The document provides a lighting plan for a building project. It includes a table of contents listing various sections and subsections describing the project site, building, rooms, lighting fixtures, and light calculations. Parameters for daylight calculations including location and sky conditions are provided in the preface.

Uploaded by

tharunarulramesh
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views

Project Report

The document provides a lighting plan for a building project. It includes a table of contents listing various sections and subsections describing the project site, building, rooms, lighting fixtures, and light calculations. Parameters for daylight calculations including location and sky conditions are provided in the preface.

Uploaded by

tharunarulramesh
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Date 28-02-2024

Project

Created with DIALux


Project

Preface

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.

The daylight was also taken into account for the calculations in the
course of this planning. The following parameters formed the basis
for the calculations:

Location: Madras
Zenith luminance: 8136 cd/m²
Pollution category: Medium to heavy traffic, dust exposure under 600
microgram/cubic metre
Project

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product data sheets


Philips - SP341P LED21S/940 O POE L1200 (1x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Philips - SP341P LED21S/940 O POE L1200 (1x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Site 1

Building 1
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
.............................

Site 1 - Building 1

Storey 1
Room list / Light scene 5 (Room 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 .............................
Calculation objects / Light scene 5 (Room 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 .............................
Calculation objects / Light scene for daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 .............................

Site 1 - Building 1 - Storey 1

Room 1
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 .............................
Summary / Light scene 5 (Room 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 .............................
Summary / Light scene for daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30 .............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31 .............................
Calculation objects / Light scene 5 (Room 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Calculation objects / Light scene for daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35.............................
Working plane (Room 1) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . 37.............................
Working plane (Room 1) / Light scene 5 (Room 1) / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . .38.............................
(adaptive)
Working plane (Room 1) / Light scene for daylight factor / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 .............................
illuminance (adaptive)
Project

Table of Contents

Daylight factor effective area (Room 1) / Light scene for daylight factor / Daylight . . . . . . . . . . . . . . . . . . . .40
.............................
factor

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
.............................
Project

Description

5
Project

Luminaire list

Φtotal Ptotal Luminous efficacy


18900 lm 206.0 W 91.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

7 Philips SP341P LED21S/940 O POE L1200 18.0 W 2100 lm 116.6 lm/W

2 Philips SP341P LED21S/940 O POE L1200 40.0 W 2100 lm 52.5 lm/W

6
Project

Product data sheet

Philips - SP341P LED21S/940 O POE L1200

P 18.0 W

ΦLamp 2100 lm

ΦLuminaire 2100 lm

η 99.98 %

Luminous efficacy 116.6 lm/W

CCT 4000 K Polar LDC

CRI 90

FlexBlend heading the way to efficient and flexible furnished offices


areas Philips FlexBlend is an attractive family of surface mounted and
suspended luminaires, next to Flexblend recessed. The luminaire
range is enabling building owners to advance their lighting
operations, by offering office-compliant lighting with a return on
investment of less than 3 to 4 years.
FlexBlend provides the required flexibility through the adaptability in
design. This gives the possibility to install the luminaires easily in the
field, at any moment. Even when todays luminaire is suspended,
tomorrow this can be adapted to a surface mounted installation at
the venue. And the other way around.
The surface mounted and suspended luminaire range fit to many
different office spaces like open plan office, corridors, reception or
meeting rooms.
FlexBlend is offered in both lines and as standalone, using the same
lighting module. This gives the option to the users to use FlexBlend
as standalone now, and tomorrow, as line. The controller is
integrated in the luminaire.
As technology is changing fast, the ideal lighting solution is also
expected to be ready to incorporate innovations that can help UGR diagram (SHR: 0.25)
optimize operations further. For this reason, FlexBlend holds all
connectivity and future ready options available. As System Ready
luminaire it can be paired with lighting management systems such as
the Philips SpaceWise, and to software-based lighting systems

7
Project

Product data sheet

Philips - SP341P LED21S/940 O POE L1200

as Interact Office wired (PoE) and Interact Office wireless and/or


existing and upcoming sensor innovations. The luminaire range is
therefore future ready and can be delivered without any system
component, and in a next phase, in the field to be upgraded. An
attractive opportunity for new installations and renovations.

8
Project

Product data sheet

Philips - SP341P LED21S/940 O POE L1200

P 40.0 W

ΦLamp 2100 lm

ΦLuminaire 2100 lm

η 99.98 %

Luminous efficacy 52.5 lm/W

CCT 4000 K Polar LDC

CRI 90

FlexBlend heading the way to efficient and flexible furnished offices


areas Philips FlexBlend is an attractive family of surface mounted and
suspended luminaires, next to Flexblend recessed. The luminaire
range is enabling building owners to advance their lighting
operations, by offering office-compliant lighting with a return on
investment of less than 3 to 4 years.
FlexBlend provides the required flexibility through the adaptability in
design. This gives the possibility to install the luminaires easily in the
field, at any moment. Even when todays luminaire is suspended,
tomorrow this can be adapted to a surface mounted installation at
the venue. And the other way around.
The surface mounted and suspended luminaire range fit to many
different office spaces like open plan office, corridors, reception or
meeting rooms.
FlexBlend is offered in both lines and as standalone, using the same
lighting module. This gives the option to the users to use FlexBlend
as standalone now, and tomorrow, as line. The controller is
integrated in the luminaire.
As technology is changing fast, the ideal lighting solution is also
expected to be ready to incorporate innovations that can help UGR diagram (SHR: 0.25)
optimize operations further. For this reason, FlexBlend holds all
connectivity and future ready options available. As System Ready
luminaire it can be paired with lighting management systems such as
the Philips SpaceWise, and to software-based lighting systems

9
Project

Product data sheet

Philips - SP341P LED21S/940 O POE L1200

as Interact Office wired (PoE) and Interact Office wireless and/or


existing and upcoming sensor innovations. The luminaire range is
therefore future ready and can be delivered without any system
component, and in a next phase, in the field to be upgraded. An
attractive opportunity for new installations and renovations.

10
Project

Building 1
Luminaire list

Φtotal Ptotal Luminous efficacy


18900 lm 206.0 W 91.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

7 Philips SP341P LED21S/940 O POE L1200 18.0 W 2100 lm 116.6 lm/W

2 Philips SP341P LED21S/940 O POE L1200 40.0 W 2100 lm 52.5 lm/W

11
Project

Building 1 · Storey 1 (Light scene 5 (Room 1))


Room list

12
Project

Building 1 · Storey 1 (Light scene 5 (Room 1))


Room list

Room 1

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


206.0 W 119.40 m² 1.73 W/m² = 0.13 W/m²/100 lx (Room) 1315 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

7 Philips SP341P LED21S/940 O POE L1200 18.0 W 2100 lm

2 Philips SP341P LED21S/940 O POE L1200 40.0 W 2100 lm

13
Project

Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


18900 lm 206.0 W 91.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

7 Philips SP341P LED21S/940 O POE L1200 18.0 W 2100 lm 116.6 lm/W

2 Philips SP341P LED21S/940 O POE L1200 40.0 W 2100 lm 52.5 lm/W

14
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

15
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 1160 lx 173 lx 63444 lx 0.15 0.003 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi).

16
Project

Building 1 · Storey 1 (Light scene 5 (Room 1))


Calculation objects

17
Project

Building 1 · Storey 1 (Light scene 5 (Room 1))


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 1315 lx 203 lx 63488 lx 0.15 0.003 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi).

18
Project

Building 1 · Storey 1 (Light scene for daylight factor)


Calculation objects

19
Project

Building 1 · Storey 1 (Light scene for daylight factor)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 330 lx 107 lx 2569 lx 0.32 0.042 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Daylight

Properties Dm Dmin Dmax Uo (g1 ) g2 Index

Daylight factor effective area (Room 1) 1.370 % 0.542 % 4.312 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Notes on planning:
Daylight proportion for Overcast Sky on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi).

20
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Ground area 119.40 m²

Reflection factors Ceiling: 70.0 %, Clearance height 3.000 m


Walls: 39.1 %,
Floor: 62.3 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

21
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Daylight D 1.370 % – DF1

Working plane Ēperpendicular 1160 lx ≥ 300 lx WP1

Uo (g1 ) 0.15 ≥ 0.40 WP1

Energy estimation(2) Consumption 0.00 kWh/a max. 4200 kWh/a

Room Lighting power density 0.00 W/m² –

0.00 W/m²/100 lx –

(1) Based on a rectangular space of 12.000 m x 9.950 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1"
are clean.

22
Project

Building 1 · Storey 1 · Room 1 (Light scene 5 (Room 1))


Summary

Ground area 119.40 m² Clearance height 3.000 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.400 m


Walls: 39.1 %,
Floor: 62.3 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

23
Project

Building 1 · Storey 1 · Room 1 (Light scene 5 (Room 1))


Summary

Results

Symbol Calculated Target Check Index

Daylight D 1.370 % – DF1

Working plane Ēperpendicular 1315 lx ≥ 300 lx WP1

Uo (g1 ) 0.15 ≥ 0.40 WP1

Glare valuation(1) RUG, max 24 ≤ 19

Energy estimation(2) Consumption [13.35 - 21.87] kWh/a max. 4200 kWh/a

Room Lighting power density 1.73 W/m² –

0.13 W/m²/100 lx –

(1) Based on a rectangular space of 12.000 m x 9.950 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1"
are clean.

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

7 Philips SP341P LED21S/940 O POE L1200 24 18.0 W 2100 lm 116.6 lm/W

2 Philips SP341P LED21S/940 O POE L1200 24 40.0 W 2100 lm 52.5 lm/W

24
Project

Building 1 · Storey 1 · Room 1 (Light scene for daylight factor)


Summary

Ground area 119.40 m²

Reflection factors Ceiling: 70.0 %, Clearance height 3.000 m


Walls: 39.1 %,
Floor: 62.3 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

25
Project

Building 1 · Storey 1 · Room 1 (Light scene for daylight factor)


Summary

Results

Symbol Calculated Target Check Index

Daylight D 1.370 % – DF1

Working plane Ēperpendicular 330 lx ≥ 300 lx WP1

Uo (g1 ) 0.32 ≥ 0.40 WP1

Energy estimation(2) Consumption 0.00 kWh/a max. 4200 kWh/a

Room Lighting power density 0.00 W/m² –

0.00 W/m²/100 lx –

(1) Based on a rectangular space of 12.000 m x 9.950 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Overcast Sky on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1" are clean.

26
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

27
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

Manufacturer Philips P 18.0 W

Article name SP341P LED21S/940 ΦLuminaire 2100 lm


O POE L1200

Fitting 1x

Individual luminaires

X Y Mounting Luminaire
height

9.100 m 7.827 m 2.400 m 1

6.100 m 7.825 m 2.400 m 2

3.000 m 7.796 m 2.400 m 3

3.000 m 5.205 m 2.400 m 6

9.100 m 2.627 m 2.400 m 7

6.100 m 2.559 m 2.400 m 8

3.000 m 2.545 m 2.400 m 9

28
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

Manufacturer Philips P 40.0 W

Article name SP341P LED21S/940 ΦLuminaire 2100 lm


O POE L1200

Fitting 1x

Individual luminaires

X Y Mounting Luminaire
height

9.100 m 5.277 m 2.400 m 4

6.100 m 5.227 m 2.400 m 5

29
Project

Building 1 · Storey 1 · Room 1


Luminaire list

Φtotal Ptotal Luminous efficacy


18900 lm 206.0 W 91.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

7 Philips SP341P LED21S/940 O POE L1200 18.0 W 2100 lm 116.6 lm/W

2 Philips SP341P LED21S/940 O POE L1200 40.0 W 2100 lm 52.5 lm/W

30
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

31
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 1160 lx 173 lx 63444 lx 0.15 0.003 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1"
are clean.

32
Project

Building 1 · Storey 1 · Room 1 (Light scene 5 (Room 1))


Calculation objects

33
Project

Building 1 · Storey 1 · Room 1 (Light scene 5 (Room 1))


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 1315 lx 203 lx 63488 lx 0.15 0.003 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1"
are clean.

34
Project

Building 1 · Storey 1 · Room 1 (Light scene for daylight factor)


Calculation objects

35
Project

Building 1 · Storey 1 · Room 1 (Light scene for daylight factor)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 330 lx 107 lx 2569 lx 0.32 0.042 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Daylight

Properties Dm Dmin Dmax Uo (g1 ) g2 Index

Daylight factor effective area (Room 1) 1.370 % 0.542 % 4.312 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Overcast Sky on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1" are clean.

36
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Working plane (Room 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 1160 lx 173 lx 63444 lx 0.15 0.003 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1"
are clean.

37
Project

Building 1 · Storey 1 · Room 1 (Light scene 5 (Room 1))


Working plane (Room 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 1315 lx 203 lx 63488 lx 0.15 0.003 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Clear sky (Direct sunlight) on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1"
are clean.

38
Project

Building 1 · Storey 1 · Room 1 (Light scene for daylight factor)


Working plane (Room 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 330 lx 107 lx 2569 lx 0.32 0.042 WP1


Perpendicular illuminance (adaptive) (≥ 300 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Overcast Sky on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1" are clean.

39
Project

Building 1 · Storey 1 · Room 1 (Light scene for daylight factor)


Daylight factor effective area (Room 1)

Properties Dm Dmin Dmax Uo (g1 ) g2 Index

Daylight factor effective area (Room 1) 1.370 % 0.542 % 4.312 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Utilisation profile: Offices (5.26.1 Filing, copying, etc.)

Notes on planning:
Daylight proportion for Overcast Sky on 28-02-2024 at 12:00 ((UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi). The ambient conditions for "Room 1" are clean.

40
Project

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464-1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated colour temperature)


Body temperature of a thermal radiator which serves to describe its light colour. Unit:
Kelvin [K]. The lesser the numerical value the redder; the greater the numerical value the
bluer the light colour. The colour temperature of gas-discharge lamps and semi-
conductors are termed "correlated colour temperature" in contrast to the colour
temperature of thermal radiators.

Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:

Light colour - colour temperature [K]


warm white (ww) < 3, 300 K
neutral white (nw) ≥ 3, 300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

Control group A group of luminaires that are dimmed and controlled together. For each lighting scene,
a control group provides its own dimming value. All luminaires within a control group
share this dimming value. The control groups with their luminaires are automatically
determined by DIALux on the basis of the created light scenes and their luminaire
groups.

CRI (Engl. colour rendering index)


Designation for the colour rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13. 3: 1995.

The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.

41
Project

Glossary

Daylight autonomy Describes what percentage of the daily working time the required illuminance is met by
daylight. The nominal illuminance is used from the room profile, unlike described in EN
17037. The calculation is not done in the centre of the room but at the placed sensor
measuring point. A room is considered sufficiently supplied with daylight if it achieves at
least 50% daylight autonomy.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Energy evaluation Based on an hourly calculation procedure for daylight in indoor spaces, considering the
project geometry and any existing daylight control systems. Orientation and location of
the project are also considered. The calculation uses the specified system power of the
luminaires to determine the energy demand. A linear relationship between power and
luminous flux in the dimmed state is assumed for daylight-controlled luminaires. Times
of use and nominal illuminance are determined from the usage profiles of the spaces.
Switched-on luminaires that are explicitly excluded from control also consider the
specified times-of-use. The daylight control systems use a simplified control logic that
closes them at an outdoor horizontal illuminance of 27,500lx.

The calendar year 2022 is used as a reference only. It is not a simulation of this year. The
reference year is only used to assign the days of the week to the calculated results. The
changeover to summer time is not considered. The reference sky type used is the
average sky described in CIE 110 without direct sunlight.

The method was developed together with the Fraunhofer Institute for Building Physics
and is available for review by the Joint Working Group 1 ISO TC 274 as an extension of
the previous annual regression-based method.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

42
Project

Glossary

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/(m² * a)

43
Project

Glossary

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square metre


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

44
Project

Glossary

Maintenance factor See MF

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

R(UG) max Measure of the psychological glare in indoor spaces.


In addition to the luminance of luminaires, the level of the R(UG) value also depends on
the observer position, the viewing direction and the ambient luminance. The calculation
is made according to the table method, see CIE 117. Among other things, EN 12464-
1: 2021 specifies maximum permissible R(UG) - values R( UGL) for various indoor workplaces.

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

45
Project

Glossary

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls which is not taken into account
for the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.

46