CHW2204-00-EL-SPE-7301 Rev1 Specification For Electrical System
CHW2204-00-EL-SPE-7301 Rev1 Specification For Electrical System
CHW2204-00-EL-SPE-7301 Rev1 Specification For Electrical System
1 NO COMMENTS
TECHNICAL REQUISITION No. 2 MINOR COMMENTS
WF2204-BD-ST-TRD-0033-1 3 MAJOR COMMENTS
4 INFORMATION ONLY
REVIEWED BY:
Procurement of Equipment/ Systems for four (4)
Blasting & Painting Workshops (BP-01/02/03/04)
DATE:
PURCHASE ORDER NO. 78-2023/PTSC-KHDT/HD
REVISION HISTORY
Revision
No Page Content Revision Date No. Note
1 20 Issued for Review 19/05/2023 A
2 20 Issued for Construction 15/06/2023 0
3 20 Issued for Construction 25/06/2023 1
PROCUREMENT OF EQUIPMENT/SYSTEMS
FORFOUR (4) BLASTING & PAINTING
WORKSHOPS (BP-01/02/03/04)
Doc No.:
CHW2204-00-EL-SPE-7301
SPECIFICATION FOR ELECTRICAL SYSTEM Page 1 of 20
Rev. 1
1. INTRODUCTION
Package’s name: “Procurement of Equipment/ Systems for four (4) Blasting & Painting
Workshops (BP-01/02/03/04)”. The project’s name: “Investment of Corrosion Protection
Equipment”. The project is comprised of:
- Blasting and Painting workshop: 04 Workshops;
- Process equipment system for blasting and painting: 04 systems;
- Equipment control system; Electrical supply system; Lighting system: 04
System;
- Fire fighting systems: 01 System;
- Utilities building; Drainage ditch; Other utilities…: 01 System
2. PURPOSE OF DOCUMENT
This document provides the design criteria for design and engineering of
electrical supply system for for “Pakage: Equipment/ Systems for four (4) Blasting &
Painting Workshops (BP-01/02/03/04)” - (PROJECT).
The Contactor shall submit technical requirements of its equipment, which meets the
requirements detailed herein.
The electrical supply system shall cover the following:
- Electrical calculation
- Power distribution system and single line diagrams
- Illumination System
- Cabling System
The designed electrical system shall provide:
- Safety to personnel and equipment
- Reliability of service
- Minimum fire risk
- Ease of maintenance and convenience of operation
- Adequate provision of future expansion or modification
- Maximum interchangeability of equipment
- Automaticprotection of all electrical equipment throughthe
MCCB’s.
3. DEFINITION AND ABBREVATION
3.1 Definition
Project Investment of Corrosion Protection Equipment/ Systems project
Client Petrovietnam Technical Services Corporation (PTSC)
PROCUREMENT OF EQUIPMENT/SYSTEMS
FORFOUR (4) BLASTING & PAINTING
WORKSHOPS (BP-01/02/03/04)
Doc No.:
CHW2204-00-EL-SPE-7301
SPECIFICATION FOR ELECTRICAL SYSTEM Page 1 of 20
Rev. 1
3.2 Abbrevation
Abbreviations used in this document are described below:
A Amperes
AC Alternative Current
ACB Air Circuit Breaker
DB Distribution Board
DC Direct Current
LP Lighting Panel
Ex-d Explosion Protection Technique Type d : Flameproof
Ex-e Explosion Protection Technique Type e : Increased Safety
ePC Engineering, Procurement and Construction
HDPE High Density Poly Ethyene
HMI Human Machine Interface
Hz Hertz (cycles per second)
IEC International Electro-technical Commission
IES Illuminating Engineering Society
IOM Installation Operation and Maintenance
IP Ingress Protection
ITP Inspection and Test Plan
LV Low Voltage, exceeding extra-low voltage, but not
exceeding 1000VAC or 1500VDC
M Motor
mA Milliampere
MCB Miniature Circuit Breaker
MCCB Molded Case Circuit Breaker
Min Minimum
MDR Manufacturer’s Data Report
NA Not applied
NC Not Controlled
PF Power Factor
PVC Polyvinyl Chloride
SHF2 Halogen free, flame retardant thermoplastic as defined byIEC
60092-359
SLD Single Line Diagram
SPD Surge Protection Device
PROCUREMENT OF EQUIPMENT/SYSTEMS
FORFOUR (4) BLASTING & PAINTING
WORKSHOPS (BP-01/02/03/04)
Doc No.:
CHW2204-00-EL-SPE-7301
SPECIFICATION FOR ELECTRICAL SYSTEM Page 1 of 20
Rev. 1
Hazardous Area
Electric Equipment
Zone 1 Zone 2
Distribution Board (Panel is not recommended Ex-d Ex-d/Ex-e
toinstalled in hazardous areas)
Low Voltage Motor Ex-d Ex-d/Ex-e
Local Control Station (LCS) Ex-d Ex-d/Ex-e
Lighting Fixture Ex-d Ex-d/Ex-e
Socket and Plug Ex-d Ex-d/Ex-e
Power Junction box Ex-d Ex-d/Ex-e
Cable gland Ex-d Ex-d/Ex-e
Frequency fluctuation:
- Steady state
5 ±0.2 Hz;
- Transient state:
±0.5 Hz
Short-circuit fault Rating
6 - Main busbar: 65kA
- Branch busbar: 36kA
7 Power factor require Existing
Nominal input voltage for power
8 distribution boards/Lighting 230V or 400V
panel/Equipment systems
12.2 Equipment Rated Voltage
Unless otherwise specified, the rated voltage of electrical loads shall be listed
asbellow:
With the enclosures completely open all live parts shall be shrouded to provide IP21
protection at a minimum.
The distribution board shall be designed in such a manner that all components shall be
operated and maintained safely and shall not present a hazard to personnel or cause damage
to other equipment.
13.3 Cable terminations
Wire ways shall be provided in the distribution board.
Wire ways, gland entries shall be dimensioned and sized to ensure that all incoming
and outgoing cables can be installed and connected easily. The Contractor shall indicate the
basis, who has used for sizing cables and shall be responsible for confirming cable sizes with
the PURCHASER prior to design and manufacture to ensure that the cables can be glanded
and terminated easily and the requirement for additional terminals identified.
Terminal block insulation shall be of non-rigid, non-hygroscopic, non- tracking, non-
inflammable material.
Terminals shall be of vibration proof construction and incorporate captive pressure
screws, which do not bear directly on the wire. The pressure screws shall have an inherent
locking feature. Locking bars shall be fitted.
14. WIRING AND TERMINATION
14.1 General
The identification colour for power cables insulation comply with IEC 60445 shall be
as follows:
- Single Conductor - BLACK
- Twin Conductors - BLACK (L) and BLUE (N)
- Twin Conductors + PE - BLACK (L1), BLUE (N) and GREEN with
YELLOW stripe
- Three Conductors - BLACK (L1), BROWN (L2) and GREY (L3)
- Three Conductors + PE - BLACK (L1), BROWN (L2), GREY (L3) and
GREEN with YELLOW stripe
- Four Conductors - BLACK (L1), BROWN (L2), GREY (L3) and BLUE(N)
- Four Conductors + PE - BLACK (L1), BROWN (L2), GREY (L3),BLUE
- (N) and GREEN with YELLOW stripe
- All control circuit wiring shall be minimum 1.5 sq. mm stranded, tinned copper.
14.2 Installation of Wiring
All internal wiring shall be run in flame retardant non-metallic ducts in such a manner
that wiring can be checked against diagrams. These cable ducts shall be fitted with a
removable cover. A minimum of 20% spare space shall be allowed in these ducts after
PROCUREMENT OF EQUIPMENT/SYSTEMS
FORFOUR (4) BLASTING & PAINTING
WORKSHOPS (BP-01/02/03/04)
Doc No.:
CHW2204-00-EL-SPE-7301
SPECIFICATION FOR ELECTRICAL SYSTEM Page 1 of 20
Rev. 1
switches shall be kept to a minimum. Lights for outdoor areas shall becontrolled by switchs
(If any).
The lighting system shall be designed to provide the average illumination level as
listed below:
Table 1: The number of lighting fixtures was used to calculate
Type of Lighting Fixtures Location Quantity
LED Highbay and Headlight 200W, Indoor-hazadous (*) set
28.600Lm
LED tube 2x18W Indoor-Non hazadous (..)
S 16 S 16
16 < S 35 S/2
S > 35