Preface
(6ES7515-2AM00-0AB0) ___________________
Documentation guide 1
___________________
2
SIMATIC Product overview
___________________
Connecting up 3
S7-1500
CPU 1515-2 PN Interrupts, error messages,
(6ES7515-2AM00-0AB0) ___________
4
diagnostics and system
alarms
Manual ___________________
Technical specifications 5
___________________
Dimensional drawing A
12/2014
A5E32332431-AB
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Conventions
STEP 7: In this documentation, "STEP 7" is used as a synonym for all versions of the
configuration and programming software "STEP 7 (TIA Portal)".
Note
A note contains important information on the product described in the documentation, on the
handling of the product or on the section of the documentation to which particular attention
should be paid.
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly
that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered. You can find more information about industrial security on the Internet
(http://www.siemens.com/industrialsecurity).
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. You can find more information on the Internet
(http://support.automation.siemens.com).
Preface ................................................................................................................................................... 4
1 Documentation guide .............................................................................................................................. 6
2 Product overview .................................................................................................................................... 8
2.1 Application ................................................................................................................................ 8
2.2 How it works ............................................................................................................................10
2.3 Properties ................................................................................................................................11
2.4 Operating and display elements .............................................................................................14
2.4.1 Front view of the module with closed front panel ...................................................................14
2.4.2 Front view of the module without front panel ..........................................................................16
2.4.3 Rear view of the module .........................................................................................................17
2.5 Mode selector switch ..............................................................................................................17
2.6 Functions ................................................................................................................................18
2.6.1 PROFINET IO .........................................................................................................................18
2.6.2 PROFIenergy ..........................................................................................................................19
2.6.3 Memory reset ..........................................................................................................................19
2.6.4 Restoring the factory settings of the CPU...............................................................................21
3 Connecting up....................................................................................................................................... 24
4 Interrupts, error messages, diagnostics and system alarms ................................................................... 28
4.1 Status and error display of the CPU .......................................................................................28
5 Technical specifications ........................................................................................................................ 31
A Dimensional drawing ............................................................................................................................. 41
Basic information
System Manual and Getting Started describe in detail the configuration, installation, wiring
and commissioning of the SIMATIC S7-1500 and ET 200MP systems. The STEP 7 online
help supports you in the configuration and programming.
Device information
Product manuals contain a compact description of the module-specific information, such as
properties, terminal diagrams, characteristics and technical specifications.
General information
The function manuals contain detailed descriptions on general topics regarding the SIMATIC
S7-1500 and ET 200MP systems, e.g. diagnostics, communication, Motion Control, Web
server.
You can download the documentation free of charge from the Internet
(http://www.automation.siemens.com/mcms/industrial-automation-systems-
simatic/en/manual-overview/tech-doc-controllers/Pages/Default.aspx).
Changes and supplements to the manuals are documented in a Product Information.
My Documentation Manager
The My Documentation Manager is used to combine entire manuals or only parts of these to
your own manual.
You can export the manual as PDF file or in a format that can be edited later.
You can find the My Documentation Manager on the Internet
(http://support.automation.siemens.com/WW/view/en/38715968).
Performance segments
The CPUs can be used for smaller and mid-range applications, as well as for the high-end
area of machine and plant automation.
Security Integrated
The CPUs are aimed at users that require the maximum possible plant security.
In combination with STEP 7, each CPU offers password-based know-how protection against
unauthorized reading or modifying of the program blocks.
The copy protection provides high-performance protection against unauthorized reproduction
of program blocks. The copy protection can be used to link individual blocks on the SIMATIC
memory card with their serial numbers. The block can only be executed if the configured
memory card is inserted in the CPU.
In addition, four different authorization levels in the CPUs can be used to assign different
access right to various user groups.
Improved manipulation protection allows the CPUs to detect changed or unauthorized
transfers of the engineering data.
Safety Integrated
The fail-safe CPUs are aimed at users that want to implement demanding standard and
fail-safe applications in both a centralized and a distributed manner.
These fail-safe CPUs allow the processing of standard and safety programs on a single
CPU. This allows fail-safe data to be evaluated in the standard user program. This
integration thus provides the system advantages and the extensive functionality of SIMATIC
also for fail-safe applications.
The fail-safe CPUs are certified for use in safety mode up to:
● Safety class (Safety Integrity Level) SIL 3 according to IEC 61508:2010
● Performance Level (PL) e and Category 4 according to ISO 13849-1:2006 or according to
EN ISO 13849-1:2008
Additional password protection for F-configuration and F-program is set up for IT security.
System diagnostics
Integrated system diagnostics is activated by default for the CPUs. The different diagnostic
types are configured instead of programmed. System diagnostics information is shown
uniformly and in plain text on the display of the CPU, in STEP 7, on the HMI and on the Web
server, even for alarms related to drives. This information is available in RUN mode, but also
in STOP mode of the CPU. An automatic update of the diagnostics information is performed
when you configure new hardware components.
IO controller
As an IO controller, CPU 1515-2 PN sends and receives data and signals from the
connected IO devices within a PROFINET IO system. You can operate the CPU with a
maximum of 256 IO devices, of which a maximum of 64 may be IRT (Isochronous Realtime)
devices.
I-device
In the "I-device" (intelligent IO device) function, CPU 1515-2 PN not only controls its own
central modules, but also acts as an I-device, exchanging data with a higher-level IO
controller. CPU 1515-2 PN thus fulfills the role of an intelligent pre-processing unit for
sub-processes.
2.3 Properties
Article number
6ES7515-2AM00-0AB0
Note
Protective film
Note that a protective film is attached to the display of the CPU when shipped from the
factory. Remove the protective film if necessary.
Properties
The CPU 1515-2 PN has the following technical properties:
● Communication:
– Interfaces
CPU 1515-2 PN has two PROFINET interfaces.
The 1st PROFINET interface (X1) has two ports (P1R and P2R). In addition to
PROFINET basic functionality, it also supports PROFINET IO RT (Realtime) and IRT
(Isochronous Realtime). PROFINET IO communication or real-time settings can only
be configured at this interface. Port 1 and port 2 can also be used as ring ports for the
configuration of redundant ring structures in Ethernet (media redundancy).
The 2nd PROFINET interface (X2) features a port (P1) and supports PROFINET basic
functionality, which means no IO controller/IO device role. PROFINET basic
functionality supports HMI communication, communication with the configuration
system, communication with a higher-level network (backbone, router, Internet) and
communication with another machine or automation cell.
Note
IP subnets
The IP subnets of both interfaces must be different. This means that the subnets of
the IP address of both interfaces must differ from each other.
● Integrated technology:
– Motion Control
PLC-Open blocks for programming motion functionality using PROFINET IO IRT with
the PROFIdrive interface.
The functionality supports speed-controlled axes, positioning axes, synchronous axes
and external encoders.
– Integrated closed-loop control functionality
- Universal PID controller and 3-point controller with integrated tuning
- Integrated temperature controller
● Trace functionality:
– All CPUs of the S7-1500 automation system support trace functionality. Trace
functionality supports you in troubleshooting and optimizing the user program,
especially for motion control or closed-loop control applications.
● Integrated system diagnostics:
– The alarms for the system diagnostics are automatically created by the system and
displayed on a PG/PC, HMI device, Web server or the integrated display. System
diagnostics information is also available when the CPU is in STOP mode.
● Integrated security:
– Know-how protection
The know-how protection protects user blocks against unauthorized access and
modifications.
– Copy protection
Copy protection links user blocks to the serial number of the SIMATIC memory card or
to the serial number of the CPU. User programs cannot run without the corresponding
SIMATIC memory card or CPU.
– Access protection
Extended access protection provides high-quality protection against unauthorized
configuration changes. You can use authorization levels to assign separate rights to
different user groups.
– Integrity protection
The system protects the data transferred to the CPU against manipulation. The CPU
detects erroneous or manipulated engineering data.
● The CPU 1515-2 PN supports the following additional functions:
– Firmware update
– PROFIenergy
– Shared device
– Configuration control
– Isochronous mode
Reference
You will find additional information on the topic of "Integrated security/Access protection" in
the S7-1500/ET 200MP system manual
(http://support.automation.siemens.com/WW/view/en/59191792).
① LEDs for the current operating mode and diagnostic status of the CPU
② Display
③ Operator control buttons
Figure 2-2 View of the CPU 1515-2 PN (with front panel) - front
Note
Temperature range for display
To increase the service life of the display, the display switches itself off when the permitted
operating temperature is exceeded. When the display cools down again, it automatically
switches itself on again. When the display is switched off, the LEDs continue to show the
status of the CPU.
For more information on the temperatures at which the display switches itself on and off,
refer to the Technical specifications (Page 31).
WARNING
Personal injury and damage to property may occur
If you pull or plug the front panel of an S7-1500 automation system during operation,
personal injury or damage to property can occur in zone 2 hazardous areas.
Always disconnect the S7-1500 automation system from the power supply before you pull
or plug the front panel in zone 2 hazardous areas.
In addition to the mechanical lock, you can also block access to a password-protected CPU
on the display (local lock). You can find additional information on the display, configurable
protection levels and local locks in the S7-1500/ET 200MP
(http://support.automation.siemens.com/WW/view/en/59191792) system manual.
Reference
You will find detailed information on the individual display options, a training course and a
simulation of the available menu commands in the SIMATIC S7-1500 Display Simulator
(http://www.automation.siemens.com/salesmaterial-as/interactive-manuals/getting-
started_simatic-s7-1500/disp_tool/start_en.html).
① LEDs for the current operating mode and diagnostic status of the CPU
② Display connector
③ Slot for the SIMATIC memory card
④ Mode selector
⑤ LEDs for the 3 ports of the PROFINET interfaces X1 and X2
⑥ MAC addresses of the interfaces
⑦ PROFINET interface (X2) with 1 port
⑧ PROFINET IO interface (X1) with 2 ports
⑨ Connector for power supply
⑩ Fixing screws
Figure 2-4 View of the CPU 1515-2 PN (without front panel) - front
2.6 Functions
2.6.1 PROFINET IO
PROFINET is a fieldbus standard of the PROFIBUS user organization that defines a
cross-vendor communications and engineering model.
As part of PROFINET, PROFINET IO is a communication concept that is used to implement
modular, distributed applications. PROFINET IO IRT allows defined response times and
highly precise plant behavior.
A PROFINET IO system consists of the following PROFINET devices:
● IO controller
Device used to address the connected IO devices.
● IO device
A distributed field device that is assigned to an IO controller.
The PROFINET IO controller operating mode allows direct access to IO devices via
Industrial Ethernet.
The PROFINET IO device operating mode enables you to operate S7 stations or distributed
I/O systems with a CPU as "intelligent" IO devices on Industrial Ethernet.
Reference
You can find additional information on the "PROFINET IO" topic in the STEP 7 online help
and in the PROFINET System Description
(http://support.automation.siemens.com/WW/view/en/19292127) manual.
2.6.2 PROFIenergy
PROFIenergy
PROFIenergy is a PROFINET-based data interface for switching off consumers centrally and
in a coordinated manner during pause times regardless of the manufacturer or device type.
Through this, the process should only be provided with the energy that is absolutely
required. The majority of the energy is saved by the process; the PROFINET device itself
only contributes a few watts of savings potential.
Additional information
● PROFINET (http://support.automation.siemens.com/WW/view/en/68039307) function
manual
● You will find more information on PROFIenergy in the PROFINET specification on the
Internet (http://www.profibus.com).
Options
You have the following options for resetting the memory of the CPU:
● Using the mode selector
● Using the display
● Using STEP 7
* The retentive tags of technology objects are retained, but the contents of certain tags are partially re-initialized.
Reference
You will find more information about "Memory reset" in the Memory reset section in the
S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792)
system manual.
Note
If you want to remove a PROFINET CPU and use it elsewhere with a different program or
put it into storage, we recommend that you reset the CPU to its factory settings. Remember
that the Reset to factory settings function also deletes the IP address parameters.
Options
You have the following options for returning the CPU to the factory settings:
● Using the mode selector
● Using the display
● Using STEP 7
Reference
You can find more information about the topic of "Reset to factory settings" in the function
manual Structure and Use of the CPU Memory
(http://support.automation.siemens.com/WW/view/en/59193101) as well as in the STEP 7
online help.
If the CPU is supplied by a system power supply, it is not necessary to connect the 24 V
supply.
Reference
You can find additional information on the topics of "Connecting the CPU" and
"Accessories/spare parts" in the S7-1500, ET 200MP
(http://support.automation.siemens.com/WW/view/en/59191792) system manual.
Assignment Labeling
MAC address 1 PROFINET interface X1 • Front, lasered
(visible in STEP 7 for accessible devices) • Right side, lasered
(start of number range)
MAC address 2 Port X1 P1 R (required for LLDP, • Front and right side, not lasered
for example)
MAC address 3 Port X1 P2 R (required for LLDP, • Front and right side, not lasered
for example)
MAC address 4 PROFINET interface X2 • Front, lasered
(visible in STEP 7 for accessible devices) • Right side, not lasered
MAC address 5 Port X2 P1 (required for LLDP, for example) • Front, not lasered
• Right side, lasered
(end of number range)
Block diagram
The following figure shows the block diagram of the CPU 1515-2 PN.
LED display
The figure below shows the CPU 1515-2 PN LEDs.
Figure 4-1 LED display of the CPU 1515-2 PN (without front panel)
6ES7515-2AM00-0AB0
CPU processing time
For bit operations, typ. 30 ns
For word operations, typ. 36 ns
For fixed-point arithmetic, typ. 48 ns
For floating-point arithmetic, typ. 192 ns
CPU blocks
Number of elements (total) 6000; elements can be taken to mean blocks
such as DBs, FBs and FCs, as well as UDTs,
global constants etc.
DB
Number range 1 to 65535
Size, max. 3 MB; the maximum size of the DB is 64 KB with
non-optimized block access
FB
Number range 1 to 65535
Size, max. 500 KB
FC
Number range 1 to 65535
Size, max. 500 KB
OB
Size, max. 500 KB
Number of free-cycle OBs 100
Number of time-of-day interrupt OBs 20
Number of time-delay interrupt OBs 20
Number of cyclic interrupt OBs 20
Number of hardware interrupt OBs 50
Number of DPV1 interrupt OBs 3
Number of isochronous mode OBs 1
Number of technology synchronization interrupt 2
OBs
Number of restart OBs 100
Number of asynchronous error OBs 4
Number of synchronous error OBs 2
Number of diagnostic interrupt OBs 1
Nesting depth
Per priority class 24
Timers/counters and their retentivity
S7 counters
Quantity 2048
Retentivity
• Adjustable Yes
6ES7515-2AM00-0AB0
IEC counters
Quantity Unlimited (limited only by work memory)
Retentivity
• Adjustable Yes
S7 timers
Quantity 2048
Retentivity
• Adjustable Yes
IEC timers
Quantity Unlimited (limited only by work memory)
Retentivity
• Adjustable Yes
• Outputs (volume) 8 KB
• Outputs (volume) 8 KB
6ES7515-2AM00-0AB0
Hardware configuration
Number of hierarchical IO systems 20
Number of DP masters
Via CM 8; a maximum of 8 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
Number of IO controllers
Integrated 1
Via CM 8; a maximum of 8 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
Rack
Modules per rack, max. 32; CPU + 31 modules
Rack, number of rows, max. 1
PtP CM
Number of PtP CMs The number of PtP CMs you can connect is only
limited by the available slots
Time
Clock
Type Hardware clock
Deviation per day, max. 10 s; typ.: 2 s
Buffered period 6 wk; at 40 °C ambient temperature, typ.
Operating hours counter
Quantity 16
Time-of-day synchronization
Supported Yes
in AS, Master Yes
in AS, Slave Yes
On Ethernet via NTP Yes
Interfaces
Number of PROFINET interfaces 2
1. Interface
Interface hardware
• Number of ports 2
Protocols
• PROFINET IO controller Yes
6ES7515-2AM00-0AB0
2. Interface
Interface hardware
• Number of ports 1
• Integrated switch No
Protocols
• PROFINET IO controller No
• PROFINET IO device No
Interface hardware
RJ-45 (Ethernet)
100 Mbps Yes
Autonegotiation Yes
Autocrossing Yes
Industrial Ethernet status LED Yes
Protocols
Number of connections
Number of connections, max. 192; via integrated interfaces of the CPU and
connected CPs/CMs
Number of connections reserved for ES/HMI/Web 10
Number of connections via integrated interfaces 108
Number of S7 routing connections 16
PROFINET IO controller
Services
• PG/OP communication Yes
• S7 routing Yes
• IRT Yes
• Number of connectable I/O devices, max. 256; a maximum of 512 distributed I/O devices
can be connected by means of PROFIBUS or
PROFINET.
• Of which IO devices with IRT and the "high 64
performance" option, max.
6ES7515-2AM00-0AB0
• Number of IO devices that you can connect for 256
RT, max.
• For IRT with the "high performance" option and Update time = set "odd-numbered" send clock
parameter assignment for so-called (any multiple of 125 µs: 375 µs, 625 µs ...
"odd-numbered" send clocks 3 875 µs)
PROFINET IO device
Services
• PG/OP communication Yes
• S7 routing Yes
• Isochronous mode No
• PROFIenergy Yes
6ES7515-2AM00-0AB0
SIMATIC communication
S7 communication, as server Yes
S7 communication, as client Yes
User data per job, max. See online help (S7 communication, user data
size)
Open IE communication
TCP/IP Yes
• Data length, max. 64 KB
DHCP No
SNMP Yes
DCP Yes
LLDP Yes
Web server
HTTP Yes; standard and user-defined pages
HTTPS Yes; standard and user-defined pages
Further protocols
MODBUS Yes; MODBUS TCP
Media redundancy
Changeover time on line interruption, typ. 200 ms
Number of ring nodes, max. 50
Isochronous mode
Isochronous mode (application synchronized up to Yes; with minimum OB 6x cycle of 500 µs
terminal)
Constant bus cycle time Yes
S7 signaling functions
Number of stations that can be logged in for sig- 32
naling functions, max.
Block-related alarms Yes
Number of configurable interrupts, max. 10000
Number of simultaneously active interrupts in
interrupt pool
• Number of reserved user interrupts 600
6ES7515-2AM00-0AB0
Test/commissioning functions
Joint commissioning (Team Engineering) Yes; parallel online access possible for up to
8 engineering systems
Status block Yes; up to 8 simultaneously (in total from all
ES clients)
Single-step No
Status/modify
Status/modify tag Yes
Tags Inputs, outputs, bit memories, DBs, timers,
counters
Of which are status tags, max. 200; per job
Of which are modify tags, max. 200; per job
Force
Forcing, tags Inputs, outputs
Number of tags, max. 200
Diagnostics buffer
Available Yes
No. of entries, max. 3200
• Of which are power failure-proof 500
Traces
Number of configurable traces 4; up to 512 KB data possible per trace
Interrupts/diagnostics/status information
Diagnostic indicator LED
RUN/STOP LED Yes
ERROR LED Yes
MAINT LED Yes
Connection display LINK TX/RX Yes
Supported technology objects
Motion Yes
• Speed-controlled axis
– Number of speed-controlled axes, max. 30; Requirement: no other motion technology
objects have been created
• Positioning axis
– Number of positioning axes, max. 30; Requirement: no other motion technology
objects have been created
• Synchronous axes (relative gearing)
– Number of axes, max. 15; Requirement: no other motion technology
objects have been created
• External encoder
– Number of external encoders, max. 30; Requirement: no other motion technology
objects have been created
6ES7515-2AM00-0AB0
Controller
• PID_Compact Yes; universal PID controller with integrated
optimization
• PID_3Step Yes; PID controller with integrated optimization
for valves
• PID temp Yes; PID controller with integrated optimization
for temperature
Counting and measuring
• High-speed counter Yes
Ambient conditions
Ambient temperature in operation
Horizontal installation, min. 0 °C
Horizontal installation, max. 60 ℃; display: 50 ℃, the display is switched off at
an operating temperature of typically 50 ℃
Vertical installation, min. 0 °C
Vertical installation, max. 40 ℃; display: 40 ℃, the display is switched off at
an operating temperature of typically 40 ℃
Configuring
Programming
Programming language
• LAD Yes
• FBD Yes
• STL Yes
• SCL Yes
• GRAPH Yes
Know-how protection
User program protection Yes
Copy protection Yes
Block protection Yes
Access protection
Password for display Yes
Protection level: Write protection Yes
Protection level: Read/write protection Yes
Protection level: Complete protection Yes
Cycle-time monitoring
Low limit Adjustable minimum cycle time
High limit Adjustable maximum cycle time
Dimensions
Width 70 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 830 g
Figure A-1 Dimensional drawing of CPU 1515-2 PN, front and side views
Figure A-2 Dimensional drawing CPU 1515-2 PN, side view with open front panel