Modbus TCP - IP Protocol

The document discusses communication between a Siemens S7-1500 PLC and a Siemens S7-1200 PLC using Modbus TCP/IP. It describes configuring the PLCs and programming blocks in TIA Portal to establish connection as client and server to transfer data.

Uploaded by

Wanderson Rainer
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
248 views

Modbus TCP - IP Protocol

The document discusses communication between a Siemens S7-1500 PLC and a Siemens S7-1200 PLC using Modbus TCP/IP. It describes configuring the PLCs and programming blocks in TIA Portal to establish connection as client and server to transfer data.

Uploaded by

Wanderson Rainer
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Eng.

BOUZID Osema

PLC communication via Modbus TCP/IP

Communication between S7-1500 PLC and S7-1200


Communication via Modbus TCP/IP

Client “S7-1500” Server “S7-1200”


OSI Model & Modbus

Modbus TCP/IP Modbus RTU

Modbus Application Layer Modbus Application Layer

TCP

IP

MAC Master / Slave

Ethernet physical Layer RS-232 , RS-485


Modbus Mode
Modbus Mode
Modbus Mode
Modbus Mode
Eng. BOUZID Osema

TIA Portal

Programming and configuration in the TIA portal


Configuring Communication S7-1200

Enable the use of clock memory byte


Configuration of Client ( S7-1500 PLC)

In the TIA Portal, after selecting the CPU S7-1500 and the CPU S7-1200, click on the Porfinet port to
create a channel between the S7-1500 and the S7-1200.
S7-1500

Put IP address of S7-1500 PLC (192.168.0.4)


Program blocks (Client)
Create DB of write_db

Proprities DB ”write_db” -> Disable optimized block access -> Ok


CONNECT ( Client )

The following structures (system data types) can be used:


TCON IP v4: Includes all address parameters that are required for establishing a programmed connection.
1 - InterfacelD :- Hardware identifier of the local interface (value range: 0 to 65535).
2 - ID Reference to this connection (value range: 1 to 4095).
3 - Connection Type Select 11 (decimal) for TCP
4 - Active Establishe ID for the manner in which the connection is established
Select TRUE for active connection establishment (Client Write data to Server)

5 - Remote Address IP address of the connection partner (Modbus server).


6 - Remote Port Port number of the remote connection partner (value range: 1 to 49151). the TCP/IP
protocol (default value: 502).
7 - Local Port Port number of the local connection partner: Any port: "0
Program blocks (Client)
Create DB of connection Cleint

Proprities DB ”connect_Client” -> Disable optimized block access -> Ok


TIA Portal

Main OB

Netw : MB_CILENT
REQ : Activate transmission
DIS CONNECT : Disable communication
MB_MODE : Modbus Mode 0 = Read , 1 = Write , ... (page 5 )
MB_DATA_ADDR : Modbus Data Addresse (page 5)
MB_DATA_LEN : ‫طول البيانات‬
MB_DATA_PIR : (page 11) )Read ‫ هو‬Mb_Mode ‫ ) أو كتلة البيانات التي يرسلها الخادم إىل العميل (إذا كان‬Write ‫ هو‬MB_Mode ‫كتلة البيانات المنقولة إىل الخادم (إذا كان‬
CONNECT : DB-CONNECT Client (page 12-13)
Configuration of Server ( S7-1200 PLC)

Add Subbnet , IP Addresse (Put IP address of S7-1200 PLC (192.168.0.5) ) .


S7-1200
Program blocks (Server)
Create DB of Holding register

Proprities DB ”hold_reg” -> Disable optimized block access -> Ok


Program blocks (Server)
Create DB of connection server

Proprities DB ”connect_server” -> Disable optimized block access -> Ok


CONNECT ( Server )

The following structures (system data types) can be used:


TCON IP v4: Includes all address parameters that are required for establishing a programmed connection.
1 - InterfacelD :- Hardware identifier of the local interface (value range: 0 to 65535).
2 - ID Reference to this connection (value range: 1 to 4095).
3 - Connection Type Select 1 1 (decimal) for TCP
4 - Active Establishe ID for the manner in which the connection is established
Select TRUE for active connection establishment (Server Write data to Client)

5 - Remote Address IP address of the connection partner (Modbus client).


6 - Remote Port Port number of the remote connection partner (value range: 1 to 49151). the TCP/IP
protocol (default value: 502).
7 - Local Port Port number of the local connection partner: Any port: "0"
TIA Portal

Main OB

Netw : MB_SERVER
DISCONNECT : Disable communication
MB_HOLD_REG : Data block of the holding register which reads or writes to or from Client (Page 16)
CONNECT : DB-CONNECT Server (page 18)
Eng. BOUZID Osema

IndustriTech Nexus

AUTOMATION
T E C H N O L O G Y