SECTION 10 2239 - FOLDING PANEL PARTITIONS PART 1 - GENERAL

RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.

SUMMARY Section Includes:

1. Manually operated, acoustical panel partitions.


2. Electrically operated, acoustical panel partitions.

Related Requirements:
1. Section055000 "Metal Fabrications" for supports that attach supporting tracks to overhead structural system.
2. Section 092900 "Gypsum Board" for fire-rated assemblies and sound barrier construction above the ceiling at track.
3. Electrical and communications Sections for electrical service and connections for motor operators, controls, and limit switches
and for system disconnect switches.

DEFINITIONS
NIC: Noise Isolation Class.
NRC: Noise Reduction Coefficient. STC: Sound Transmission Class.

ACTION SUBMITTALS
Product Data: For each type of product. LEED Submittals:
1. Product Data for Credit MR 4: For products having recycled content, documentation indicating percentages by weight of
postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content.
2. Certificates for Credit MR 7: Chain-of-custody certificates certifying that operable panel partitions comply with forest
certification and chain-of-custody requirements. Include statement indicating cost for each certified wood product.
3. Product Data for Credit IEQ 4.4: For composite wood products, documentation indicating that products contain no urea
formaldehyde.

Shop Drawings: For operable panel partitions.


1. Include plans, elevations, sections, details, numbered panel installation sequence, and attachments to other work.
2. Indicate stacking and operating clearances. Indicate location and installation requirements for hardware and track, blocking,
and direction of travel.
3. Include diagrams for power, signal, and control wiring.

Samples for Initial Selection: For each type of exposed material, finish, covering, or facing.
1. Include Samples of accessories involving color selection.
Samples for Verification: For each type of exposed material, finish, covering, or facing, prepared on Samples of size indicated
below:
1. Textile Facing Material: Full width by not less than 36-inch- (914-mm-) long section of [fabric] [carpet] from dye lot to be used
for the Work, with specified treatments applied. Show complete pattern repeat.
2. Panel Facing Material: Manufacturer's standard-size unit, not less than 3 inches (75 mm) square.
3. Panel Edge Material: Not less than 3 inches (75 mm) long.

Delegated-Design Submittal: For operable panel partitions.


1. Include design calculations for seismic restraints.

INFORMATIONAL SUBMITTALS
Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following items are shown and coordinated with
each other, using input from installers of the items involved:
1. Partition track, track supports and bracing, switches, turning space, and storage layout.
2. Suspended ceiling components.
3. Structural members to which suspension systems are attached.
4. Size and location of initial access modules for acoustical tile.
5. Items penetrating finished ceiling, including the following:
a. Lighting fixtures.
b. HVAC ductwork, outlets, and inlets.
c. Speakers.
d. Sprinklers.
e. Smoke detectors.
f. Access panels.
6. Plenum acoustical barriers.
Setting Drawings: For embedded items and cutouts required in other work, including support- beam, mounting-hole template.

Qualification Data: For qualified Installer testing agency manufacturer and vendor.

Seismic Qualification Certificates: For operable panel partitions, tracks, accessories, and components, from manufacturer.
Include seismic capacity of partition assemblies to remain in vertical position during a seismic event and the following:
1. Basis for Certification: Indicate whether certification is based on analysis, testing, or experience data, according to ASCE/SEI 7.
2. Detailed description of partition anchorage devices on which the certification is based and their installation requirements.

Product Certificates: For each type of operable panel partition.


1. Include approval letter signed by manufacturer acknowledging Owner-furnished panel facing material complies with
requirements.
Product Test Reports: For each operable panel partition, for tests performed by a qualified testing agency.
Field quality-control reports.
Sample Warranty: For manufacturer's special warranty.

CLOSEOUT SUBMITTALS
Operation and Maintenance Data: For operable panel partitions to include in maintenance manuals.
1. In addition to items specified in Section 017823 "Operation and Maintenance Data," include the following:
a. Panel finish facings and finishes for exposed trim and accessories. Include precautions for cleaning materials and methods that
could be detrimental to finishes and performance.
b. Seals, hardware, track, track switches, carriers, and other operating components.
c. Electric operator and controls.

MAINTENANCE MATERIAL SUBMITTALS


Furnish extra materials, from the same production run, that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1. Panel Finish-Facing Material: Furnish full width in quantity to cover both sides of two panels when installed.

QUALITY ASSURANCE
Comply with the most current edition of the Northwestern University Design Standards.
Manufacturer Qualifications: A qualified manufacturer that is certified for chain of custody by an FSC-accredited certification
body.
Vendor Qualifications: A vendor that is certified for chain of custody by an FSC-accredited certification body.

Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer.

DELIVERY, STORAGE, AND HANDLING


Protectively package and sequence panels in order for installation. Clearly mark packages and panels with numbering system
used on Shop Drawings. Do not use permanent markings on panels.

WARRANTY
Special Warranty: Manufacturer agrees to repair or replace components of operable panel partitions that fail in materials or
workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Faulty operation of operable panel partitions.
b. Deterioration of metals, metal finishes, and other materials beyond normal use.
2. Warranty Period: Two years from date of Substantial Completion.

PART 2 - PRODUCTS
PERFORMANCE REQUIREMENTS
Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design
seismic bracing of tracks to structure above.
Seismic Performance: Operable panel partitions shall withstand the effects of earthquake motions determined according to
ASCE/SEI 7.
1. The term "withstand" means "the partition panels will remain in place without separation of any parts from the system when
subjected to the seismic forces specified."
Acoustical Performance: Provide operable panel partitions tested by a qualified testing agency for the following acoustical
properties according to test methods indicated:
1. Sound-Transmission Requirements: Operable panel partition assembly tested for laboratory sound-transmission loss
performance according to ASTM E 90, determined by ASTM E 413, and rated for not less than the STC indicated.
2. Noise-Reduction Requirements: Operable panel partition assembly, identical to partition tested for STC, tested for sound-
absorption performance according to ASTM C 423, and rated for not less than the NRC indicated.
Fire-Test-Response Characteristics: Provide panels with finishes complying with one of the following as determined by testing
identical products by UL or another testing and inspecting agency acceptable to authorities having jurisdiction:
1. Surface-Burning Characteristics: Comply with ASTM E 84 or UL 723; testing by a qualified testing agency. Identify products
with appropriate markings of applicable testing agency.

Flame-Spread Index: 25 or less. Smoke-Developed Index: 450 or less.


2. Fire Growth Contribution: Complying with acceptance criteria of local code and authorities having jurisdiction when tested
according to NFPA 265 Method B Protocol or NFPA 286.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and
marked for intended location and application.
OPERABLE ACOUSTICAL PANELS
Operable Acoustical Panels: Partition system, including panels, seals, finish facing, suspension system, operators, and
accessories.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Hufcor, Inc.
b. KWIK-WALL Company.
c. Moderco Inc.
d. Modernfold, Inc.
Panel Operation: [Manually operated, individual] [Manually operated, paired] [Manually operated, continuously hinged]
[Electrically operated, continuously hinged] panels.
Panel Construction: As required to support panel from suspension components and with reinforcement for hardware
attachment. Fabricate panels with tight hairline joints and concealed fasteners. Fabricate panels so finished in-place partition is
rigid; level; plumb; aligned, with tight joints and uniform appearance; and free of bow, warp, twist, deformation, and surface
and finish irregularities.
Dimensions: Fabricate operable acoustical panel partitions to form an assembled system of dimensions indicated and verified by
field measurements.
1. Panel Width: Standard widths.
STC: Not less than 52.
NRC: Not less than [0.50] [0.60] [0.65] [0.90] <Insert number>. Panel Weight: <Insert value> maximum.
Panel Thickness: Not less than 4 inches (102 mm).
Panel Materials:
1. Certified Wood: Wood for operable panel partitions shall be certified as "FSC Pure" according to FSC STD-01-001, "FSC
Principles and Criteria for Forest Stewardship," and to FSC STD-40-004, "FSC Standard for Chain of Custody Certification."
2. Recycled Content of Operable Panel Partitions:

a. Recycled Content of Steel: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25
percent by weight.
3. Steel Frame: Steel sheet, manufacturer's standard nominal minimum thickness for uncoated steel.
4. Steel Face/Liner Sheets: Tension-leveled steel sheet, manufacturer's standard minimum nominal thickness for uncoated steel.
5. Aluminum: Alloy and temper recommended by aluminum producer and finisher for type of
use, corrosion resistance, and finish indicated; ASTM B 221 (ASTM B 221M) for extrusions; manufacturer's standard strengths
and thicknesses for type of use.
a. Frame Reinforcement: Manufacturer's standard steel or aluminum.
6. Gypsum Board: ASTM C 1396/C 1396M.
7. Medium-Density Fiberboard: ANSI A208.2, made with binder containing no urea
formaldehyde.
8. Plywood: DOC PS 1; made with adhesive containing no urea formaldehyde.
Panel Closure: Manufacturer's standard unless otherwise indicated.
1. Initial Closure: Flexible, resilient PVC, bulb-shaped acoustical seal.
2. Final Closure: Constant-force, lever-operated mechanical closure expanding from panel
edge to create a constant-pressure acoustical seal.
Hardware: Manufacturer's standard as required to operate operable panel partition and accessories; with decorative, protective
finish.
1. Hinges: Concealed (invisible).
SEALS
General: Provide seals that produce operable panel partitions complying with performance requirements and the following:
1. Manufacturer's standard seals unless otherwise indicated.
2. Seals made from materials and in profiles that minimize sound leakage.
3. Seals fitting tight at contact surfaces and sealing continuously between adjacent panels
and between operable panel partition perimeter and adjacent surfaces, when operable panel partition is extended and closed.
Vertical Seals: Deep-nesting, interlocking astragals mounted on each edge of panel, with continuous PVC acoustical seal.
Horizontal Top Seals: Continuous-contact, extruded-PVC seal exerting uniform constant pressure on track.
1. Mechanically Operated for Acoustical Panels: Extension and retraction of bottom seal by operating handle or built-in
operating mechanism, with operating range not less than 1- 1/2 inches (38 mm) between retracted seal and floor finish.