Annexure-1 - DG Synchronization Panel
Annexure-1 - DG Synchronization Panel
Annexure-1 - DG Synchronization Panel
Buchanan
Tokadeh
A
Prepared by Reviewed by Approved by Reviewed by Approved by
Revision Date
(MISPL) (MISPL) (MISPL) (AML) (AML)
Document No: Page 2 of 14
CONTENTS
9.0 WARRANTY
1.0 GENERAL
The scope of this specification is to define technical requirements of design, engineering, fabrication,
manufacture, assembly, inspection, testing, shop painting, packing, transportation, delivery, erection,
testing and Commissioning of 3 phase, 415 V, 50 Hz DG Synchronization Panel with all the
accessories which shall be installed at Arcelor Mittal Liberia Limited (AML) Buchanan and Tokadeh
Site
1. The scope of work shall also include, at the option of the purchaser, the services of a senior
engineer for
i. Complete checking of materials at site and advising the purchaser of any discrepancy thereof
ii. Advice on procedure of erection to be followed
iii. Supervision of erection, testing, commissioning and putting into successful commercial
operation
iv. Configuration and testing of protection relays. Vendor’s engineer shall bring the necessary test
kits
• In case of any contradiction between various referred standards / specifications and statutory
regulations for following order of priority shall governs:
o Statutory regulations
o This specification
o Codes and standards
Document No: Page 4 of 14
Site Data
Equipments shall be suitable for operating in humid & corrosive atmosphere found in petrochemical
plants. Service conditions shall be defined as
Parameters Description
Altitude from above Sea Level Less than 1000 m from Mean Sea
Level
Design Ambient Temperature 55 °C
Annual average Rainfall 5100 mm
Ambient Temperature (Min. / Max.) 21 / 36 °C
DG Synchronizing System to be used to power saving and Start and Stop DG as per required load in
auto AMF function. From this system we can save fuel consumption of DG, wastage of power, DG
protection, auto load sharing. On AGC controller screen we can see the status of system as below:
If all the required data is ok then Controller will start DG otherwise it stops DG.
DG Synchronizing Panel System to be Start DG as per required load. Basically, it can be operated by
Auto Mode and Manual Mode. As per required Load we can change Consumption mode it Night Mode
and Day Mode. In Night production is very less so we activate any one 180/250 KVA DG, but in Day
Mode first DG 180/ 250 KVA will start and if load in field is more then automatically 2nd DG 180/250
KVA will be start automatically start and sync and start load sharing with already running DG.
In Case we want to operated DG by Manual mode, in this mode you start DG one by one through push
bottom on controller and close breaker from DG controller button or from PCC panel. If you start 2nd
Document No: Page 5 of 14
DG in this mode, then at the time of breaker closing from DG controller button it will sync before
closing breaker.
• Auto Mode
• Manual Mode
• Day Mode
• Night Mode
The abbreviation of AMF is Auto Mains failure, it means if the main supply will fail then AMF panel
will start DG but main condition is DG Sync controller should be in AUTO mode and in healthy
condition.
Controller Logic for Auto Synchronizing, Auto sharing & Auto Load Management including
auto start / auto stop of DG Set
The system will come in operation after sensing of grid failure initiation of DG operation from
Man machine interface to automatically control the start and stop of the engine, depending on
the predefined load setting in the controller.
In case engine does not start in the first cranking, two more auto commands will be given with
proper interval. Even then if engine fails to starts indication will appear on MMI (main machine
Document No: Page 7 of 14
interface). In the event, the engines are under loaded load sensed is capable of being catered by
less then running engines, command will be given to engine running for shortest duration at the
moment. Provision to select number of DG sets to be started at no load to cope up with sudden
load without tripping ready the DG’s.
The entire operation of the captive power generation system will be controlled automatically
through a controller. These controllers will be state of art equipments using latest technology
and of most rugged and reliable design. Since they shall be operating in the harsh & unfriendly
environment of DG room, they will be suitable to operate trouble free in those conditions. The
chosen equipment will be able to withstand high temperature, humidity and voltage fluctuations,
thus making it suitable for the operating conditions described above and will perform the
following functions
Tripping of less priority loads in the plant in case of under frequency of bus both in isolation as
well as synchronized mode.
Control of all the auxiliary drive of DG set will Auto Synchronizing, start / stop automatically
with proper interlock.
Controller system shall have provision to test the DG in auto mode without closing the breaker
to do the routine electrical / mechanical testing of set without interruption to power generation.
The System supplier will supply built drawing. Along with trouble shooting and operation and
maintenance guidelines.
6.1.1
a. System Operation
While the normal mains supply is healthy, the DG set shall be at rest and the load shall be
supplied by mains. During this period all the DG INCOMERS shall be in OPEN position.
The controller system shall monitor supply voltage on each phase. When the mains supply
fails completely or falls below set value (variable between 80% to 95% of the nominal
value) on any phase, the monitor module shall initiate start-up of diesel engine. To avoid
initiation due to momentary dips or system disturbance, a time delay adjustable between 0.5
to 5 seconds (adjustable) shall be incorporated in the start-up initiation.
Suitable adjustable timers shall be incorporated which shall make it feasible to vary
independently ON-OFF setting periods from 1-10 seconds. If the alternator does not build
up voltage after the first or any start, as may, further starting attempt shall not be made and
the starting facility shall be reset.
Once engine has built up voltage, signals shall be provided to operate the alternator, mains
and bus coupler circuit breakers as per logic sequence required. The Mains supply circuit
breaker shall open before the alternator circuit breaker closes. Before giving close command
to alternator breaker, all the bus couplers shall be given close command. At this point of
time all the load shall be on one DG. System provided in the DG Synchronization control
Panel shall check and ensure that all the engine auxiliaries like cub oil pump, CT fan,
cooling water pump are running and healthy. In case of any fault in engine auxiliaries, the
system shall automatically stop the DG set and an audio-visual alarm shall be given.
Suitable inputs for overload and single phase preventor for alternator and for each of the
engine auxiliaries shall also be considered as inputs for this function.
DG Synchronization control system shall continuously monitor total load on the DG set. In
case the load on any of the DG sets is less than 60 % of the rated value, the controller shall
assess the load on the adjacent DG set. In case the summation of the loads is within 90% of
the rating of one of the DG sets, one DG set shall shut down and load shall be transferred to
the second DG set.
In case the total load on the system is not more than 90% of the full load rating of a single
DG set, the controller shall shut down due to non-availability of adequate load and will the
Document No: Page 9 of 14
load increase, the controller shall automatically start the DG set and shall isolate the
buses/loads on the Main LT panel bus.
The Automatic Load Management system shall be designed to provide optimum utilization
of the DG sets so that operation of the DG sets is need based with higher load factor on each
set. The system would therefore transfer loads from one bus to the other on the Main LT
panel with Main L.T. panel as per logic sequence required. The controller shall ensure that
that the ACB’s on the closed and opened and DG sets are started and stopped according to
the predetermined logic and interlocking scheme to provide a fail-safe system.
When the voltage in the mains get restored, its quality shall be monitored for about one
minute and if proven satisfactory, the main supply breaker shall close automatically for
retransfer of the load from Diesel engine to the main supply at LT panel. However, prior to
this operation DG incomer breakers shall open position before the mains breaker closed.
The Automatic Logic Management system shall also consider that in the eventuality of
failure of any component of the controller, adequate safeguards shall be provided in that the
system shall revert to the manual mode with visual and audible alarms. These safeguards
and the system shall be detailed in the offer.
The Logic Panel shall automatically arrange for sequential starting of DG sets to be based
on number of operating hours of each DG set so that to ensure that all DG sets are operated
as equally as possible.
In case of over load on the DG system, the logic panel shall give audio visual alarm to
enable the operators to switch off loads as required and if this is not taken care of in
predetermined time, the Logic Panel shall put the DG in shut down mode with alarm.
The DG set shall stop after idle running of one minute after restoration of main supply.
The DG set reverts to standby conditions and is ready to start will the mains supply fail
again.
b. Sequence of operation for Auto start, Auto load management & Auto Synchronizing
One failure of grid supply, DG-1 shall start automatically and close its breaker shall start
feeding the load.
On DG-1 attaining its full rated capacity, DG-2 shall start automatically.
Voltage and frequency of DG-2 shall be monitored and necessary commands shall adjust the
parameters of DG-2 with bus.
System shall also monitor the slip frequency and the beat voltage of the machine or system.
Document No: Page 10 of 14
It shall be possible to alter sequence of DG set starting through manual selectors or through
Man Machine Interface.
Active Power shall be made equal on both the machines automatically with the help of
active load balancing system through governor control.
On restoration of grid supply, DG breakers and Bus coupler breakers shall be switched off
in sequence with time delays to cover dips and grids supply breakers shall be switched On.
Dg sets shall continue to run for one-minutes after DG breaker has been switched OFF.
It shall be possible to alter crucial settings / time delays thru. Man-Machine Interface.
Controller, annunciation system, protection system and metering system shall have
compatibility for future interface with PC for graphics displays / report generation.
Tenderers may note that the controller controls and sequence of operation are indicative of
requirements and the controller shall not with-standing the above, be complete in all
respects to achieve the control, monitoring and operation of DG sets indicated above.
Under manual mode it shall be possible for the operator to start up the generator set by pressing
the (START) push button.
Three attempt starting facility shall also be operative for the start-up function.
Alternator, mains and bus coupler circuit breakers ‘CLOSE’ and ‘TRIP’ operations as per logic
sequence required shall be manual by pressing the appropriate push button on the panel. Closure
shall be feasible only after alternator has built up full voltage. If the load is already on ‘MAINS’
pressure on ‘CLOSE’ button shall be ineffective.
When running under manual mode, if the mains supply has failed, the load shall automatically
get transferred to the alternator immediately overriding the stipulation of pressure on ‘CLOSE’
button.
Engine shut down, other than due to faults shall be manual by pressing a ‘STOP’ button.
When under ‘TEST’ mode pressure of ‘TEST’ button shall complete the start-up sequence
simulation and start the engine. The simulation will be that of mains failure.
Document No: Page 11 of 14
Engine-shall build up voltage but the set shall not close alternator circuit breaker when the load
is on the mains. Monitoring performance for voltage / frequency etc. will be feasible without
supply to load.
If during TEST run the power supply has failed, the load shall automatically get transferred to
alternator.
Bringing the mode selector to auto position shall shut down the sets.
1. Service 0utdoor
2. Type Metal enclosed, fully compartmentalized
3. Mounting Floor (Free standing)
4. Connections Cable entry – Bottom
5. Configuration Single front
6. Panel height Preferably <= 2500 mm
7. Working height from ground >= 300 mm and <= 1950 mm
8. Enclosure degree of protection IP 55
9. Enclosure Material CRCA sheets
10. Enclosure Sheet Thickness i. Minimum 2.0 mm for load bearing members
Document No: Page 12 of 14
1. Surface preparation Surface shall be sand blasted, pickled and ground as required to
produce a smooth, clean surface free of scale, grease and rust
2. Painting The surface shall be given a phosphate coating followed by 2 coats of
high-quality primer. The coating shall be done electro-statically
followed by stoving
3. Tropical protection Shall have fungus protection, involving special treatment of
insulation and metal against fungus, insects and corrosion
4. Suitability i. Shall withstand heat and weather conditions.
ii. Shall not scale - off or crinkle or get removed by abrasion due to
normal handling
1. Packing Protection Protection against corrosion, dampness, heavy rains, breakage and
vibration
2. Packing for accessories and spares Robust wooden non-returnable packing case
3. Packing Identification Label on each case i. Individual serial number
with details as listed ii. PO number (along with SAP item code, if any) and date
iii. Equipment Tag no. (if any)
iv. Manufacturer / Supplier’s name and address
v. Description and Quantity
Document No: Page 13 of 14
1. It is not the intent to specify completely herein all details of the equipment. Nevertheless, the
equipment shall be complete and operative in all aspects and shall conform to highest standard of
engineering, design and workmanship and be capable of performing in continuous commercial
operation up to the guarantees in a manner acceptable to the purchaser, who will interpret the
meaning of drawings and specifications and shall be entitled to reject any work or material which in
his judgment is not in full accordance therewith
2. Any material or accessory which may not have been specifically mentioned but which is necessary
or usual for satisfactory and trouble-free operation and maintenance of the equipment shall be
furnished without any extra charge.
3. The bidder shall supply all brand-new equipment and accessories as specified herein with such
modification and alteration as agreed upon in writing after mutual discussion
1. The performance figures quoted in Schedule, Technical Particulars shall be guaranteed within the
tolerance permitted by relevant standards. In case of failure of the equipment to meet the guarantee,
the equipment may be liable for rejection
8.3 DEVIATION
1. Should the Bidder wish to deviate from this specification in any way, it shall be clearly mentioned
in Schedule, Technical Deviation with reference to the respective clause of the specification
2. Unless such deviations are recorded as above and submitted with the offer, it will be taken for
granted that the offer is made in conformity with this specification in all respects
Document No: Page 14 of 14
1. Before starting manufacture of any equipment, the bidder shall have to take approval of the relevant
drawings, data sheet and Quality Assurance Plan from Purchaser in writing
2. Any manufacture done prior to the approval of drawings / data shall be rectified in accordance with
the approved drawings / data by the Bidder at his own cost and the equipment shall be supplied
within the stipulated period.
Bidder shall ensure that other necessary write-ups, curves and information required to fully describe the
equipment are submitted along with this bid.
Drawing submission shall be within 1 month from kick off meeting (KOM). Bidder shall not start
manufacturing unless manufacturing clearance is provided by Owner / Consultant in writing.
9.0 WARRANTY
Bidder shall have final and total responsibility for the design and performance of charger, battery and
DCDB supplied under this specification. The equipment and the system shall be guaranteed for troubles
free operation for a period of 12 months from the date of commissioning. Any defects discovered
during this period shall be rectified free of charge.
Manufacturer shall follow his standard procedures for quality assurance and control. However, the
standard procedures shall be submitted to the Owner in event of order. Bidder shall submit the QAP for
Owner’s approval prior to dispatch at supplier’s works and during commissioning at site.
The procedures shall be in such a form as to clearly delineate the manufacturing sequence and major
inspection points and to reference manufacturer’s test and inspection procedures.
The Owner will inform the manufacturer as to which of the inspection points and tests will be
witnessed.