Klima-Set
Differential pressure
switch for air
KS…A2-7
5.21
Technical description Application
Two separate pressure chambers with The equipment is used in ventilation and
pressure-side connection to hose nip- air-conditioning systems, DDC.
ples. It is specially designed for monitoring air
Connection of ø 4 mm for each pressure ducts, filters, drive units and blowers.
chamber.
Reference value (pressure difference) Type testing
can be set directly. Reference value Tested according to DIN EN 1854
can be read off externally through the
transparent hood.
Printed in Germany • Edition 2024.01 • Nr. 260 520
Precise function through special switch-
ing system in a frictionless bearing.
Contact switchover is performed when
the set reference value is exceeded
or undershot. Complete mounting kit
enclosed.
1…4
Functional description Make sure that no condensate
DDC application
Differential pressure switch in pressure can enter into the pressure
The switching contacts of the Klima-
and vacuum ranges. The differential switch. Icing may occur at temperatures
Set are made of gold-plated silver,
pressure acts via the diaphragm against below zero which may lead to a malfunc-
for 24 V DC; 0.02 A.
the force of the setting spring on the tion or failure of the equipment.
When using the Klima-Set in con-
microswitch.
ventional systems at 250 V AC, 4 A
If the set reference value is exceeded
ohmic load, 2 A inductive load, cos
or undershot, the circuit is switched
ϕ 0.6, the gold-plated coating on the
on, off or over.
switching contacts burns off.
The differential pressure switch of the
This makes a subsequent DDC
Klima-Set works without an auxiliary
application impossible.
power.
Specifications
Max. operating pressure 10 kPa (100 mbar)
Pressure connection Hose connector for hose ø 4
Temperature range Ambient temperature -15 °C to +85 °C
Medium temperature -15 °C to +85 °C
Storage temperature -30 °C to +85 °C
Materials Housing Polycarbonate
Switching part Polycarbonate
Diaphragms NBR
Switching contact gold-plated silver (Au), suitable for
DDC applications: 24 V DC; 0.02 A
Switching voltage Au contact DC min. 5 V max. 24 V
Nominal current Au contact DC 20 mA
Switching current Au contact DC min. 5 mA max. 20 mA
Electrical connection On terminal screws via cable duct M20 x 1,5
Protection type IP 54 as specified in IEC 529 (EN 60529), optional IP 65
Setting tolerance see setting range page 4, switching point deviation, relative to nominal value,
with vertical mounting position. Rising (↑) or falling (↓) setting available on site.
Deviation Permissible deviation of the set value ≤ ± 15 % in the service life test according
to EN 1854
Klima-Set scope of supply with
accessories
1. LGW...A2/7 differential pressure switch
2. Mounting plate
3. Connection hose 4 x 1.5, 2 m
4. fixing screws (6 x)
5. hose connection (2 x)
6. Extension tube (2 x)
7. Operating and assembly instructions
Mounting plate Hose connection Connection hose
dia. 4 x 1.5 x 2000
Fixing screws Extension tube
2…4
Dimensions [mm]
50,3 105
47,3 92
72,5
53,7 ø4
ø 4,2
+ connection P1
higher pressure
- connection P2
53,7
60
77
lower pressure
20
ø4
ø 4,6
,9
54
R
Switching functions Switching difference ∆p
As differential
2 NO
Pressure
pressure rises: at meter
Setting tolerance ± 15 %
1 NC opens
COM
Upper switching
pressure
Switching difference
2 NO closes
Falling
As differential 3
Adjustment as
pressure falls
1 NC
Rising
pressure falls:
Lower switching
± 15 % pressure
1 NC closes
2 NO opens P The switching difference ∆p is the pres-
sure difference between the upper and
lower switching pressures.
2 NO
Schematic diagram COM
Application and connection examples
3 1 NC
P N
+ + + + + + + + +
Connection Connection
P1 P1 Connection
Connection Connection
P2 P1P2 Connection
Connection Connection
P1 P2
P1 Connection
ConnectionConnectionP1
P2 Connection
P2 Connection Connection
P2 P2 Connection
P2
ConnectionConnection
P1 P2
P1 Connection P1
must remain must remain must remain
+ + + + + +
open open open
2 NO
COM
Monitoring system vacuum 3 Filter monitoring
1 NC Blower monitoring
To monitor the pressure in vacuum To monitor filter fouling, Klima-Set can In the blower monitoring system, con-
systems. be connected as shown above. Con- nection p1 (+) is connected on the pres-
Connect Klima-Set to the air duct via nection p1 (+) is connected upstream sure side downstream of the blower and
connection p2 (-). P N
of the filter and connection p2 (-) down- connection p2 (-) is connected to the
Do not connect connection p1 (+) to stream of the filter with the air channel air duct upstream of the blower.
the air duct. in flow direction of volumetric flow.
Do not close the hose connection
sleeve of connection p1 (+), a connec-
tion to atmosphere must exist.
Important: No dirt must enter into the
equipment through connection p1 (+).
Always connect higher pressure to Example - System pressure Example - System vacuum
connection p1 (+). Higher pressure: Lower vacuum:
Always connect higher vacuum to e.g. 240 Pa: Connection p1 (+) e.g. -130 Pa: Connection p1 (+)
connection p2 (-). Lower pressure: Higher vacuum:
e.g. 180 Pa: Connection p2 (-) e.g. -210 Pa: Connection p2 (-)
3…4
Klima-Set
Differential pressure switch for air
KS…A2-7
Brief technical data
1mbar = 100 Pa = 0.1 kPa ≈ 10 mm WS 1 Pa = 0.01 mbar ≈ 0.1 mm WS
Type Order No. Setting range Adjust- Switching Max.
with ment difference ∆p operating
accesssories [Pa] pressure
1 piece [Pa] min. / max. [kPa]
KS 150 A2-7 257 842 20-150 ± 8 Pa / ± 15 % ≤ 18 10
KS 300 A2-7 257 843 20-300 ± 8 Pa / ± 15 % ≤ 20 10
KS 600 A2-7 257 844 30-600 ± 10 Pa / ± 15 % ≤ 30 10
KS 1000 A2-7 257 845 0,1-1,0 kPa - ± 15 % ≤ 40 10
Accesssories/Spare parts for Klima-Set
KS-accessories complete 258 247
Mounting plate 230 301
Connecting tube ø 4 x 1,5, 2 m (10 x) 230 303
Hose connection (50 x) 230 306
Synthetic tubes (50 x) 230 307
Connector socket 231 770
Line socket 210 317
Assembly set display yellow 24 V 231 774
Assembly set display yellow 230 V 231 773
Assembly set display green 24 V 248 240
Assembly set display green 230 V 248 239
Replacement set cover IP 54 230 276
Replacement set cover IP 65 257 841
Adapter ø 4/6 (2 x) 266 037
Cylinder head screw ø 3x14 (2 x) 266 045
We reserve the right to make any changes in the interest of technical progress.