption based on balancing their demands and resources with the electric system’s
capability to meet those demands. Dedicated demand response (DR) programs will help
satisfying basic consumers’ need, i.e., the ability and flexibility in deciding when and where
from energy is purchased. Such participation of consumers would help in reducing or shifting
Realizing the Smart Grid will facilitate linking buyers and sellers together, starting from
consumers to generators and all those in between. It will also support the creation of new
electricity markets and tools that ensure efficient electricity trading. This will range from the
home energy management system at the consumers’ premises to the technologies that allow
consumers and third parties to bid their energy into the electricity market. This will help in
making consumers feel price fluctuations through real-time pricing. The reaction of
consumers to price increases will inevitably lead to mitigate demand and energy usage. This
in turn will drive lower-cost solutions, which will lead to new technology development. New
and clean energy-related products will also be offered as market options. The Smart Grid is
also expected to support consistent market operation across regions.