LVSG REV004
LVSG REV004
LVSG REV004
GENCON OR
PM LOGO
Carmona, Cavite
2. CONSTRUCTION TESTING
YES NO Remarks:
3. AS-BUILT DRAWINGS
YES NO Remarks:
Company
Signature
Print name
Date
General Comments:
Conforme
Item No. Descriptions Comments
Yes No
Is the LVS conform in accordance with the approved plans,
1
shopdrawing/submittals, and specification. ü
Are the bus bar joint connection/bolts has been tighthen base
2
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances
ü
Verify that the current and voltage transformer ratios corresponds to drawing.
4
ü
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
5
ü
I s the equipment grounding has been check and tested.
6
ü
Lubrication requirements:
7 •
•
Verify appropriate lubrication on moving current-carrying parts.
Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 •
•
Mechanical Interlock
Electrical Interlock
ü
Is the LVS Control Interface to Generator Sychronizing Panel
9
Control has been completed. ü
Check if the all the contruction punchlist has been completed, the
10
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
ü
Verify correct functioning of drw-out disconnecting and grounding contacts and
15 interlocks.
ü
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
16 enclosure
ü
Verify if insulation resistance test for main bus and sections are performed or
17 conducted
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •
•
connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •
•
connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •
•
connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •
•
connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •
•
connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510067
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.040 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.427 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Breaker closing mecahnism ü PASSED
Breaker tripping mechanism ü PASSED
Mechanical interlocking ü PASSED
Breaker withdrawing facilities ü PASSED
Breaker on and off indication ü PASSED
Padlocking facilities ü PASSED
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510076
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.047 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.402 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510090
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.179 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410345
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.488 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.261 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410329
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.478 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.047 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.266 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410362
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.497 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.106 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.261 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410353
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.529 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.106 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN23150949
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.496 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.287 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 800 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150899
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.8 3.215 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.121 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150982
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.255 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.259 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN22150416
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.321 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Breaker closing mecahnism ü PASSED
Breaker tripping mechanism ü PASSED
Mechanical interlocking ü PASSED
Breaker withdrawing facilities ü PASSED
Breaker on and off indication ü PASSED
Padlocking facilities ü PASSED
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN23520298
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.450 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.287 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510079
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.023 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.397 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510080
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.043 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.431 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510104
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.779 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410339
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.522 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.047 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.258 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410397
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.473 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.097 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.036 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.269 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22150633
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.439 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.097 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.039 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN80952629
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.529 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.106 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN22150782
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.498 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.287 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 800 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150899
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.8 3.229 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.120 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150882
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.244 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.103 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.265 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150976
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.339 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.109 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.257 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Breaker closing mecahnism ü PASSED
Breaker tripping mechanism ü PASSED
Mechanical interlocking ü PASSED
Breaker withdrawing facilities ü PASSED
Breaker on and off indication ü PASSED
Padlocking facilities ü PASSED
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN22150782
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.446 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.288 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.259 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
WINDING RESISTANCE TESTER TELDAR/TRM-1OP 15310041 3K0594
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
Line Side Load Side Load Side Line Side (Volts) (Amps) (Hz)
LINE 1 - LINE 2
LINE 2 - LINE 3
LINE 1 - LINE 3
LINE 1 - NEUTRAL
LINE 2 - NEUTRAL
LINE 3 - NEUTRAL
LINE 1 - GROUND
LINE 2 - GROUND
LINE 3 - GROUND
NEUTRAL - GROUND
B. TRANSFER SWITCH OPERATIONAL / FUNCTIONAL TEST
1. Auto Mode :
Yes No Remarks
1.1 Normal Power to Emergency Power (Timer Setting :_________secs.)
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
TIM-CTR-
045
LVSB ME-A (MAIN NORMAL) ü 4.71 GΩ 4.65 GΩ 610 GΩ 1,59 GΩ 2.11 GΩ 439 GΩ 731 GΩ 1.95 GΩ 4.49 GΩ 129 GΩ 100 MΩ ü
TIM-CTR-
045
LVSB ME-A (EMERGENCY) ü 44.1 GΩ >1.00 TΩ >1.00 TΩ 560 GΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
TIM-CTR-
045
LVSB ME-A (TIE BREAKER) ü >1.00 TΩ >1.00 TΩ 916 GΩ 965 GΩ >1.00 TΩ 239 GΩ 962 GΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
TIM-CTR-
045
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
045
ABCN 1/2 SAE Grade 8.9 74 ü
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
TEST RESULT
DESCRIPTION STATUS
REMARKS
MANUAL OPERATIONS Functioning Mal-Functioning
1. Normal Breaker On and Off
2. Emergency Breaker On and Off
ELECTRICAL OPERATIONS
1. Normal Breaker On and Off
2. Emergency Breaker On and Off
BREAKER INTERLOCKING
1. Normal Breaker On-Emergency Breaker Interlock
2. Normal Breaker Off-Emergency Breaker Operates
3. Emergency Breaker On-Normal Breaker Interlock
4. Emergency Breaker Off-Normal Breaker Operates
AUTOMATIC TRANSFER
1. Normal - Emergency
2. Emergency - Normal
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
EQUIPMENT DATA
MANUFACTURER / BRAND :
LVS NAME :
ENCLOSURE TYPE :
VOLTAGE / PHASE / FREQUENCY :
Timer : Ammeter :
Switches : Others :
Noted by:
Owner Representative Signature Date
Remarks :
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :
ITEM COMPLIANCE
PUNCHLIST DESCRIPTION REMARKS
No. YES NO
EQUIPMENT RELATED
WORKMANSHIP
DOCUMENTS RELATED
Noted by:
Owner Representative Signature Date
Remarks :