0% found this document useful (0 votes)
269 views196 pages

LOD Spec

Uploaded by

jafar elshahir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
269 views196 pages

LOD Spec

Uploaded by

jafar elshahir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 196

10th Anniversary Edi on

2005 2019 2022

LEVEL OF DEVELOPMENT (LOD)


SPECIFICATION PART I

COLLABORATING ORGANIZATIONS

AIA American Ins tute of American Society of


Contract Documents Steel Construc on Landscape Architects

Associated General Design‐Build Ins tute Na onal Ins tute of US Ins tute of
Contractors of America of America Building Sciences Building Documenta on

Copyright © 2023 BIMForum


Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

2023
Level of Development (LOD)
Specification
Nothing contained in this work shall be considered the rendering of legal advice. Readers are responsible for obtaining such advice
from their own legal counsel. This work and any forms herein are intended solely for educational and informational purposes.

All images are intended to illustrate building conditions in compliance with common building codes. However, the images do not take
into account site specific conditions, regional building codes and other important information that may require a material change for
specific projects. These illustrations do not make representation for fitness for a particular project nor for code or design compliance.

Copyright © 2023 by BIMForum. All rights reserved.

The LOD Specification Part I and Part II as well as the LOD Specification Guide are made available to the public without charge. In
order to maintain the integrity and usefulness of these documents as a reference standard, certain restrictions apply to their use. These
documents are licensed to the public under Creative Commons licenses as follows:

Part I of this work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License
(http://creativecommons.org/licenses/by-nc-nd/4.0/).

Part II of this work is licensed under the Creative Commons Attribution-NonCommercial 4.0 International License
(http://creativecommons.org/licenses/by-nc/4.0/).

Licensing questions should be directed to [email protected].

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 1
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Underwriters
This important document was made possible by the generous support of these organizations:

American Institute of Steel Construction

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 2
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

EXECUTIVE SUMMARY
For a detailed guide on the use of this Specification see User Guide below.
The Level of Development (LOD) Specification is a reference tool intended to improve the quality of communication among users of
Building Information Models (BIMs) about the characteristics of elements in models. The LOD Specification expands upon the LOD
schema developed by AIA Contract Documents for its E201 2022 BIM Exhibit for Sharing Models with Project Participants1 by
providing definitions and illustrations of BIM elements of different building systems at different stages of their development and use in
the design and construction process.
Building Information Modeling presents information about a construction project or structure in the form of three-dimensional graphical
representations of elements (e.g., doors, beams, etc.), which can be further associated with information about other characteristics of
those elements. It is possible for the graphical representation of an element, taken alone, to suggest that greater accuracy or intention
can be attributed to the element than is in fact the case. The AIA’s LOD Schema was developed to provide a more systematic way of
conveying the extent of reliance that may be placed on an element. Many participants in the design and construction process felt,
however, that the industry would benefit from a more detailed treatment of the AIA’s brief narrative definitions.
Discussions within the BIMForum led to the creation of a multi-disciplinary task force to develop and maintain the LOD Specification.
The LOD Specification is an organized collection of interpretations of the AIA’s LOD definitions describing input and information
requirements and providing graphical examples of the different levels of development of a broad variety of building element classes.
Users of the LOD Specification are cautioned that it does not prescribe the necessary levels of development for different steps in the
construction process. That determination is left to each project team. It is believed, however, that the availability of more precise
definitions will reduce the risks of miscommunication among members of project teams when the expectations for different stages in the
design and construction process are established, through easier identification of what each member of the team is expected to deliver
and greater predictability of the level of effort that is required to create each member’s deliverables.
The LOD Specification is organized by CSI Uniformat 2010 and Omniclass2, with the subclasses expanded to Level 4 (and in a few
cases to Level 5) to provide detail and clarity to the element definitions. Breakdown indices are also provided per Uniclass 20153, a UK
initiative that is gaining international acceptance. See BIMForum LOD Spec Part II, tab 3, for a Uniclass-to-Omniclass/Uniformat cross-
reference table.
The LOD Specification does not prescribe who the author of a particular component at a given LOD should be, as that will vary from
one project or firm to another. However, the document does provide a concise schematic means through the spreadsheet in Part II for
a project team to identify model element authors, again in the interest of improving communication among model users. In addition, the
LOD Specification Working Group has been working with software developers to provide a means within the software of tagging
individual elements within a model with their current LOD level.
The LOD Specification is intended as a reference standard, but is also intended to evolve as the use of BIM develops. The
Specification is updated annually, and previous versions are maintained on the BIMForum website (www.bimforum.org/lod). Users are
invited to provide comments and recommendations for consideration in future editions. These should be sent by email to
[email protected].

1 AIA Contract Document E201 2022 BIM Exhibit for Sharing Models with Project Participants where Model Versions may be
enumerated as a Contract Document is part of a series of digital practice documents AIA Contract Documents published in
July 2022. Additional documents in the series include E201 2022 BIM Exhibit for Sharing Models with Project Participants
(does not support use as a contract), E401-2022 BIM Exhibit for Sharing Models Solely Within the Design Team, E402-2022
BIM Exhibit for Sharing Models Solely Within the Construction Team, G203-2022 BIM Execution Plan, G204-2022 Model
Element Table, and G205-2022 Abbreviated Model Element Table. For general information on the documents and executable
versions visit https://www.aiacontracts.com.
2UniFormatTM and Omniclass Numbers and Titles used in this publication are from UniFormatTM, published by CSI and
Construction Specifications Canada (CSC), and are used with permission from CSI. For a more in-depth explanation of
UniFormatTM and its use in the construction industry visit http://www.csinet.org or contact CSI, 110 South Union Street, Suite
100, Alexandria, VA 22314. (800) 689-2900.
3 Uniclass 2015 © NBS Enterprises Ltd
Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 3
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

PREFACE TO THE 2023 EDITION


In order to incorporate lessons learned from 10 years of extensive use on real-world projects, the BIMForum LOD Working Group
undertook a major review and update of this Specification. The major thrust of the update is to resolve conflicts and improve
consistency and readability in the logic and format of the text and graphics. Very few changes were made in the actual requirements in
the Specification’s LOD narrative descriptions. The following are the major global adjustments:
• Elimination of nebulous terms. E.g., use of the term “major openings” has been replaced by a defined size. This size can
be modified through the use of the Notes function in Part II.
• Simplification. An example of this is the Interior Finishes section. In looking at the section as a whole it was realized that the
modeling needs were dictated by the thickness of the finish rather than the material. Thus requirements based on thickness
are defined for “C20 Interior Finishes”, and these requirements apply to all children of that heading.
• Defined Terms. This section has been added to succinctly define terms that have specialized meaning in this Spec. The
defined terms are in boldface where they appear in the LOD narrative descriptions.
• LOD Requirements. In the narrative descriptions of LOD requirements only items required to be included are listed. No
reference is made to items that are not required and no items have been listed as prohibited.
• Narrative Descriptions. These have been organized into lists of specific required items to facilitate use of the Spec as a
checklist.
• Non-geometric information. On the principle that any number of non-geometric attributes can be attached to a model
element of any LOD, non-geometric information is not addressed in Part I.
• Duplicated Content. The Spec was scrubbed for duplicated content – where found it was deleted or replaced with cross-
references

Evolution of the Level of Development (LOD) Definitions


AIA Effort
In 2008, the AIA published the first set of Level of Development definitions for AIA Document E202™-2008 Building Information
Modeling Protocol. Due to the rapidly evolving nature of the use of BIM, the AIA updated the LOD definitions for its G202-2013 Project
BIM Protocol Form and again, in collaboration with other industry organizations, for its E201-2022 BIM Exhibit for Sharing Models with
Project Participants,

BIMForum Effort
In 2011 BIMForum initiated the development of the LOD Specification and formed a working group comprising contributors from both
the design and construction sides of the major disciplines. To help further the standardization and consistent use of the LOD schema,
and to increase its usefulness as a foundation for collaboration, the AIA licensed BIMForum to utilize its latest LOD definitions in this
Specification. The BIMForum working group interpreted the AIA’s basic LOD definitions for each building system, and then compiled
examples to illustrate the interpretations. Because BIM is being put to an ever-increasing number of uses, the group decided that it was
beyond the initial scope to address all of them. Instead, the definitions were developed to address model element geometry, with three
of the most common uses in mind – quantity take-off, 3D coordination, and 3D control and planning. The group felt that in taking this
approach the interpretations would be complete enough to support other uses.
In working with the AIA definitions the working group identified the need for an LOD that would define model elements sufficiently
developed to enable detailed coordination between disciplines – e.g. clash avoidance/detection, layout, etc. The requirements for this
level are higher than those for 300, but not as high as those for 400, thus it was designated LOD 350. The 2022 AIA Digital Practice
documents include LOD 350.
The working group also decided that since the AIA’s definition of LOD 500 related only to field verification and thus had no impact on
modeling of elements the Specification would not develop interpretations for LOD 500.
In developing the system- and component-specific interpretations of the LODs the working group found it useful to define some
fundamental interpretations, adding some color and shade to the AIA’s definitions in order to guide the development of the specific
interpretations.
The LOD definitions included in the LOD Specification versions 2013 through 2021 are the definitions from the AIA 2013 suite of Digital
Practice documents plus the BIMForum’s definition of LOD 350 and minus the definition of LOD 500, along with the BIMForum’s
fundamental interpretations.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 4
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

2022 LOD Definition Update


In December of 2021 a collaborative effort was convened to incorporate lessons learned from almost a decade of practical application
of the LOD framework into an updated set of LOD definitions. The following organizations were represented:
• AIA Contract Documents (ACD)
• American Association of State Highway Officials (AASHTO)
• American Institute of Architects (AIA)
• Canada’s Integrated Project Delivery Alliance (IPDA)
• National BIM Standard (NBIMS)
• National Institute of Building Sciences (NIBS)

Basically, the group ratified the BIMForum interpretations and folded them into the new definitions, also simplifying and clarifying the
language. As a result of this outcome the existing narrative and graphic interpretations of specific systems and components included in
the 2013-2021 versions of the LOD Spec remain valid.
Some notable tweaks:
1. The sentence “Non-graphic information may also be attached to the Model Element” has been removed from all definitions.
Since non-graphic information in any quantity and degree of accuracy can be attached to a model element of any LOD, the
issue is addressed with a single over-arching statement in AIA E201-2022. This approach will be followed in future versions of
the LOD Spec.
2. While the BIMForum 2013 interpretations assigned space-reservation volumes to LOD 200, the 2022 LOD 200 definition
requires the element to show recognizable geometry. Thus space-reservation volumes are assigned to LOD 100.
3. The group developed a more succinct definition of LOD 500, making it clear that this LOD applies to existing elements rather
than the “as-designed” elements addressed by LODs 100-400. The definition also requires that the accuracy of an LOD 500
element must be specified by some means other than LOD 100-400. The BIMForum will be collaborating with other industry
organizations to develop a schema to specify this accuracy.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 5
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

ACKNOWLEDGEMENTS
Many thanks to all the individuals and organizations who reviewed and contributed to this work, and to the following industry association
representatives and co-chairs of the major discipline subgroups who made this document possible:

LOD SPEC WORKING GROUP


The widespread industry adoption of the BIMForum LOD Spec is primarily due to the broad range of built-environment industry
knowledge, perspectives, and expertise that generates and maintains it. The component-specific interpretations of the fundamental
LOD definitions contained in the Spec are not developed solely by experts in that system, but through a collaborative, consensus-based
approach bringing to bear design, construction, and operations expertise from all disciplines.

Chair and Editor: Jim Bedrick, FAIA, AEC Process Engineering


Vice Chair: Jan Reinhardt, Adept Project Delivery

Domain Group Co-Chairs


Design Construction
Structures Jan Reinhardt
Adept Project Delivery

Exterior Skin Michael F. Czap, AIA


The Beck Group

Interior Construction Brian Skripac, DBIA Brian Filkins


The Beck Group
DBIA
South Cole
Texas Steel Tech LLC
Conveying Michael F. Czap, AIA Ken Flannigan, LEED AP
The Beck Group Tech Frontiers LLC

Building Services David Francis


Dome Construction

Civil/Landscape Lauren Schmidt Jake Fears, PE


Parallax Team JHF Engineering
Radu Dicher
SWA Group
Estimating with BIM Brent pilgrim Ryan Short
Beck Group Rudick Construction
Nicholas Grinnan
Rudick Construction
Legal Carl G. Roberts,
Law Offices of Carl G. Roberts LLC

Graphics
Annotated graphics were provided by the following organizations. Graphics not annotated were provided by BIMForum
1 Kone US
2 American Society of Landscape Architects (ASLA)

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 6
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

INDUSTRY AND ASSOCIATION REPRESENTATIVES


AIA Contract Documents Jim Bedrick, FAIA
American Institute of Steel Construction Luke Falkner
Associated General Contractors Benjamin Crosby
Design-Build Institute of America Brian Skripac, DBIA, Assoc. AIA
Integrated Project Delivery Alliance (Canada) Markku Allison
NBS (UK) Tina Pringle

Current and Previous Contributors


In addition, we’d like to thank the many contributors from all sectors of the industry who helped make this specification possible,
including:
Andy Jizba, US CAD
Benjamin Crosby, Yates Construction
Bill Klorman, Klorman Construction & ACI 131 BIM Committee Member (Concrete)
Brenda Ikerd, Ikerd Consulting, (Structures, Civil)
Chuck Eastman, Ph.D, Georgia Institute of Technology
David Merrifield, National Institute of Steel Detailers
Jamie L. Davis, PE. LEED AP, Ryan Biggs | Clark Davis Engineering & Surveying (Masonry)
Jason P. Lien, PE, Precast Concrete Institute (PCI) BIM Committee, EnCon United (Precast)
Jonathan Koller, Ikerd Consulting, (Graphics Editing, Structures, and Anchors)
Joe Cipra, Vulcraft/Verco Group (Structural Steel Open Web Joists and Metal Deck)
Joe Powell, EIT, Ikerd Consulting, (MEP)
Kirk Capristo, Astorino (Cover)
Lee Garduno, Southland Industries (MEP)
Luke Faulkner, LEED AP, AISC (Structural Steel)
Matthew J. Gomez PE, SE, Trimble (Structural Steel)
Michael Bolduc, PE (MA), Simpson Gumpertz & Heger (Structural)
Michael Gustafason, PE, Autodesk (Structural)
Michael Mulder, Southland Industries (MEP)
Michael Perdue, Ikerd Consulting, (LOD Part II Data Tables)
Murat Karakas, Arup (MEP)
Paul J. Hause, PE, Structural Consultants Inc. (Structural)
Peter J. Carrato, Ph.D., PE, SE, Bechtel & ACI 131 BIM Committee Chair (Concrete)
R. Wayne Muir, P.E., Structural Consultants Inc. & SEI-CASE BIM Committee Co-Chair (Structures)
Roger Becker, PE, SE, Precast Concrete Institute (PCI) Managing Director of Research and Development (Precast)
Ron Dellaria, AIA, CSI, Collaborative Construction Consultants

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 7
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Scott Babin, ITW Building Components Group (Wood)


Soheil Seiqali, Klorman Construction (Concrete)
Steven Bumbalough (Wood)
Will Ikerd PE, PhD, Ikerd Consulting
William Northcutt, Ikerd Consulting, (Graphics Editing, Structures, and Anchors)

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 8
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Contents
TABLE OF CONTENTS STRUCTURE:
UNIFORMAT # / OMNICLASS # / UNICLASS # SECTION TITLE

EXECUTIVE SUMMARY ...................................................................................................................... 3

DEFINITIONS AND NOTES ............................................................................................................... 14


Level of Development vs. Level of Detail ......................................................................................................................... 14

Fundamental LOD Definitions............................................................................................................................................ 14

Defined Terms ..................................................................................................................................................................... 15

General Notes ...................................................................................................................................................................... 16

REVISION HISTORY .......................................................................................................................... 17


Specific Changes to 2023 Edition ..................................................................................................................................... 17
Part I................................................................................................................................................................................... 17

PART I – ELEMENT GEOMETRY ...................................................................................................... 19

A / 21-01 / SS 20 05 SUBSTRUCTURE ........................................................................................... 19


A10 / 21-01 10 / Ss 20 05 15 Foundations ....................................................................................................................... 19
A1010 / 21-01 10 10 / Ss 20 05 Standard Foundations .................................................................................................. 19
A1010.10 / 21-01 10 10 10 / Ss 20 05 15 Wall Foundations ........................................................................................... 19
A1020 / 21-01 10 20 / Ss 20 05 Special Foundations ..................................................................................................... 22

A20 / 21-01 20 / Ss 20 05 15 Subgrade Enclosures ........................................................................................................ 25


A2010 / 21-01 20 10 / Ss 20 60 Walls for Subgrade Enclosures .................................................................................... 25

A40 / 21-01 40 / Pr 20 85 14 16 Slabs-on-Grade.............................................................................................................. 25


A4010 / 21-01 40 10 / Pr 20 85 14 16 Standard Slabs-on-Grade ................................................................................... 26
A4020 / 21-01 40 20 / Pr 20 85 14 16 Structural Slabs-on-Grade .................................................................................... 26
A4030 / 21-01 40 30 / -- Slab Trenches TBD .................................................................................................................. 27
A4040 / 21-01 40 40 / Ss 37 16 90 63 Pits and Bases TBD............................................................................................ 27
A4090 / 21-01 40 90 / -- Slab-On-Grade Supplementary Components .......................................................................... 27

A60 / 21-01 60 / -- Water and Gas Mitigation TBD .......................................................................................................... 27


A6010 / 21-01 60 10 / Ss 50 35 8 85 Building Subdrainage TBD ................................................................................... 27
A6020 / 21-01 60 20 / Ss 15 10 33 34 Off-Gassing Mitigation TBD ................................................................................ 27

A90 / 21-01 90 / -- Substructure Related Activities TBD ................................................................................................ 27


A9010 / 21-01 90 10 / Ss 15 10 30 25 Substructure Excavation TBD ............................................................................ 27
A9020 / 21-01 90 20 / Ss 15 10 76 21 Construction Dewatering TBD ............................................................................ 27
A9030 / 21-01 90 30 / TE 20 50 65 Excavation Support TBD ......................................................................................... 27
A9040 / 21-01 90 40 / Ss 15 10 35 Soil Treatment TBD ................................................................................................. 27

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 9
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

B / 21-02 / -- SHELL .......................................................................................................................... 28


B10 / 21-02 10 / -- Superstructure .................................................................................................................................... 28
B1010 / 21-02 10 10 / Ss 30 12 Floor Construction ........................................................................................................ 28
B1020 / 21-02 10 20 / Ss 30 10 Roof Construction ......................................................................................................... 43
B1080 / 21-02 10 80 / Ss 35 Stairs .................................................................................................................................. 45

B20 / 21-02 20 / EF 25 10 Exterior Vertical Enclosures ................................................................................................. 52


B2010 / 21-02 20 10 / EF 25 10 Exterior Walls ............................................................................................................... 52
B2020 / 21-02 20 20 / Ss 25 30 95 26 Exterior Windows ................................................................................................ 62
B2050 / 21-02 20 50 / Ss 25 30 20 Exterior Doors and Grilles........................................................................................ 64
B2070 / 21-02 20 70 / Ss 25 50 45 45 Exterior Louvers and Vents ................................................................................ 66
B2080 / 21-02 20 80 / -- Exterior Wall Appurtenances .................................................................................................... 67
B2090 / 21-02 20 90 / Ss 25 60 Exterior Wall Specialties ............................................................................................... 68

B30 / 21-02 30 / -- Exterior Horizontal Enclosures ......................................................................................................... 68


B3010 / 21-02 30 10 / Ss 30 10 Roofing.......................................................................................................................... 69
B3020 / 21-02 30 20 / -- Roof Appurtenances ................................................................................................................. 70
B3040 / 21-02 30 40 / Ss 30 12 20 Traffic Bearing Horizontal Enclosures ..................................................................... 71
B3060 / 21-02 30 60 / -- Horizontal Openings ................................................................................................................. 72
B3080 / 21-02 30 80 / -- Overhead Exterior Enclosures.................................................................................................. 73

C / 21-03 / -- INTERIORS ................................................................................................................. 74


C10 / 21-03 10 / -- Interior Construction .......................................................................................................................... 74
C1010 / 21-03 10 10 / Ss 25 10 30 Interior Partitions ..................................................................................................... 74
C1020 / 21-03 10 20 / Ss 25 30 95 41 Interior Windows ................................................................................................. 80
C1030 / 21-03 10 30 / Ss 25 30 20 25 Interior Doors ...................................................................................................... 81
C1040 / 21-03 10 40 / -- Interior Grilles and Gates ......................................................................................................... 84
C1060 / 21-03 10 60 / Ss 30 20 70 Raised Floor Construction ....................................................................................... 84
C1090 / 21-03 10 90 / -- Interior Specialties .................................................................................................................... 86

C20 / 21-03 20 / Ss 25 45 Interior Finishes ...................................................................................................................... 88


C2010 / 21-03 20 10 / Ss 25 45 Wall Finishes ................................................................................................................ 89
C2020 / 21-03 20 20 / Ss 25 25 45 Interior Fabrications ................................................................................................. 91
C2030 / 21-03 20 30 / Ss 30 42 Flooring ......................................................................................................................... 91
C2050 / 21-03 20 50 / Ss 30 47 Ceiling Finishes ............................................................................................................ 94

D / 21-04 00 00 / -- SERVICES ......................................................................................................... 96


D10 / 21-04 10 / Ss 80 20 Conveying ............................................................................................................................... 96
D1010 / 21-04 10 10 / Ss 80 50 Vertical Conveying Systems ......................................................................................... 96
D1010.20 / 21-04 10 10 20 / Ss 80 50 60 Lifts ................................................................................................................ 99
D1030 / 21-04 10 30 / Ss 80 20 62 Horizontal Conveying ............................................................................................ 100
D1050 / 21-04 10 50 / Ss 80 20 10 Material Handling................................................................................................... 101
D1080 / 21-04 10 80 / Ss 80 30 25 Operable Access Systems .................................................................................... 104

D20 / 21-04 20 / -- Plumbing............................................................................................................................................ 105


D2010 / 21-04 20 10 / Ss 55 70 38 Domestic Water Distribution .................................................................................. 105
D2020 / 21-04 20 20 / Ss 50 30 4 Sanitary Drainage .................................................................................................... 110
D2030 / 21-04 20 30 / -- Building Support Plumbing Systems ...................................................................................... 113
D2050 / 21-04 20 50 / Ss 55 20 15 General Service Compressed-Air.......................................................................... 117
D2060 / 21-04 20 60 / Ss 55 60 Process Support Plumbing Systems .......................................................................... 117

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 10
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

D30 / 21-04 30 / Ss 60 Heating, Ventilation, and Air Conditioning (HVAC) ................................................................ 119
D3010 / 21-04 30 10 / Ss 55 50 Facility Fuel Systems.................................................................................................. 120
D3020 / 21-04 30 20 / Ss 60 40 37 Heating Systems ................................................................................................... 123
D3030 / 21-04 30 30 / Ss 60 40 17 Cooling Systems.................................................................................................... 125
D3050 / 21-04 30 50 / Ss 60 40 84 Facility HVAC Distribution Systems ...................................................................... 127
D3060 / 21-04 30 60 / Ss 65 40 0 0 Ventilation ............................................................................................................... 130
D3070 / 21-04 30 70 / Ss 60 Special Purpose HVAC Systems .................................................................................... 133

D40 / 21-04 40 / Ss 55 30 Fire Protection ...................................................................................................................... 134


D4010 / 21-04 40 10 / Ss 55 30 Fire Suppression ........................................................................................................ 134
D4030 / 21-04 40 30 / Ss 55 30 Fire Protection Specialties .......................................................................................... 136

D50 / 21-04 50 / -- Electrical ............................................................................................................................................ 137


D5010 / 21-04 50 10 / -- Facility Power Generation ...................................................................................................... 137
D5020 / 21-04 50 20 / Ss 70 30 Electrical Service and Distribution .............................................................................. 140
D5030 / 21-04 50 30 / Ss 70 30 45 45 General Purpose Electrical Power ................................................................... 147
D5040 / 21-04 50 40 / Ss 70 80 Lighting ....................................................................................................................... 149
D5080 / 21-04 50 80 / Ss 70 Miscellaneous Electrical Systems ................................................................................... 151

D60 / 21-04 60 / Ss 75 10 Communications................................................................................................................... 152


D6010 / 21-04 60 10 / Ss 75 10 21 21 Data Communications ...................................................................................... 153
D6020 / 21-04 60 20 / Ss 75 10 21 88 Voice Communications ..................................................................................... 154
D6030 / 21-04 60 30 / -- Audio-Video Communication .................................................................................................. 155
D6060 / 21-04 60 60 / Ss 75 70 54 15 Distributed Communications and Monitoring ................................................... 155
D6090 / 21-04 60 90 / Ss 75 10 Communications Supplementary Components .......................................................... 155

D70 / 21-04 70 / Ss 75 40 Electronic Safety and Security ........................................................................................... 155


D7010 / 21-04 70 10 / Ss 75 40 Access Control and Intrusion Detection ..................................................................... 155
D7030 / 21-04 70 30 / Ss 75 40 53 Electronic Surveillance .......................................................................................... 155
D7050 / 21-04 70 50 / Ss 75 50 Detection and Alarm ................................................................................................... 156
D7070 / 21-04 70 70 / Ss 75 70 54 15 Electronic Monitoring and Control .................................................................... 156
D7090 / 21-04 70 90 / Ss 75 50 Electronic Safety and Security Supplementary Components..................................... 156

D80 / 21-04 80 / Ss 75 70 Integrated Automation ......................................................................................................... 156


D8010 / 21-04 80 10 / Ss 75 70 Integrated Automation Facility Controls ..................................................................... 156

E / 21-05 00 00 / -- EQUIPMENT & FURNISHINGS ....................................................................... 157


E10 / 21-05 10 00 / -- Equipment .................................................................................................................................... 157
E1010 / 21-05 10 10 / -- Vehicle and Pedestrian Equipment ........................................................................................ 157
E1030 / 21-05 10 30 / Ss 40 20 15 Commercial Equipment ......................................................................................... 158
E1060 / 21-05 10 60 / Ss 40 45 70 Residential Equipment ........................................................................................... 162
E1070 / 21-05 10 70 / Ss 40 70 Entertainment and Recreational Equipment ............................................................... 163
E1090 / 21-05 10 90 / Ss 40 15 35 35 Other Equipment............................................................................................... 163

E20 / 21-05 20 / Ss 40 45 Furnishings ........................................................................................................................... 164


E2010 / 21-05 20 10 / Ss 40 45 Fixed Furnishings ....................................................................................................... 164
E2050 / 21-05 20 50 / Pr 40 50 Movable Furnishings ................................................................................................... 166

F / 21-06 00 00 / -- SPECIAL CONSTRUCTION & ...................................................... DEMOLITION


.......................................................................................................................................................... 168
F10 / 21-06 10 / -- Special Construction ........................................................................................................................ 168

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 11
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

F1010 / 21-06 10 10 / Ss 20 10 60 Integrated Construction.......................................................................................... 168


F1020 / 21-06 10 20 / -- Special Structures ................................................................................................................... 168
F1030 / 21-06 10 30 / -- Special Function Construction ................................................................................................ 168
F1050 / 21-06 10 50 / -- Special Facility Components .................................................................................................. 169
F1060 / 21-06 10 60 / Ss 40 70 75 Athletic and Recreational Special Construction ..................................................... 169
F1080 / 21-06 10 80 / -- Special Instrumentation ......................................................................................................... 169

F20 / 21-06 20 00 / Ss 15 30 Facility Remediation ........................................................................................................ 169


F2010 / 21-06 20 10 / Ss 15 30 Hazardous Materials Remediation ............................................................................. 169

F30 / 21-06 30 00 / Ac 10 10 25 Demolition ................................................................................................................... 169


F3010 / 21-06 30 10 / Ac 10 10 25 Structure Demolition ............................................................................................. 170
F3030 / 21-06 30 30 / Ac 10 10 25 Selective Demolition ............................................................................................. 170
F3050 / 21-06 30 50 / Ac 10 80 Structure Moving ........................................................................................................ 170

G / 21-07 00 00 / -- SITEWORK ..................................................................................................... 171


G10 / 21-07 10 00 / Ac 10 Site Preparation .................................................................................................................... 171
G1010 / 21-07 10 10 / Ac 10 30 Site Clearing ............................................................................................................... 171
G1020 / 21-07 10 20 / Ac 10 10 25 Site Elements Demolition ...................................................................................... 171
G1030 / 21-07 10 30 / -- Site Element Relocations ...................................................................................................... 171
G1050 / 21-07 10 50 / Ac 10 75 65 Site Remediation ................................................................................................... 171
G1070 / 21-07 10 70 / -- Site Earthwork ........................................................................................................................ 171

G20 / 21-07 20 / -- Site Improvements ........................................................................................................................... 172


G2010 / 21-07 20 10 / Ss 30 14 05 Roadways .............................................................................................................. 172
G2020 / 21-07 20 20 / Ss 40 85 72 11 Parking Lots ..................................................................................................... 174
G2030 / 21-07 20 30 / Ss 30 14 Pedestrian Plazas and Walkways .............................................................................. 175
G2050 / 21-07 20 50 / Ss 30 14 Athletic, Recreational, and Playfield Areas ............................................................... 177
G2060 / 21-07 20 60 / -- Site Development ................................................................................................................... 177
G2080 / 21-07 20 80 / -- Landscaping ........................................................................................................................... 178

G30 / 21-07 30 / Ss 55 20 Liquid and Gas Site Utilities ................................................................................................ 183


G3010 / 21-07 30 10 / Ss 55 70 Water Utilities ............................................................................................................. 183
G3020 / 21-07 30 20 / -- Sanitary Sewerage Utilities .................................................................................................... 184
G3030 / 21-07 30 30 / Ss 50 35 80 Storm Drainage Utilities......................................................................................... 185
G3050 / 21-07 30 50 / Ss 70 30 Site Energy Distribution .............................................................................................. 185
G3060 / 21-07 30 60 / -- Site Fuel Distribution .............................................................................................................. 185
G3090 / 21-07 30 90 / -- Liquid and Gas Site Utilities Supplementary Components ................................................... 185

G40 / 21-07 40 / -- Electrical Site Improvements .......................................................................................................... 185


G4010 / 21-07 40 10 / -- Site Electric Distribution Systems .......................................................................................... 186
G4050 / 21-07 40 50 / Ss 70 80 25 Site Lighting ........................................................................................................... 186

G50 / 21-07 50 / Ss 75 10 Site Communications ........................................................................................................... 187


G5010 / 21-07 50 10 / Ss 75 10 Site Communications Systems .................................................................................. 187

G90 / 21-07 90 / -- Miscellaneous Site Construction .................................................................................................... 187


G9010 / 21-07 90 10 / Ss 37 50 92 Tunnels .................................................................................................................. 187

USER GUIDE.................................................................................................................................... 188

0 OVERVIEW.................................................................................................................................... 188
Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 12
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

0.1 Description ............................................................................................................................................................... 188


BIM as a Communication Tool ......................................................................................................................................... 188
0.1.1 LODs and Design Phase .................................................................................................................................... 188
0.1.2 LODs and Model Definition ................................................................................................................................. 189

0.2 Intent ......................................................................................................................................................................... 189


0.2.1 Not a Set of Requirements ................................................................................................................................. 189
0.2.2 Complements a BIM Execution Plan (BEP) ....................................................................................................... 189

0.3 Background.............................................................................................................................................................. 189


0.3.1 AIA Effort ............................................................................................................................................................. 189
0.3.2 BIMForum Effort.................................................................................................................................................. 189

1 USING THE SPECIFICATION ....................................................................................................... 190


1.1 Details ....................................................................................................................................................................... 190
1.1.1 Order of Precedence........................................................................................................................................... 190
1.1.2 LOD Definitions as Minimum Requirements ....................................................................................................... 190
1.1.3 LOD Definitions are Cumulative ......................................................................................................................... 190
1.1.4 Model Element Author ........................................................................................................................................ 190
1.1.5 2D Supplementary Drawings .............................................................................................................................. 190

1.2 Project-Specific Information .................................................................................................................................. 190


1.2.1 Size Thresholds .................................................................................................................................................. 190

1.3 Using the Specification with a BEP ....................................................................................................................... 191


1.3.1 Reliance .............................................................................................................................................................. 191
1.3.2 Multiple uses ....................................................................................................................................................... 191
1.3.3 Efficient sequencing ............................................................................................................................................ 191
1.3.4 Avoidance of over-modeling ............................................................................................................................... 191

1.4 Implementation of the Specification ..................................................................................................................... 191


1.4.1 Rely on the Model Element Table....................................................................................................................... 191
1.4.2 Include LOD Designations as Attributes of Individual Model Elements.............................................................. 191

2 ORGANIZATION OF THE SPECIFICATION................................................................................. 192


2.1 Geometric and Attribute Information .................................................................................................................... 192
2.1.1 Part I: Element Geometry .................................................................................................................................. 192
2.1.2 Part II: Associated Attribute Information ........................................................................................................... 192
2.1.3 Model Element Table .......................................................................................................................................... 192
2.1.4 Building Systems ................................................................................................................................................ 192
2.1.5 Milestones/Deliverables ...................................................................................................................................... 192
2.1.6 Attribute Tables ................................................................................................................................................... 193
2.1.7 Attribute Table Anatomy ..................................................................................................................................... 193
2.1.8 MEPF Attribute Tables ........................................................................................................................................ 194
2.1.9 Using the Attribute Tables .................................................................................................................................. 195

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 13
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

DEFINITIONS AND NOTES

Level of Development vs. Level of Detail


LOD is sometimes interpreted as Level of Detail rather than Level of Development. This Specification uses the concept of Level of
Development. There are important differences.
Level of Detail is essentially how much detail is included in the model element. Level of Development is the degree to which the
element’s geometry has been thought through – the degree to which project team members may rely on the information when using the
model.
It is important to note that the international terminology regarding Level of Development and Level of Detail varies. Some countries
refer to the Level of Development concept defined within this specification as the Level of Detail and use different numbering systems.

Fundamental LOD Definitions4


LOD Requirements are Cumulative. For a given element requirements for each LOD (except LOD 500 – see below) include the
requirements for all lower LODs.

LOD 100
The Model Element may be graphically represented in the Model with a symbol or other generic representation, but does not satisfy the
requirements for LOD 200. Information related to the Model Element (e.g., cost per square foot, tonnage of HVAC, etc.) can be derived
from other Model Elements.
BIMForum Interpretation: LOD 100 elements are not necessarily geometric representations. Examples are information attached to
other model elements: symbols showing the existence of a component but not its shape, size, or precise location; or space reservation
volumes. In essence, if information about an element can be derived from the model but the element is not at LOD 200 it is said to be
at LOD 100. Any information derived from LOD 100 elements must be considered approximate.

LOD 200
The Model Element is generically and graphically represented within the Model with approximate quantity, size, shape, location, and
orientation.
BIMForum interpretation: LOD 200 elements are generic placeholders but are recognizable as the components they represent (e.g. a
pump, a light fixture, a beam, etc.). Any information derived from LOD 200 elements must be considered approximate.

LOD 300
The Model Element, as designed, is graphically represented within the Model such that its quantity, size, shape, location, and
orientation can be measured.
BIMForum Interpretation. LOD 300 elements are sufficiently developed to fully convey the design intent for the represented item. Note
that while neither the LOD definitions nor this Specification specify who models the element, designers rarely generate model elements
higher than 300. See interpretation of LOD 350 below.

4The LOD definitions included in this Specification represent the updated language that appears in AIA Contract Document E201-2022,
BIM Exhibit for Sharing Models with Project Participants, Where Model Versions May be Enumerated as a Contract Document. The
LOD definitions are used by permission. Copyright © 2022. ACD Operations, LLC. All rights reserved.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 14
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

LOD 350
The Model Element, as designed, is graphically represented within the Model such that its quantity, size, shape, location, orientation,
and interfaces with adjacent or dependent Model Elements can be measured.
BIMForum Interpretation. LOD 350 is intended to define requirements for model elements that are sufficiently developed to support
construction-level coordination. This LOD usually requires craft knowledge, thus the caveat in the LOD 300 interpretation above that
designers rarely generate elements at LODs higher than 300. It should be remembered, though, that neither the LOD definitions nor
this Specification specify who models the element – if a design team has craft knowledge available they might choose to develop
elements to LOD 350 or higher.

LOD 400
The Model Element is graphically represented within the Model with detail sufficient for fabrication, assembly, and installation.
BIMForum Interpretation. Essentially LOD 400 describes a model element developed to the level of shop drawings – in most cases, if a
project’s specifications call for shop drawings of an item, the project team might model the item at LOD 400. Thus most models contain
few LOD 400 elements.

LOD 500
The Model Element is a graphic representation of an existing or as-constructed condition developed through a combination of
observation, field verification, or interpolation. The level of accuracy shall be noted or attached to the Model Element.
BIMForum Interpretation. LOD 500 does not indicate a higher level than LOD 400, rather it indicates that the element’s geometry is
determined through observation of an existing item rather than design of a future item. The LOD 500 definition requires that the model
element’s accuracy be specified – BIMForum recommends USIBD’s Level of Accuracy (LOA) Specification for this purpose.

Defined Terms
The definitions below are not necessarily the dictionary definition of the term. Rather they describe specialized use of the term in this
Specification. These terms are shown in bold face when used in the body of this document.

Accurate. Conforming exactly with the intended dimension.


Many Landscape Architecture elements are subject to growth, erosion, and other similar natural processes, and therefore application of
the term “accurate” to these elements differs somewhat from its application to manufactured or constructed elements. For the purposes
of this Specification “accurate” for these natural elements denotes a sufficient level of exactness to communicate design intent, but
does not necessarily imply exact dimensions.
Actual. The dimension needed for construction-level coordination. E.g., in defining an opening in a precast wall the precast plant must
know the real dimensions of the rough opening.
Nominal. The dimension that is available at the design phase. E.g., the dimensions of the opening that is automatically generated by
the model authoring tool when a door is placed in a wall. Note that these dimensions will usually differ from the rough opening
dimensions.
Element envelope. The exterior surfaces of the element. This term is used at both LOD 200 and 300 – at 200 the surfaces may be
approximate but must encompass the extents of the element, at 300 they must be accurate.
Penetration Elements. Elements that are used to reinforce or otherwise augment a point where one element passes through another,
e.g., a pipe sleeve in a concrete wall. Penetration elements are addressed under the penetrating element – e.g., pipe sleeves are
addressed in the sections on piping.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 15
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

General Notes
Appurtenances. This heading is used by Uniformat to indicate items that may or may not be attached to other elements under the
same parent heading (e.g., waterproofing, insulation) – as such each Supplementary Components section will include a wide range of
elements. In most cases these elements are not modeled. If it is deemed necessary to model any of the elements this can be
addressed in the Part II template by either adding one or more child lines or using the notes function.
Supplementary Components. Similar to Appurtenances.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 16
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

REVISION HISTORY
2/28/2024 Level of Development Specification
2023
12/31/2023 Level Of Development Specification 2023
Draft for Public Comment
12/31/2022 Supplement to 2021 LOD Specification
12/29/2021 Level Of Development Specification 2021
10/24/2021 Level Of Development Specification 2021
Draft for Public Comment
12/31/2020 Level Of Development Specification 2020
11/23/2020 Level Of Development Specification 2020
Draft for Public Comment
01/18/2019 Level Of Development Specification 2019
09/25/2018 Level Of Development Specification 2019
Draft for Public Comment
09/04/2018 Level Of Development Specification 2018
07/16/2018 Level Of Development Specification 2018
Draft for Public Comment
11/07/2017 Level Of Development Specification 2017
08/25/2017 Level Of Development Specification 2017
Draft for Public Comment
10/17/2016 Level Of Development Specification 2016
08/25/2016 Level Of Development Specification 2016 Definitions have not been changed except for minor
Draft for Public Comment grammatical corrections and formatting. Engineered metal
building structures, precast concrete, highway and rail road
bridge content moved from Appendix to main body.
10/30/2015 Level Of Development Specification 2015 Definitions have not been changed except for minor
grammatical corrections and formatting. New content released
as an Appendix to Part A for engineered metal building
structures, precast concrete, highway bridge content and rail
road bridge content.
4/30/2015 Level Of Development Specification 2015 Definitions have not been changed except for minor
Draft For Public Comment grammatical corrections and formatting. Part B, Model Element
Table, and Attribute Tables were added.
12/30/2014 Level Of Development Specification 2014 Definitions have not been changed except for minor
grammatical corrections and formatting. Images and image
notes have been added in blue italics font.
8/22/2013 Level Of Development Specification 2013
4/24/2013 Initial Draft for Public Review

Specific Changes to 2023 Edition

Part I
In addition to the overall updates described in the Preface to the 2023 Edition above the content of these sections has been updated

Uniformat Omniclass Uniclass

F1020.40 21-06 10 20 40 Ss 40 5 Special Structures: Metal Building Systems Requirements simplified


to align with design-team
needs. Removed
inconsistencies with
other sections.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 17
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

G20 21-07 20 __ Site Improvements Substantial update to


landscape-related items
per ASLA

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 18
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

PART I – ELEMENT GEOMETRY

A / 21-01 / Ss 20 05
SUBSTRUCTURE
Associated Masterformat Sections: 01 82 00

A10 / 21-01 10 / Ss 20 05 15
Foundations
Associated Masterformat Sections: 01 82 13
100 See Fundamental LOD Definitions
200 Inclusions
● Element envelope

A1010 / 21-01 10 10 / Ss 20 05
Standard Foundations
Includes: Formwork, concrete, unit masonry and reinforcement. Includes Standard Foundation Supplementary Components as
appropriate. May Include: Related Activities: Excavation, dewatering, excavation support systems, backfill and compaction, and soil
treatment.
Associated Masterformat Sections: 01 82 13
100 See A10
200 See A10
300 Inclusions
● Openings with any dimension
greater than 6” (15 cm) or as
noted
● Surface slopes
● Area of Influence

A1010.10 / 21-01 10 10 10 / Ss 20 05 15
Wall Foundations
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 06 14 00
100 See A10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 19
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

200 See A10.

300 Inclusions
● Openings with any dimension
greater than 6” (15 cm) or as
noted
● Surface slopes
● Area of influence

350 Inclusions
● All penetrations, modeled at
rough opening dimensions
● Expansion joints
● Chamfer
● Dowels
● Embeds
● Lintels
● Keyways

400 Inclusions
● Rebar including hooks and lap
splices
● Post-tensioning tendons
● Coursing for unit masonry
● Pour Joints

A1010.30 / 21-01 10 10 30 / Ss 20 05 15
Column Foundations
Associated Masterformat Sections: 03 30 00
100 See A10
200 See A10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 20
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

300 Inclusions
● Design specified bearing depth
● Top of Pier
● Size of pier
● Area of influence

350 Inclusions
● Dowels

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 21
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

400 Inclusions
● Depth to bearing stratum
● Penetration into bearing stratum
● Rebar including hooks and lap
splices
● Pier sled or Pier wheel for side
clear cover
● Pier bolster for bottom clear cover

A1010.90 / 21-01 10 10 90 / Ss 20 05 15
Standard Foundation Supplementary Components TBD
See General Notes: Supplementary Components

A1020 / 21-01 10 20 / Ss 20 05
Special Foundations
Includes: Drilling, casing, bell bottom, excavation, dewatering, removal of excavated, materials, reinforcing, and concrete. Drilled Piers,
Driven Piles, Mat Foundation, elevator pits.
Associated Masterformat Sections: 31 60 00
100 See A10

200 See A10

300 See A1010


350 See A1010.10

400 See A1010.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 22
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

A1020.10 / 21-01 10 20 10 / Ss 20 05 65 24
Driven Piles TBD
Includes: Piles, pile driving, pile cut off, pile testing.

A1020.10.10 / 21-01 10 20 10 10 / --
Helical Piles, Helical Piers
Associated Masterformat Sections: N/A
100 See A10
200

300 Inclusions
● Length
● Largest outside diameter
● Area of influence

350 Inclusions
● Connection detail at top of pier

400 Inclusions:
• True shape of pier

A1020.20 / 21-01 10 20 20 / Ss 37 50 80
Caissons TBD

A1020.30 / 21-01 10 20 30 / ss 20 05 15
Special Foundation Walls TBD
Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 23
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

A1020.40 / 21-01 10 20 40 / Pr 20 29 03
Foundation Anchors TBD

A1020.50 / 21-01 10 20 50 / Ss 20 05 90
Underpinning TBD

A1020.60 / 21-01 10 20 60 / Ss 20 05 15 72
Raft Foundations TBD

A1020.70 / 21-01 10 20 70 / Ss 20 05 65
Pile Caps TBD

A1020.80 / 21-01 10 20 80 / Ss 20 05 15 71
Grade Beams
Includes: Formwork, reinforcement, and concrete.
Associated Masterformat Sections: 03 30 00
100 See A10
200 See A10

300 See A1010

350 Inclusions:
● All penetrations, modeled at rough
opening dimensions
● Expansion joints
● Chamfer
● Dowels
● Embeds
● Keyway
● Void boxes

400 See A1010.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 24
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

A20 / 21-01 20 / Ss 20 05 15
Subgrade Enclosures
Associated Masterformat Sections: 01 82 16
100 Inclusions
● Solid mass model representing
overall subgrade volume or
schematic wall elements that are not
distinguishable by type or material.

A2010 / 21-01 20 10 / Ss 20 60
Walls for Subgrade Enclosures
Includes: Perimeter walls enclosing building space below grade. Includes formwork, reinforcing, concrete and unit masonry. Includes
Subgrade Enclosure Wall Supplementary Components as appropriate. May Include: Related Activities: Excavation, dewatering,
excavation support systems, backfill and compaction, and soil treatment.
Associated Masterformat Sections: 01 82 16
100 See B20
200 See B2010.20
300 See B2010.20
350 See B2010.20.50
400 See B2010.20.50

A2010.10 / 21-01 20 10 10 / Ss 20 60
Subgrade Enclosure Wall Construction TBD

A2010.20 / 21-01 20 10 20 / Ss 20 60
Subgrade Enclosure Wall Interior Skin TBD

A2010.90 / 21-01 20 10 90 / Ss 20 60
Subgrade Enclosure Wall Supplementary Components
See General Notes: Supplementary Components

A40 / 21-01 40 / Pr 20 85 14 16
Slabs-on-Grade
Associated Masterformat Sections: 01 82 00
100 N/A
200 Inclusions
● Generic slab with approximate
thickness.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 25
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

A4010 / 21-01 40 10 / Pr 20 85 14 16
Standard Slabs-on-Grade
Includes: Slab construction supported continuously by earth or compacted fill. Includes fine grading, subbase layer, mud slab,
insulation, vapor retarder, waterproofing, formwork, expansion joints, control joints, reinforcement, concrete, and finishing includes:
Slabs-On-Grade Supplementary Components as appropriate. May Include: Related Activities: Excavation, dewatering, excavation
support systems, backfill and compaction, and soil treatment.
Associated Masterformat Sections: 03 30 00
100 See A40
200 See A40

300 Inclusions:
● Overall size, thickness, and geometry
of the slab
● Openings with any dimension greater
than 6” (15 cm) or as noted
● Slab depressions
● Edge turn downs
● Surface slopes
● Area of influence

350 Element modeling to include:


● All penetrations, modeled to rough
opening dimensions.
● Control joints
● Expansion joints
● Void boxes
● Anchor elements
● Dowels
● Post-tension anchor points.

400 Inclusions:
● Pour joints
● Rebar
● Post tensioning components

A4020 / 21-01 40 20 / Pr 20 85 14 16
Structural Slabs-on-Grade
Includes: Self-supporting slab construction not supported continuously by earth or compacted fill. Includes formwork, accessories,
reinforcement, concrete, and finishing. Includes Slabs-On-Grade Supplementary Components as appropriate. May Include: Related
Activities: Excavation, dewatering, excavation support systems, backfill and compaction, and soil treatment.
Associated Masterformat Sections: 03 30 00
All See A4010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 26
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

A4030 / 21-01 40 30 / --
Slab Trenches TBD

A4040 / 21-01 40 40 / Ss 37 16 90 63
Pits and Bases TBD

A4090 / 21-01 40 90 / --
Slab-On-Grade Supplementary Components
See General Notes: Supplementary Components

A60 / 21-01 60 / --
Water and Gas Mitigation TBD

A6010 / 21-01 60 10 / Ss 50 35 8 85
Building Subdrainage TBD

A6020 / 21-01 60 20 / Ss 15 10 33 34
Off-Gassing Mitigation TBD

A90 / 21-01 90 / --
Substructure Related Activities TBD

A9010 / 21-01 90 10 / Ss 15 10 30 25
Substructure Excavation TBD

A9020 / 21-01 90 20 / Ss 15 10 76 21
Construction Dewatering TBD

A9030 / 21-01 90 30 / TE 20 50 65
Excavation Support TBD

A9040 / 21-01 90 40 / Ss 15 10 35
Soil Treatment TBD

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 27
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B / 21-02 / -- SHELL
Associated Masterformat Sections: 01 83 00

B10 / 21-02 10 / --
Superstructure
Associated Masterformat Sections: 01 83 13

B1010 / 21-02 10 10 / Ss 30 12
Floor Construction
Associated Masterformat Sections: 01 83 13
100 Inclusions
• Abstraction of element indicating approximate location
200 Inclusions
• Element envelope of individual members

B1010.10 / 21-02 10 10 10 / Ss 30 12 33
Floor Structural Frame
Includes: Structural elements required for support of floor construction within basements and above grade. Includes columns, girders,
beams, trusses, joists. Includes cast-in-place concrete, precast concrete, unit masonry, metal framed, and wood framed systems.
Includes framed and sleeved openings for services. Includes Floor Construction Supplementary Components as appropriate.
Specific structural systems within this section are listed as follows:
Concrete B1010.10.10
Precast Structural Inverted T Beam B1010.10.11
Concrete Structural Column B1010.10.12
Masonry B1010.10.20
Steel Framing Columns B1010.10.30
Steel Framing Beams B1010.10.40
Steel Framing Bracing Rods B1010.10.50
Steel Joists B1010.10.60
Cold-Formed Metal Framing B1010.10.70
Wood Floor Trusses B1010.10.80
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 10 00 / 05 20 00
05 21 23 / 05 42 00 / 05 44 00 / 06 11 00 / 06 13 00 / 06 13 26 / 06 17 33 / 06 17 36
06 17 53 / 06 18 13 / 06 18 16 / 06 50 00

B1010.10.10 / 21-02 10 10 10 10 / Ss 30 12 85 18
Floor Structural Frame (Concrete)
Associated Masterformat Sections: 03 30 00 / 03 40 00
100 See B1010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 28
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See B1010
300 Inclusions:
• Overall size, thickness, and geometry of elements
• Openings with any dimension greater than 6” (15 cm) or
as noted
• Surface slopes
350 Inclusions
• All penetrations, modeled to rough opening dimensions.
• Control joints
• Expansion joints
• Anchor elements
• Embeds
• Dowels
• Post-tension anchor points.

400 Inclusions:
• Shear reinforcing and stud rails
• Pour joints
• All reinforcement
• Chamfer
• Camber

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 29
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


B1010.10.11 / 21-02 10 10 10 11 / Ss 20 20 75 15
Structural Beam, Concrete, Precast or Cast-in-Place
Includes: Structural elements required for support of floor construction within basements and above grade. Includes columns, girders,
beams, trusses, joists. Includes cast-in-place concrete, precast concrete, unit masonry, metal framed, and wood framed systems.
Includes framed and sleeved openings for services.Includes Floor Construction Supplementary Components as appropriate.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 10 00 / 05 20 00
05 21 23 / 05 42 00 / 05 44 00 / 06 11 00 / 06 13 00 / 06 13 26 / 06 17 33 / 06 17 36
06 17 53 / 06 18 13 / 06 18 16 / 06 50 00
100 See B1010

200 See B1010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 30
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Element envelope of structural elements
• Openings with any dimension greater than 6” (15 cm) or
as noted
• Slopes

350 Inclusions
• All penetrations, modeled to rough opening dimensions.
• Anchor elements
• Embeds
• Dowels
• Post-tension anchor points.
• Critical structural zones such as zones that cannot be
penetrated or cut
• Lifting points

400 Inclusions:
• All reinforcement
• Chamfer
• Camber

B1010.10.12 / 21-02 10 10 10 12 / Ss 20 30 75 15
Structural Column, Concrete, Precast or Cast-inPlace
Includes: Structural elements required for support of floor construction within basements and above grade. Includes columns, girders,
beams, trusses, joists. Includes cast-in-place concrete, precast concrete, unit masonry, metal framed, and wood framed systems.
Includes framed and sleeved openings for services. Includes Floor Construction Supplementary Components as appropriate.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 10 00 / 05 20 00
05 21 23 / 05 42 00 / 05 44 00 / 06 11 00 / 06 13 00 / 06 13 26 / 06 17 33 / 06 17 36
06 17 53 / 06 18 13 / 06 18 16 / 06 50 00
100 See B1010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 31
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See B1010

300 Inclusions:
• Overall Geometry
• Openings with any dimension greater than 6” (15 cm) or
as noted
• Slopes

350 Inclusions
• All penetrations, modeled to rough opening dimensions.
• Anchor elements
• Embeds
• Dowels
• Post-tension anchor points.
• Critical structural zones such as zones that cannot be
penetrated or cut
• Lifting points

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 32
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• All reinforcement
• Chamfer
• Camber

B1010.10.20 / 21-02 10 10 10 20 / Ss 25 13 50
Floor Structural Frame, Masonry
Associated Masterformat Sections: 04 20 00
100 See B1010
200 See B1010
300 Inclusions:
• Overall Geometry of elements
• Openings with any dimension greater than 6” (15 cm) or
as noted
• Slopes
350 Inclusions
• All penetrations, modeled to rough opening dimensions.
• Anchor elements
• Exposed embeds
• Lintels
• Dowels
• Critical structural zones such as zones that cannot be
penetrated or cut
• Expansion joints
• Lifting points
• Grouted cells, e.g., bond beams
400 Inclusions:
• Coursing
• Reinforcements

B1010.10.30 21-02 10 10 10 30
Floor Structural Frame, Steel Framing Columns
Associated Masterformat Sections: 05 10 00
100 See B1010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 33
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See B1010

300 Inclusions:
• Specific section type and size

350 Inclusions:
• Member connections such as, base plates and gusset
plates, anchor rods
• Connection details with correct and reliable dimensions
• Steel structure reinforcements and stiffeners (e.g. for
penetrations)
• Cap plates

400 Inclusions:
• Welds
• Coping of members
• Washers, nuts, etc.

B1010.10.40 / 21-02 10 10 10 40 / Ss 20 20 75 80
Floor Structural Frame, Steel Framing Beams
Associated Masterformat Sections: 05 10 00 / 05 20 00 / 05 21 23
100 • See B1010
200 • See B1010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 34
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Specific section type and size
• Nominal size and shape of penetrations of any size
• Slopes

350 Inclusions:
• Member connections such as, base plates and gusset
plates, anchor rods
• Actual size of penetrations
• Reinforcement of penetrations
• Stiffeners
• Connection details
• Cap plates

400 Inclusions
• Welds
• Coping of members
• Bent plates, cap pates, etc.
• Bolts, washers, nuts, etc.
• All assembly elements

B1010.10.50 / 21-02 10 10 10 50 / Pr 20 85 84 88
Floor Structural Frame, Steel Framing Bracing
Associated Masterformat Sections: 05 10 00
100 See B1010
200 See B1010
300 Inclusions
• Type of brace (e.g., cable, rod, section, etc.)

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 35
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions
• Connection details
• Actual location of member connections
• Main elements of typical connections such as base
plates, gusset plates, anchor rods, etc.
• miscellaneous steel members with correct size, shape,
orientation and material

400 Inclusions
• Welds
• Clevis
• Bolts, washers, nuts, etc.
• All assembly elements

B1010.10.60 / 21-02 10 10 10 60 / Pr 20 85 90 11
Floor Structural Frame, Steel Joists
Associated Masterformat Sections: 05 10 00 / 05 20 00 / 05 21 23
100 See B1010
200 See B1010

300 Inclusions
• Element envelope of chords and web
• Spacing and end elevations
• Joist seat depth

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 36
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions
• Actual final chord and web members with accurate
panel points
• Joist bridging and lateral braces.
• Any miscellaneous steel pertaining to the joist
• Joist seat width
• Erection details for installation
• Joist layout in coordination with metal deck fasteners
• Non-standard joist seat depths and\or sloping joist
seat

400 Inclusions
• Welds
• Connection plates
• Anchorage

B1010.10.70 / 21-02 10 10 10 70 / Ss 20 10 75 45
Floor Structural Framing (Cold Formed Metal Framing)
Associated Masterformat Sections: 05 10 00 / 05 42 00 / 05 44 00
100 See B1010
200 See B1010
300 Inclusions:
• Specific section type and size
• Nominal size and shape of penetrations of any size
350 Inclusions
• Members at any interface with wall edges (top, bottom,
sides) or opening through wall
• Bridging or straps

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 37
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions
• Welds
• Connections
• Any part required for complete installation

B1010.10.80 / 21-02 10 10 10 80 / Pr 20 85 90 81
Floor Structural Frame (Wood Floor Trusses)
Associated Masterformat Sections: 06 11 00 / 06 13 26 / 06 17 53
100 See B1010
200 See B1010

300 Inclusions
• Element envelope of chords and web
• Spacing and end elevations
• Joist seat depth

350 Inclusions
• Actual final chord and web members with accurate
panel points
• Joist bridging and lateral braces.
• Joist seat width
• Erection details for installation
• Non-standard joist seat depths and\or sloping joist
seat

400 Inclusions
• Connection plates
• Anchorage
• Elements required for proper installation

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 38
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B1010.20 / 21-02 10 10 20 / Ss 30 12
Floor Decks, Slabs, and Toppings
Includes: Structural slab, deck, and sheathing floor construction at intermediate floors of basement construction and above grade.
Includes cast-in-place concrete, precast concrete, cementitious decks and toppings, metal decking, wood sheathing, and wood decking.
Includes framed and sleeved penetrations for services and housekeeping pads for equipment. Includes Floor Construction
Supplementary Components as appropriate.
Specific structural systems within this section are listed as follows:
Wood Floor Deck B1010.20.10
Metal Floor Deck B1010.20.20
Composite Floor Deck B1010.20.30
Concrete B1010.20.40
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 03 50 00 / 05 30 00 / 05 34 00
05 35 00 / 06 12 00 / 06 15 00 / 06 16 00 / 06 18 00 / 06 53 00 / 06 73 00
100 Inclusions
• Abstraction of element indicating approximate location
200 Inclusions
• Overall Element envelope

B1010.20.10 / 21-02 10 10 20 10 / Ss 30 12 85 90
Floor Decks, Slabs, and Toppings (Wood Floor Deck)
Associated Masterformat Sections: 06 12 00 / 06 15 00 / 06 16 00 / 06 18 00
100 See B1010.20
200 See B1010.20
300 Inclusions:
• Slopes and elevation changes (e.g., depressions)
• Openings with any dimension greater than 6” (15 cm) or
as noted
• changes of material
• Edge location
350 Inclusions:
• Openings at rough opening dimensions
• Opening support framing

400 Inclusions:
• Fasteners

B1010.20.20 / 21-02 10 10 20 20 / Ss 30 12 85 40
Floor Decks, Slabs, and Toppings (Metal Floor Deck)
Associated Masterformat Sections: 05 30 00 / 05 34 00 / 05 35 00
100 See B1010
200 See B1010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 39
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Slopes and elevation changes (e.g., depressions)
• Drainage low points
• Openings with any dimension greater than 6” (15 cm) or
as noted
• changes of material
• Edge location defined
• Framing members

350 Inclusions:
• Splices and end laps
• Embeds and structural connection points
• Actual deck profile and flute locations per manufacturer
• All miscellaneous framing including braces, kickers, etc.
• Openings at rough opening dimensions

400 Element modeling to include:


• Framing accessories and fasteners
• Welds

B1010.20.30 / 21-02 10 10 20 30 / Ss 30 12 85 16
Floor Decks, Slabs, and Toppings (Composite Floor Deck)
Associated Masterformat Sections: 06 73 00
100 See B1010
200 See B1010
300 Inclusions:
• Slopes and elevation changes (e.g., depressions)
• Drainage low points
• Openings with any dimension greater than 6” (15 cm) or
as noted
• changes of material
• Edge location defined
• Framing members

350 Inclusions:
• Splices and end laps
• Embeds and structural connection points
• Actual deck profile and flute locations per manufacturer
• All miscellaneous framing including braces, kickers, etc.
• Openings at rough opening dimensions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 40
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Framing accessories and fasteners
• Welds

B1010.20.40 / 21-02 10 10 20 40 / Ss 30 12 85 18
Floor Decks, Slabs, and Toppings (Concrete)
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 03 50 00
100 See B1010
200 See B1010
300 Inclusions:
• Slopes and elevation changes (e.g., depressions)
• Drainage low points
• Openings with any dimension greater than 6” (15 cm) or
as noted
• Changes of material
• Edge locations
• Framing members

350 Inclusions
• Chamfer
• Expansion Joints
• Embeds and anchor rods
• Locations of post-tension tendons
• Openings with any dimension greater than 6” (15 cm) or
as noted
• Shear reinforcing and stud rails

400 Inclusions
• Reinforcement

B1010.20.41 / 21-02 10 10 20 50 / Pr 20 85 08 66
Precast Structural Double Tee (Concrete)
Includes: Structural elements required for support of floor construction within basements and above grade. Includes columns, girders,
beams, trusses, joists. Includes cast-in-place concrete, precast concrete, unit masonry, metal framed, and wood framed systems.
Includes framed and sleeved openings for services. Includes Floor Construction Supplementary Components as appropriate
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 10 00 / 05 20 00
05 21 23 / 05 42 00 / 05 44 00 / 06 11 00 / 06 13 00 / 06 13 26 / 06 17 33 / 06 17 36
06 17 53 / 06 18 13 / 06 18 16 / 06 50 00
100 Inclusions
• Conceptual depth

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 41
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 Inclusions
• Element envelope

300 Inclusions
• Main concrete structural members
• Surface slopes

350 Inclusions
• Lifting points
• Expansion Joints
• Embeds and anchor rods
• Locations of post-tension tendons
• Openings with any dimension greater than 6”
(15 cm) or as noted
• Shear reinforcing and stud rails

400 Inclusions
• Chamfer
• Reinforcement

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 42
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B1010.30 / 21-02 10 10 30 / Ss 30 12 85
Balcony Floor Construction TBD

B1010.40 / 21-02 10 10 40 / Ss 30 12 85
Mezzanine Floor Construction TBD

B1010.50 / 21-02 10 10 50 / Ss 35 10 85
Ramps
Inclusions
100
• None required
200 Inclusions
• Element envelope
300 Inclusions
• Major ramp support elements
• Changes of materials
• Handrails

350 Inclusions
• Secondary support elements
• Connection points etc.).
• Elements needed for installation
400 Inclusions
• Elements needed for fabrication

B1010.90 / 21-02 10 10 90 / Ss 30 12
Floor Construction Supplementary Components
See General Notes: Supplementary Components

B1020 / 21-02 10 20 / Ss 30 10
Roof Construction
Associated Masterformat Sections: 01 81 13
Note: This classification refers to roofs modeled as single composite objects (excluding structural frame). If individual layers are to be
modeled see:
B1020.10 21-02 10 20 10 Roof Structural Frame
B1020.20 21-02 10 20 20 Roof Decks, Slabs, and Sheathing
B3010 21-02 30 10 Roofing

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 43
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B1020.10 / 21-02 10 20 10 / Ss 30 10 30
Roof Structural Frame
Description: Structural elements required for support of floor construction within basements and above grade. Includes columns,
girders, beams, trusses, joists. Includes cast-in-place concrete, precast concrete, unit masonry, metal framed, and wood framed
systems. Includes framed and sleeved openings for services. Includes Floor Construction Supplementary Components as appropriate.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 10 00 / 05 20 00 / 05 21 23 / 05 42 00 / 05 44 00
06 11 00 / 06 13 00 / 06 13 26 / 06 17 33 / 06 17 3606 17 53 / 06 18 13 / 06 18 16 / 06 50 00
See B1010.10

B1020.20 / 21-02 10 20 20 / Ss 30 12 85
Roof Decks, Slabs, and Sheathing
Includes: Structural roof deck, slab, and sheathing construction. Includes cast-in-place concrete, precast concrete, cementitious decks
and toppings, metal decking, wood sheathing, wood decking, timber decking and expansion control. Includes framed and sleeved
penetrations for services and housekeeping pads for equipment. Includes Roof Construction Supplementary Components as
appropriate.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 03 50 00 / 03 52 00 / 05 30 00
05 34 00 / 05 35 00 / 06 12 00 / 06 15 00 / 06 16 00 / 06 18 00 / 06 53 00 / 06 73 00
100 Inclusions
• Conceptual depth
200 Inclusions:
• Element envelope
300 Inclusions
• Main structural members
• Surface slopes
• Openings with any dimension greater than 6” (15 cm) or
as noted
350 Inclusions
• Framing members at openings

B1020.30 / 21-02 10 20 30 / Ss 25 50 45 10
Canopy Construction
Includes: Structural frame and decks, slabs, and sheathing for canopy construction.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 05 10 00 / 05 19 19 / 05 20 00 / 06 11 00 / 06 12 00 / 06 13 00 / 06
15 00 / 06 16 00 / 06 17 00 / 06 18 00 / 06 50 00 / 06 73 00
See B1010.20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 44
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B1020.90 / 21-02 10 20 90 / Ss 30 10
Roof Construction Supplementary Components
Includes: Vapor retarders, air barriers, insulation, fireproofing, firestopping, and expansion control to be included with roof construction
elements above as appropriate
See General Notes: Supplementary Components

B1080 / 21-02 10 80 / Ss 35
Stairs
Includes: Stairs, fire escapes, metal walkways, and ladders.
Associated Masterformat Sections: 01 84 16
100 Inclusions:
• Approximate location

B1080.10 / 21-02 10 80 10 / Ss 35 10
Stair Construction
Includes: Structural framing for exterior and interior stairs including treads, risers, and landings. Includes fire escapes and ladders.
Associated Masterformat Sections: 03 11 23 / 03 30 00 / 03 41 23 / 03 48 19 / 05 51 00
05 55 00 / 05 71 00 / 06 43 00
100 See B1080
200 Inclusions:
• Reliable number and arrangement of landings and
flights

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 45
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Overall geometry of landings and flights
• Number of risers and treads
• Tread width
• Riser height
• Stringers
• Railing
• Nosing geometry

350 Inclusions:
• Railing support locations
• Openings in structural elements
• Secondary support elements (hangers, brackets, etc.).

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 46
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Elements necessary for fabrication and installation

B1080.20 / 21-02 10 80 10 / Ss 35 10
Precast Structural Stairs (Concrete)
Includes: Structural framing for exterior and interior stairs including treads, risers, and landings. Includes fire escapes and ladders.
Associated Masterformat Sections: 03 11 23 / 03 30 00 / 03 41 23 / 03 48 19 / 05 51 00
05 55 00 / 05 71 00 / 06 43 00
100 See B1080
200 Inclusiuons:
• Reliable number and arrangement of
landings and flights

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 47
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Overall geometry of landings and
flights
• Number of risers and treads
• Tread width
• Riser height
• Stringers
• Railing
• Nosing geometry

350 Inclusions:
• Railing support locations
• Openings in structural elements
• Embeds
• Secondary support elements (hangers,
brackets, etc.).
• Reinforcing Post-tension profiles and
tendon locations
• Joint locations
• Attachment points for Lifting devices
• All penetrations modeled to rough
opening dimensions.
• Any permanent forming or shoring
components

400 Inclusions:
• Elements necessary for fabrication and
installation
• Chamfer

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 48
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B1080.30 / 21-02 10 80 30 / Ss 30 25 10 35
Stair Soffits TBD

B1080.50 / 21-02 10 80 50 / Ss 25 15 60 35
Stair Railings
Associated Masterformat Sections: 05 15 00 / 05 52 00 / 05 73 00 / 06 43 16 / 06 63 00
06 81 00
100 N/A
200 Inclusions:
• Element envelope
300 Inclusions
• Individual members (e.g., uprights and
longitudinal)

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 49
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions
• Attachment points

400 Inclusions
• Attachment points

B1080.60 / 21-02 10 80 60 / Ss 35 10 30 40
Fire Escapes
Associated Masterformat Sections: 05 51 23
See B1080.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 50
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B1080.70 / 21-02 10 80 70 / Ss 35 10 30 95
Metal Walkways
Includes: Catwalks and gratings over horizontal openings
Associated Masterformat Sections: 05 51 36 / 05 51 36.13 / 05 53 00
See B1080.10 and B1080.50
100 See B1080
200 Inclusions:
• Element envelope

300 Element modeling to include:


• Overall geometry.
• Thickness

350 Inclusions
• Panel layout and grating deck
edges.
• Openings with any dimension
greater than 6” (15 cm) or as noted
• Indication of span direction
• Configuration of grating elements

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 51
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Elements necessary for fabrication
and installation

B1080.80 / 21-02 10 80 80 / Ss 35 10 30
Ladders
Associated Masterformat Sections: 05 51 33 / 05 51 33.13 / 05 51 33.16 / 05 51 33.23
See B1080.10 and B1080.50

B20 / 21-02 20 / EF 25 10
Exterior Vertical Enclosures
Associated Masterformat Sections: 01 83 16
100 Inclusions:
• Solid mass model representing overall building volume;
or, schematic wall elements that are not distinguishable
by type or material.

B2010 / 21-02 20 10 / EF 25 10
Exterior Walls
Includes: Exterior Wall Supplementary Components as appropriate. Includes Exterior Wall Opening Supplementary Components as
appropriate. Includes: Solid wall construction that is composite in nature; in other words, multiple layers of materials to form an overall
assembly.
Associated Masterformat Sections: 01 83 16
Note: This classification refers to walls modeled as single composite elements. If individual layers are to be modeled refer to:
B2010.10 21-02 20 10 10 Exterior Wall Veneer
B2010.20 21-02 20 10 20 Exterior Wall Construction
B2010.30 21-02 20 10 30 Exterior Wall Interior Skin
100 See B20
200 Inclusions:
• Approximate overall wall thickness represented by a
single element.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 52
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Single model element separated by type of material
with accurate overall thickness and shape
• Openings with any dimension greater than 6” (15 cm) or
as noted, at nominal dimensions

350 Inclusions:
• Single element showing all layers such that they can be
measured
• All penetrations modeled to rough opening dimensions.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 53
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2010.10 / 21-02 20 10 10 / EF 25 10
Exterior Wall Veneer
Includes: Nonstructural outside face elements of exterior walls. Includes precast concrete, unit masonry, EIFS, manufactured siding,
and stucco Includes water repellents, coatings, and painting.
Associated Masterformat Sections: 03 40 00 / 04 20 00 / 04 26 13 / 04 42 00 / 04 43 13
04 70 00 / 05 19 13 / 06 20 13 / 06 61 00 / 07 19 00 / 07 24 00 / 07 42 00 / 07 44 00
07 46 00 / 09 24 00 / 09 24 23 / 09 90 00
100 N/A
200 Inclusions:
• Approximate overall wall thickness represented by a
single assembly.

300 Inclusions:
• Model elements separated by type of material
• Openings with any dimension greater than 6” (15 cm)
or as noted
• Window and door openings at nominal dimensions

350 Inclusions:
• Single element showing all layers such that they can
be measured
• All penetrations modeled to rough opening
dimensions.
• Precast concrete panels are individually modeled.
Connection points are specified.
• Connection to interfacing systems

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 54
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2010.20 / 21-02 20 10 20 / EF 25 10
Exterior Wall Construction
Includes: Exterior wall construction including backup systems for wall veneer. May be vertical load bearing. Includes cast-in-place
concrete walls, precast concrete walls, unit masonry walls, metal framed wall systems, and wood framed wall systems.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 41 00 / 06 11 00
06 12 00 / 06 16 00
100 N/A
200 Inclusions
• Approximate thickness of layer represented by a single
element.
300 Inclusions:
• Single model element with accurate thickness and
shape
• Openings with any dimension greater than 6” (15 cm) or
as noted at nominal dimensions

B2010.20.10 / 21-02 20 10 20 10 / Ss 25 11 90
Exterior Wall Construction (Wood)
Includes: Exterior Wall Supplementary Components as appropriate. Includes Exterior Wall Opening Supplementary Components as
appropriate. Includes: Solid wall construction that is composite in nature; in other words, multiple layers of materials to form an overall
assembly.
Associated Masterformat Sections: 01 83 16
100 N/A
200 See B2010.20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 55
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 See B2010.20

350 Inclusions:
• All studs
• Backing and blocking
• Shear panels
• All penetrations modeled at rough-opening
dimensions.
• Cladding and sheathing

B2010.20.20 / 21-02 20 10 20 20 / Ss 25 10 32 45
Exterior Wall Construction (Cold-Form Metal Framing)
See B2010.20.10
100 N/A
200 See B2010.20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 56
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 See B2010.20

350 Inclusions:
• All studs
• Backing and blocking
• Shear panels
• All penetrations modeled at rough-opening
dimensions.
• Cladding and sheathing

B2010.20.30 / 21-02 20 10 20 30 / Ss 25 13 50
Exterior Wall Construction (Masonry)
Includes: Exterior Wall Supplementary Components as appropriate. Includes Exterior Wall Opening Supplementary Components as
appropriate. Includes: Solid wall construction that is composite in nature; in other words, multiple layers of materials to form an overall
assembly.
Associated Masterformat Sections: 01 83 16
100 N/A
200 See B2010.20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 57
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 See B2010.20

350 Inclusions
• All penetrations, modeled to rough opening dimensions.
• Anchor elements
• Exposed embeds
• Lintels
• Dowels
• Critical structural zones such as zones that cannot be
penetrated or cut
• Expansion joints
• Bond beams

400 Inclusions:
• Waterproofing
• Coursing
• Reinforcements

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 58
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


B2010.20.40 / 21-02 20 10 20 40 / Ss 25 16 65
Precast Wall Construction (Concrete)
Includes: Exterior wall construction including backup systems for wall veneer. May be vertical load bearing. Includes cast-in-place
concrete walls, precast concrete walls, unit masonry walls, metal framed wall systems, and wood framed wall systems.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 41 00 / 06 11 00
06 12 00 / 06 16 00
100 N/A
200 See B2010.20
300 See B2010.20
350 Inclusions:
• Reinforcing Post-tension profiles and strand locations
• Expansion Joints
• Control joints
• Lifting devices
• Embeds
• All penetrations are modeled at actual rough-opening
dimensions.
• Any permanent forming or shoring components
• Dowels

400 Inclusions:
• Rebar including hooks and lap splices
• Post-tensioning tendons
• Pour Joints

B2010.20.50 / 21-02 20 10 20 50 /
Exterior Wall Construction (Cast-in Place Concrete)
Includes: Exterior Wall Supplementary Components as appropriate. Includes Exterior Wall Opening Supplementary Components as
appropriate. Includes: Solid wall construction that is composite in nature; in other words, multiple layers of materials to form an overall
assembly.
Associated Masterformat Sections:
100 N/A
200 See B2010.20
300 See B2010.20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 59
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Penetrations at rough opening dimensions.
• Pour joints
• Control joints
• Expansion joints
• Anchor elements
• Embeds
• Dowels
• Post tension anchor points

400 Inclusions:
• Rebar including hooks and lap splices
• Post-tensioning tendons
• Pour Joints

B2010.30 / 21-02 20 10 30 / Ss 25 45
Exterior Wall Interior Skin
Includes: Materials to provide finish or protective covering on inside of face of exterior walls. May include insulation and vapor retarder.
Associated Masterformat Sections: 09 20 00
100 N/A
200 Inclusions:
• approximate thickness of layer

300 Inclusions:
• Single model element separated by type of material
with accurate overall thickness and shape
• Openings with any dimension greater than 6” (15 cm) or
as noted, at nominal dimensions

350 Inclusions:
• Single element showing all layers such that they can be
measured
• All penetrations modeled to rough opening dimensions.
• Connection to interfacing systems

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 60
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Studs and tracks
• Individual masonry units
• Reinforcing
• Wall board
• Insulation

B2010.40 / 21-02 20 10 40 / Ss 25 12
Fabricated Exterior Wall Assemblies TBD
Includes: Manufactured or fabricated assemblies that include exterior veneer and wall construction within one fabricated assembly and
may also include interior skin. Includes Exterior Wall Supplementary Components as appropriate.
Associated Masterformat Sections: 04 25 00 / 07 42 63 / 07 44 63 / 08 44 00 / 08 45 00

B2020.30 / 21-02 20 20 30 / --
Exterior Window Wall

B2010.50 / 21-02 20 10 50 / Ss 25 15 60 5
Parapets
Includes: Exterior wall construction above plane of roof.
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 41 00 / 06 11 00
06 12 00 / 06 16 00
See B2010, B2010.10, B2010.20, and B2010.30

B2010.60 / 21-02 20 10 60 / EF 25 10
Equipment Screens
Includes: Exterior wall construction to screen equipment from public view.
Associated Masterformat Sections: 03 40 00 / 04 20 00 / 08 92 00
100 N/A
200 Inclusions
• Location of face
300 Inclusions
• Support structure elements
• Doors
• ladders
350 Inclusions
• connections

B2010.80 / 21-02 20 10 80 / Ss 25 60
Exterior Wall Supplementary Components
See General Notes: Supplementary Components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 61
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2010.90 / 21-02 20 10 90 / Ss 25 38
Exterior Wall Opening Supplementary Components
See General Notes: Supplementary Components

B2020 / 21-02 20 20 / Ss 25 30 95 26
Exterior Windows
Includes: Fixed or operable windows used singly and in multiples located in the exterior vertical enclosure. Includes Exterior Window
Supplementary Components as appropriate. Includes windows units with louver blinds integrally set between glass panels. Includes
metal, wood, plastic, and composite window units. May Include: Wall Opening Supplementary Components as appropriate.
Associated Masterformat Sections: 01 83 16 / 08 50 00
100 N/A
200 Inclusions:
• Generic window object

B2020.10 / 21-02 20 20 10 / Ss 25 30 95 26
Exterior Operating Windows
Includes: Window screens and storm windows.
Associated Masterformat Sections: 08 50 00 / 08 51 66 / 08 52 66 / 08 53 66 / 08 54 66
08 51 69 / 08 52 69 / 08 53 69 / 08 54 69
100 N/A
200 See B2020

300 Inclusions:
• specific type and size
• Direction of opening
350 Inclusions:
• Attachment elements of window to structure
400 Inclusions:
• Detailed frame extrusion profiles
• Fasteners

B2020.20 / 21-02 20 20 20 / Ss 25 30 95 26
Exterior Fixed Windows
Associated Masterformat Sections: 08 50 00
See B2020.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 62
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2020.30 / 21-02 20 20 30 / Ss 25 30 95 96
Exterior Window Wall
Associated Masterformat Sections: 08 43 00
100 See B20
200 Inclusions
• Area of wall
• Thickness of wall

300 Inclusions
• Mullions
• Glazing elements
• Operable components

350 Inclusions
• Anchorage points

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 63
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions
• mullion extrusion profiles.
• sealants,
• end dams,
• flashings

B2020.50 / 21-02 20 20 50 / Ss 25 30 95 26
Exterior Special Function Windows
Includes: Exterior windows with special characteristics for a special function.
Associated Masterformat Sections: 08 56 00 / 08 55 00 / 08 88 39 / 08 56 19 / 08 56 46
08 56 49 / 08 88 49 / 08 56 53 / 08 88 53 / 08 88 56 / 08 56 63 / 08 56 73 / 08 75 00
08 80 00
See B2020.10

B2050 / 21-02 20 50 / Ss 25 30 20
Exterior Doors and Grilles
Includes: Doors, grilles, and gates located in the exterior vertical enclosure. Includes screen and storm door assemblies. Includes
Exterior Door Supplementary Components as appropriate. May Include: Wall Opening Supplementary Components as appropriate.
Associated Masterformat Sections: 01 83 16
100 N/A
200 Inclusions
• Generic object

B2050.10 / 21-02 20 50 10 / Ss 25 30 20 25
Exterior Entrance Doors
Includes: Exterior personnel door assemblies at main entrances. Includes automatic, revolving, balanced, and other special operating
entrance doors, and sliding storefront wall systems.
Associated Masterformat Sections: 08 32 00 / 08 42 00 / 08 42 26 / 08 42 29 / 08 42 33
08 42 36 / 08 43 29
100 N/A
200 See B2050

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 64
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions
• Specific door panels and frames (if applicable).
• Operation
• If clearances are to be modeled indicate in a note
• Panic bars if applicable
350 Inclusions
• Grillwork if applicable
• jambs
• Thresholds
• Operation and mechanism element envelopes
• Connections and interfaces
• hardware
400 Inclusions TBD

B2050.20 / 21-02 20 50 20 / Ss 25 30 20 25
Exterior Utility Doors
Includes: Exterior personnel door assemblies other than at main entrances.
Associated Masterformat Sections: 08 10 00
See B2050.10

B2050.30 / 21-02 20 50 30 / Ss 25 30 20 25
Exterior Oversize Doors
Includes: Large exterior door assemblies to allow for passage of large objects involving various operating methods. Includes Exterior
Door Supplementary Components as appropriate including operators and drive mechanisms.
Associated Masterformat Sections: 08 33 00 / 08 36 00 / 08 36 13 / 08 36 16 / 08 36 19
08 36 23 / 08 34 16
100 N/A
200 See B2050
300 Inclusions
• Specific door panels and frames (if applicable).
• Operation
• If clearances are to be modeled indicate in a note
• Indication of hardware set
350 Inclusions
• jambs
• Thresholds
• Operation and mechanism element envelopes
• Connections and interfaces
400 Inclusions TBD

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 65
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2050.40 / 21-02 20 50 40 / Ss 25 30 20 25
Exterior Special Function Doors
Includes: Exterior door assemblies for a variety of special functions and applications involving a variety of operating methods. Includes
Exterior Door Supplementary Components as appropriate including controls and operators.
Associated Masterformat Sections: 08 30 00 / 08 34 13 / 08 34 19 / 08 34 46 / 08 34 49
08 34 53 / 08 34 63 / 08 34 73 / 08 38 00 / 08 39 00 / 08 88 49 / 08 88 53 / 08 88 56
See B2050.10

B2050.60 / 21-02 20 50 60 / Ss 25 50 35
Exterior Grilles
Includes: Exterior devices of open construction to provide moveable barrier to provide access through wall or other divider.
Associated Masterformat Sections: 08 33 00 / 08 35 16
See B2050.10

B2050.70 / 21-02 20 50 70 / Ss 25 32 35
Exterior Gates
Includes: Exterior devices of solid or open construction to provide moveable barrier to provide access through wall or other divider.
Associated Masterformat Sections: 08 34 56
See B2050.10

B2050.90 / 21-02 20 50 90 / Ss 25 38 20
Exterior Door Supplementary Components
Includes frames, hardware, glazing and louvers that are part of door to be included with exterior door elements above as appropriate.
Associated Masterformat Sections: 08 10 00 / 08 30 00 / 08 71 00 / 08 80 00 / 08 91 26
See General Notes: Supplementary Components

B2070 / 21-02 20 70 / Ss 25 50 45 45
Exterior Louvers and Vents
Includes: Exterior louvers which are not an integral part of mechanical equipment, including louvers connected to ducts.
Associated Masterformat Sections: 08 90 00
100 Inclusions
• symbol
200 Inclusions
• Generic model element
300 Inclusions
• element envelope
350 Inclusions
• vanes

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 66
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2070.10 / 21-02 20 70 10 / Ss 25 50 45 45
Exterior Louvers
Associated Masterformat Sections: 01 83 16 / 08 91 00
See B2070

B2070.50 / 21-02 20 70 50 / Ss 30 30 73
Exterior Vents
Associated Masterformat Sections: 08 95 00
See B2070

B2080 / 21-02 20 80 / --
Exterior Wall Appurtenances
Includes: Exterior enclosures, grilles and screens of wood, metal, plastic, and other materials for a variety of purposes including
screening of equipment.
Associated Masterformat Sections:
See General Notes: Appurtenances

B2080.10 / 21-02 20 80 10 / Ss 25 50 75
Exterior Fixed Grilles and Screens
Includes: Exterior enclosures, grilles and screens of wood, metal, plastic, and other materials for a variety of purposes including
screening of equipment.
Associated Masterformat Sections: 05 70 00 / 06 49 00 / 06 60 00 / 06 80 00 / 10 82 13
See B2080

B2080.30 / 21-02 20 80 30 / Ss 25 50
Exterior Opening Protection Devices
Includes: Manufactured items such as louvers, fins, shutters, demountable panels, awnings, and sun screens to provide sun control,
privacy, security, insulation, and storm protection on exterior of windows, skylights, and entrances. Includes fixed and moveable,
manually and electrically operated, and automatically controlled devices.
Associated Masterformat Sections: 10 71 00 / 10 71 13 / 10 71 16 / 10 73 13
See B2080

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 67
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B2080.50 / 21-02 20 80 50 / Ss 25 15 60 35
Exterior Balcony Walls and Railings
Includes: Complete balcony wall and railing assemblies. Includes cast-in-place concrete,
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 41 00 / 06 11 00
06 16 00 / 05 52 00 / 05 73 00 / 06 43 16 / 06 63 00 / 06 81 00
Walls: See B2010
Railings: See B1080.50

B2080.70 / 21-02 20 80 70 / Pr 25 71 14 16
Exterior Fabrications
Includes: Exterior fabrications of a variety of materials formed to various profiles for a variety of purposes including column covers,
decorative metal, ornamental woodwork, and plaster fabrications.
Associated Masterformat Sections: 03 49 00 / 05 50 00 / 05 58 13 / 05 70 00 / 06 44 00
06 60 00 / 06 61 00 / 06 80 00 / 09 27 00
See Fundamental LOD Definitions

B2080.80 / 21-02 20 80 80 / Ss 45 10 10 10
Bird Control Devices
Includes: Mechanical, electrical, physical, and chemical repellant systems, and protective devices.
Associated Masterformat Sections: 10 81 13
See Fundamental LOD Definitions

B2090 / 21-02 20 90 / Ss 25 60
Exterior Wall Specialties
Includes: Complete fabrication of metal, wood, and fiberglass, including accessories and appurtenances. For example, clocks, below-
grade egress assemblies, and window wells.
Associated Masterformat Sections: 07 77 00 / 10 74 00 / 10 74 13 / 10 74 43 / 10 74 46
See Fundamental LOD Definitions

B30 / 21-02 30 / --
Exterior Horizontal Enclosures
Associated Masterformat Sections: 01 83 16
100 Inclusions:
• Solid mass model representing overall building
volume; or, schematic wall elements that are not
distinguishable by type or material.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 68
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B3010 / 21-02 30 10 / Ss 30 10
Roofing
Associated Masterformat Sections: 01 83 19
100 See B30
200 Inclusions
• Element envelope at average thickness
300 Inclusions
• Surface slopes
• Intended location of roof drains
• Openings with any dimension greater than 6” (15 cm)
or as noted

350 Inclusions
• All penetrations at actual rough-opening dimensions.
• Flashing

B3010.10 / 21-02 30 10 10 / Ss 30 10
Steep Slope Roofing
Includes: Lapped roofing shingles, shakes and roofing tiles, including fastening and flashing products and methods. Includes Roofing
Supplementary Components as appropriate.
Associated Masterformat Sections: 01 83 19 / 07 30 00 / 07 31 00 / 07 32 00 / 07 41 00
07 61 00 / 07 63 00
See B3010

B3010.50 / 21-02 30 10 50 / Ss 30 10
Low-Slope Roofing
Includes: Membrane roofing of various types and protected membrane roofing, including fastening and flashing products. Includes
Roofing Supplementary Components as appropriate.
Associated Masterformat Sections: 01 83 19 / 07 50 00 / 07 55 00 / 07 55 63 / 07 76 00
See B3010

B3010.70 / 21-02 30 10 70 / Ss 30 10
Canopy Roofing
Includes: Roofing of various types over canopies. Includes Roofing Supplementary Components as appropriate.
Associated Masterformat Sections:
See B3010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 69
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B3010.90 / 21-02 30 10 90 / --
Roofing Supplementary Components
Includes: substrate boards, vapor retarder, air barriers, deck insulation, flashing and sheet metal, and expansion joints to be included
with roofing elements above as appropriate.
Associated Masterformat Sections: 07 22 00 / 07 26 00 / 07 27 00 / 07 62 00 / 07 65 00
07 71 13 / 07 71 16 / 07 71 19 / 07 71 29 / 09 28 00
See General Notes: Supplementary Components

B3020 / 21-02 30 20 / --
Roof Appurtenances
Includes: Roof specialties and accessories installed on or in roofing or traffic bearing horizontal enclosure systems. Includes
components for the management of rainwater, but excludes mechanical and structural items.
Associated Masterformat Sections:
See General Notes: Appurtenances

B3020.10 / 21-02 30 20 10 / --
Roof Accessories
Includes: Ladders, curbs, vents, walkways, and snow guards.
Associated Masterformat Sections: 05 51 33 / 07 72 00 / 07 72 13 / 07 72 23 / 07 72 26
07 72 46 / 07 72 53
100 See Fundamental LOD Definitions
200 See Fundamental LOD Definitions
300 See Fundamental LOD Definitions
350 Inclusions
• Attachment points
400 See Fundamental LOD Definitions

B3020.30 / 21-02 30 20 30 / --
Roof Specialties
Includes: Cupolas, spires, steeples, and weathervanes.
Associated Masterformat Sections: 10 74 00 / 10 74 23 / 10 74 26 / 10 74 29 / 10 74 33
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 70
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B3020.70 / 21-02 30 20 70 / Ss 50 30 02
Rainwater Management
Includes: Components to manage rain water from roofing and traffic bearing horizontal enclosures. Includes: Conductor heads, gutters,
downspouts, scuppers, and splash blocks.
Associated Masterformat Sections: 07 71 23 / 07 71 33 / 03 48 16
See Fundamental LOD Definitions

B3040 / 21-02 30 40 / Ss 30 12 20
Traffic Bearing Horizontal Enclosures
Includes: Horizontal enclosures that are also traffic bearing. Includes Horizontal Enclosure Supplementary Components as
appropriate.
Associated Masterformat Sections: 01 83 16
See Fundamental LOD Definitions

B3040.10 / 21-02 30 40 10 / Ss 30 42 30 30
Traffic Bearing Coatings
Includes: Surface applied waterproofing exposed to weather and suitable for pedestrian or vehicular traffic.
Associated Masterformat Sections: 07 18 00

B3040.30 / 21-02 30 40 30 / Ss 32 80 79
Horizontal Waterproofing Membrane
Includes: Substrate board, deck insulation, vapor retarder, sheet metal flashing and trim, flexible flashing, and expansion joints.
Associated Masterformat Sections: 07 10 00
See membrane note

B3040.50 / 21-02 30 40 50 / Ss 30 14
Wear Surfaces
Includes: Wearing surfaces on top of horizontal waterproofing membrane that are suitable for pedestrian or vehicular traffic.
Associated Masterformat Sections: 07 76 00 / 32 13 00 / 32 14 00
See membrane note

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 71
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B3040.90 / 21-02 30 40 90 / --
Horizontal Enclosure Supplementary Components
Includes: Substrate board, deck insulation, vapor retarder, sheet metal flashing and trim, flexible flashing, and expansion joints to be
included with horizontal enclosure elements above as appropriate.
Associated Masterformat Sections: 07 20 00 / 07 26 00 / 07 62 00 / 07 65 00 / 07 71 13
07 71 16 / 07 71 19 / 07 71 29 / 09 28 00
See Fundamental LOD Definitions

B3060 / 21-02 30 60 / --
Horizontal Openings
Includes: Openings in horizontal enclosures including roofing and traffic bearing horizontal enclosures. Includes Horizontal Opening
Supplementary Components as appropriate.

B3060.10 / 21-02 30 60 10 / Ss 30 30 72
Roof Windows and Skylights
Includes: Operable and non-operable roof windows. Includes: Skylights without framing with plastic and glass glazing. Includes:
Skylights with framing.
Associated Masterformat Sections: 01 83 16 / 08 60 00 / 08 61 00 / 08 62 00 / 08 63 00
08 64 00 / 08 67 00
See B2020.10

B3060.50 / 21-02 30 60 50 / Ss 30 30
Vents and Hatches
Includes: Other roof openings such as roof hatches, smoke vents, and gravity roof ventilators.
Associated Masterformat Sections: 07 72 33 / 07 72 36
See B2070

B3060.90 / 21-02 30 60 90 / --
Horizontal Opening Supplementary Components
Includes: Frames, hardware, glazing, flashing, and joint sealants to be included with horizontal opening elements above as
appropriate.
Associated Masterformat Sections: 08 75 00 / 08 80 00 / 07 60 00 / 07 92 00
See General Notes: Supplementary Components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 72
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

B3080 / 21-02 30 80 / --
Overhead Exterior Enclosures
Includes: Exposed to weather construction under horizontal enclosure construction. Includes suspension and support systems,
insulation, vapor retarders, and air barriers.
Associated Masterformat Sections: 01 83 16
100 N/A
200 Inclusions:
• Overall scope
• thickness/depth of system.

B3080.10 / 21-02 30 80 10 / Ss 30 25 10 26
Exterior Ceilings
Associated Masterformat Sections: 07 42 00 / 07 44 00 / 09 20 00 / 09 54 00 / 09 56 00
09 90 00
100 N/A
200 See B3080
300 Inclusions:
• Overall assembly
• Structural backing.
• Location of expansion or control joints indicated,
but not modeled.
350 Inclusions:
• Face material.
• Structural backing members including
bracing/lateral framing/kickers.
• Expansion or control joints at accurate width.
400 Inclusions
• Connections

B3080.20 / 21-02 30 80 20 / Ss 30 25 10 28
Exterior Soffits
Associated Masterformat Sections: 07 42 93 / 07 44 00 / 08 95 13 / 09 20 00 / 09 54 00
09 56 00 / 09 90 00
See B3080.10

B3080.30 / 21-02 30 80 30 / --
Exterior Bulkheads
Associated Masterformat Sections: 07 42 00 / 07 44 00 / 09 20 00 / 09 54 00 / 09 56 00
09 90 00
See B3080.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 73
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C / 21-03 / --
INTERIORS

C10 / 21-03 10 / --
Interior Construction
Associated Masterformat Sections: 01 84 13

C1010 / 21-03 10 10 / Ss 25 10 30
Interior Partitions
Includes: Enclosures and partitions which are fixed and secured in place. Includes walls of concrete; and unit masonry; and wood and
metal stud partitions with associated wall surfaces. Includes partitions of an open nature, such as wire mesh partitions. Partitions may
be load bearing or non-load bearing. Includes Interior Partition Supplementary Components as appropriate.
Associated Masterformat Sections: 10 22 00 / 01 84 13

C1010.10 / 21-03 10 10 10 / Ss 25 10 30
Interior Fixed Partitions
Associated Masterformat Sections: 03 30 00 / 03 40 00 / 04 20 00 / 05 41 00 / 06 11 00 /
09 20 00 / 10 22 13
100 N/A
200 Inclusions
• Approximate overall wall thickness represented by a
single element.
• full vs. partial height not differentiated
300 Inclusions
• Composite model element at overall thickness
• Measurable individual layers (e.g. GWB, studs)
• locations, heights (full vs. partial height),
• Openings with any dimension greater than 6” (15 cm)
or as noted, at nominal dimensions

C1010.10.10 / 21-03 10 10 10 10 / Ss 25 13 50 56
Interior Wall (Masonry)

100 N/A

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 74
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See C1010.10

300 See C1010.10

350 Inclusions
• All penetrations at actual rough-opening dimensions.
• Any regions that would impact coordination with other
systems such as:
• Bond Beams & Lintels
• Jams

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 75
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions
• Individual masonry units
• Reinforcing
• dowels
• Grouting

C1010.10.20 / 21-03 10 10 10 20 / Ss 25 10 32 45
Interior Wall (Cold-Form Metal Framing)

100 N/A

200 See C1010.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 76
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 See C1010.10

350 Inclusions
• All studs
• Backing and blocking
• Elements necessary for detailed interface
coordination with other systems.
• All penetrations at actual rough-opening
dimensions.
• Diagonal bracing

C1010.10.30 / 21-03 10 10 10 30 / Ss 25 10 32 90
Interior Wall (Wood)

100 N/A
200 See C1010.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 77
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 See C1010.10

350 Inclusions
• All studs
• Backing and blocking
• Elements necessary for detailed interface
coordination with other systems.
• All penetrations at actual rough-opening
dimensions.
• Diagonal bracing

400 Inclusions
• sufficient detail to support prefabrication
• Openings and penetrations through studs
• Connections

C1010.20 / 21-03 10 10 20 / Ss 25 10 30
Interior Glazed Partitions
Includes: Partitions primarily composed of glazed elements that may be fabricated or field constructed. Includes Interior Partition
Supplementary Components as appropriate.
Associated Masterformat Sections: 08 43 00
100 N/A
200 See C1010.10
300 Inclusions
• Specified location and orientation of face of glass.
• Nominal face dimensions and thickness of glazing.
• Structural support systems.
• Spacing, location, size and orientation of mullions.
• Operable components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 78
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions
• Actual anchorage layouts and types.
• Connection points between glass and supporting
structure
• Actual panel dimensions (including seating).
400 Inclusions
• mullion extrusion profiles.

C1010.40 / 21-03 10 10 40 / Ss 25 12 65 75
Interior Demountable Partitions
Associated Masterformat Sections: 10 22 19 / 01 84 13 / 10 22 19.13 / 10 22 19.23 / 10 22 19.33
10 22 19.43 / 10 22 19.53
100 See C10
200 Inclusions
• Approximate overall wall thickness represented by a
single element.
• Indication that it is a demountable partition (Uniformat
number, name, etc.)
300 Inclusions
• Element envelopes of individual panels
• Space reservation for support system
350 Inclusions:
• Attachment points to support system
400 Inclusions
• See Fundamental LOD Definitions

C1010.50 / 21-03 10 10 50 / Ss 25 12 70
Interior Operable Partitions
Includes: Track-supported, operable panels and partitions, top hung and floor supported, and manually and power operated. Includes
auditorium partitions and dividers. Includes overhead supports.
Associated Masterformat Sections: 01 84 13 / 01 84 13 / 10 22 33 / 10 22 36 / 10 22 39
10 22 43
100 See C10
200 Inclusions
• Approximate overall wall thickness represented by a
single element.
• Indication that it is an operable partition (Uniformat
number, name, etc.)

300 Inclusions
• Element envelopes of individual panels
• Space reservation for support system, storage pocket,
operating mechanisms
• Clearances for swing radii
350 Inclusions:
• Attachment points to support system
400 Inclusions
• See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 79
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1010.70 / 21-03 10 10 70 / Ss 25 50 75
Interior Screens
Portable and open dividers.
Associated Masterformat Sections: 10 22 23 / 10 82 23
See C1010.40

C1010.90 / 21-03 10 10 90 / --
Interior Partitions Supplementary Components
Sound isolation components, firestopping, and expansion control to be included with interior partition elements above as appropriate.
Associated Masterformat Sections: 13 48 00 / 09 81 00 / 07 84 00 / 07 95 00
See General Notes: Supplementary Components

C1020 / 21-03 10 20 / Ss 25 30 95 41
Interior Windows
Includes: Interior fixed or operable windows used singly and in multiples. Includes Interior Window Supplementary Components as
appropriate. Includes metal, wood, plastic, and composite window units.
Associated Masterformat Sections: 08 50 00 / 01 84 13
100 See C10
200 Inclusions
• Generic window objects

C1020.10 / 21-03 10 20 10 / Ss 25 30 95 41
Interior Operating Windows
Includes: Interior fixed or operable windows used singly and in multiples. Includes Interior Window Supplementary Components as
appropriate. Includes metal, wood, plastic, and composite window units.
Associated Masterformat Sections: 08 50 00
100 N/A
200 See C1020
300 Inclusions:
• specific type and size
• Direction of opening
350 Inclusions:
• Attachment elements of window to structure
400 Inclusions:
• Detailed frame extrusion profiles
• Fasteners

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 80
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1020.20 / 21-03 10 20 20 / Ss 25 30 95 41
Interior Fixed Windows
Includes: Interior fixed or operable windows used singly and in multiples. Includes Interior Window Supplementary Components as
appropriate. Includes metal, wood, plastic, and composite window units.
Associated Masterformat Sections: 08 50 00
See C1020.1010

C1020.50 / 21-03 10 20 50 / Ss 25 30 95 41
Interior Special Function Windows
Includes interior windows with special characteristics for a special function.
Associated Masterformat Sections: 08 56 00 / 08 56 19 / 08 56 46 / 08 56 49 / 08 88 49 /
08 56 53 / 08 88 53 / 08 88 56 / 08 56 63 / 08 56 73
See B2020.10

C1020.90 / 21-03 10 20 90 / Ss 25 30 95 41
Interior Window Supplementary Components
Includes: Frames, sills, operating hardware, glazing to be included with interior window elements above as appropriate.
Associated Masterformat Sections: 08 75 00 / 08 80 00
See General Notes: Supplementary Components

C1030 / 21-03 10 30 / Ss 25 30 20 25
Interior Doors
Includes: Interior door assemblies. Includes metal doors and frames, wood doors and frames, plastic doors, and composite doors.
Includes Interior Door Supplementary Components as appropriate.
Associated Masterformat Sections: 08 10 00 / 01 84 13
See B2050.10

C1030.10 / 21-03 10 30 10 / Ss 25 30 20 25
Interior Swinging Doors
Includes: Interior door assemblies. Includes metal doors and frames, wood doors and frames, plastic doors, and composite doors.
Includes Interior Door Supplementary Components as appropriate.
Associated Masterformat Sections: 08 10 00
See B2050.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 81
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1030.20 / 21-03 10 30 20 / Ss 25 30 20 25
Interior Entrance Doors
Includes: Exterior personnel door assemblies at interior main entrances. Includes automatic, revolving, balanced, and other special
operating entrance doors, and sliding storefront wall systems. Includes Interior Door Supplementary Components as appropriate when
not part of storefront system.
Associated Masterformat Sections: 08 42 00 / 08 42 26 / 08 42 29 / 08 42 33 / 08 42 36
08 43 29
[See B2050.10]

C1030.25 / 21-03 10 30 25 / Ss 25 30 20 77
Interior Sliding Doors
Associated Masterformat Sections: 08 11 73 / 08 32 00
100 N/A

200 See B2050

300 See B2050

350 Inclusions
• jambs
• Thresholds
• Operation and mechanism element envelopes
• Track
• Connections and interfaces

400 Inclusions TBD

C1030.30 / 21-03 10 30 30 / Ss 25 30 20 78
Interior Folding Doors
Associated Masterformat Sections: 08 35 13
[See C1030.25]

C1030.40 / 21-03 10 30 40 / Ss 25 30 20 74
Interior Coiling Doors
Associated Masterformat Sections: 08 33 00 / 08 33 13
100 N/A
200 See C2050.10
300 Inclusions
• Element envelopes of individual panels
• Space reservation for support system, storage pocket,
operating mechanisms
• Clearances for swing radii

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 82
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Attachment points for support system
• Support system
• Storage pocket
• Operating mechanism

400 Inclusions
• connections and interfaces
• brackets, supports,
• sealants,
• thresholds.

C1030.50
Interior Panel Doors
Includes: Interior large opening doors constructed of panels that move.
Associated Masterformat Sections: 08 36 00 / 08 36 13 / 08 36 16 / 08 36 19 / 08 36 23
[See C1030.40]

C1030.70 / 21-03 10 30 70 / Ss 25 30 20 25
Interior Special Function Doors
Includes: Interior door assemblies for a variety of special functions and applications involving a variety of operating methods. Includes
Interior Door Supplementary Components as appropriate.
Associated Masterformat Sections: 08 30 00. / 08 34 13 / 08 34 19 / 08 34 33 / 08 34 36
08 34 46 / 08 34 49 / 08 88 49 / 08 34 53 / 08 42 33.13 / 08 88 53 / 08 88 56 / 08 34 59
08 34 63 / 08 34 73 / 08 38 00 / 08 39 00
[See C1030.40]

C1030.80 / 21-03 10 30 80 / Ss 25 30 20 35
Interior Access Doors and Panels
Includes: Doors and panels in walls, ceilings, and floors to provide access to concealed spaces. Includes frames and hardware.
Associated Masterformat Sections: 08 31 00
[See B2050]

C1030.90 / 21-03 10 30 90 / Ss 25 30 20 25
Interior Door Supplementary Components
Includes: Frames, hardware, glazing, and louvers that are part of door to be included with interior door elements above as appropriate.
Associated Masterformat Sections: 08 10 00 / 08 30 00 / 08 71 00 / 08 80 00 / 08 91 26
See General Notes: Supplementary Components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 83
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1040 / 21-03 10 40 / --
Interior Grilles and Gates
Includes: Interior operable grilles and gates Includes frames and hardware.

C1040.10 / 21-03 10 40 10 / Ss 25 50 35
Interior Grilles
Associated Masterformat Sections: 08 11 74 / 08 33 00 / 08 35 16
See B2050.10

C1040.50 / 21-03 10 40 50 / Ss 25 32 35
Interior Gates
Includes: Interior devices of solid or open construction, usually hinged, to provide moveable barrier for access through partition or other
divider. Includes hardware, accessories, and finishing.
Associated Masterformat Sections: 08 34 56 / 10 22 16
[See B2050.10

C1060 / 21-03 10 60 / Ss 30 20 70
Raised Floor Construction
Associated Masterformat Sections: 01 84 13 / 01 84 13 / 01 84 13 / 01 84 13 / 01 84 13
01 84 13 / 01 84 13 / 01 84 13 / 01 84 13

C1060.10 / 21-03 10 60 10 / Ss 30 20 70 70
Access Flooring
Includes: Free-standing, elevated accessible floor assembly forming an underfloor cavity that may be used for utility or other purposes.
Associated Masterformat Sections: 09 69 00
100 N/A
200 Inclusions:
Floor level
300 Inclusions
Floor element
Access panels
350 Inclusions:
Locations of vertical supports

C1060.30 / 21-03 10 60 30 / Ss 30 12 64
Platform/Stage Floors
Includes: Fixed construction of raised floor for platforms or stages.
[See B1010]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 84
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1070 / 21-03 10 70 / --
Suspended Ceiling Construction
Includes: Ceiling Suspension Components.
Associated Masterformat Sections: 01 84 13 / 01 84 13
100 N/A
200 Inclusions:
Element envelope

C1070.10 / 21-03 10 70 10 / Ss 30 25 22 1
Acoustical Suspended Ceilings
Includes: Suspended tiles and panels with specific characteristics for acoustical purposes.
Associated Masterformat Sections: 09 51 00 / 09 81 00
100 See C1070
200 See C1070
300 Inclusions:
• System thickness.
• Changes in ceiling system indicated
• expansion or control joints shown as linework or
modeled.
• Ceiling grid shown as linework.
350 Inclusions:
• Ceiling suspension grid.
• Insulation
• Openings with any dimension greater than 6” (15 cm)
or as noted
• Hangers and kickers.
• Expansion or control joints at accurate width.

C1070.20 / 21-03 10 70 20 / Ss 30 25 10 10
Suspended Plaster and Gypsum Board Ceilings
Includes: Suspended assemblies with plaster and gypsum board surfaces.
Associated Masterformat Sections: 09 20 00 / 09 22 26 / 09 81 00
100 See C1070
200 See C1070
300 Inclusions:
• Overall system thickness including framing.
• Bulkheads
• Openings with any dimension greater than 6” (15 cm)
or as noted
350 Inclusions
• Framing and bracing elements.
• Insulation
• expansion or control joints shown as linework or
modeled.
400 Inclusions:
• All assembly components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 85
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1070.50 / 21-03 10 70 50 / Ss 30 25 22
Specialty Suspended Ceilings
Includes: Suspended specialty ceiling panels, units, and materials manufactured as finished
Associated Masterformat Sections: 09 54 00 / 09 56 00
[See C1070.10 or C1070.20]

C1070.70 / 21-03 10 70 70 / Ss 30 25 22
Special Function Suspended Ceilings
Includes: Suspended ceiling assemblies with an additional special function including integrated ceiling assemblies.
Associated Masterformat Sections: 09 57 00 / 09 57 53 / 09 58 00
[See C1070.10 or C1070.20]

C1070.90 / 21-03 10 70 90 / Ss 30 25 22
Ceiling Suspension Components
Includes: Hangers and framing to suspend ceiling and sound isolation components to be included with suspended ceiling construction
elements above as appropriate.
Associated Masterformat Sections: 13 48 00
See C1070.10 or C1070.20 for hanger requirements

C1090 / 21-03 10 90 / --
Interior Specialties

C1090.10 / 21-03 10 90 10 / Ss 25 15 60 35
Interior Railings and Handrails
Includes: Complete interior railing assemblies of various types including glazed railings.
Associated Masterformat Sections: 01 84 00 / 01 84 00 / 01 84 00 / 01 84 00 / 05 52 00
05 73 00 / 06 43 16 / 06 63 00 / 06 81 00
100 N/A
200 Inclusions:
• Element envelope
300 Inclusions
• Individual members (e.g., uprights and longitudinal)
350 Inclusions
• Attachment points
400 Inclusions
• All assembly components including fasteners and
supports.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 86
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1090.15 / 21-03 10 90 15 / Ss 25 50 45 45
Interior Louvers
Includes: Interior louvers, and other items for ventilation which are not an integral part of the mechanical system. Includes operable and
stationary louvers.
Associated Masterformat Sections: 08 91 00 / 01 84 00
100 Inclusions
• symbol

200 Inclusions
• Generic model element

300 Inclusions
• element envelope

350 Inclusions
• vanes

C1090.20 / 21-03 10 90 20 / Ss 40 25 26
Information Specialties
Includes: Visual display units, display cases, directories, interior signage, telephone specialties, and informational kiosks.
Associated Masterformat Sections: 10 10 00 / 10 11 00 / 10 11 13 / 10 11 16 / 10 11 23
10 11 33 / 10 11 36 / 10 11 39 / 10 11 43 / 10 11 46 / 10 12 00 / 10 13 00 / 10 14 00 10 17 00 / 10 18 00

C1090.25 / 21-03 10 90 25 / Ss 25 12 60 60
Compartments and Cubicles
Includes: Manufactured compartments and cubicles for specific purposes. Includes toilet compartments, shower stalls, etc.
Associated Masterformat Sections: 10 21 00 / 10 21 13 / 10 21 16 / 10 21 23 / 10 28 19

C1090.30 / 21-03 10 90 30 / Ss 25 12 65
Service Walls
Includes: Wall assemblies and wall-mounted units incorporating services.
Associated Masterformat Sections: 10 25 00 / 10 25 13 / 10 25 16
[See C1010.10]

C1090.35 / 21-03 10 90 35 / Pr 35 90 43
Wall and Door Protection
Includes: Manufactured protective devices for walls and doors. Includes corner guards, bumper guards, and protective wall covering.
Associated Masterformat Sections: 10 26 00 / 10 26 13 / 10 26 16 / 10 26 23 / 10 26 33

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 87
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C1090.40 / 21-03 10 90 40 / Pr 40 20 76
Toilet, Bath and Laundry Accessories
Includes: Manufactured items for use in conjunction with toilets, baths, and laundries.
Associated Masterformat Sections: 10 28 00 / 10 28 13 / 10 28 16 / 10 28 23

C1090.45 / 21-03 10 90 45 / Ss 70 80 33
Interior Gas Lighting
Associated Masterformat Sections: 10 84 16

C1090.50 / 21-03 10 90 50 / Pr 70 60 82
Fireplaces and Stoves
Includes: Masonry fireplaces and manufactured and fabricated fireplaces, stoves, chimneys, dampers, and specialties for use in
construction of fireplaces and stove units.
Associated Masterformat Sections: 10 30 00 / 04 50 00 / 04 57 00 / 10 31 00 / 10 31 13
10 32 00 / 10 35 00

C1090.60 / 21-03 10 90 60 / Ss 75 50
Safety Specialties
Includes: Accessories that provide emergency aid.
Associated Masterformat Sections: 10 40 00 / 10 41 00 / 10 43 00

C1090.70 / 21-03 10 90 70 / Pr 40 30 78
Storage Specialties
Includes: Lockers, postal specialties, storage specialties, and wardrobe and closet specialties.
Associated Masterformat Sections: 10 50 00 / 10 51 00 / 10 51 53 / 10 55 00 / 10 55 23 / 10 55 91 / 10 56 00 / 10 56 29 / 10
56 33 / 10 57 00 / 10 57 13 / 10 57 33

C1090.90 / 21-03 10 90 90 / Ss 40
Other Interior Specialties
Includes: Pest control devices, flags and banners, security mirrors and domes, and scales.
Associated Masterformat Sections: 10 80 00 / 10 81 00 / 10 81 16 / 10 81 19 / 10 83 00 / 08 83 00 / 10 86 00 / 10 88 00

C20 / 21-03 20 / Ss 25 45
Interior Finishes
Associated Masterformat Sections: 01 84 19
100 N/A

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 88
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 Inclusions
• Area defined
300 Inclusions
• Thickness if greater than ¼” (6 mm) or as noted
350 Inclusions:
• Measurable individual layers (e.g. grout and tile for
mudset tile)

C2010 / 21-03 20 10 / Ss 25 45
Wall Finishes
Includes: Wall finishes applied over solid substrates. Includes Wall Finish Supplementary Components as appropriate.
Associated Masterformat Sections: 09 70 00 / 01 84 19 / 01 84 19 / 01 84 19 / 01 84 19 / 01 84

C2010.10 / 21-03 20 10 10 / Ss 25 45 88
Tile Wall Finish
Includes: Manufactured surfacing units of impervious, vitreous, semi-vitreous, and non-vitreous materials; glazed, unglazed,
conductive, and textured surfaces.
Associated Masterformat Sections: 09 30 00
See C20

C2010.20 / 21-03 20 10 20 / Ss 25 25
Wall Paneling
Includes: Covering or cladding of interior walls with paneling. Includes associated furring, fastening, and trim.
Associated Masterformat Sections: 06 42 00 / 06 25 00 / 06 26 00 / 06 64 00 / 06 83 00
See C20

C2010.30 / 21-03 20 10 30 / Ss 25 45 74
Wall Coverings
Includes: Wall coverings applied over solid substrates. Includes vinyl-coated fabric, vinyl and cork wall coverings; wall papers; and
flexible wood sheets.
Associated Masterformat Sections: 09 72 00 / 09 74 00
See C20

C2010.35 / 21-03 20 10 35 / Ss 25 45 74
Wall Carpeting
Includes: Wall carpet materials and accessories.
Associated Masterformat Sections: 09 73 00
See C20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 89
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C2010.50 / 21-03 20 10 50 / Ss 25 20 85
Stone Facing
Includes: Natural stone applied as an interior veneer surface.
Associated Masterformat Sections: 09 75 00
See C20

C2010.60 / 21-03 20 10 60 / Ss 25 45
Special Wall Surfacing
Includes: Manufactured decorative interior wall surface products including plastic blocks.
Associated Masterformat Sections: 09 77 00 / 09 77 13 / 09 77 23 / 09 76 00
See C20

C2010.70 / 21-03 20 10 70 / Ss 40 90 60
Wall Painting and Coating
Includes: Interior painting and coating with transparent and opaque finishes. Includes stains, varnishes, lacquers, primers, fillers, paint
removers, and waxes, and preparation of surfaces.
Associated Masterformat Sections: 09 90 00
See C20

C2010.80 / 21-03 20 10 80 / Ss 25 45 02
Acoustical Wall Treatment
Includes: Sound absorbing, reflecting, and diffusing wall units, and accessories.
Associated Masterformat Sections: 09 83 13 / 09 84 00 / 09 84 33
See C20

C2010.90 / 21-03 20 10 90 / Ss 25 45
Wall Finish Supplementary Components
Includes: Furring to be included with wall finish elements above as appropriate.
Associated Masterformat Sections: 06 10 00 / 09 22 13
See General Notes: Supplementary Components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 90
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C2020 / 21-03 20 20 / Ss 25 25 45
Interior Fabrications
Includes: Interior fabrications of a variety of materials formed to various profiles for a variety of purposes including column covers.
Associated Masterformat Sections: 03 49 00 / 05 50 00 / 05 58 13 / 05 70 00 / 06 44 00 / 06 60 00 / 06 61 00 / 06 80 00 / 09
27 00
For drywall fabrications see C1010.10
For all others See Fundamental LOD Definitions

C2030 / 21-03 20 30 / Ss 30 42
Flooring
Includes: Flooring Supplementary Components as appropriate.
Associated Masterformat Sections: 09 60 00 / 01 84 19
See C20

C2030.10 / 21-03 20 30 10 / Ss 30 42
Flooring Treatment
Includes: Coatings and surfacings for finished floor, applied to provide a specific performance characteristic.
Associated Masterformat Sections: 09 61 00 / 09 61 13
See C20

C2030.20 / 21-03 20 30 20 / Ss 30 42 32 40
Tile Flooring
Includes: Manufactured surfacing units of impervious, vitreous, semi-vitreous, and non-vitreous materials; glazed, unglazed,
conductive, abrasive, and textured surfaces. Includes wall base units.
Associated Masterformat Sections: 09 30 00
See C20

C2030.30 / 21-03 20 30 30 / Ss 30 42
Specialty Flooring
Includes: Heavy duty and other specialty flooring. Includes asphaltic plank, laminate, bamboo, leather, cork, acoustic, synthetic turf,
metal, structural glass, chemical-resistant, acid resistant, conductive, and static control flooring.
Associated Masterformat Sections: 09 62 00 / 09 35 00 / 09 63 13.35 / 09 62 35 / 09 33 00 / 09 65 33 / 09 66 33 / 09 61 36 /
09 65 36
See C20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 91
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C2030.40 / 21-03 20 30 40 / Ss 30 42 50
Masonry Flooring
Includes: Fired clay unit masonry, cat stone, and stone flooring. Includes wall base.
Associated Masterformat Sections: 09 63 00 / 09 63 13 / 09 63 40 / 09 63 43
See C20

C2030.45 / 21-03 20 30 45 / Ss 30 20 90
Wood Flooring
Includes: Strip, parquet, block, and composition wood flooring.
Associated Masterformat Sections: 09 64 00
See C20

C2030.50 / 21-03 20 30 50 / Ss 30 42 72 72
Resilient Flooring
Includes: Resilient tile and sheet flooring. Includes integral and applied wall bases.
Associated Masterformat Sections: 09 65 00
See C20

C2030.60 / 21-03 20 30 60 / Ss 30 42 90 90
Terrazzo Flooring
Includes: Cast-in-place, sand-cushion, monolithic, bonded and adhesively- bonded portland cement terrazzo; poured-in-place epoxy,
polyester, and resinous matrix terrazzo; and precast terrazzo. Includes integral or precast wall bases, accessories, and finish sealers.
Associated Masterformat Sections: 09 66 00 / 09 66 13 / 09 66 16 / 09 66 23
See C20

C2030.70 / 21-03 20 30 70 / Ss 30 42 54 75
Fluid-Applied Flooring
Includes: Flooring applied in a viscous state.
Associated Masterformat Sections: 09 67 00 / 09 67 13 / 09 67 16 / 09 67 19 / 09 67 23 / 09 67 26
See C20

C2030.75 / 21-03 20 30 75 / Ss 30 42 72
Carpeting
Includes: Floor carpet materials including cushions, accessories, and wall base.
Associated Masterformat Sections: 09 68 00 / 09 68 13 / 09 68 16
See C20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 92
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C2030.80 / 21-03 20 30 80 / Ss 30 20 95 15
Athletic Flooring
Includes: Flooring for athletic purposes.
Associated Masterformat Sections: 09 64 66 / 09 65 66 / 09 67 66
See C20

C2030.85 / 21-03 20 30 85 / Ss 30 60 30 26
Entrance Flooring
Includes: Special floor surfaces at entrances.
Associated Masterformat Sections: 12 48 13 / 12 48 16 / 12 48 19 / 12 48 23 / 12 48 26
See C20

C2030.90 / 21-03 20 30 90 / Pr 35 90 31
Floor Supplementary Components
Includes: Furring, underlayment, and sound and vibration control to be included with flooring elements above as appropriate.
Associated Masterformat Sections: 06 10 00 / 06 16 26 / 09 60 13 / 09 62 48
See General Notes: Supplementary Components

C2040 / 21-03 20 40 / Ss 35 40
Stair Finishes
Includes: Stair tread, riser, and landing finish of various materials.
Associated Masterformat Sections: 01 84 19
See C20

C2040.20 / 21-03 20 40 20 / Ss 35 40
Tile Stair Finish
See C20

C2040.40 / 21-03 20 40 40 / Ss 35 40
Masonry Stair Finish
See C20

C2040.45 / 21-03 20 40 45 / Ss 35 40
Wood Stair Finish
See C20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 93
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C2040.50 / 21-03 20 40 50 / Ss 35 40
Resilient Stair Finish
See C20

C2040.60 / 21-03 20 40 60 / Ss 35 40
Terrazzo Stair Finish
See C20

C2040.75 / 21-03 20 40 75 / Ss 35 40 82
Carpeted Stair Finish
See C20

C2050 / 21-03 20 50 / Ss 30 47
Ceiling Finishes
Includes: Finishes applied to interior ceiling substrates. Ceiling finishes may be applied to suspended ceiling construction. Includes
Ceiling Finish Supplementary Components as appropriate.
See C20

C2050.10 / 21-03 20 50 10 / Ss 30 25 10
Plaster and Gypsum Board Finish
See C20

C2050.20 / 21-03 20 50 20 / Ss 30 25 10
Ceiling Paneling
See C20

C2050.70 / 21-03 20 50 70 / Ss 40 90 60
Ceiling Painting and Coating
See C20

C2050.80 / 21-03 20 50 80 / Ss 30 25 22 1
Acoustical Ceiling Treatment
See C20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 94
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

C2050.90 / 21-03 20 50 90 / Ss 30 47
Ceiling Finish Supplementary Components
See General Notes: Supplementary Components

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 95
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D / 21-04 00 00 / --
SERVICES
Associated Masterformat Sections: 01 86 00

D10 / 21-04 10 / Ss 80 20
Conveying
Associated Masterformat Sections: 01 85 00 / 14 00 00
100 Inclusions:
• Schematic model elements.
• indication of entry and exit points

D1010 / 21-04 10 10 / Ss 80 50
Vertical Conveying Systems

D1010.10 / 21-04 10 10 10 / Ss 80 50 60 26
Elevators
Includes: Passenger and freight elevators of all types, including cars, enclosures, controls, safety equipment, hoist way equipment, and
elevator machinery. Includes associated metal fabrications including pit ladders.
Associated Masterformat Sections: 01 85 00 / 14 20 00 / 14 21 13 / 14 21 23 / 14 21 33
14 21 43 / 14 24 13 / 14 24 23 / 14 24 33 / 14 24 43 / 14 26 00 / 14 27 00 / 14 28 00
100 See D10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 96
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 Inclusions
• Assumed envelope of shaft
• Pit
• Location and nominal size of all stops and doors
• Specify conveyance type (e.g., hydraulic vs. traction
elevator)
• Specify what is being conveyed (e.g., people vs.
freight)
• Location of elevator machine

300 Inclusions
• Pathway envelope of moving parts (e.g., cab,
counterweight), including required clearances
• system elements(e.g., tracks)
• Pits, control rooms, machine rooms, and associated
equipment if applicable.
• Major structural support elements (e.g., elevator
beam).

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 97
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Connections: mechanical and/or electrical services.
• connection points between elevator components and
building structure
• Sizing adjusted to the actual manufacturer
specifications.
• Guiding tracks/rails
• Service/access zones

400 Inclusions
• All connections, supports, framing, and other
supplementary components.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 98
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D1010.20 / 21-04 10 10 20 / Ss 80 50 60
Lifts
Includes: Vertical or inclined lifts and related equipment for a variety of purposes. Sidewalk lifts include doors.
Associated Masterformat Sections: 01 85 00 / 14 40 00 / 14 41 00 / 14 42 00 / 14 43 00
14 43 13 / 14 43 16 / 14 44 00 / 14 45 00
See D1010.10

D1010.30 / 21-04 10 10 30 / Ss 80 20 62 28
Escalators
Includes: Passenger conveying systems composed of moving treads installed in inclined position including associated components,
hardware, controls, safety equipment, and related items.
Associated Masterformat Sections: 01 85 00 / 14 31 00
100 See D10
200 Inclusions:
• Element envelope
300 Inclusions
• Balustrade
• Clear Egress Zones
350 Inclusions:
• Connections to services (e.g., mechanical, electrical).
• connection points between elevator components and
building structure
• Modeled actual manufacturer dimensions.
• Guiding tracks/rails
• Service/access zones
• Fixing points of truss

D1010.50 / 21-04 10 10 50 / Ss 80 50 60 50
Dumbwaiters
Includes: Packaged and field assembled, motorized and hand- operated dumbwaiters including associated components for book lifts,
cart lifts, and other applications. Systems include associated components, hardware, controls, and safety equipment.
Associated Masterformat Sections: 01 85 00 / 14 10 00
[See D1010.10]

D1010.60 / 21-04 10 10 60 / Ss 80 20 62
Moving Ramps
Includes: Passenger conveying systems composed of moving belts installed in inclined position including associated components,
hardware, controls, safety equipment, and related items.
Associated Masterformat Sections: 01 85 00 / 14 33 00

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 99
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D1030 / 21-04 10 30 / Ss 80 20 62
Horizontal Conveying
Associated Masterformat Sections: 01 85 00
100 [See D10]
200 Inclusions:
• Generic representation of the material handling system
envelope, including critical path of travel zones
• Specify conveyance type
• Specify what is being conveyed
300 Inclusions:
• Specific system elements modeled by type, including
all path of travel zones. Including:
• Clear Egress Zones
• Structural Clearance zones
• Material path clearance zones
350 Inclusions:
• Service/access zones
• Modeled at actual manufacturer dimensions.
• Fixing points of truss

D1030.10 / 21-04 10 30 10 / Ss 80 20 62 53
Moving Walks
Includes: Passenger conveying systems composed of moving belts installed in horizontal position including associated components,
hardware, controls, safety equipment, and related items.
Associated Masterformat Sections: 01 85 00 / 14 32 00
[See D1030]

D1030.30 / 21-04 10 30 30 / Ss 80 80
Turntables
Includes: Structural turntables for various applications.
Associated Masterformat Sections: 01 85 00 / 14 70 00 / 14 71 00 / 14 71 11 / 14 72 00
14 72 25 / 14 73 00 / 14 73 59 / 14 74 00 / 14 74 61
[See D1030]

D1030.50 / 21-04 10 30 50 / Ss 80 90 05 60
Passenger Loading Bridges
Includes: Operating bridges for loading and unloading of passengers to and from aircraft and ships.
Associated Masterformat Sections: 01 85 00 / 34 77 13
[see D1030]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 100
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D1030.70 / 21-04 10 30 70 / Ss 80 20 62
People Movers
Includes: Single rail vehicles suspended from or straddle the guideway. Includes associated track, equipment, controls, and
accessories. Includes: Steep cable railways in which ascending cars counterbalance descending cars. Includes associated track,
cable. Includes: Steep slope transportation system utilizing moving cable. Includes associated cable, support structures, equipment,
controls, and accessories.
Associated Masterformat Sections: 01 85 00 / 34 12 00 / 34 13 00 / 34 14 00
[see D1030]

D1050 / 21-04 10 50 / Ss 80 20 10
Material Handling
Associated Masterformat Sections: 01 85 00
100 See D10
200 Inclusions:
• Generic representation of the material handling system
envelope, including critical path of travel zones
• Specify conveyance type
• Specify what is being conveyed
300 Inclusions:
• Specific system elements modeled by type, including
all path of travel zones. Including:
• Clear Egress Zones
• Structural Clearance zones
• Material path clearance zones
350 Inclusions:
• Sizing adjusted to the actual manufacturer
specifications.
• Fixing points of truss
• Service/access zones
400 Inclusions:
• All connections, supports, framing, and other
supplementary components.

D1050.10 / 21-04 10 50 10 / Ss 80 30 15
Cranes
Includes: Hoisting towers, cranes, crane rails, and related accessories.
Associated Masterformat Sections: 41 22 13
100 See D10
200 Inclusions:
• Envelope of zone of operation
300 Inclusions:
• Specific system elements
• Structural support elements.
• Guiding tracks and rails

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 101
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Sizing adjusted to the actual manufacturer
dimensions.
• Service and access zones
• Connections to mechanical or electrical services

D1050.20 / 21-04 10 50 20 / Ss 80 30 40
Hoists
Includes: Manual and motor operated hoists and related accessories.
Associated Masterformat Sections: 41 22 23
[See D1050.10]

D1050.30 / 21-04 10 50 30 / Ss 80 30 20
Derricks
Includes: Manual and motor operated derricks and related accessories.
Associated Masterformat Sections: 41 22 33
[See D1050.10]

D1050.40 / 21-04 10 50 40 / Ss 80 20
Conveyors
Includes: Automatic guided vehicles, conveyors, diverters, and chutes. Includes controls and accessories.
Associated Masterformat Sections: 41 21 00
[See D1050.10]

D1050.50 / 21-04 10 50 50 / Ss 80 20 06
Baggage Handling Equipment
Includes: Operating equipment for handling, scanning, and weighing of baggage at terminals. Includes controls and accessories.
Associated Masterformat Sections: 34 77 16
[see D5010.10]

D1050.60 / 21-04 10 50 60 / Ss 37 14
Chutes
Includes: Chutes which support the operation of the building or structure.
Associated Masterformat Sections: 14 91 00 / 14 91 13 / 14 91 23 / 14 91 33 / 14 91 82
[see D5010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 102
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D1050.70 / 21-04 10 50 70 / Ss 80 20 65
Pneumatic Tube Systems
Includes: Pneumatically operated tube system for the delivery of small items within a facility. Includes controls and accessories.
Associated Masterformat Sections: 14 92 00
100 Inclusions:
• Diagrammatic elements or quantitative call outs;
• Conceptual and/or schematic flow diagrams;

200 Inclusions:
• Generic elements;
• layout with approximate size, shape, and location of
equipment and tubing;

300 Inclusions:
• design-specified elements;
• Specified size, shape, spacing, and location of
equipment and tubing;

350 Inclusions:
• actual size, shape, spacing, and location/connections
of equipment and tubing;
• actual size, shape, spacing, and clearances of all
hangers, supports, vibration and seismic control
• floor and wall penetrations.
• Service/access zones.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 103
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation

D1080 / 21-04 10 80 / Ss 80 30 25
Operable Access Systems
Associated Masterformat Sections:
See Fundamental LOD Definitions

D1080.10 / 21-04 10 80 10 / Ss 80 30 25 0
Suspended Scaffolding
Includes: Suspended scaffolding when part of the completed project.
Associated Masterformat Sections: 14 81 00
See Fundamental LOD Definitions

D1080.20 / 21-04 10 80 20 / Ss 80 30 25
Rope Climbers
Includes: Powered rope climbers to access exterior façade.
Associated Masterformat Sections: 14 82 00
See Fundamental LOD Definitions

D1080.30 / 21-04 10 80 30 / Ss 80 30 25 0
Elevating Platforms
Includes: Fixed elevating platforms to provide a movable elevated working platform for people and materials.
Associated Masterformat Sections: 14 83 00
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 104
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D1080.40 / 21-04 10 80 40 / Ss 80 30 25
Powered Scaffolding
Includes: Powered scaffolding when part of the completed project.
Associated Masterformat Sections: 14 84 00 / 14 84 13
See Fundamental LOD Definitions

D1080.50 / 21-04 10 80 50 / Ss 80 30 25
Building Envelope Access
Associated Masterformat Sections: 11 24 23
See Fundamental LOD Definitions

D20 / 21-04 20 / --
Plumbing
Associated Masterformat Sections: 01 86 16 / 22 00 00
100 Inclusions:
• Diagrammatic or schematic elements;

D2010 / 21-04 20 10 / Ss 55 70 38
Domestic Water Distribution
Includes: Facility domestic water distribution system. Include Domestic Water Distribution Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 16 / 22 11 00
100 See D20
200 Inclusions:
• Schematic layout of generic model elements with
approximate size, shape, and location of elements;

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 105
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2010.10 / 21-04 20 10 10 / Ss 55 15 65
Facility Potable-Water Storage Tanks
Includes: Tanks for storage of potable water serving a facility and located within, on, under, or closely associated with a structure.
Associated Masterformat Sections: 22 12 00
100 See D20

200 Inclusions:
• layout with approximate size, shape, and location
300 Inclusions:
• Design-specified size, shape, spacing, and location
• Access/code clearance requirements
• Approximate allowances for clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of tanks(s) are
modeled or accommodated by model checking
software;

350 Inclusions:
• Actual construction elements size and shape,
spacing, and location/connections of tank(s)
• Actual size and shape, spacing, and clearances
required for all specified anchors, supports, vibration
and seismic control that are utilized in the layout of
tanks(s) are modeled or accommodated by model
checking software.

400 Inclusions:
• Supplementary components required for fabrication
and field installation.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 106
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2010.20 / 21-04 20 10 20 / Ss 55 70 38
Domestic Water Equipment
Includes: Equipment for domestic water distribution system. Includes: Equipment for the softening of domestic water. Includes:
Equipment for the filtering of domestic water. Includes: Equipment to heat domestic water. Includes electric and fuel-fired equipment.
Includes: Equipment to heat domestic water by means of heat exchange.
Associated Masterformat Sections: 22 11 23 / 22 31 00 / 22 32 00 / 22 33 00 / 22 34 00
22 35 00
100 See D20

200 Inclusions:
• Schematic layout with approximate size, shape, and
location

300 Inclusions:
• Design-specified size, shape, spacing, and location of
equipment;
• Approximate allowances for clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual construction elements size, shape, spacing,
and location/connections
• Actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout of
equipment.
• Actual access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 107
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 See D2010.10

D2010.40 / 21-04 20 10 40 / Ss 55 70 38
Domestic Water Piping
Includes: Piping, valves, and specialties associated with domestic water distribution located within, under, or closely associated with a
structure. Includes circulating pumps. May Include: Water service from the structure to the utility water service line.
Associated Masterformat Sections: 22 11 16 / 22 11 19
100 Inclusions:
• Diagrammatic or schematic elements;
• Conceptual and/or schematic flow diagrams;

200 Inclusions:
• Schematic layout with approximate size, shape, and
location of mains and risers;

300 Inclusions:
• Design-specified size, shape, spacing, and location of
pipe, valves, fittings, and insulation for risers, mains,
and branches;
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all risers,
mains, and branches;
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 108
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
•Actual construction elements;
•Actual size, shape, spacing, and location/connections
of pipe, valves, fittings, and insulation for risers,
mains, and branches;
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all risers, mains, and
branches;
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled.
400 See D2010.10

D2010.60 / 21-04 20 10 60 / Ss 40 15 75
Plumbing Fixtures
Includes: Terminal devices on the domestic water plumbing system. Includes rough-in piping, trim, fittings, and connection to vent
piping.
Associated Masterformat Sections: 22 40 00 / 22 41 00 / 22 41 13 / 22 41 16 / 22 41 19
22 41 23 / 22 41 26 / 22 41 36 / 22 41 39 / 22 42 00 / 22 42 13 / 22 42 16 / 22 42 19
22 42 23 / 22 42 26 / 22 42 29 / 22 42 33 / 22 42 36 / 22 42 39 / 22 42 43 / 22 43 00
22 43 13 / 22 43 16 / 22 43 19 / 22 43 23 / 22 43 39 / 22 43 43 / 22 45 00 / 22 45 13
22 45 16 / 22 45 26 / 22 45 29 / 22 45 33 / 22 45 36 / 22 46 00 / 22 46 13 / 22 46 16
22 46 39 / 22 46 43 / 22 46 53 / 22 47 00 / 22 47 13 / 22 47 23
100 See D20
200 Inclusions:
• Schematic layout with approximate size, shape, and
location;
• Carrier and wall width requirements;

300 Inclusions:
• Modeled as design-specified size, shape, spacing,
and location;
• Approximate allowances for clearances required for all
specified supports that are to be utilized in the layout
of all fixtures;
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 109
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Modeled as actual construction elements size, shape,
spacing, and location/connections of fixtures/carriers;
• Actual size, shape, spacing, and clearances required
for all supports that are utilized in the layout of all
fixtures.
• Actual access/code clearance requirements modeled.

400 See D2010.10

D2010.90 / 21-04 20 10 90 / Ss 55 70
Domestic Water Distribution Supplementary Components
Includes: Common work results for plumbing, plumbing insulation, and instrumentation. Includes: expansion fittings, meters, gages,
valves, hangers, supports, heat tracing, vibration and seismic controls.
Associated Masterformat Sections: 05 45 13 / 22 05 00 / 22 05 16 / 22 05 19 / 22 05 23
22 05 29 / 22 05 33 / 22 05 48 / 22 05 53 / 22 07 00 / 22 09 00
See General Notes: Supplementary Components

D2020 / 21-04 20 20 / Ss 50 30 4
Sanitary Drainage
Includes: Facility sanitary sewerage system located within, under, or closely associated with a structure. Include Sanitary Drainage
Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 16 / 22 13 00
100 See D20
200 See D2010

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 110
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2020.10 / 21-04 20 20 10 / Ss 50 30 04
Sanitary Sewerage Equipment
Includes: Interceptor, separator, pumps, and septic tanks that are part of facility sanitary sewerage system.
Associated Masterformat Sections: 22 13 23 / 22 13 26 / 22 13 29 / 22 13 33 / 22 13 36
22 13 43 / 22 13 53
100 See D20
200 Inclusions:
• Schematic layout with approximate size, shape, and
location.

300 Inclusions:
• design specified size, shape, spacing, and location of
equipment.
• Approximate allowances for clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment are
modeled.
• Access/code clearance requirements modeled.

350 Inclusions:
• Actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout of
equipment.
• Actual access/code clearance requirements modeled.

400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 111
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2020.30 / 21-04 20 20 30 / Ss 50 30 04
Sanitary Sewerage Piping
Includes: Sanitary waste and vent piping system within and under structures. May Include: Sanitary piping from the structure to the
utility sanitary sewer.
Associated Masterformat Sections: 22 13 13 / 22 13 16 / 22 13 19 / 22 05 73 / 22 05 76
100 See D20
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of mains and risers.

300 Inclusions:
• design-specified size, shape, spacing, location, and
slope of pipe, valves, fittings, and insulation for risers,
mains, and branches.
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all risers,
mains, and branches.
• Access/code clearance requirements modeled
350 Inclusions:

Actual construction elements.

Actual size, shape, spacing, location, connections,
and slope of pipe, valves, fittings, and insulation for
risers, mains, and branches.
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all risers, mains, and
branches.
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled
400 See D2020.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 112
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2020.90 / 21-04 20 20 90 / Ss 50 30 04
Sanitary Drainage Supplementary Components
Includes: Common work results for plumbing, plumbing insulation, and instrumentation and control for plumbing to be included with
sanitary drainage elements above as appropriate. Includes expansion fittings, meters, gages, valves, hangers, supports, heat tracing,
vibration and seismic controls.
Associated Masterformat Sections: 05 45 13 / 22 05 00 / 22 05 16 / 22 05 19 / 22 05 23
22 05 29 / 22 05 33 / 22 05 48 / 22 05 53 / 22 07 00 / 22 09 00
See General Notes: Supplementary Components

D2030 / 21-04 20 30 / --
Building Support Plumbing Systems
Includes: Facility storm water drainage and gray water systems. Include Building Support Plumbing System Supplementary
Components as appropriate.
Associated Masterformat Sections: 01 86 16 / 22 14 00
100 See D20
200 See D2010

D2030.10 / 21-04 20 30 10 / Ss 50 35 80
Stormwater Drainage Equipment
Includes: Drainage pumps, and sump pumps that are part of stormwater drainage system.
Associated Masterformat Sections: 22 14 29 / 22 14 33 / 22 14 36 / 22 14 53
100 Inclusions:
• Diagrammatic or schematic model elements.
• Conceptual and/or schematic layout;
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment.
• Approximate access/code clearance requirements.

300 Inclusions:
• design-specified size, shape, spacing, and location.
• Approximate allowances for clearances required for
all specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 113
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• actual construction elements size, shape, spacing,
and location/connections of equipment,
• Actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout of
equipment.
• Actual access/code clearance requirements
modeled.

400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D2030.20 / 21-04 20 30 20 / Ss 50 35 80
Stormwater Drainage Piping
Includes: Storm drainage piping system within, under, or closely associated with a structure. Includes storm drains for areas closely
associated with a structure such as courtyards, plazas, and loading dock areas. May Include: Storm drainage piping from the structure
to the utility storm drain.
Associated Masterformat Sections: 22 05 73 / 22 05 76 / 22 14 13 / 22 14 16 / 22 14 23
100 See D20
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of mains and risers.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 114
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• design-specified size, shape, spacing, location, and
slope of pipe, valves, fittings, and insulation for
risers, mains, and branches.
• Approximate allowances for clearances required for
all specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all
risers, mains, and branches.
• Access/code clearance requirements modeled.

350 Inclusions:
• actual size, shape, spacing, location, connections,
and slope of pipe, valves, fittings, and insulation for
risers, mains, and branches.
• Actual size and shape, spacing, and clearances
required for all hangers, supports, vibration and
seismic control that are utilized in the layout of all
risers, mains, and branches.
• Actual access/code clearance requirements
modeled.
• Actual floor and wall penetration elements.

400 See D2030.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 115
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2030.30 / 21-04 20 30 30 / Ss 50 35 80
Facility Stormwater Drains
Includes: Various types of drains to collect storm water.
Associated Masterformat Sections: 22 14 26
100 See D20

200 Inclusions:
• Schematic layout with approximate size, shape, and
location.

300 Inclusions:
• design-specified size, shape, spacing, and location of
components.
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all
components.
• Access/code clearance requirements modeled.

350 Inclusions:
• actual construction elements size, shape, spacing,
and location/connections of components.
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all components.
• Actual access/code clearance requirements modeled.

400 See D2030.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 116
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2030.60 / 21-04 20 30 60 / Ss 55 70 97 35
Gray Water Systems
Includes: Systems to collect, treat, and distribute gray water for other uses such as irrigation.
Associated Masterformat Sections: 22 13 63
[See D2030.20]

D2030.90 / 21-04 20 30 90 / --
Building Support Plumbing System Supplementary Components
Includes: Common work results for plumbing, plumbing insulation, and instrumentation and control for plumbing to be included with
building support plumbing system elements above as appropriate. Includes expansion fittings, meters, gages, valves, hangers,
supports, heat tracing, vibration and seismic controls.
Associated Masterformat Sections: 05 45 13 / 22 05 00 / 22 05 16 / 22 05 19 / 22 05 23
22 05 29 / 22 05 33 / 22 05 48 / 22 05 53 / 22 07 00 / 22 09 00
See General Notes: Supplementary Components

D2050 / 21-04 20 50 / Ss 55 20 15
General Service Compressed-Air
Includes: Compressed air system serving general service requirements
Associated Masterformat Sections: 01 86 16 / 22 15 00 / 22 15 13 / 22 15 16 / 22 15 19
[See D2060.10 – Compressed-Air Systems]

D2060 / 21-04 20 60 / Ss 55 60
Process Support Plumbing Systems
Includes: Process Support Plumbing System Supplementary Components as appropriate.
Associated Masterformat Sections:
100 See D20
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of mains and risers.

D2060.10 / 21-04 20 60 10 / Ss 55 20 15
Compressed-Air Systems
Associated Masterformat Sections: 01 86 16 / 22 61 00 / 22 61 13 / 22 61 19
100 See D20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 117
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See D2060

300 Inclusions:
• design-specified size, shape, spacing, location, and
slope of equipment/pipe, valves, fittings, and insulation
for risers, mains, and branches.
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all risers,
mains, and branches.
• Access/code clearance requirements modeled.
350 Inclusions:
• actual size, shape, spacing, location, connections,
and slope of equipment/pipe, valves, fittings, and
insulation for risers, mains, and branches.
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all risers, mains, and
branches.
• Actual access/code clearance requirements modeled.
• Actual floor and wall penetration elements.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D2060.20 / 21-04 20 60 20 / Ss 55 20 94
Vacuum Systems
Includes: Vacuum systems for laboratory and healthcare purposes.
Associated Masterformat Sections: 01 86 16 / 22 62 00 / 22 62 13 / 22 62 19 / 22 62 23
[See D2060.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 118
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D2060.30 / 21-04 20 60 30 / Ss 55 20 34
Gas Systems
Includes: Gas systems for laboratory and healthcare purposes.
Associated Masterformat Sections: 01 86 16 / 22 63 00 / 22 63 13 / 22 63 19
[See D2060.10]

D2060.40 / 21-04 20 60 40 / Ss 50 20
Chemical-Waste Systems
Includes: Chemical-waste systems for laboratory and healthcare purposes.
Associated Masterformat Sections: 01 86 16 / 22 66 00 / 22 66 53 / 22 66 70 / 22 66 83
[See D2060.10]

D2060.50 / 21-04 20 60 50 / Ss 55 70
Processed Water Systems
Includes: Processed water systems for laboratory and healthcare purposes.
Associated Masterformat Sections: 01 86 16 / 22 67 00 / 22 67 13 / 22 67 19
[See D2060.10]

D2060.90 / 21-04 20 60 90 / Ss 55 60
Process Support Plumbing System Supplementary Components
Includes expansion fittings, meters, gages, valves, hangers, supports, heat tracing, vibration and seismic controls. Includes: Common
work results for plumbing, plumbing insulation, and instrumentation and controls to be included with process support plumbing systems
elements above as appropriate.
Associated Masterformat Sections: 05 45 13 / 05 45 23 / 22 05 00 / 22 05 23 / 22 05 29 /
22 05 33 / 22 05 48 / 22 05 53 / 22 07 00 / 22 09 00
See General Notes: Supplementary Components

D30 / 21-04 30 / Ss 60
Heating, Ventilation, and Air Conditioning (HVAC)
Associated Masterformat Sections: 01 86 19 / 23 00 00
100 Inclusions:
• Diagrammatic or schematic model elements.
• conceptual and/or schematic layout/flow diagram;

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 119
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D3010 / 21-04 30 10 / Ss 55 50
Facility Fuel Systems
Includes: Fuel-oil, gasoline, natural-gas, and liquefied-petroleum fuel systems associated with a structure.
Associated Masterformat Sections: 01 86 19 / 23 10 00
100 See D30
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of element(s);
• Approximate access/code clearance requirements
modeled.

D3010.10 / 21-04 30 10 10 / Ss 55 50 46
Fuel Piping
Includes: Fuel piping, valves, piping specialties, and other components within, under, or closely associated with a structure.
Associated Masterformat Sections: 23 11 00
100 See D30
200 See D3010

300 Inclusions:
• design-specified size, shape, spacing, and location
of pipe, valves, fittings, and insulation for risers,
mains, and branches.
• Approximate allowances for clearances required for
all specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all
risers, mains, and branches.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 120
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• actual size, shape, spacing, and
location/connections of pipe, valves, fittings, and
insulation for risers, mains, and branches.
• Actual size, shape, spacing, and clearances
required for all hangers, supports, vibration and
seismic control that are utilized in the layout of all
risers, mains, and branches.
• Actual access/code clearance requirements.
• Actual floor and wall penetration elements
modeled.

400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation

D3010.30 / 21-04 30 10 30 / Ss 55 50
Fuel Pumps
Includes: Fuel pumps within or closely associated with a structure.
Associated Masterformat Sections: 23 12 00 / 23 12 13 / 23 12 16
100 See D30
200 See D3010
300 Inclusions:
• design-specified size, shape, spacing, and location of
equipment.
• Approximate allowances for clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment.
• Access/code clearance requirements modeled.
350 Inclusions:
• Modeled as actual size, shape, spacing, and
location/connections of equipment.
• Actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout of
equipment.
• Actual access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 121
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 See D3010.10

D3010.50 / 21-04 30 10 50 / Ss 55 10 75 0
Fuel Storage Tanks
Includes: Fuel tanks under or closely associated with a structure.
Associated Masterformat Sections: 23 13 00
100 See D30

200 See D3010

300 Inclusions:
• design-specified size, shape, spacing, and location of
tank(s).
• approximate allowances for spacing and clearances
required for all specified anchors, supports, vibration
and seismic control that are utilized in the layout.
• access/code clearance requirements modeled.

350 Inclusions:
• actual size, shape, spacing, and location/connections
of tank(s).
• actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout actual
access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 122
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 See D3010.10

D3020 / 21-04 30 20 / Ss 60 40 37
Heating Systems
Includes: Associated ductwork, piping, valves, and specialties. Includes: Heating System Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 19
100 See D30
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of element(s).

D3020.10 / 21-04 30 20 10 / Ss 60 40 37
Heat Generation
Includes: Boilers, furnaces, solar, geothermal, and biomass heat generation, fuel fired heaters, and heat exchangers. Includes: Fuel-
fired boilers and generators for hot water and steam systems. Includes breechings, chimneys, and stacks. Includes: Electric boilers
and generators for hot water and steam systems. Includes: Equipment to remove oxygen and other dissolved gases in boiler feed.
Includes: Fuel-fired and electric furnaces. Includes: Equipment powered by solar energy. Includes: Fuel-fired radiant and unit heaters.
Includes: Equipment used to transfer heat from one medium to another.
Associated Masterformat Sections: 23 51 00 / 23 52 00 / 23 52 13 / 23 53 00 / 23 53 13 /
23 53 16 / 23 54 00 / 23 56 00 / 23 56 13 / 23 56 16 / 23 55 00 / 23 57 00
100 See D30
200 See D3020

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 123
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• design-specified size, shape, spacing, and location of
equipment.
• Approximate allowances for clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment.
• Access/code clearance requirements modeled.

350 Inclusions:
• actual size, shape, spacing, and location/connections
of equipment,
• Actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout of
equipment.
• Actual access/code clearance requirements modeled.

400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D3020.30 / 21-04 30 20 30 / Ss 60 40 37
Thermal Heat Storage
Includes: Equipment to store thermal energy for use in heating and with charging or discharging this energy at a controllable rate.
Associated Masterformat Sections: 23 71 13
[See D3020.10]

D3020.70 / 21-04 30 20 70 / Ss 60 40 37
Decentralized Heating Equipment
Includes: Heating equipment that serves a portion of a HVAC system. Includes: Convection units may provide heating and cooling.
Includes: Electric cables or panels and hydronic piping used for radiant heating for space heating.
Associated Masterformat Sections: 23 80 00 / 23 82 00 / 23 82 13 / 23 82 14 / 23 82 16 /
23 82 19 / 23 82 23 / 23 82 26 / 23 82 29 / 23 82 33 / 23 82 36 / 23 82 39 / 23 83 00
[See D3020.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 124
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D3020.90 / 21-04 30 20 90 / Ss 60 40 37
Heating System Supplementary Components
Includes: Common work results for HVAC, insulation, and instrumentation and control to be included in heating system elements above
as appropriate.
Associated Masterformat Sections: 05 45 13 / 23 05 00 / 23 05 19 / 23 05 23 / 23 05 29 /
23 05 48 / 23 05 53 / 23 05 63 / 23 05 66 / 23 05 93 / 23 07 00 / 23 09 00
See General Notes: Supplementary Components

D3030 / 21-04 30 30 / Ss 60 40 17
Cooling Systems
Includes: Associated ductwork, piping, valves, and specialties. Includes: Cooling System Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 19
100 See D30
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of element(s).

D3030.10 / 21-04 30 30 10 / Ss 60 40 17 0
Central Cooling
Includes: Refrigerant compressors, condensers, packaged compressor and condenser units, water chillers, and cooling towers.
Includes: Various type of compressors used in refrigeration process. Includes: Condensing units used to reject heat from the
refrigeration process. Includes: Compressor in combination with condensing units used to reject heat from the refrigeration process.
Includes: Various types of chillers used for building space cooling. Includes: Factory- and field-fabricated cooling towers and liquid
coolers. Includes piping and specialties. chemical water treatment. vibration and seismic controls. and integral controls not a part of the
condenser water distribution systems.
Associated Masterformat Sections: 23 60 00 / 23 61 00 / 23 62 00 / 23 63 00 / 23 64 00 /
23 65 00
100 See D30
200 See D3030

300 Inclusions:
• s design-specified size, shape, spacing, and location
of equipment.
• Approximate allowances for clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 125
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• actual size, shape, spacing, and location/connections
of equipment.
• Actual size, shape, spacing, and clearances required
for all specified anchors, supports, vibration and
seismic control that are utilized in the layout of
equipment.
• Actual access/code clearance requirements modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D3030.30 / 21-04 30 30 30 / Ss 65 80 45 25
Evaporative Air-Cooling
Includes: Equipment used to reject heat from the refrigeration process by evaporation.
Associated Masterformat Sections: 23 76 00
100 See D3030.10
200 See D3030.10

300 See D3030.10

350 See D3030.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 126
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 See D3030.10

D3030.50 / 21-04 30 30 50 / Ss 60 40 17
Thermal Cooling Storage
Includes: Equipment to store thermal energy for use in cooling and with charging or discharging this energy at a controllable rate.
Associated Masterformat Sections: 23 71 00 / 23 71 16 / 23 71 19
[See D3030.10]

D3030.70 / 21-04 30 30 70 / Ss 60 40 17
Decentralized Cooling
Includes: Cooling equipment that serves a portion of a HVAC system. Note: Convection units may provide heating and cooling.
Associated Masterformat Sections: 23 80 00 / 23 81 13 / 23 81 16 / 23 81 19 / 23 81 23 /
23 81 26 / 23 81 43 / 23 81 46 / 23 82 00 / 23 82 13 / 23 82 14 / 23 82 16 / 23 82 19 /
23 82 23 / 23 82 26
[See D3030.10]

D3030.90 / 21-04 30 30 90 / Ss 60 40 17
Cooling System Supplementary Components
Includes expansion fittings, meters, gages, valves, hangers, supports, heat tracing, vibration and seismic controls. Includes: Common
work results for HVAC, insulation, and instrumentation and control to be included in cooling system elements above as appropriate.
Associated Masterformat Sections: 05 45 13 / 23 05 00 / 23 05 19 / 23 05 23 / 23 05 29 /
23 05 48 / 23 05 53 / 23 05 63 / 23 05 66 / 23 05 93 / 23 07 00 / 23 09 00
See General Notes: Supplementary Components

D3050 / 21-04 30 50 / Ss 60 40 84
Facility HVAC Distribution Systems
Includes: Facility Distribution Systems Supplementary Components as appropriate.
Associated Masterformat Sections:
100 See D30
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of element(s).

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 127
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D3050.10 / 21-04 30 50 10 / Ss 60 40 84 0
Facility Hydronic Distribution
Includes: Piping systems and equipment for distribution of heating hot water and cooling chilled water. Includes piping systems,
pumps, tanks, supports and anchors, vibration and seismic controls, identification, and piping and equipment insulation.
Associated Masterformat Sections: 01 86 19 / 23 21 13 / 23 21 23 / 23 25 00
100 See D30
200 See D3050

300 Inclusions:
• design-specified size, shape, spacing, location, and
slope of pipe, valves, fittings, and insulation for risers,
mains, and branches.
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all risers,
mains, and branches.
• Access/code clearance requirements modeled.

350 Inclusions:
• actual size, shape, spacing, location, connections, and
slope of pipe, valves, fittings, and insulation for risers,
mains, and branches.
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all risers, mains, and
branches.
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 128
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D3050.30 / 21-04 30 50 30 / Ss 55 40
Facility Steam Distribution
Includes: Piping systems and equipment for distribution of steam and condensate return. Includes piping systems, pumps, tanks,
supports and anchors, vibration and seismic controls, identification, and piping and equipment insulation.
Associated Masterformat Sections: 01 86 19 / 23 22 13 / 23 22 23 / 23 25 19
[See D3050.10]

D3050.50 / 21-04 30 50 50 / Ss 65 80 0 0
HVAC Air Distribution
Includes: Systems for distribution of air including supply systems, return systems, and general exhaust systems. Does not include
special exhaust systems such as kitchen hood, paint booth, and fume hood exhaust systems. Includes: Air-handling units consisting of
fans, coils, dampers, control devices, and other accessories. Includes: Ducts, duct accessories, fans, terminal units, and air inlets and
outlets. Includes: Devices of a variety of types to clean distribution air. Includes: Equipment that adds or removes moisture from a
medium in order to control the humidity.
Associated Masterformat Sections: 01 86 19 / 23 73 00 / 23 74 00 / 23 75 00 / 23 30 00 /
23 34 00 / 23 31 00 / 23 32 00 / 23 33 00 / 23 36 00 / 23 37 00 / 23 40 00 / 23 41 00 /
23 42 00 / 23 43 00 / 23 84 00
100 See D30
200 See D3050
300 Inclusions:
• design-specified size, shape, spacing, and location of
duct, dampers, fittings, and insulation for risers, mains,
and branches.
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic
control that are to be utilized in the layout of all risers,
mains, and branches.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 129
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
•actual size, shape, spacing, and location/connections
of duct, dampers, fittings, and insulation for risers,
mains, and branches.
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all risers, mains, and
branches.
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled.
400 See D3050.10

D3050.90 / 21-04 30 50 90 / Ss 60 40 84
Facility Distribution Systems Supplementary Components
Includes expansion fittings, meters, gages, valves, hangers, supports, heat tracing, vibration and seismic controls. Includes: Common
work results for HVAC, insulation, and instrumentation and control to be included in distribution system elements above as appropriate.
Associated Masterformat Sections: 05 45 13 / 23 05 00 / 23 05 16 / 23 05 19 / 23 05 23 /
23 05 29 / 23 05 33 / 23 05 48 / 23 05 53 / 23 05 63 / 23 05 66 / 23 05 93 / 23 07 00 /
23 09 00
See General Notes: Supplementary Components

D3060 / 21-04 30 60 / Ss 65 40 0 0
Ventilation
Includes: Supply air, return air, exhaust air, outside air, and air cleaning systems. Includes Ventilation Supplementary Components as
appropriate.
Associated Masterformat Sections: 01 86 19
100 See D30
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of mains and risers.

D3060.10 / 21-04 30 60 10 / Ss 65 40 33 51
Supply Air
Associated Masterformat Sections: 23 34 00 / 23 31 00 / 23 32 00 / 23 33 00 / 23 36 00 /
23 37 00
100 See D30

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 130
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See D3060

300 Inclusions:
• design-specified size, shape, spacing, and location of
duct, dampers, fittings, and insulation for risers, mains,
and branches.
• Approximate specified allowances for clearances
required for all hangers, supports, vibration and seismic
control that are to be utilized in the layout of all risers,
mains, and branches.
• Access/code clearance requirements modeled.

350 Inclusions:
• actual size, shape, spacing, and location/connections
of duct, dampers, fittings, and insulation for risers,
mains, and branches.
• Actual size, shape, spacing, and clearances required
for all hangers, supports, vibration and seismic control
that are utilized in the layout of all risers, mains, and
branches.
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled.

400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D3060.20 / 21-04 30 60 20 / Ss 65 40
Return Air
Associated Masterformat Sections: 23 34 00 / 23 31 00 / 23 32 00 / 23 33 00 / 23 37 00
[See D3060.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 131
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D3060.30 / 21-04 30 60 30 / Ss 65 40
Exhaust Air
Includes: Special systems for exhausting air such as kitchen hood, paint booth, and fume hood exhaust systems.
Associated Masterformat Sections: 23 35 00 / 23 35 13.13 / 23 35 16 / 23 38 00 / 23 38 13 /
23 38 16 / 23 34 00 / 23 31 00 / 23 32 00 / 23 33 00 / 23 37 00
100 See D30
200 See D3060

300 Inclusions:
• design-specified size, shape, spacing, location, duct slope (if
required), dampers, fittings, insulation for risers, mains, and
branches.
• Approximate specified allowances for clearances required for
all hangers, supports, vibration and seismic control that are to
be utilized in the layout of all risers, mains, and branches.
• Access/code clearance requirements modeled.

350 Inclusions:
• actual size, shape, spacing, location, and slope (if
required)/connections of duct, dampers, fittings, and insulation
for risers, mains, and branches.
• Actual size, shape, spacing, and clearances required for all
hangers, supports, vibration and seismic control that are
utilized in the layout of all risers, mains, and branches.
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled.

400 See D3060.10

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 132
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D3060.40 / 21-04 30 60 40 / Ss 65 40 33 51
Outside Air
Associated Masterformat Sections: 23 34 00 / 23 31 00 / 23 32 00 / 23 33 00 / 23 36 00 /
23 37 00
[See D3060.10]

D3060.60 / 21-04 30 60 60 / Pr 60 60 36
Air-to-Air Energy Recovery
Includes: Air-to-air energy recovery units.
Associated Masterformat Sections: 23 72 00
[See D3060.10]

D3060.70 / 21-04 30 60 70 / Pr 65 57 02
HVAC Air Cleaning
Associated Masterformat Sections: 23 40 00
[See D3060.10]

D3060.90 / 21-04 30 60 90 / Ss 65 40
Ventilation Supplementary Components
Includes expansion fittings, meters, gages, valves, hangers, supports, heat tracing, vibration and seismic controls. Includes: Common
work results for HVAC, insulation, and instrumentation and control to be included in ventilation elements above as appropriate.
Associated Masterformat Sections: 05 45 13 / 23 05 00 / 23 05 29 / 23 05 48 / 23 05 53 /
23 05 63 / 23 05 66 / 23 05 93 / 23 07 00 / 23 09 00
See General Notes: Supplementary Components

D3070 / 21-04 30 70 / Ss 60
Special Purpose HVAC Systems
Associated Masterformat Sections:
100 See D30
200 Inclusions:
• Schematic layout with approximate size, shape, and location of
components.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 133
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D3070.10 / 21-04 30 70 10 / Ss 60 30 60
Snow Melting
Includes: Electric cables and hydronic piping used for snow and ice control.
Associated Masterformat Sections: 23 83 13 / 23 83 16
100 See D30
200 See D3070
300 Inclusions:
• design-specified size, shape, spacing, and location of
supplementary components.
• approximate allowances for clearances required for all specified
hangers, supports, vibration and seismic control that are to be
utilized in the layout of all supplementary components.
• access/code clearance requirements.
350 Inclusions:
• Modeled as actual size, shape, spacing, and
location/connections of supplementary components.
• Actual size, shape, spacing, and clearances required for all
hangers, supports, vibration and seismic control that are utilized
in the layout of all supplementary components.
• Actual access/code clearance requirements.
400 Inclusions:
• Supplementary components added to the model required for
fabrication and field installation.

D40 / 21-04 40 / Ss 55 30
Fire Protection
100 Inclusions:
• Diagrammatic or schematic model elements.
• Conceptual and/or schematic layout/flow diagram.

D4010 / 21-04 40 10 / Ss 55 30
Fire Suppression
Includes: Fire Suppression Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 13 / 21 00 00
100 See D40
200 Inclusions:
• Schematic layout with approximate size, shape, and location of
mains and risers.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 134
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D4010.10 / 21-04 40 10 10 / Ss 55 30 98
Water-Based Fire-Suppression
Includes: Systems that use water for fire extinguishing and suppression. Includes piping, fittings, and specialties; hoses, valves,
cabinets; fire pumps, accessories, and controls. Includes: Piping, fittings, valves, hangers, supports, other specialties, and sprinklers
for fire protection systems. Includes limited area sprinkler systems, fire pumps, accessories, and controls.
Associated Masterformat Sections: 01 86 13 / 21 10 00 / 21 11 00 / 21 12 00 / 21 13 00 /
21 13 13 / 21 13 16 / 21 13 19 / 21 13 23 / 21 13 26 / 21 13 29 / 21 13 36 / 21 13 39 /
21 30 00 / 21 40 00
100 See D40
200 See D4010

300 Inclusions:
• design-specified size, shape, spacing, and location of
pipe/slope (if required)/valves/fittings/insulation for risers,
mains, and branches/standpipes.
• Approximate allowances for clearances required for all
specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all risers, mains, and
branches/standpipes.
• Access/code clearance requirements modeled.
350 Inclusions:
• actual size, shape, spacing, and location/ slope (if
required)/connections of pipe, valves, fittings, and
insulation for risers, mains, and branches/standpipes.
• Actual size, shape, spacing, and clearances required for
all hangers, supports, vibration and seismic control that
are utilized in the layout of all risers, mains, and
branches/standpipes.
• Actual floor and wall penetration elements.
• Actual access/code clearance requirements modeled.
400 Inclusions:
• Supplementary components added to the model required
for fabrication and field installation.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 135
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D4010.50 / 21-04 40 10 50 / Ss 55 30
Fire-Extinguishing
Includes: Systems that use other than water for fire extinguishing and suppression. Includes piping, fittings, and specialties; valves,
accessories, and controls.
Associated Masterformat Sections: 21 20 00 / 21 21 00 / 21 22 00 / 21 23 00 / 21 24 00
[See D4010.10]

D4010.90 / 21-04 40 10 90 / Ss 55 30
Fire Suppression Supplementary Components
Includes: Expansion fittings and loops, meters and gages, general-duty valves, hanger and supports, heat tracing, vibration and seismic
controls, identification, insulation, and instrumentation and control to be included in fire protection elements above as appropriate.
Associated Masterformat Sections: 05 45 13 / 21 05 00 / 21 05 16 / 21 05 19 / 21 05 23 /
21 05 29 / 21 05 33 / 21 05 48 / 21 05 53 / 21 07 00 / 21 09 00
See General Notes: Supplementary Components

D4030 / 21-04 40 30 / Ss 55 30
Fire Protection Specialties
Includes: Firefighting devices and storage cabinets except devices connected to a fire suppression system.
Associated Masterformat Sections: 10 44 00
100 See D40
200 Inclusions:
• Schematic layout with approximate size, shape, and location of
components.

D4030.10 / 21-04 40 30 10 / Pr 80 77 28 28
Fire Protection Cabinets
Associated Masterformat Sections: 10 44 13
100 See D40
200 See D4030
300 Inclusions:
• design-specified size, shape, spacing, and location of
components.
• Approximate allowances for clearances required for all specified
hangers, supports, vibration and seismic control that are to be
utilized in the layout of all components.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 136
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• actual size, shape, spacing, and location/connections of
components.
• Actual size, shape, spacing, and clearances required for all
hangers, supports, vibration and seismic control that are utilized
in the layout of all components.
• Actual access/code clearance requirements modeled.
400 Inclusions:
• Supplementary components added to the model required for
fabrication and field installation.

D4030.30 / 21-04 40 30 30 / Ss 55 30 65
Fire Extinguishers
Associated Masterformat Sections: 10 44 16
[See D4030.10]

D4030.50 / 21-04 40 30 50 / TE 70 20 20 10
Breathing Air Replenishment Systems
Associated Masterformat Sections: 10 44 33
[See D4030.10]

D4030.70 / 21-04 40 30 70 / Ss 55 30 65 65
Fire Extinguisher Accessories
Associated Masterformat Sections: 10 44 43
[See D4030.10]

D50 / 21-04 50 / --
Electrical
Associated Masterformat Sections: 26 00 00 / 01 86 26
100 Inclusions:
• Diagrammatic or schematic model elements:
• conceptual and/or schematic layout;

D5010 / 21-04 50 10 / --
Facility Power Generation
Includes: Power Generation Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 26
100 See D50

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 137
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 Inclusions:
• Schematic layout with approximate size, shape, and location
of equipment;

D5010.10 / 21-04 50 10 10 / Ss 70 10 30
Packaged Generator Assemblies
Includes: Generator, frequency changers, and rotary converters and uninterruptible power units.
Associated Masterformat Sections: 26 32 00 / 26 32 13 / 26 32 16 / 26 32 19 / 26 32 23 /
26 32 26 / 26 32 29 / 26 32 33
100 See D50
200 See D5010

300 Inclusions:
• Design-specified size, shape, spacing, and location of
equipment and associated components.
• Approximate allowances for clearances required for all
specified supports and seismic control.
• Access/code clearance requirements modeled.

350 Inclusions:
• Actual size, shape, spacing, location of equipment, and
associated components.
• Actual size, shape, spacing, location for supports, and
seismic control.
• Actual size, shape, and location/connections of equipment
and support structure/pads.
• Actual access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 138
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Supplementary components added to the model required
for fabrication and field installation.

D5010.20 / 21-04 50 10 20 / Pr 60 70 06
Battery Equipment
Includes: Batteries, battery racks, battery chargers, static power converters, uninterruptible power supplies, and accessories.
Associated Masterformat Sections: 26 33 00 / 26 33 13 / 26 33 16 / 26 33 19 / 26 33 23 /
26 33 33 / 26 33 43 / 26 33 46 / 26 33 53
[See D5010.10]

D5010.30 / 21-04 50 10 30 / Ss 70 10 70 35
Photovoltaic Collectors
Includes: Solar cells to convert sunlight to electricity.
Associated Masterformat Sections: 26 31 00
[See D5010.10]

D5010.40 / 21-04 50 10 40 / Pr 60 70 65 30
Fuel Cells
Includes: Fuel cell electricity generating equipment.
Associated Masterformat Sections: 48 18 00
[See D5010.10]

D5010.60 / 21-04 50 10 60 / Pr 65 72 43
Power Filtering and Conditioning

D5010.70 / 21-04 50 10 70 / Ss 70 30
Transfer Switches
Includes: Switches that transfer from one source of electricity to another.
Associated Masterformat Sections: 26 36 00
[See D5010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 139
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D5010.90 / 21-04 50 10 90 / Ss 70 10 30 72
Facility Power Generation Supplementary Components
See General Notes: Supplementary Components

D5020 / 21-04 50 20 / Ss 70 30
Electrical Service and Distribution
Includes: Electrical Service and Distribution Supplementary Components as appropriate.
100 See D50
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment;
300 Inclusions:
• Design-specified size, shape, spacing, and location
of equipment and associated components;
• Approximate allowances for clearances required for
all specified supports and seismic control;
• Access/code clearance requirements modeled.

D5020.10 / 21-04 50 20 10 / Ss 70 30 45 45
Electrical Service Entrance
Includes: Meters, substations, transformers, switchgear, switchboards, and protective devices where electrical power enters structure.
Associated Masterformat Sections: 26 21 00 / 26 16 00 / 26 11 00 / 26 12 00 / 26 22 00 /
26 13 00 / 22 23 00 / 26 18 00 / 22 28 00
100 See D50
200 See D5020
300 Inclusions:
• Design-specified size, shape, spacing, location of
equipment, and associated components.
• approximate allowances for clearances required for
all specified supports and seismic control.
• access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 140
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Actual size, shape, spacing, location of equipment,
and associated components.
• Actual size, shape, spacing, location for supports
and seismic control
• Actual size, shape, and location/connections of
equipment and support structure/pads.
• Actual access/code clearance requirements
modeled.

400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5020.30 / 21-04 50 20 30 / Ss 70 30 45 45
Power Distribution
Includes: Bus assemblies, distribution equipment, and electrical wiring system to distribute electrical power to switchboards,
panelboards, and motor control centers.
Associated Masterformat Sections: 26 20 00 / 26 24 00 / 26 24 13 / 26 24 16 / 26 24 19 /
26 25 00 / 26 27 00 / 26 27 16 / 26 05 33 / 26 05 43 / 26 05 36 / 26 05 13
100 See D50

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 141
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 See D5020

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 142
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Design-specified size, shape, spacing, location of
raceways, boxes, enclosures, and equipment.
• Approximate allowances for spacing and clearances
required for all specified hangers, supports and
seismic control.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 143
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Actual size, shape, spacing, and location of
raceways, boxes, and enclosures.
• Actual size, shape, spacing, and location for
supports and seismic control.
• Actual size, shape, and location/connections of
equipment and support structure/pads.
• Actual floor and wall penetration elements are
modeled.
• Actual access/code clearance requirements
modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 144
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5020.70 / 21-04 50 20 70 / Ss 70 30 45 45
Facility Grounding
Includes: Raceways, wiring and devices for grounding and bonding an electrical distribution system.
Associated Masterformat Sections: 26 05 26 / 26 05 33 / 26 05 13
100 See D50
200 See D5020
300 Inclusions:
• Design-specified size, shape, spacing, location of
raceways, boxes, enclosures, and the electrical
equipment and end-devices served.
• Approximate allowances for clearances required for
all specified hangers, supports, and seismic control.
• Access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 145
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Actual size, shape, spacing, and location of
raceways, boxes, enclosures, and the electrical
equipment and end-devices served.
• Actual size, shape, spacing, and location for
supports and seismic control.
• Penetration elements
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5020.90 / 21-04 50 20 90 / Ss 70 30 45 45
Electrical Service and Distribution Supplementary Components
Includes: Grounding and bonding, hanger and supports, raceways and boxes, cable trays, utility poles, vibration and seismic controls,
identification, wiring connectors, and instrumentation and control to be included in electrical service and distribution systems elements
above as appropriate.
Associated Masterformat Sections: 05 45 16 / 26 05 00 / 26 05 26 / 26 05 29 / 26 05 33 / 26 05 36 / 26 05 46 / 26 05 48 / 26
05 53 / 26 05 83 / 26 09 00
100 See D50
200 See D5020
300 Inclusions:
• Design-specified size, shape, spacing, and location
of raceways, boxes, enclosures, and the electrical
equipment and end-devices served;
• Approximate allowances for clearances required for
all specified hangers, supports, and seismic control;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of
raceways, boxes, enclosures, and the electrical
equipment and end-devices served;
• Actual size, shape, spacing, and location for
supports and seismic control;
• Penetration elements.
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 146
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D5030 / 21-04 50 30 / Ss 70 30 45 45
General Purpose Electrical Power
Includes: General Purpose Electrical Power Supplementary Components as appropriate.
Associated Masterformat Sections: 01 86 26
100 See D50
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment;

D5030.10 / 21-04 50 30 10 / Ss 70 30 45 45
Branch Wiring System
Includes: Raceways, ducts, cable trays, and wiring to deliver power from branch panelboards to the point of use.
Associated Masterformat Sections: 26 05 33 / 26 05 43 / 26 05 36 / 26 05 19
100 See D50
200 See D5030
300 Inclusions:
• Design-specified size, shape, spacing, and location
of raceways, boxes, and enclosures;
• Approximate allowances for clearances required for
all specified hangers, supports and seismic control;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of
raceways, boxes, enclosures;
• Actual size, shape, spacing, and location for
supports and seismic control;
• Penetration elements.
• Actual access/code clearance requirements
modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 147
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5030.50 / 21-04 50 30 50 / Ss 70 30 45 45
Wiring Devices
Includes: Electrical devices at point of use including electrical outlets and switches.
Associated Masterformat Sections: 26 27 26
100 See D50
200 See D5030
300 Inclusions:
• Design-specified size, shape, and location of outlet
boxes and devices
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of outlet
boxes and devices.
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5030.90 / 21-04 50 30 90 / Ss 70 30 45 45
General Purpose Electrical Power Supplementary Components
Includes: Grounding and bonding, hanger and supports, raceways and boxes, cable trays, vibration and seismic controls, identification,
wiring connectors, and instrumentation and control to be included in general purpose electrical power elements above as appropriate.
Associated Masterformat Sections: 05 45 16 / 26 05 00 / 26 05 26 / 26 05 29 / 26 05 33 / 26 05 36 / 26 05 48 / 26 05 53 / 26
05 83 / 26 09 00
100 See D50
200 See D5030

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 148
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Design-specified size, shape, and location of
Supplementary Components
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of outlet
boxes and devices.
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5040 / 21-04 50 40 / Ss 70 80
Lighting
Includes: Lighting Supplementary Components as appropriate.
Associated Masterformat Sections: 26 50 00 / 01 86 26
100 See D50
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment;

D5040.10 / 21-04 50 40 10 / Pr 70 70 47
Lighting Control
Includes: Clock and calendar, photoelectric switches, occupancy sensors, and light-leveling control devices.
Associated Masterformat Sections: 26 09 23 / 26 09 26 / 26 09 33 / 26 09 36 / 26 09 43 /
26 09 61
100 See D50
200 See D5040
300 Inclusions:
• Design-specified size, shape, and location of
enclosures, equipment, and devices;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of
enclosures, equipment, and control devices;
• Actual size, shape, and location/connections of
equipment and control devices.
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 149
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D5040.20 / 21-04 50 40 20 / Ss 70 80 33 35
Branch Wiring for Lighting
Includes: Raceways, ducts, cable trays, and wiring beyond branch circuit panelboards to lighting fixtures.
Associated Masterformat Sections: 26 05 33 / 26 05 43 / 26 05 36 / 26 05 19 / 26 27 26
100 See D50
200 See D5040
300 Inclusions:
• Design-specified size, shape, and location of
raceways, boxes, and enclosures to fixture locations;
• Approximate allowances for clearances required for
all specified hangers, supports, and seismic control.
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of
raceways, boxes, and enclosures to fixture locations;
• Actual size, shape, spacing, and location for
supports and seismic control;
• Penetration elements.
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5040.50 / 21-04 50 40 50 / Ss 70 80
Lighting Fixtures
Includes: Luminaires, lighting equipment, ballasts, and accessories. Includes fluorescent, high intensity discharge, incandescent,
mercury vapor, neon, and sodium vapor lighting.
Associated Masterformat Sections: 26 50 00 / 26 51 00 / 26 52 00 / 26 53 00 / 26 54 00 /
26 55 00 / 26 55 23 / 26 55 29 / 26 55 33 / 26 55 36 / 26 55 39 / 26 55 53 / 26 55 59 /
26 55 61 / 26 55 63 / 26 55 70
100 See D50
200 See D5040
300 Inclusions:
• Design-specified size, shape, and location of lighting
fixtures;
• Approximate allowances for spacing and clearances
required for all specified hangers, supports and
seismic control;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of lighting
fixtures.
• Actual size, shape, spacing, and location for
supports and seismic control.
• Actual access/code clearance requirements
modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 150
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5040.90 / 21-04 50 40 90 / Ss 70 80
Lighting Supplementary Components
See General Notes: Supplementary Components

D5080 / 21-04 50 80 / Ss 70
Miscellaneous Electrical Systems
Includes: Miscellaneous Electrical Systems Supplementary Components as appropriate.
100 See D50
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment;

D5080.10 / 21-04 50 80 10 / Ss 75 50 45 45
Lightning Protection
Includes: Wiring and equipment for lightning protection.
Associated Masterformat Sections: 26 41 00 / 01 86 26 / 26 41 13 / 26 41 16 / 26 41 19 /
26 41 23
100 See D50
200 See D5080
300 Inclusions:
• Design-specified size, shape, and location of
raceways, boxes, enclosures including the electrical
equipment and end-devices served;
• Approximate allowances for clearances required for
all specified hangers, supports and seismic control;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of
raceways, boxes, enclosures including the electrical
equipment, fixtures, and end-devices served
• Actual size, shape, spacing, and location for
supports and seismic control;
• Actual size, shape, and location/connections of
equipment and support structure/pads;
• Penetration elements .
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 151
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D5080.40 / 21-04 50 80 40 / Ss 75 50 15
Cathodic Protection

D5080.70 / 21-04 50 80 70 / Pr 65 72 27 88
Transient Voltage Suppression
Includes: Devices to protect against voltage surges on electrical distribution systems.
Associated Masterformat Sections: 26 43 00
100 See D50
200 See D5080
300 Inclusions:
• Design-specified size, shape, and location of
equipment;
• Approximate allowances for clearances required for
all specified hangers, supports and seismic control;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of the
equipment;
• Actual size, shape, spacing, and location for
supports and seismic control.
• Actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D5080.90 / 21-04 50 80 90 / Pr 65 72
Miscellaneous Electrical Systems Supplementary Components
See General Notes: Supplementary Components

D60 / 21-04 60 / Ss 75 10
Communications
Associated Masterformat Sections: 27 00 00 / 01 86 29
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 152
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D6010 / 21-04 60 10 / Ss 75 10 21 21
Data Communications
Includes: Communications Supplementary Components as appropriate.
Associated Masterformat Sections: 27 20 00 / 01 86 29
See Fundamental LOD Definitions

D6010.10 / 21-04 60 10 10 / Ss 75 10 21 21
Data Communications Network Equipment
Includes: Switching and routing equipment for data communications.
Associated Masterformat Sections: 27 21 00 / 27 21 13 / 27 21 16 / 27 21 29 / 27 21 33
100 See D50
200 See D5010
300 Inclusions:
• design-specified size, shape, spacing, and location
of equipment and associated components;
• approximate allowances for clearances required for
all specified supports and seismic control;
• access/code clearance requirements modeled.
350 Inclusions:
• actual size, shape, spacing, and location of
equipment and associated components;
• actual size, shape, spacing, and location for
supports and seismic control;
• actual size, shape, and location/connections of
equipment and support structure/pads.
• actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D6010.20 / 21-04 60 10 20 / Pr 70 75 52
Data Communications Hardware
Includes: Computer equipment for data communications.
Associated Masterformat Sections: 27 22 00 / 07 22 13 / 07 22 16 / 07 22 19 / 07 22 23 / 07 22 26 / 07 22 29
100 See D50
200 See D5010
300 Inclusions:
• design-specified size, shape, and location of
equipment and associated components.
• approximate allowances for clearances required for
all specified supports and seismic control.
• access/code clearance requirements modeled.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 153
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• actual size, shape, spacing, and location of
equipment and associated components;
• actual size, shape, spacing, and location for
supports and seismic control;
• actual size, shape, and location/connections of
equipment and support structure/pads.
• actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D6010.30 / 21-04 60 10 30 / Pr 70 75 15
Data Communications Peripheral Data Equipment
Includes: Additional equipment for data communications.
Associated Masterformat Sections: 27 24 00 / 27 24 13 / 27 24 26 / 27 24 19 / 27 24 23 / 27 24 26 / 27 24 29
100 See D50
200 See D5010
300 Inclusions:
• design-specified size, shape, and location of
equipment and associated components;
• approximate allowances for clearances required for
all specified supports and seismic control;
• access/code clearance requirements modeled.
350 Inclusions:
• actual size, shape, spacing, and location of
equipment and associated components;
• actual size, shape, spacing, and location for
supports and seismic control;
• actual size, shape, and location/connections of
equipment and support structure/pads.
• actual access/code clearance requirements
modeled.
400 Inclusions:
• Supplementary components added to the model
required for fabrication and field installation.

D6020 / 21-04 60 20 / Ss 75 10 21 88
Voice Communications
Includes: Communications Supplementary Components as appropriate.
Associated Masterformat Sections: 27 30 00 / 01 86 29
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 154
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D6030 / 21-04 60 30 / --
Audio-Video Communication
Includes: Communications Supplementary Components as appropriate.
Associated Masterformat Sections: 27 40 00 / 01 86 29
See Fundamental LOD Definitions

D6060 / 21-04 60 60 / Ss 75 70 54 15
Distributed Communications and Monitoring
Includes: Communications Supplementary Components as appropriate.
Associated Masterformat Sections: 27 50 00 / 01 86 29
See Fundamental LOD Definitions

D6090 / 21-04 60 90 / Ss 75 10
Communications Supplementary Components
See Fundamental LOD Definitions

D70 / 21-04 70 / Ss 75 40
Electronic Safety and Security
Associated Masterformat Sections: 28 00 00 / 01 86 33
See Fundamental LOD Definitions

D7010 / 21-04 70 10 / Ss 75 40
Access Control and Intrusion Detection
Includes: Electronic Safety and Security Supplementary Components as appropriate.
Associated Masterformat Sections: 28 10 00 / 01 86 33
See Fundamental LOD Definitions

D7030 / 21-04 70 30 / Ss 75 40 53
Electronic Surveillance
Includes: Equipment for detecting and controlling access by persons to a facility site, building, or within a building. Includes Electronic
Safety and Security Supplementary Components as appropriate.
Associated Masterformat Sections: 28 20 00 / 01 86 33
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 155
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

D7050 / 21-04 70 50 / Ss 75 50
Detection and Alarm
Includes: Equipment for detecting hazardous conditions in a building or on a facility site and communicating an alarm signal. Includes
alarm devices, detection devices, safety switches, and associated items. Includes Electronic Safety and Security Supplementary
Components as appropriate.
Associated Masterformat Sections: 28 30 00 / 01 86 33

D7070 / 21-04 70 70 / Ss 75 70 54 15
Electronic Monitoring and Control
Includes: Electronic Safety and Security Supplementary Components as appropriate.
Associated Masterformat Sections: 28 46 00 / 01 86 33

D7090 / 21-04 70 90 / Ss 75 50
Electronic Safety and Security Supplementary Components
See General Notes: Supplementary Components

D80 / 21-04 80 / Ss 75 70
Integrated Automation
Associated Masterformat Sections: 25 00 00 / 01 86 23
See Fundamental LOD Definitions

D8010 / 21-04 80 10 / Ss 75 70
Integrated Automation Facility Controls
Includes: Hardware and/or software that allows the building automation system to monitor and control other facility equipment and
systems. Includes Integrated Automation Supplementary Components as appropriate.
Associated Masterformat Sections: 25 50 00 / 01 86 23
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 156
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E / 21-05 00 00 / --
EQUIPMENT & FURNISHINGS

E10 / 21-05 10 00 / --
Equipment
Associated Masterformat Sections: 11 00 00 / 01 87 13
100 Inclusions
• Diagrammatic or schematic model elements:
• conceptual and/or schematic layout;

E1010 / 21-05 10 10 / --
Vehicle and Pedestrian Equipment
Associated Masterformat Sections: 11 10 00
100 See E10
200 Inclusions
• Schematic layout with approximate size, shape, and location of
equipment;

E1010.10 / 21-05 10 10 10 / Ss 40 85 72 33
Vehicle Servicing Equipment
Includes: Equipment associated with vehicle service facilities.
Associated Masterformat Sections: 11 11 00 / 11 11 19 / 11 11 23 / 11 11 26
100 See E10
200 See E1010
300 Inclusions:
•design-specified size, shape, spacing, and location of equipment
and associated components;
• Geometry of required clearances
350 Inclusions
• actual size, shape, spacing, and location of equipment and
associated components;
• actual size, shape, spacing, and location for supports and
seismic control;
• actual size, shape, and location of service connections and
support structure/pads.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 157
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400 Inclusions
• Supplementary components required for fabrication and field
installation.

E1010.30 / 21-05 10 10 30 / Ss 40 85 72 11
Interior Parking Control Equipment
Includes: Equipment associated with the control of movement of vehicle parking.
Associated Masterformat Sections: 11 12 00 / 11 12 13 / 11 12 16 / 11 12 23 / 11 12 26 /
11 12 33
[See E1010.10]

E1010.50 / 21-05 10 10 50 / Ss 80 50 60
Loading Dock Equipment
Includes: Equipment for the protection of service docks and for the loading and unloading of service vehicles.
Associated Masterformat Sections: 11 13 00 / 11 13 13 / 11 13 16 / 11 13 19.13 / 11 13 19.23 /
11 13 26
[See E1010.10]

E1010.70 / 21-05 10 10 70 / Ss 40 10
Interior Pedestrian Control Equipment
Includes: Equipment associated with the control of movement of pedestrians.
Associated Masterformat Sections: 11 14 00 / 11 14 13 / 11 14 16 / 11 14 26 / 11 14 43 /
11 14 53
[See E1010.10]

E1030 / 21-05 10 30 / Ss 40 20 15
Commercial Equipment
Associated Masterformat Sections: 11 20 00
[See E1010]

E1030.10 / 21-05 10 30 10 / Ss 40 20 15 71
Mercantile and Service Equipment
Includes: Equipment used in retail and service stores.
Associated Masterformat Sections: 11 21 00 / 11 21 13 / 11 21 23 / 11 21 33 / 11 21 43 /
11 21 53
[See E1010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 158
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E1030.20 / 21-05 10 30 20 / Pr 40 30 75 94
Vault Equipment
Includes: Equipment specifically designed for money or valuable material storage, including vault ventilators and specialized security
equipment.
Associated Masterformat Sections: 11 16 00 / 11 16 13 / 11 16 16 / 11 16 23
[See E1010.10]

E1030.25 / 21-05 10 30 25 / Ss 40 20 15 71
Teller and Service Equipment
Includes: Equipment specifically designed for handling and transfer of money and other high-security items.
Associated Masterformat Sections: 11 17 00 / 11 17 13 / 11 17 16 / 11 17 23 / 11 17 33 /
11 17 36
[See E1010.10]

E1030.30 / 21-05 10 30 30 / Ss 40 20 15 71
Refrigerated Display Equipment
Includes: Display cases that include refrigeration.
Associated Masterformat Sections: 11 22 00
[See E1010.10]

E1030.35 / 21-05 10 30 35 / Ss 40 15 46 15
Commercial Laundry and Dry Cleaning Equipment
Includes: Equipment for commercial laundry and dry-cleaning operations including coin-operated equipment.
Associated Masterformat Sections: 11 23 00 / 11 23 13 / 11 23 16 / 11 23 19 / 11 23 23 /
11 23 26 / 11 23 33 / 11 23 43
[See E1010.10]

E1030.40 / 21-05 10 30 40 / --
Maintenance Equipment
Includes: Built-in and free-standing equipment for building maintenance.
Associated Masterformat Sections: 11 24 00 / 11 24 13 / 11 24 16 / 11 24 19 / 11 24 23.13
[See E1010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 159
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E1030.50 / 21-05 10 30 50 / Ss 40 45 37
Hospitality Equipment
Includes: Specialized equipment for the purpose of registering, admitting, and controlling rooms and other information at hotels, motels,
hospitals, and other similar facilities.
Associated Masterformat Sections: 11 25 00 / 11 25 13
[See E1010.10]

E1030.55 / 21-05 10 30 55 / Ss 40 45 37 45
Unit Kitchens
Includes: Manufactured units incorporating plumbing fixtures, appliances, casework and countertops.
Associated Masterformat Sections: 11 26 00
[See E1010.10]

E1030.60 / 21-05 10 30 60 / Ss 40 25 75 21
Photographic Processing Equipment
Includes: Photographic film processing equipment and other products for darkroom use.
Associated Masterformat Sections: 11 27 00 / 11 27 13 / 11 27 16
[See E1010.10]

E1030.70 / 21-05 10 30 70 / Ss 40 15 58
Postal, Packaging and Shipping Equipment
Includes: Equipment for normal mailing, packaging, shipping, and delivery operations for professional, commercial, and institutional
applications.
Associated Masterformat Sections: 11 29 00 / 11 29 23 / 11 29 33 / 11 29 55 / 11 28 23
[See E1010.10]

E1030.75 / 21-05 10 30 75 / Ss 40 15 58
Office Equipment
Includes: Computers, printers, copiers, drafting equipment, plotters, carto-stereographs, and other equipment used in offices.
Associated Masterformat Sections: 11 28 00 / 11 28 13 / 11 28 16 / 11 28 19 / 11 28 23
[See E1010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 160
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E1030.80 / 21-05 10 30 80 / Ss 40 15 25
Foodservice Equipment
Includes: Equipment used for liquid and solid food storage, preparation, display, serving, and clean-up in commercial and institutional
kitchens and bars.
Associated Masterformat Sections: 11 40 00 / 11 41 00 / 11 41 13 / 11 41 23 / 11 41 26 /
11 41 33 / 11 42 00 / 11 43 00 / 11 41 13 / 11 41 16 / 11 44 00 / 11 44 13 / 11 44 16 /
11 46 00 / 11 46 13 / 11 46 16 / 11 46 19 / 11 47 00 / 11 48 00 / 11 48 13
[See E1010.10]

E1040 / 21-05 10 40 / --
Institutional Equipment
Associated Masterformat Sections: 11 50 00
[See E1010]

E1040.10 / 21-05 10 40 10 / Ss 40 25 26
Educational and Scientific Equipment
Includes: Equipment associated with libraries, education facilities, laboratories, planetariums, observatories, and museums.
Associated Masterformat Sections: 11 50 00 / 11 51 00 / 11 51 13 / 11 51 16 / 11 51 19 /
11 51 23 / 11 52 00 / 11 52 13 / 11 52 16 / 11 52 19 / 11 53 00 / 11 53 13 / 11 53 16 /
11 53 19 / 11 53 23 / 11 53 33 / 11 53 43 / 11 53 53 / 11 55 00 / 11 55 13 / 11 55 16 /
11 56 00 / 11 56 13 / 11 57 00 / 11 59 00 / 11 95 00 / 11 95 13
[See E1010.10]

E1040.20 / 21-05 10 40 20 / Ss 40 50 50
Healthcare Equipment
Includes: Specialized equipment for healthcare facilities for humans and animals. Includes film illuminators, fluoroscopes, hubbard
tubs, radio isotopic equipment, and surgical equipment.
Associated Masterformat Sections: 11 70 00 / 05 45 23 / 11 71 00 / 11 72 00 / 11 73 00 /
11 74 00 / 11 75 00 / 11 76 00 / 11 77 00 / 11 78 00 / 11 78 13 / 11 78 16 / 11 78 19 /
11 79 00
[See E1010.10]

E1040.40 / 21-05 10 40 40 / Ss 40 25 71
Religious Equipment
Includes: Built-in and free-standing religious equipment, including baptistery and chancel fittings.
Associated Masterformat Sections: 11 91 00 / 11 91 13
[See E1010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 161
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E1040.60 / 21-05 10 40 60 / Ss 25 38 20
Security Equipment
Includes: Equipment specifically designed for secure operations.
Associated Masterformat Sections: 11 18 00 / 11 18 13 / 11 18 16 / 11 18 23
[See E1010.10]

E1040.70 / 21-05 10 40 70 / Ss 40 20 65 22
Detention Equipment
Includes: Equipment specifically designed for detention facilities.
Associated Masterformat Sections: 11 19 00 / 01 87 13 / 11 19 13 / 11 19 16
[See E1010.10]

E1060 / 21-05 10 60 / Ss 40 45 70
Residential Equipment
Includes: Built-in and free-standing appliances and other components specifically for residential use.
Associated Masterformat Sections: 11 30 00
[See E1010]

E1060.10 / 21-05 10 60 10 / Pr 40 70 24
Residential Appliances
Associated Masterformat Sections: 11 31 00 / 11 31 13 / 11 31 23
[See E1010.10]

E1060.50 / 21-05 10 60 50 / Ss 35 10 40
Residential Stairs
Associated Masterformat Sections: 11 33 00
[See B1080]

E1060.70 / 21-05 10 60 70 / Pr 65 67 29 23
Residential Ceiling Fans
Associated Masterformat Sections: 11 34 00
[See E1010.10]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 162
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E1070 / 21-05 10 70 / Ss 40 70
Entertainment and Recreational Equipment
Includes: Equipment for use in athletic, recreational, and therapeutic activities.
Associated Masterformat Sections:
[See E1010]

E1070.10 / 21-05 10 70 10 / Ss 40 25 20 90
Theater and Stage Equipment
Includes: Equipment for support of theatrical, instrumental, and voice programs. Includes cycloramas, entertainment ticket dispensers,
scenery and flats, and tormentors.
Associated Masterformat Sections: 11 61 00 / 11 61 13 / 11 61 23 / 11 61 33 / 11 61 43
[See E1010.10]

E1070.20 / 21-05 10 70 20 / Ss 40 25 20
Musical Equipment
Includes: Musical instruments, including prefabricated and field assembled instruments.
Associated Masterformat Sections: 11 62 00 / 11 62 13 / 11 62 16 / 11 62 19
[See E1010.10]

E1070.50 / 21-05 10 70 50 / Ss 40 70 75
Athletic Equipment
Includes: Equipment for use in interior athletic and exercise activities.
Associated Masterformat Sections: 11 66 00 / 11 66 13 / 11 66 23 / 11 66 43 / 11 66 53
[See E1010.10]

E1070.60 / 21-05 10 70 60 / Ss 40 70
Recreational Equipment
Includes: Equipment for use in recreational activities. Includes curling rinks and pistol and rifle range equipment.
Associated Masterformat Sections: 11 67 00 / 11 67 13 / 11 67 23 / 11 67 33 / 11 67 43 /
11 67 53
[See E1010.10]

E1090 / 21-05 10 90 / Ss 40 15 35 35
Other Equipment
Associated Masterformat Sections: 11 90 00
[See E1010]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 163
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E1090.10 / 21-05 10 90 10 / Ss 50 80
Solid Waste Handling Equipment
Includes: Equipment involving the collection, shredding, compaction, removal and incineration of trash and other solid waste
Associated Masterformat Sections: 11 82 00 / 01 87 13 / 11 82 13 / 11 82 19 / 11 82 23 /
11 82 26 / 11 82 29 / 11 82 33 / 11 82 36
[See E1010.10]

E1090.30 / 21-05 10 90 30 / Ss 40 30 02
Agricultural Equipment
Includes: Equipment related to land cultivating, raising crops, and feeding, breeding, and raising of livestock.
Associated Masterformat Sections: 11 92 00 / 11 92 13 / 11 92 16 / 11 92 19 / 11 92 23
[See E1010.10]

E1090.40 / 21-05 10 90 40 / Ss 40 30 02 37
Horticultural Equipment
Includes: Equipment related to cultivating flowers, fruits, vegetables, or ornamental plants.
Associated Masterformat Sections: 11 93 00 / 11 93 13 / 11 93 16 / 11 93 19 / 11 93 23 /
11 93 26 / 11 93 29 / 11 93 33 / 32 86 00
[See E1010.10]

E1090.60 / 21-05 10 90 60 / Ss 40 30 42
Decontamination Equipment
Includes: Equipment associated with decontamination operations.
Associated Masterformat Sections:
[See E1010.10]

E20 / 21-05 20 / Ss 40 45
Furnishings
Associated Masterformat Sections: 12 00 00 / 01 87 16
100 Inclusions
• A schematic model element or symbol

E2010 / 21-05 20 10 / Ss 40 45
Fixed Furnishings
Associated Masterformat Sections:
100 See E20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 164
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 Inclusions
• Generic model elements with approximate size.
300 Inclusions
• Model element with as-designed dimensions

E2010.10 / 21-05 20 10 10 / Ss 40 25 20 4
Fixed Art
Includes: Interior and exterior fixed art objects.
Associated Masterformat Sections: 12 10 00 / 12 11 00 / 12 12 00 / 12 12 23 / 12 12 26 /
12 14 00 / 12 17 00 / 12 19 00
See E2010

E2010.20 / 21-05 20 10 20 / Ss 25 50 45
Window Treatments
Includes: Interior window coverings and associated hardware and controls.
Associated Masterformat Sections: 12 20 00 / 12 21 00 / 12 22 00 / 12 23 00 / 12 24 00 /
12 25 00
[See E2010.10]

E2010.30 / 21-05 20 10 30 / Ss 40 15 35
Casework
Includes: Custom and manufactured stock design steel, wood, and laminate faced cabinets and other casework units. Includes
countertops with integral sinks, fixtures and accessories.
Associated Masterformat Sections: 12 30 00 / 12 35 00 / 12 35 17 / 12 35 25 / 12 35 30 /
12 35 33 / 12 35 50 / 12 35 53 / 12 35 59 / 12 35 70 / 12 35 91 / 12 36 00
See E2010

E2010.70 / 21-05 20 10 70 / Pr 40 30 29
Fixed Multiple Seating
Includes: Fixed, and telescoping seating for theaters, auditoriums, lecture halls, stadiums, arenas, gymnasiums, religious buildings,
restaurants, and other facilities where multiple seating is required.
Associated Masterformat Sections: 12 60 00 / 12 61 00 / 12 63 00 / 13 34 16.53 / 12 64 00 / 12 65 00 / 12 66 00 / 12 67 00 /
12 68 00
[See E2010]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 165
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E2010.90 / 21-05 20 10 90 / Pr 40 30
Other Fixed Furnishings
Includes: Fixed artificial plants, planters, and accessories.
Associated Masterformat Sections: 12 90 00 / 12 92 00 / 12 92 13 / 12 92 33 / 12 92 43
See E2010

E2050 / 21-05 20 50 / Pr 40 50
Movable Furnishings
Includes: Items of moveable furniture and furnishing accessories. Includes furniture for a variety of uses including classroom,
dormitory, ecclesiastical, hotel and motel, laboratory, library, lounge, medical, office, restaurant, and residential.
Associated Masterformat Sections:
[See E2010]

E2050.10 / 21-05 20 50 10 / Ss 40 25 20 4
Movable Art
Includes: Interior and exterior moveable art objects such as paintings, and sculpture.
Associated Masterformat Sections: 12 10 00 / 12 14 00 / 12 19 0
[See E2010]

E2050.30 / 21-05 20 50 30 / Pr 40 50
Furniture
Includes: Movable interior furniture.
Associated Masterformat Sections: 12 50 00 / 12 51 00 / 12 52 00 / 12 52 23 / 12 52 70 /
12 53 00 / 12 54 00 / 12 54 13 / 12 54 16 / 12 55 00 / 12 56 00 / 12 56 33 / 12 56 39 /
12 56 43 / 12 56 51 / 12 56 52 / 12 56 53 / 12 56 70 / 12 57 00 / 12 57 13 / 12 57 16 /
12 58 00 / 12 59 00
[See E2010]

E2050.40 / 21-05 20 50 40 / Pr 40 50
Accessories
Includes: Interior furnishing accessories not attached to permanent construction.
Associated Masterformat Sections: 12 40 00 / 12 41 00 / 12 42 00 / 12 43 00 / 12 44 00 /
12 44 16 / 12 45 00 / 12 46 00 / 12 48 00
[See E2010]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 166
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

E2050.60 / 21-05 20 50 60 / Pr 40 50 12
Movable Multiple Seating
Includes: Portable seating for auditoriums, lecture halls, stadiums, arenas, gymnasiums, religious buildings, restaurants, and other
facilities where multiple seating is required.
Associated Masterformat Sections: 12 60 00 / 12 62 00 / 12 65 00 / 12 67 00 / 12 68 00
[See E2010]

E2050.90 / 21-05 20 50 90 / Pr 40 50
Other Movable Furnishings
Includes: Moveable artificial plants, and planters.
Associated Masterformat Sections: 12 90 00 / 12 92 00 / 12 92 13 / 12 92 33 / 12 92 43
[See E2010]

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 167
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

F / 21-06 00 00 / --
SPECIAL CONSTRUCTION & DEMOLITION

F10 / 21-06 10 / --
Special Construction
Associated Masterformat Sections: 01 88 13

F1010 / 21-06 10 10 / Ss 20 10 60
Integrated Construction
Associated Masterformat Sections:
See Fundamental LOD Definitions

F1020 / 21-06 10 20 / --
Special Structures
Associated Masterformat Sections: 13 30 00 / 01 88 13
See Fundamental LOD Definitions

F1020.40 / 21-06 10 20 40 / Ss 40 5
Special Structures: Metal Building Systems
Includes: Prefabricated buildings and structures assembled on temporary and permanent foundations.
Associated Masterformat Sections: 13 34 00 / 01 88 13 / 13 34 13 / 13 34 16 / 13 34 19 / 13 34 56
100 Inclusions:
• Schematic layout
200 Inclusions:
• Element envelope
300 Inclusions:
• Element envelope

F1030 / 21-06 10 30 / --
Special Function Construction
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 168
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

F1050 / 21-06 10 50 / --
Special Facility Components
See Fundamental LOD Definitions

F1060 / 21-06 10 60 / Ss 40 70 75
Athletic and Recreational Special Construction
Includes: Special construction for athletic and recreational activities that are directly related to the adjacent construction.
Associated Masterformat Sections: 13 28 00
See Fundamental LOD Definitions

F1080 / 21-06 10 80 / --
Special Instrumentation
Includes: Instrumentation for measuring and recording phenomena such as stresses in structures, solar and wind energy, and effects
of earthquakes.
Associated Masterformat Sections: 13 50 00
See Fundamental LOD Definitions

F20 / 21-06 20 00 / Ss 15 30
Facility Remediation
Associated Masterformat Sections:

F2010 / 21-06 20 10 / Ss 15 30
Hazardous Materials Remediation
Includes: Remediation for abatement and removal and disposal of contaminated materials within structures.
Associated Masterformat Sections: 02 80 00
See Fundamental LOD Definitions

F30 / 21-06 30 00 / Ac 10 10 25
Demolition
Associated Masterformat Sections:

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 169
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

F3010 / 21-06 30 10 / Ac 10 10 25
Structure Demolition
Includes: Complete removal and disposal of structures.
Associated Masterformat Sections: 02 41 16
See Fundamental LOD Definitions

F3030 / 21-06 30 30 / Ac 10 10 25
Selective Demolition
Includes: Removal and disposal of parts of structures.
Associated Masterformat Sections: 02 41 19
See Fundamental LOD Definitions

F3050 / 21-06 30 50 / Ac 10 80
Structure Moving
Includes: Preparation and processes of relocating and raising structures.
Associated Masterformat Sections: 02 43 00
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 170
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G / 21-07 00 00 / --
SITEWORK
Associated Masterformat Sections:

G10 / 21-07 10 00 / Ac 10
Site Preparation
Associated Masterformat Sections: 01 89 13

G1010 / 21-07 10 10 / Ac 10 30
Site Clearing
Includes: Removal of vegetation from the site, including stripping of sod and soil, and tree pruning for site clearing.
Associated Masterformat Sections: 31 10 00 / 31 11 00 / 31 13 00 / 31 14 00 / 31 14 13 / 31 14 16

G1020 / 21-07 10 20 / Ac 10 10 25
Site Elements Demolition
Includes: Removal of above and below grade site improvements.
Associated Masterformat Sections: 02 41 13

G1030 / 21-07 10 30 / --
Site Element Relocations
Includes: Relocation of utility systems.

G1050 / 21-07 10 50 / Ac 10 75 65
Site Remediation
Includes: Remediation of contaminated sites.
Associated Masterformat Sections: 02 50 00 / 01 89

G1070 / 21-07 10 70 / --
Site Earthwork
Includes: Moving earth to establish new contours and elevations.
Associated Masterformat Sections: 31 20 00 / 01 89 13

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 171
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G1070.10 / 21-07 10 70 10 / --
Grading
Includes: Earthmoving to reshape contours.
Associated Masterformat Sections: 31 20 00 / 01 89 13
100 Inclusions:
• Surface as a plane
200 Inclusions:
• Surface interpolation between identified control elevations (e.g.,
building floor levels, existing hardscape)
300 Inclusions:
• Complete surface definition

G20 / 21-07 20 / --
Site Improvements
Associated Masterformat Sections: 01 89 16
100 Inclusions:
• Diagrammatic or schematic model elements.

G2010 / 21-07 20 10 / Ss 30 14 05
Roadways
Includes: Pavement, curbs and gutters, appurtenances, lighting, and vehicle fare collection for roadways. May Include: Site
earthwork.
Associated Masterformat Sections: 01 89 16

G2010.10
Roadway Pavement
100 See G20
200 Inclusions:
• Plan extent of pavement
• Nominal thickness

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 172
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Thickness of buildup
• Grading information (points and edges)
• 2D Pattern of joints

350 Inclusions:
• Grading information (points and edges)
• Expansion joints
• Path intersections
• Curb ramps
• Thickened edges

G2010.20
Roadway Curbs and Gutters
100 See G20
200 Inclusions:
• Full plan extents

300 Inclusions:
• Profile of curb
• Finish grade (top)
• Curb cuts and tapers (e.g. for ramps)

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 173
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Rough openings for storm drains or inlets

400 Inclusions:
• Chamfers and nosing
• joints

G2010.40
Roadway Appurtenances
See General Notes: Appurtenances

G2020 / 21-07 20 20 / Ss 40 85 72 11
Parking Lots
Includes: Pavement, curbs and gutters, appurtenances, lighting, and parking control equipment for parking lots.May Include: Site
earthwork
Associated Masterformat Sections: 01 89 16

G2020.10 / 21-07 20 20 10 / Ss 30 14 05 6
Parking Lot Pavement
Includes: Prepared and compacted soil and granular layers placed prior to installation of parking lot pavement. Includes: Finished
parking lot pavement of granular and asphaltic materials. Includes: Finished parking lot pavement with high bending resistance, usually
of concrete. Includes: Blocks or tiles used for parking lot pavement. Unit pavers set in mastic, sand, or mortar.
Associated Masterformat Sections: 32 10 00 / 32 12 00 / 32 13 00 / 32 14 00 / 32 15 00
See G2010.10

G2020.20 / 21-07 20 20 20 / Ss 30 75 45
Parking Lot Curbs and Gutters
Includes: Construction at perimeter of parking lot pavement to separate pavement from adjacent surfaces, provide vehicular restraint,
and facilitate drainage.
Associated Masterformat Sections: 32 16 13
See G2010.20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 174
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G2020.40 / 21-07 20 20 40 / Ss 40 85 72
Parking Lot Appurtenances
Includes traffic signals, signage, striping.
Associated Masterformat Sections: 32 17 00 / 32 17 13 / 32 17 43 / 10 14 53 / 32 17 23
See General Notes: Appurtenances

G2030 / 21-07 20 30 / Ss 30 14
Pedestrian Plazas and Walkways
Includes: Pavement, curbs and gutters, appurtenances, lighting, and pedestrian control equipment for pedestrian plazas and walkways.
Includes exterior steps and ramps. May Include: Site earthwork.
Associated Masterformat Sections: 01 89 16
For Pedestrian control equipment and other street or exterior furniture see E2010 / 21-05 20 10 Fixed Furnishings
For Handrails see C1090.10 / 21-03 10 90 10 Interior Railings and Handrails
For Site Earthwork and Grading see G1070 / 21-07 10 70 10 Grading
For Drainage see G3030 / 21-07-30-30

G2030.10
Pedestrian Pavement
See G2010.10

G2030.20
Pedestrian Pavement Curbs and Gutters
See G2010.20

G2030.30
Exterior Steps and Ramps
100 See G20
200 Inclusions:
• Full plan extents

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 175
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Stair grades at top and bottom
• Nosing

350 Inclusions:
• Thickened edges and/or footings

400 Inclusions:
• Additional profile and nosing details
• Dowels and reinforcing

G2030.40
Pedestrian Pavement Appurtenances
See General Notes: Appurtenances

G2030.70
Plaza and Walkway Lighting
See G4050

G2030.80
Exterior Pedestrian Control Equipment
See Fundamental LOD Definitions

G2040 / 21-07 20 40 /
Airfields
Includes: Pavement, curbs and gutters, appurtenances, lighting, and airfield signally and control equipment for airfields. May Include:
Site earthwork.
Associated Masterformat Sections: 01 89 16

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 176
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G2050 / 21-07 20 50 / Ss 30 14
Athletic, Recreational, and Playfield Areas
Includes: Surfacing, fencing, equipment, grandstands and bleachers, and lighting for athletic, recreational, and playfield areas. May
Include: Site earthwork.
Associated Masterformat Sections: 01 89 16
For Equipment and Play Structures, see sections 21-01 Substructure & 21-02 Shell.
100 See G20
200 See G20
300 Element modeling to include:
• Overall size and geometry of all elements
• Crossfalls & drainage slopes
• Linemarking

350 Element modeling to include:


• Fall zones
• Subsurface structure

G2060 / 21-07 20 60 / --
Site Development

G2060.60 Retaining Walls


100 See G20
200 Inclusions:
• Full plan extents

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 177
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• thickness of wall
• Top of wall
• depth may be approximate

350 Inclusions:
• All layers
• Footing

400 Inclusions:
• Joints
• Reinforcing

G2060.60 Stairs
See G2030.30

G2080 / 21-07 20 80 / --
Landscaping
Includes: Trees, grass, and planting
Associated Masterformat Sections: 31 20 00 / 01 89 13

G2080.10 Planting Irrigation


100 See G20
200 Inclusions:
• Schematic layout with approximate size, shape,
and location of mainline.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 178
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


300 Inclusions:
• Accurate mainline and point of connection
(POC)
• Major components (pumps, controllers, flow
sensors, etc.) and all fittings (valves, sprinkler
heads, etc) and other are shown, though may be
diagrammatic and not fully sized on laterals
• Major servicing and access clearance
requirements are depicted
• Concrete pads modeled at nominal thickness if
applicable
• Drip areas designated in plan
2

350 Inclusions:
• Mainline sleeving
• Drip lines, may be delineated as massing/area
element at specified elevation (in 3d model)
• Lateral lines and sleeving are modeled as
design-specified size and location

400 Inclusions:
• Modeled as actual construction elements
• Actual size, shape, spacing, and
location/connections of pipe, valves, fittings, and
sleeves

G2080.20 Turf and Grasses


Includes: Lawns and grasses including seeding and sodding.
For Grasses see G2080.40
100 See G20
200 Inclusions:
• Turf and seeding areas are shown. Areas may be
flat or not represented as 3D elements

300 Inclusions:
• All areas are separated by distinct species or mix
• Areas or masses follow the grading surface

350 Inclusions:
• Root system is accounted for within the depth of
the massing element.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 179
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


400

G2080.30 Plants: Trees and Large Shrubs

G2080.30.10 Groundcovers and Smaller Shrubs.


100 See G20
200 Inclusions:
• Larger mass, zones, or areas.
• May be a flat mass or mesh

300 Inclusions:
• All areas are separated by distinct species or mix
• 3D form that drapes on grade (mass or individual
plants)

350 Inclusions:
• Clear zones around trees
• Individual plants may be shown, though exact
location may not be precise.
• Root or container element shown for smaller
plants or included in thickness for massed areas

400 Inclusions:
• All individual plants are shown
• Location is exact for install

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 180
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G2080.30.20. Trees and Large Shrubs.


100 See G20
200 Inclusions:
• Individual trees location is shown

300 Inclusions:
• 3D rootball and clear zone for hole (at
installation) - Canopy size at maturity (75-100%
height or as noted)

350 Inclusions:
• Staking and/or guying
• Canopy clearances at maturity

400

G2080.80 Landscaping Activities

G2080.80.10 Planting Soil (Planting Preparation)


100 See G20

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 181
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


200 Inclusions:
• Full plan extents
• Nominal thickness of build up

300 Inclusions:
• Finish grade
• Actual thickness of buildup, including varying
bottom slope(s)

350 • Inclusions:
• Tapered edges

400

G2080.80.20 Existing Trees and Plant Protection


Includes: existing trees.
100 See G20
200 Inclusions:
• Existing trees, both to be removed and to retain
• Model representation of planting size and extents
may be approximate.
• Tree protection zone/massing for existing trees

300 Inclusions:
• Location of existing root zone is delineated in
plan in the model.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 182
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass


350 Inclusions:
• Tree protection element/fencing for existing trees
is modeled at correct height and shape

400

G30 / 21-07 30 / Ss 55 20
Liquid and Gas Site Utilities
Associated Masterformat Sections: 01 89 19
100 Inclusions:
• Diagrammatic or schematic elements;
200 Inclusions:
• Schematic layout of generic model elements with approximate
size, shape, and location of elements;

G3010 / 21-07 30 10 / Ss 55 70
Water Utilities
Includes: Water distribution for domestic consumption, fire fighting, and irrigation for a facility site and for multiple facilities. Includes
trenching and backfilling. Includes Liquid and Gas Site Utilities Supplementary Components as appropriate.
Associated Masterformat Sections: 33 10 00
100 See G30
200 See G30

G3010.10 / 21-07 30 10 10 / Ss 55 70 38
Site Domestic Water Distribution
Includes: Supply wells, piping, equipment, storage tanks, and water ponds and reservoirs.
Associated Masterformat Sections: 01 89 19 / 33 21 00 / 33 11 00 / 33 12 00 / 33 12 13
33 12 16 / 33 12 19 / 33 12 23 / 33 12 33 / 33 13 00 / 33 16 00 / 33 47 19.13 / 33 47 13.13
33 47 16.13
100 See G30
200 See G30

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 183
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G3010.30 / 21-07 30 10 30 / Ss 55 30 96
Site Fire Protection Water Distribution
Includes: Supply wells, piping, equipment, storage tanks, and water ponds and reservoirs.
Associated Masterformat Sections: 01 89 19 / 33 21 00 / 33 11 19 / 33 12 00 / 33 12 13 / 33 12 16 / 33 12 19 / 33 12 23 / 33
12 33 / 33 16 00 / 33 47 19.33 / 33 47 13.13 / 33 47 16.13
100 See G30
200 See G30

G3020 / 21-07 30 20 / --
Sanitary Sewerage Utilities
Includes: Sanitary sewerage for a facility site and for multiple facilities. Includes piping, septic tanks that serve multiple facilities,
structures, and lagoons. Includes trenching and backfilling. Includes Liquid and Gas Site Utilities Supplementary Components as
appropriate.
Associated Masterformat Sections: 33 30 00 / 01 89 19
100 See G30
200 See G30

G3020.20 / 21-07 30 20 20 / Ss 50 35 08 30
Sanitary Sewerage Piping
Associated Masterformat Sections: 33 31 00 / 33 33 00 / 33 34 00
100 See G30
200 See G30
300 Inclusions
Design-specified elements

G3020.50 / 21-07 30 20 50 / Ss 50 35 08
Sanitary Sewerage Structures
Associated Masterformat Sections: 33 39 00 / 33 39 13 / 33 39 23
100 See G30
200 Inclusions:
Element envelopes
300 Inclusions:
Design-specified elements

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 184
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G3030 / 21-07 30 30 / Ss 50 35 80
Storm Drainage Utilities
Includes: Storm drainage for surface or combination of surface and subsurface water for a facility site or for multiple facilities.Includes
piping, culverts, water drains, drainage pumps, Subdrainage, and storm drainage ponds and reservoirs. Includes trenching and
backfilling. Includes Liquid and Gas Site Utilities Supplementary Components as appropriate.
Associated Masterformat Sections: 01 89 19
100 See G30
200 See G30

G3050 / 21-07 30 50 / Ss 70 30
Site Energy Distribution
Includes: Energy distribution for a facility site or multiple facilities. Includes hydronic heating, steam energy, and hydronic cooling
distribution. Includes trenching and backfilling. Includes Liquid and Gas Site Utilities Supplementary Components as appropriate.
100 See G30
200 See G30

G3060 / 21-07 30 60 / --
Site Fuel Distribution
Includes: Gas, fuel-oil, gasoline, diesel fuel, and aviation fuel distribution for a facility site or multiple facilities. Includes trenching and
backfilling. Includes Liquid and Gas Site Utilities Supplementary Components as appropriate.
100 See G30
200 See G30

G3090 / 21-07 30 90 / --
Liquid and Gas Site Utilities Supplementary Components
Includes: Common work results for utilities and instrumentation and control to be included in liquid and gas utility elements above as
appropriate.
See General Notes: Supplementary Components

G40 / 21-07 40 / --
Electrical Site Improvements
Associated Masterformat Sections: 01 89 26
100 Inclusions:
• Diagrammatic or schematic model elements:
• conceptual and/or schematic layout;

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 185
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G4010 / 21-07 40 10 / --
Site Electric Distribution Systems
Description: Electrical wiring systems to distribute electrical power to on the Site. Includes Duct Banks, Pullboxes, vaults and
transformers from the utility point of connection, to the building’s main electric room.
Associated Masterformat Sections: 01 89 26
100 See G40
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment;
300 Inclusions:
• Design-specified size, shape, spacing, and location of
equipment and associated components;
• Approximate allowances for clearances required for all
specified supports and seismic control;
• Access/code clearance requirements modeled.
350 Inclusions:
• Actual size, shape, spacing, and location of raceways,
boxes, and enclosures.
• Actual size, shape, spacing, and location for supports
and seismic control.
• Actual size, shape, and location/connections of
equipment and support structure/pads.
• Actual floor and wall penetration elements are
modeled.
• Actual access/code clearance requirements modeled.

G4050 / 21-07 40 50 / Ss 70 80 25
Site Lighting
Description: Luminaires, lighting equipment, ballasts, and accessories. Includes fluorescent, high intensity discharge, incandescent,
mercury vapor, neon, and sodium vapor lighting. Includes Pole Mount, Building Mount and on-grade fixtures for exterior lighting.
Associated Masterformat Sections: 26 56 29
100 See G40
200 Inclusions:
• Schematic layout with approximate size, shape, and
location of equipment;
300 Inclusions:
• Design-specified size, shape, and location of lighting
fixtures;
• Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control;
• Access/code clearance requirements modeled.
• Poles

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 186
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

Uniformat / Omniclass / Uniclass

G50 / 21-07 50 / Ss 75 10
Site Communications
100 Diagrammatic or schematic model elements:
• conceptual and/or schematic layout;
• design performance parameters as defined in the BEP
to be associated with model elements as non-graphic
information.

G5010 / 21-07 50 10 / Ss 75 10
Site Communications Systems
Description: Conduit Systems for routing of Communication trunk systems.
Associated Masterformat Sections: 33 80 00
100 See G40
200 See D6010.10
300 See D6010.10

G90 / 21-07 90 / --
Miscellaneous Site Construction
Associated Masterformat Sections: 01 89 29

G9010 / 21-07 90 10 / Ss 37 50 92
Tunnels
Includes: Vehicular, pedestrian, and service tunnels. Includes tunnel boring, bracing and jacking work, linings and casing, grouting
support systems, boring machines, and control and spoil removal systems. Includes Tunnel Construction Related Activities as
appropriate.
Associated Masterformat Sections: 31 70 00 / 01 89 29
See Fundamental LOD Definitions

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 187
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

USER GUIDE

0 Overview

0.1 Description
The Level of Development (LOD) Specification is a reference that enables practitioners in the AEC Industry to specify and articulate
with a high degree of clarity the content and reliability of Building Information Models (BIMs) at various stages in the design and
construction process.
The Specification is a detailed interpretation of the LOD schema developed by AIA Contract Documents for its E201 2022 BIM Exhibit
for Sharing Models with Project Participants defining and illustrating characteristics of model elements of different building systems at
different Levels of Development, organized according to CSI Uniformat 20105. Its intent is to help explain the LOD framework and
standardize its use so that it becomes more useful as a communication tool.
For Level of Development Definitions See Fundamental LOD Definitions above.

BIM as a Communication Tool


The LOD schema addresses several issues that arise when a BIM is used as a communication or collaboration tool, i.e., when
someone other than the author extracts information from it:
1) During the design process, building systems and components progress from a vague conceptual idea to a precise description.
In the past, there has been no simple way to designate where a model element is along this path. The author knows, but
others often don’t.
2) It’s easy to misinterpret the precision at which an element is modeled. Hand drawings range from pen strokes on a napkin to
hard lines with dimensions called out, and the precision of the drawing can be inferred from its appearance. In a model
though, a generic component placed approximately can look exactly the same as a specific component located precisely, so
we need something besides appearance to tell the difference.
3) It is possible to infer or extract information from a BIM that the author doesn’t intend – unconfirmed dimensions can be
measured with precision, assembly information often exists before it’s been finalized, etc. In the past, this issue has been
sidestepped with all-encompassing disclaimers that basically say, “Since some of the information in the model is unreliable,
you may not rely on any of it.” The LOD framework allows model authors to clearly state the reliability of given model
elements, so the concept becomes “Since some of the information in the model is unreliable, you may only rely on it for what I
specifically say you can.”
4) In a collaborative environment, where people other than the model author are depending on information from the model in
order to move their own work forward, the design work plan takes on high importance – it is necessary for the model users to
know when information will be available in order to plan their work. The LOD framework facilitates this.
The LOD Framework addresses these issues by providing an industry-developed standard to describe the state of development of
various systems, assemblies, and components within a BIM. This standard enables consistency in communication and execution by
facilitating the detailed definition of BIM milestones and deliverables.

0.1.1 LODs and Design Phase


The LODs are not defined by design phases. Rather, design phase completion, as well as any other milestone or deliverable, can be
defined through the LOD language. There are several important reasons for this approach:

5
UniFormatTM Numbers and Titles used in this publication are from UniFormatTM, published by CSI and
Construction Specifications Canada (CSC), and are used with permission from CSI. For a more in-depth
explanation of UniFormatTM and its use in the construction industry visit http://www.csinet.org or contact CSI, 110
South Union Street, Suite 100, Alexandria, VA 22314. (800) 689-2900.
Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 188
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

1) There is currently no detailed standard for the design phases. Many architects have created in-house standards, but these
differ from one firm to the next, and even within a single firm the requirements are sometimes adjusted to the needs of a
project.
2) Building systems progress from concept to precise definition at different rates, so at any given time different elements will
be at different points along this progression. At completion of the Schematic Design phase, for example, the model will
include many elements at LOD 200, but will also include many at LOD 100, as well as some at LOD 300, and possibly
even LOD 400.

0.1.2 LODs and Model Definition


There is no such thing as an “LOD ### model.” As previously noted, project models at any stage of delivery will invariably contain
elements and assemblies at various levels of development. As an example, it is not logical to require an “LOD 200 model” at the
completion of the schematic design phase. Instead, the “100% SD Model” will contain modeled elements at various levels of
development.

0.2 Intent
0.2.1 Not a Set of Requirements
The Specification is not a set of requirements as to what is modeled when or by whom. Rather it is a language by which users can
define these requirements for their own firms or projects. This clear articulation allows model authors to define what their models can be
relied on for, and allows downstream users to clearly understand the usability and the limitations of models they are receiving.
To accomplish the Specification’s intent, its primary objectives are:
1) To help teams, including owners, to specify BIM deliverables and to get a clear picture of what will be included in a BIM
deliverable
2) To help design managers explain to their teams the information and detail that needs to be provided at various points in the
design process, and to track progress of their models
3) To allow downstream users to rely on specific information in models they receive from others.
4) To provide a standard that can be referenced by contracts and BIM execution plans.

0.2.2 Complements a BIM Execution Plan (BEP)


This Specification does not replace a project BEP, but rather is intended to be used in conjunction with such a plan, providing a means
of defining models for specific information exchanges, milestones in a design work plan, and deliverables for specific functions.

0.3 Background
0.3.1 AIA Effort
In 2008, the AIA published its first set of Level of Development definitions in AIA Document E202™-2008 Building Information Modeling
Protocol. Due to the rapidly evolving nature of the use of BIM, the AIA evaluated the E202–2008, including the LOD definitions. The
result is the updated and reconfigured Digital Practice documents, AIA E203™–2013, Building Information Modeling and Digital Data
Exhibit, AIA G201™–2013, Project Digital Data Protocol Form, and AIA G202™–2013, Project Building Information Modeling Protocol
Form, which are accompanied by a detailed guide document entitled Guide and Instructions to the AIA Digital Practice Documents. The
AIA’s updated Digital Practice documents include revised LOD definitions.

0.3.2 BIMForum Effort


In 2011 the BIMForum initiated the development of this LOD Specification and formed a working group comprising contributors from
both the design and construction sides of the major disciplines. To help further the standardization and consistent use of the LOD
schema, and to increase its usefulness as a foundation for collaboration, the AIA licensed the BIMForum to utilize its latest LOD
definitions in this Specification. The BIMForum working group first interpreted the AIA’s basic LOD definitions for each building system,
and then compiled examples to illustrate the interpretations. Because BIM is being put to an ever-increasing number of uses, the group

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 189
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

decided that it was beyond the initial scope to address all of them. Instead, the definitions were developed to address model element
geometry, with three of the most common uses in mind – quantity take-off, 3D coordination and 3D control and planning. The group felt
that in taking this approach the interpretations would be complete enough to support other uses.

1 Using the Specification

1.1 Details
1.1.1 Order of Precedence
The body of this Specification expands on the Fundamental Definitions as they apply to specific building systems and sub-systems. In
the event of any conflict, more specific expansions take precedence over less specific expansions and Fundamental Definitions, e.g.
the expanded definitions for C1010 take precedence over those for C10, which in turn take precedence over the Fundamental
Definitions.

1.1.2 LOD Definitions as Minimum Requirements


The LODs provide five snapshots of the progression of an element from conceptual to specified – there are many steps in this
progression between the defined LODs. The LOD definitions, then, should be considered minimum requirements – i.e. an element has
progressed to a given LOD only when all the requirements stated in the definition have been met.

1.1.3 LOD Definitions are Cumulative


For a given element each LOD definition includes the requirements of all previous LODs. Thus, for an element to qualify for LOD 300 it
must meet all the requirements for 200 and 100 as well as those stated in the LOD 300 definition.

1.1.4 Model Element Author


This document does not prescribe who the author of a particular component at a given LOD should be – the sequence of responsibility
for modeling various systems will vary from one project to another. To accommodate this variation this document defers to the concept
of Model Element Author (MEA) as defined in the AIA E203-2013: “The Model Element Author is the entity (or individual) responsible
for managing and coordinating the development of a specific Model Element to the LOD required for an identified Project milestone,
regardless of who is responsible for providing the content in the Model Element." 6

1.1.5 2D Supplementary Drawings


In current practice models are often supplemented with 2D information such as detail drawings. This Specification does not address
this supplementation, but rather deals only with what is modeled in 3D and non-graphic information associated with the modeled
elements.

1.2 Project-Specific Information


As mentioned in the Overview above, this Specification is intended to be used in conjunction with a project BIMXP. Many information
needs will vary from project to project, even for identical elements. This kind of information is therefore not included in the LOD
definitions specified here, but rather is left to be addressed in individual BIMXPs. The following are some notable examples.

1.2.1 Size Thresholds


In most projects, a determination is made to model certain elements only if they are over a specified size – e.g. conduit less than 1/2”
(10 mm) diameter is not modeled. These size thresholds do not consistently correspond to certain LODs, and they vary from project to

6
AIA Document E203-2013 Building Information Modeling and Digital Data Exhibit, Article 1.4.6. Copyright ©
American Institute of Architects 2013. All rights reserved. Definition quoted here by permission.
Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 190
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

project. Thus, they are not specified in the LOD definitions but rather in the project’s BIMXP, for example using the “Notes” cells in the
Model Element Table of the AIA G202-2013.

1.3 Using the Specification with a BEP


Most BEPs include a section that details milestones as well as information exchanges – models to be produced to exchange specific
information at specific points in a specific BIM use. In most cases, though, current practice is to accompany these models with the
common “for reference only” disclaimer, diluting the effectiveness of the exchange. Referencing this Specification in the BIMXP and
using it to concisely define the milestone and information exchange models brings many efficiencies to the process – among them:

1.3.1 Reliance
As noted above (see “BIM as a Communication Tool”), a major problem with allowing others to rely on a BIM is that it can contain
information the author doesn’t intend. By defining a model through the LOD Specification the author can limit reliance to only what
he/she specifically states.

1.3.2 Multiple uses


Much model information is common across several information exchanges. This Specification facilitates the definition of models that
will support multiple exchanges.

1.3.3 Efficient sequencing


The development of models as the design and construction process progresses follows logical sequences – much information
depending on the prior development of other information. The definition of milestones, information exchanges, and other deliverables
through this Specification facilitates the orderly sequencing of models to align with efficient development of information.

1.3.4 Avoidance of over-modeling


The LOD Specification facilitates the application of a pull-planning process to the modeling effort, limiting the development of model
elements and information to that which the team identifies as useful.
Note that the definition and sequencing of models usually cannot be set in stone when the BIMXP is first developed. In most cases the
modeling plan must evolve as the project progresses.

1.4 Implementation of the Specification


Currently, two methods of implementation have been developed.

1.4.1 Rely on the Model Element Table


Project team refers to a Model Element Table such Article 3.3 of the AIA G202-2013 or Part II of this Specification for the LODs of
model elements. In this method, all elements referred to in a given Model Element Table line item are assumed to be at the LOD stated
there. E.g. if the table lists interior doors as LOD 200 for a given model, all interior doors within the model are assumed to be at LOD
200.

1.4.2 Include LOD Designations as Attributes of Individual Model Elements


All elements within the model are provided with two attributes – Current LOD (the actual LOD of the element) and Target LOD (the LOD
specified for that element in the Model Element Table). Elements default to a Current LOD of 100 or 200 as appropriate, and this
attribute is elevated as the element is more fully developed. This method offers more flexibility and reliability, allowing differentiation
between individual elements within a single model element table line item. Several software offerings provide the functionality of
highlighting elements of various LODs or elements whose Current LOD is less than the Target LOD.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 191
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

2 ORGANIZATION OF THE SPECIFICATION

2.1 Geometric and Attribute Information


To facilitate use of this Specification Attachment 1, Model Development Specification (MDS) has been provided. This attachment is a
set of spreadsheets that can be used to collect and correlate LOD Information for a specific project.
A model element can contain two types of information: a) the element’s geometry and b) associated numeric and/or textual attributes.
To address these types of information this Specification contains two parts:

2.1.1 Part I: Element Geometry


Part I consists of narrative descriptions and illustrations of specific model elements at each LOD. Part I forms the bulk of this
document.

2.1.2 Part II: Associated Attribute Information


Part II is contained in Attachment 1, a workbook that begins with the Model Element Table which mirrors the layout of the Model
Element Table in the AIA G202-2013 Building Information Modeling Protocol Form, and can be referenced by that document. The
Model Element Table references Attribute Tables that contain attribute information for various building systems.

2.1.3 Model Element Table

Figure 1. Model Element Table

2.1.4 Building Systems


The rows of the Model Element Table (Figure 1) are building elements listed in accordance with CSI Uniformat 2010. The table also
lists Relevant Attribute Tables for each system, referring to the tabs containing attribute information for the associated system(s). If
desired, users can add Attribute Tables for specific line items.

2.1.5 Milestones/Deliverables
The table includes columns for defining the LODs for various milestones within a project. Each milestone column has three sub-
columns: Level of Development (LOD), Model Element Author (MEA), and Notes. The table in Attachment 1 shows standard milestones
for the completion of the traditional design phases as well as examples of Project-Specific Milestones for interim reviews, specific

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 192
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

deliverables, BIM-Use information exchanges, etc. Users are encouraged to modify and add to these milestones as necessary. Once
the milestones for a project have been determined, they can be re-ordered into a logical sequence as in Figure 2.

Figure 2. Adding Milestones/Deliverables to the Model Element Table

2.1.6 Attribute Tables

Figure 3. Typical Attribute Table

2.1.7 Attribute Table Anatomy


Attribute Tables consist of two parts.
1) Part 1, Attribute Description, lists Attributes relevant to the associated building system(s).
• Attributes are grouped into two categories as shown – Baseline and Additional.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 193
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

o The Baseline is the suggested list of attributes to be populated when no other requirements are known (BIM Uses,
specific deliverables, etc.).
o The Additional category may be thought of as a “shopping list” – a list of possible attributes the team may want to
consider.
• Data Types. For simplicity, the published Attribute Tables use only the following data types, but users setting up data for
use in specific software may want to add others.
Text An alphanumeric string not intended for use in
calculations. E.g. room numbers are often considered
text (even where they only contain numbers) since the
numbers are not useful for calculations.
Number A numerical value that can be entered directly into a
program that will use it as input to calculations. Note
that no distinction is made here between integers and
real numbers.
Logical Boolean in computer science terminology. A binary
yes/no indication. Values for this type can be T or F, 1 or
0.
Date ISO format is used in these tables: yyyy-mm-dd
Time ISO format is used in these tables: hh:mm:ss
Datetime ISO format is used in these tables: yyyy-mm-
ddThh:mm:ss

2) Part 2, Milestones, is used to mark the attributes required for specific milestones and deliverables. The tables in Attachment 1
include example milestones, but users will customize the tables by copying the milestones they created for the Model Element
Table.

2.1.8 MEPF Attribute Tables


The MEPF attribute tables use a somewhat different format than other sections, since components from
multiple systems might be used to make up a specific element. For example, an air handler is primarily a D30
HVAC element, but can include plumbing, fire protection and electrical elements as well.
The MEP Systems tabs are grouped into two types:
• System component elements: D20 Plumbing, D30 HVAC, D40 Fire Protection and D50 Electrical.
• System distribution elements such as ducts, pipes, and cables: D Air Distribution, D Fluid Gas
Distribution and D Electrical Distribution.
MEPF attribute tables are broken down into two main sections
• Global: Attributes that are common to all elements within the table
• Item-Specific: The suggested set of additional attributes that are specific to an individual type of
element. In many tables, the Individual elements are organized into a hierarchy of classes and sub-classes.
In these cases, the attributes applicable to a specific element include those listed for the element itself plus
those listed in any of the classes above it in the hierarchy. E.g. as Figure 4 shows, the attributes for an oil
meter include all those shown in bold.
Note: System Component elements use both the Global and Item-Specific attributes sections, while System
Distribution elements use only the Item-Specific attribute section.

Figure 4. MEPF
Attribute Table
Breakdown Structure

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 194
Level of Development Specification Part I www.bimforum.org/lod
Version: 2023

2.1.9 Using the Attribute Tables


There are many ways to use the Attribute Tables – three are shown here.
1) Project teams adopt the Baseline attribute lists. The pre-populated correlation between Attributes and LODs represents
current practices of proficient BIM users in the AEC industry.
2) Project teams create a custom correlation between LODs and Attribute population requirements. In this case the project team
would edit the LOD Profile section to reflect the specific requirements of the project.
3) Project teams create new, project specific milestones and define Attribute population requirements in the Milestones
sections. This approach will give project teams the greatest flexibility for defining Attribute population requirements.
Note that the element attribute author can be entered in the LOD profile instead of an “x” to indicate who is responsible for providing the
information.

Send feedback to [email protected]

Copyright © 2023 BIMForum. All rights reserved


This document is copyrighted under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License. 195

You might also like