Types AKR-75/100 and AKS-50: Voltage Power Circuit Breakers
Types AKR-75/100 and AKS-50: Voltage Power Circuit Breakers
• Low Voltage
Power Circuit Breakers
AKR-6D-75
AKR-9D-100
AKS-5A-50
Courtesy of NationalSwitchgear.com
Low-Voltage Power Circuit Breakers
Table of Contents
Description Page Description Page
Courtesy of NationalSwitchgear.com
Insert to document GEK-64459D and GEK-64460A 2/10/97
LEGEND
CC CLOSING SOLENOID
F CUTOFF SWITCH, CLOSED WHEN
CLOSING SPRING IS FULLY
CHARGED.
G CUTOFF SWITCH. OPEN WHEN
CLOSING SPRING IS FULLY
CHARGED.
L AUXILIARY SWITCH
M CHARGING MOTOR
PB CLOSE PUSH-BUTTON ON BREAKER
(Y)
ESCUTCHEON, OPTIONAL.
(-) X CONTROL RELAY
FIG.E1 - ELEMENTARY DIAGRAM FOR OS ONE-SHOT ELECTRONIC. PULSES
ELECTRICALLY OPERATED DRAWOUT BREAKER. THE CLOSING SOLENOID FOR
CONTACT POSITIONS ARE SHOWN WITH BREAKER 250 MSEC.
OPEN AND CLOSING SPRINGS DISCHARGED. TYP #
183L712 &# 568B736 "E" SERIES
Courtesy of NationalSwitchgear.com
FIG. 13 - MANUAL OPERATION OF CLOSING SOLENOID
Courtesy of NationalSwitchgear.com
Table of Contents
Description Page Description Page
8.4.2 Resistance Values , 55 SECTION 13-Type EC
8.4.3 False Tripping - Breakers
Equipped with Ground Fault , 55
Overcurrent
8.5 SST Cabling Diagrams 55 Trip Device 85
13.1 Direct Acting Tripping Device EC-1 B 87
SECTION 9-Type ECS 13.1.1 Long Time Delay Tripping 87
Overcurrent 13.1.2 Short Time Delay Tripping 87
Trip Device " " 58 13.1.3 Instantaneous Tripping - High Set 87
9.1 ECS Cabling Diagram 59 13.1.4 Instantaneous Tripping - Low Set , 87
13.2 Replacement ,.......................... 87
SECTION 10- MicroVersaTrip ™ 13.3 Adjustments 88
Overcurrent 13.4 Series Overcurrent Tripping
Trip Device , 60 Device EC·2A , .. , . . . . . . . . . . . . . . . . .. 89
10.1 Programmer Unit , 60 13.4.1 Long Time-Delay and High Set
10.1.1 Fault Trip Indicators 60 Instantaneous Tripping , 89'
10.1.2 Remote Fault Indication , 60 13.4.2 Instantaneous Low Set Tripping , 89
10.2 MicroVersaTrip TM Installation , 62 13.4.3 Instantaneous High Set Tripping 89
10.2.1 AKS 50 Installation , 62 13.5 Series Overcurrent Tripping Device EC-1 91
10.2.2 13.5.1 Short Time-Delay Tripping 91
AKR 50/100 Installation , 63
10.3 13.5.2 Long Time-Delay Tripping 91
Current Sensors 64
10.3.1 Replacement of Currenl Sensors 13.5.3 Instantaneous Tripping 92
- AKS 50 65 13.5.4 EC-1 Adjustment 92
10.3.2 Replacement of Curent Sensors 13.6 Positive Trip Adjustment 92
13.7 Reverse Current Tripping Device 93
- AKR 75/100 65
13.7.1 Adjustments 94
10.4 Flux Shift Trip Device 65
13.7.2 Replacements 94
10.5 Troubleshooting 65
13.8 Switchette Feature , 94
10.5.1 Resistance Values , 66
13.9 Trip Device Replacement ., 94
10.5.2 False Tripping-Breakers
Equipped With Ground Fault 67 SECTION 14 - Electrical Characteristics ... 95
106 MicroVersaTrip TM Cabling Diagrams. . . . . . . . . . .. 67
Table 23
SECTION 11-RMS-9/Epic Charging and Closing Operating Currents 95
MicroVersaTrip® 71 Table 24
Bell Alarm Contact-Rating 95
11.1 Programmer Unit 71
Table 25
11.1.1 Fault Trip Indicators 71
Auxiliary Switch Contact Sequence 95
11.2 RMS-9 & Epic MicroVersaTrip Installation 71
Table 26
11.3 Current Sensors ' 72
Auxiliary Switch Contact Ratings 95
11.3.1 Replacement of Current Sensors 75
Table 27
11.4 Flux Shifter Trip Device 75
Charging Times 95
11.5 Troubleshooting 75
11.5.1 Resistance Values 75 Table 28
11.5.2 False Tripping-Breakers Equipped Shunt Trip and Undervoltage Device 96
With Ground Fault , 76 Table 29
11.6 Cabling Diagrams 76 Coil Resistance 96
Table 30
SECTION 12-MicroVersaTrip Plus and N
Instantaneous Undervoltage Device Settings 97
MicroVersaTrip PM Trip Units . .. 79 Table 31
Time-Delay Undervoltage Device Settings 97
12.1 Trip Unit " 79
12.2 Read This First 80
12.3 Product Structure 80 THESE INSTRUCTIONS ARE INTENDED FOR USE BY QUALIFIED
12.4 Trip Unit Removal and Replacement 81 PERSONNEL FOR INSTRUCTION AND MAINTENANCE PURPOSES.
12.5 Phase Current Sensors 82 REPRODUCTION IN WHOLE OR IN PART IS NOT PERMITTED
WITHOUT THE EXPRESS PERMISSION OF GENERAL ELECTRIC.
12.6 Neutral Current Sensors ' 83
12.7 Rating Plug Removal and Replacement , 83
12.8 Trip Unit Functions 83
3
12.9 Trouble-Shooting Guide 84
Courtesy of NationalSwitchgear.com
SECTION 1-1 ntroduction
Courtesy of NationalSwitchgear.com
Table 2-AKR 75/100 Designations
Example: AKR-5B-75 identifies a drawout, substructure-mounted breaker equipped with the SST trip device.
The EC trip devices are electro-mechanical, refer to GEl 86157 for detailed information.
Breaker Models
(*) This digit identifies N = Non-automatic.
the trip device: In addition, all
2 = EC-1 B. Dc only, non-automatic 250V.
4 = ECS Dc breaker types carry the
5 = SST 50/60 Hertz only. suffix letter D after the
6 = MicroVersaTrip 50/60 Hertz only. frame number,
7 = RMS-9 e.g., AKR-NB-75D.
9 = MVT-PLUS or MVT-PM CD AKR-75H not available for DC applications.
For detailed information on
these trip devices refer to
Sections 8 thru 11.
Courtesy of NationalSwitchgear.com
SECTION 2-General Description
Courtesy of NationalSwitchgear.com
Table 3-Mounting Type Codes
Breaker Type
Code
Letter Drawout Stationary
None AKD ---
A AKD-5,6 ---
B Substructure ---
C AKD-6 Only ---
D AKD-8 ---
F Substructure ---
S --- AKR-75/100 (25" wide)
2.4-Trip Device
There are six types of solid-state, direct-acting self-
powered trip device systems associated with AKR
breakers. These systems are for AC applications only. For
DC applications an electromechanical system is available.
Fig. 2. Electrically operated, AKD type The trip device system is identified by the first middle digit
in the breaker's nameplate designation as follows:
AKR-(t) C-75
(t) = trip device code per Table 4
Courtesy of NationalSwitchgear.com
Table 5- Breaker Interruption Ratings
30 Interruption Rating
KA RMS Symmetrical
Frame Instantaneous Trip
Size Breaker Rated Maximum Short
(Amperes) Type Voltage (60 Hz AC) With Without Time
635 42 42 42
AKS-50 508 50 50 50
254 65 50 42
1600 AC 635
AKS-50H 508 65 65 65
254
AKSU-50 600 200 200 -
635 42 42
2000 AC AKST-50H 508 42
65 65
254
635
65 65
AKR-75 508 65
254 85 65
3200 AC 635
85 85
AKR-75H 508 85
254 130 85
AKR-75 (fused) 600 200 200 -
635
85 85
AKR-100 508 85
4000 AC
254 130 85
AKR-100 (fused) 600 200 200 -
AKS50
2000 DC 300V DC 50 CD (2) -
AKS 50V
4000 DC AKR 75 300V DC 50 50 -
6000 DC AKR 100 300iJ DC 50 50 -
Q) With 200-2000 amp trip coils
® Consult factory for application data
Courtesy of NationalSwitchgear.com
SECTION 3-Storage, Safety & Maintenance
3.1-Storage tions, National Electric Safety Code (ANSI C2), The National
Electrical Code, and NFPA 70B Electrical Equipment Mainte-
It is recommended that the breaker be put into service nance must be closely studied and followed. During actual
immediately in its permanent location. If this is not work, supervision should audit practices to assure conformance.
possible, the following precautions must be taken to insure 3. Excellent maintenance is essential for reliability and safety of
the p roper storage of the breaker: any electrical equipment. Industry publications of recom-
1. The breaker should be carefully protected against mended maintenance practices such as ANSI/NFPA 70B, Elec-
condensation, preferably by storing it in a warm trical Equipment Maintenance, should be carefully studied and
dry room, since water absorption has an adverse applied in each user's formation of planned maintenance.
effect on the insulation parts. Circuit breakers for
outdoor switchgear should be stored in the
3.3
equipment only when power is available and the Both long and short term maintenance of all electrical equip-
heaters are in operation to prevent condensation. ment is essential for reliability and safety. Maintenance pro-
grams must be tuned to the specific application, well planned
2. The breaker should be stored in a clean location and carried out consistent with both industry experience and
free from corrosive gases or fumes. Particular care manufacturer's recommendations. Local environment must
should be taken to protect the equipment from always be considered in such programs, including such vari-
moisture and cement dust, as this combination has ables as ambient temperatures, extreme moisture, number of
a very corrosive effect on many parts. operations, corrosive atmosphere or major insect problems
and any other unusual or abusive condition of the application.
One of the critical service activities, sometimes neglected,
CAUTION: IF THE BREAKER IS STORED FOR involves the calibration of various control devices. These
ANY LENGTH OF TIME, IT SHOULD BE monitor conditions in the primary and secondary circuits,
INSPECTED PERIODICALLY TO SEE THAT sometimes initiating emergency corrective action such as
RUSTING HAS NOT STARTED AND TO opening or closing circuit breakers. In view of the vital role
ASSURE GOOD MECHANICAL CONDITION. of these deVices, it is important that a periodic test program
SHOULD THE BREAKER BE STORED UNDER be followed. As was outlined above, it is recognized that the
UNFAVORABLE ATMOSPHERIC CONDI- interval between periodic checks will vary depending upon
TIONS. IT SHOULD BE CLEANED AND DRIED environment, the type of device and the user's experience. It
OUT BEFORE BEING PLACED IN SERVICE. is the General Electric recommendation that, until the user
has accumulated enough experience to select a test interval
better suited to his indiVidual requirements, all significant
3.2 calibrations be checked at an interval of one to two years.
Each user must maintain a safety program for the protection To accomplish this, some items, such as "EC" direct operating
of personnel, as well as other equipment, from the potential trip systems for low voltage breakers, must be tested with
hazards associated with electrical equipment. primary current injection. Others can be adequately tested
using test sets. Specific calibration instructions on particular
The following requirements are intended to augment the devices typically are provided by supplied instruction books.
user's safety program, but NOT supplant the user's respon-
sibility for devising a complete safety program. The follow- Instruction books supplied by manufacturers address com-
ing basic industry practiced safety requirements are appli- ponents that would normaliy require service or maintenance
cable to all major electrical equipment such as switchgear or during the useful life of the equipment. However, they can
switchboards. General Electric neither condones nor assumes not include every possible part that could require attention,
any responsibility for practices which deviate from the following: particularly over a very long service period or under adverse
environments. Maintenance personnel must be alert to dete-
1. ALL CONDUCTORS MUST BE ASSUMED TO BE ENER- rioration of any part of the supplied switchgear, taking ac-
GIZED UNLESS THEIR POTENTIAL HAS BEEN MEASURED AS tions, as necessary to restore it to serviceable status.
GROUND AND SUITABLE GROUNDING CONDUCTORS HAVE
BEEN APPLIED TO PREVENT ENERGIZING. Many accidents Industry publications of recommended maintenance practices
have been caused by back feeds from a wide variety of such as ANSIINFPA 70B, Electrical EqUipment Maintenance,
sources. should be carefully studied and applied in each user's forma-
tion of planned maintenqnce.
2. Although interlocks to reduce some of the risks are provided,
the individual's actions while performing service or maintenance Some users may require additional assistance from General
are essential to prevent accidents. Each person's knowledge; Electric in the planning and performance of maintenance.
his mental awareness; and his planned and executed actions The General Electric Company can be contracted to either
often determine if an accident will occur. The most important undertake maintenance or to provide technical assistance
method of avoiding accidents is for all associated personnel to such as the latest pUblications.
carefully apply a thorough :.Jnderstanding of the specific equip- The performance and safety of this equipment may be com-
rrent from the viewpoints of it's purpose, it's construction, it's promised by the modification of supplied parts or their re-
opJration and the situations which could be hazardous. placement by non identical substitutes. All such design
All personnel associated with installation, operation and mainte- changes must be qualified to ANSI/IEEE Standard C37.59.
nance of electrical equipment, such as power circuit breakers The user should methodically keep wr(tten maintenance
and other power handling equipment, must be thoroughly in- records as an aid in future service planning and equipment
structed, with periodic retraining, regarding power equipment in reliability improvement. Unusual experiences should be
general as well as the particular model of equipment with which promptly communicated to the General Electric Company.
they are working. Instruction books, actual devices and appro- 9
priate safety and maintenance practices such as OSHA publica-
Courtesy of NationalSwitchgear.com
SECTION 4-Breaker Operation
LEGEND
CC - CLOSING SOLENOID
CONTROL
SOURCE F- CUTOFF SWITCH, CLOSED
WHEN CLOSING SPRING IS
FULLY CHARGED.
G- CUTOFF SWITCH. OPEN WHEN
CLOSING SPRING IS
FULLY CHARGED.
CC
L- AUXILIARY SWITCH
M- CHARGING MOTOR
PB - CLOSE PUSHBUnON ON
BREAKER ESCUTCHEON,
OPTIONAL.
TC TC - SHUNT TRIP DEVICE
W- ANTI-PUMP RELAY
X- CONTROL RELAY
Courtesy of NationalSwitchgear.com
4.2.1-Alternate Control Circuit equipped) or by a remote closing switch. Operation of the
closing switch energizes the W-relay, which in turn
Later production breakers use the electrical control circuit
energizes the closing solenoid. This removes the prop,
shown in Fig. 3B. This circuit is similar to the circuit shown
in Fig. 3A except that the X-relay and 'F' switch are elimi- releasing the closing springs to close the breaker.
nated. If the closing switch is maintained closed, the anti-pump re-
lay will remain picked-up to prevent a second motor charge
The motor is energized through the 'G' switch and the W-
and closing operation on the breaker in the event it is tripped
relay contact. The 'G' switch deenergizes the motor when
open automatically. The closing impulse must be released
the closing springs are charged and the prop is engaged.
and reapplied after the closing springs are fully-charged be-
With the closing spring propped fUlly-charged, the breaker fore a second closing operation can occur. The charging
is ready for closing. This may be accomplished electrically time is typically 1 to 3 seconds depending on voltage and
by depressing the closing switch on the breaker (if so the maximum time permitted is 5 seconds.
REMOTE
CLOSE
0-------0- - -1 ~ -.., LEGEND
)...
CONTROL
SOURCE
t~ PB
CC -
G-
CLOSING SOLENOID
CUTOFF SWITCH. OPEN WHEN
CLOSING SPRING IS
FULLY CHARGED.
W L- AUXILIARY SWITCH
M - CHARGING MOTOR
PB - CLOSE PUSHBUTTON ON
BREAKER ESCUTCHEON,
OPTIONAL.
TC ....... SHUNT TRIP DEVICE
L W- ANTI-PUMP RELAY
CC w TC
Fig. 38. Alternate elementary diagram. Contact positions are shown breaker open and
closing springs discharged. TYP #5688736 "8" series.
11
Courtesy of NationalSwitchgear.com
SECTION 4-Breaker Operation
Q d 9 0 o 0 0 0 0 0
TERMINAL BOARD 2 3 4 5 6 7 8 9 10
MOUNTED ON FRONT
OF BREAKER AT TO AUX. SW
UPPER LEFT "a" CONTACT
CUSTOMER
CONNECTIONS "-t---'
UV
TRIP
SOURCE 1-) 1+)
REVERSE
CURRENT
'-.,-' '-.,-' DEVICE
POTENTIAL
CLOSING TRIP SOURCE
SOURCE SOURCE
IYI
IY)}
TRIP CLOSING
SOURCE FUSE
SOURCE
{
(X)~ IX)
TRIP
/\/\/\/\/\/\/\ /\ /\ /\ /\ /\ /\ /\
765432 765432 765432
1 J
Fig. 5. Control connections to drawout breakers - front view of breaker compartment
12
Courtesy of NationalSwitchgear.com
4.4-Tripping 4.5-Charging and Closing Using
In the closed position, the breaker movable contacts are the Maintenance Handle
held in by a toggle linkage, The breaker is tripped open by
In the absence of control power, an electric breaker can be
displacing a mechanism latch which allows this toggle
closed manually by using the maintenance handle to
linkage to collapse, The trip latch is rigidly fastened to a
charge the closing springs. Referring to Fig. 6:
horizontal trip shaft running from left to right through the
breaker, In turn, the trip shaft carries paddles actuated by (a) With the breaker open and springs discharged
the manual trip button and the various other trip devices- release holding pawl slide per instruction label (2).
overcurrent, reverse current, shunt trip, undervoltage, (b) Install maintenance crank (1) (5686386Gl) to the motor
open fuse lockout. Viewing the breaker from the right, gear reducer shaft on the front right side of the breaker. Rat-
rotating the trip shaft counterclockwise trips the breaker; chet the maintenance crank up and down until the springs are
clockwise movement resets the mechanism latch, fully charged as indicated by the distinct click as the prop is
In addition to tripping the breaker, some devices hold the set. This prevents any further charging of the closing springs.
breaker trip free, i.e" prevent the contacts from closing After the prop is set do not apply undue force to the
even though a closing impulse is applied to the maintenance handle.
mechanism. Such devices are the undervoltage, bell alarm (c) Depress the "Spring Discharge" lever (3) located
and lockout, electric lockout, open fuse lockout, and the under the horizontal su pport on the front frame. The
key operated locks. springs should discharge and if the latch is properly reset,
These devices and the drawout mechanism interlocks must the breaker will close. Some style breakers, because of an
be in the reset position before the breaker can be closed. interlock in the SWitchgear, can not be manually closed in
the fully engaged position.
(d) Open the breaker by pushing the trip button (4).
1. Maintenance crank
2. Instruction label
3. Spring discharge lever
4. Trip button
13
Courtesy of NationalSwitchgear.com
SECTION 5-Contact Maintenance
14
Courtesy of NationalSwitchgear.com
1. Maintenance
2. Guide rods
3. Safety pins
4. Prop
5. Closing springs
15
Courtesy of NationalSwitchgear.com
SECTION 5-Contact Maintenance
e. Lift arc quenchers clear of the movable arcing contact 5.3-Separation of Front and
arms.
Back Frames
f. Inspect arc quenchers carefully and replace if
In order to perform some repair and replacement
necessary.
operation, the front frame must be separated from the back
g. During replacement, tighten jack screw nuts (4) first, frame. Proceed as follows: referring to Fig. 9.
then the two hex head bolts that secure the channel-
a. Open the breaker, manually compress the closing
shaped retaining bar to side sheet. DO NOT
springs and insert the safety pin as described under
OVERTIGHTEN THESE TWO SOLTS.
SLOW CLOSING, Section 5.1. Restraining the springs
properly positions the main operating cam to facilitate the
separation operation.
16
Courtesy of NationalSwitchgear.com
~-
E1-
1]-
b. Remove the two opening springs (1) (on lower part of k. Remove the six nuts from the back frame using a
the breaker) from the outside pole units. socket wrench with an extension. These include the two
nuts at the top of the frame.
c. Remove the clevis pin (2) from the center pole unit.
I. Check along the trip shaft for a mechanical
d. Disconnect the programmer CT wire harness at each CT
interference or connection between the overcurrent trip
and remove any tye wraps holding leads to back frame.
device and the trip paddles. Remove mechanical
e. Disconnect the flux shifter actuator bracket from the connection if present, or if interference exists, use extreme
crossbar assembly (4). care when removing or reassembling front and back
frames to avoid mechanical breakage of trip devices.
f. Remove the auxiliary switch operating rod (5).
When reassembling the front and back frames, both should
g. Remove outside phase barriers (6).
be positioned vertically so that the trip shaft is horizontally
h. Remove side support bolts (7). aligned. It is recommended that the breaker back frame
i. Remove position interlock on AKD, AKD 5. AKD be fastened to a suitable mounting surface so that the front
6 type (8). frame can be supported by a sling or hook as the bolts are
being installed.
j. Remove arc quencher retainer and bolts (9).
17
Courtesy of NationalSwitchgear.com
SECTION 5-Contact Maintenance
5.4-Back Frame Assembly Mating with the stationary contacts is a moveable contact
assembly consisting of multiple main and intermediate con-
The breaker backframe consists of a frame assembly to
tact fingers (10) and (8). These moveable contact fingers
which the pole units are mounted. Each pole unit is
pivot on a stationary pin (11), which fasten them to the lower
connected to a common crossbar which provides for
contact block. The insulated link (13) which is attached to
simultaneous pole unit operation by the breakers
the breaker crossbar (1) and moveable contact assembly
mechanism. A typical backframe is shown in Fig. 10. gives the open and close motion to the contact arm.
The pole units consist of a molded base which supports
The stationary arcing contact assembly (3) is a separate
the line and load stud assemblies, stationary and moveable
set of contact fingers, pins, springs and pivot block.
contact assemblies and the actuating linkage.
The moveable arcing contact assembly (5) consists of
The stationary main contact assembly (9) comprises of a
multiple contact arms carried on two moveable pins (6)
spring loaded contact fingers. Interlocked with these are
and (12). The arcing contact arms interleave the main
the intermediate contact fingers (7) whose contact surface
contacts and pivot with them about pin (6). This relative
project beyond that of the mai n such that the
motion is obtained by the insulating links (13) from the
intermediates make before, and break after the mains.
contact arms to the breaker crossbar.
18
Courtesy of NationalSwitchgear.com
5.5-Measuring Contact Force 5.6-Measuring Contact Wipe
a. Remove the arc quenchers. Referring to Fig.11:
19
Courtesy of NationalSwitchgear.com
SECTION 5-Contact Maintenance
Open gap
/
2'12 to 2314
Clevis
A_.v--+~ (centerpole)
Stationary
Arcing Contact
Lower
UPPER Stationary main contact Stud
STUD
Table 6
Main Contacts Intermediate Contacts Arcing Contacts
Column 1 2 3 4 5 6 7 8 9
Wipe Wipe Wipe
Oty. Force in Oty. Force in Oty. Force In
Breaker Per in Inches Per in Inches Per in Inches
Type Pole Lbs. (B) Pole Lbs. (B) Pole Lbs. (A)
AKS-50 (AC)
AKS-!iO 10C;\
3
~
35-55 1
1
35-55 ·· 2
3 5/32 to
AKR-75 (AC)
AKR-75 (DC)
5
5
25-55
'/'6 to
'/64
1
1 25-55
·· 3
5
31-43 9/32
AKR-100 (AC/DC) 6 2
· 5
'The intermediate contact wipe should be at least '/16 in. greater than main contact wipe.
20
Courtesy of NationalSwitchgear.com
5.B-Measuring Contact Open Gap Measure the contact open gap between the movable and
stationary contacts as shown in Fig. 13. This distance
Prior to measuring the open gap verify that the cross arm
buffer assemblies, refer to Fig. 12, are touching. The stack- should be between 2-1/2" to 2-3/4". This gap may be
up dimension of each buffer should be within .015" of each adjusted by repositioning shims on crossbar assembly.
other. Adjust to this dimension by adding or removing wash- The locking nuts on the buffer bolts should be locked in
ers. such a position that the buffer bolt may be rotated freely.
21
Courtesy of NationalSwitchgear.com
SECTION 5-Contact Maintenance
5.9-Checking Contact Sequence 5.10-Replacement of Contacts
On the horizontal plane, the difference in the making of the Criteria for replacement:
arci ng contacts on the same pole must be no greater than
a. Arcing contacts should be replaced when eroded to a
1/16 in.; this difference between arcing contacts on
thickness of 5/64.
separate poles must be 1/16 in. If it is desired to advance
or retard the closing of the main contacts of a pole, loosen b. Intermediate contacts should be replaced when flush
the bolts holding the adjustment plate, refer to Fig. 21, of with main contacts (.062 lead when new).
that pole and slide plate to the left to advance contact c. Main contact very seldom needs replacement.
closing, or to the right to retard contact closing. Make this Replace when arcing contacts have been neglected
adjustment on the outer poles, using the center pole as a causing severe erosion of mains so you can not obtain
reference. Upon retightening adjustment plate bolts, make proper contact depression.
sure the locking tabs are turned up around bolt heads,
locking the bolts securely in place. When replacing the arcing contact assemblies you do not
have to separate the front frame from the back frame.
Contact sequence in the vertical plane should be such that
when the arcing contacts are just touching, the 5.1 O.1-Stationary Arcing Contacts
intermediate contact gap should be at least 3/16 in. and
the main contacts gap at least 1/4 in., see Fig. 14. a. Refer to Fig. 15.
b. Remove insulator block (1).
NOTE: This check can best be made by means c. Slide pin (2) to side. Contact assembly (3) will lift
of the maintenance handle, with the safety pin freely exposing two springs (4) and button (5) ..
restraining the closing springs. See Section 5.1
d. Install new parts inreverse order.
for this procedure.
Courtesy of NationalSwitchgear.com
5.10.3-Moveable Main and d. Remove contact arms, noting two spring washers (9)
on each contact pivot.
Intermediate Contacts
Upon re-assembly, position two spring washers into
a. Refer to Fig. 16.
counter bore on one side of contact arm (9). Note left and
b. Loosen crossbar bolts so link (10) can move freely. right hand orientation of contact arms and position of
intermediate contact.
c. Remove retaining rings (7) from pins (8).
Slide pins (8) until contact arms can be withdrawn. e. Before tightening crossbar see assembly and
adjustment of crossbar, Section 5.11.
iE----
7. Retaining rings
8. Pins
9. Spring washers
10. Crossbar bolts
11. Intermediate contact
23
Courtesy of NationalSwitchgear.com
SECTION 5-Contact Maintenance
5.10.4-Stationary Intermediate and f. Remove contact, noting two spring washers on each
contact pivot. Upon re-assembly, position two spring
Main Contacts washers into counter bore on one side of contact arm. Fig.
a. Separate the front frame from the back frame. Refer 19.
to Section 5.3.
b. Remove crossbar. NOTE: Left and righthand orientation of
contact arms and position of intermediate
NOTE:ln the steps below, refer to Fig. 17 to contact. Fig. 19.
identify the numbers in the parenthesis.
g. Depress main and intermediate contacts to relieve
c. Remove arcing contact block (3) by removing allen spring pressure on contact stop bracket before starting
screws (4) and (5). screws. Tighten screws before releasing pressure.
Fig. 18.
d. Depress main and intermediate contacts as shown in
Fig. 18 to relieve spring pressure on contact stop bracket h. Re-install arcing contact block by holding arcing
(6) before removing mounting screws. On AKR100 you contacts depressed (Fig. 20) while tightening screws.
must remove the outside moveable contact arm before i. Assemble crossbar.
trying to remove contact stop bracket mounting screws.
j. Always check contact wipe following contact
e. Remove retaining ring (7) and slide pin (8) to side and replacement. See Secton 5.6.
withdraw the contact arm. Fig. 17.
ill
1. Main contact arm 6. Contact stop bracket
2. I ntermediate contact arm
3. Arcing contact block Fig. 18. Relieving spring pressure
4. Arcing contact
5. Allen screws
6. Contact stop bracket
7. Retaining ring
8. Pivot pin
24
Courtesy of NationalSwitchgear.com
Fig. 19. Upper stud details Fig. 20. Re-assembly of arcing contacts
5.11-Assembly and Adjustment of screws with locking plates on crossbar finger tight and set
crossbar to dimension shown making sure that all three
Crossbar poles of moveable arcing contacts are touching stationary
When assembling crossbar to back frame push moveable arcing contacts within .032. Tighten screws as shown first
arcing contacts forward until they touch stationary arcing "A", second "B", and finally "C" to 400 inch pounds. Bend
contacts on upper terminal. Then lay crossbar on top of tabs on locking plates to secure screws. Refer to Fig. 21.
links on pole units. Assemble adjusting plates as shown After assembling crossbar always check contact wipe and
making sure slots in plates are properly oriented. Fasten open gap, see Sections 5.6 thru 5.8.
25
Courtesy of NationalSwitchgear.com
SECTION 6-Breaker Maintenance
26
Courtesy of NationalSwitchgear.com
ill] 7----iE
I
11~----iE
iJ'
[II
~--It-I~
-ml
~ d >'-~J--~
II i- ---1
Q---rlJ
\\~,~:---a
.4t=====,;m
~
~
1. Spring 10. Trip latch
2. Cam 11. Trip shaft
3. Link 12. Clevis pin
4. Reset spring 13. Clevis
4A. Spring adjusting nuts 14. Reset latch
5. Prop 15. Roller
6. Adjusting screw 16. Prop
7. Adjusting screw stop pin 17. Bearing
8. Prop return spring 18. Buffer
9. Roller 19. Nut
Fig. 22C. Mechanism in closed position Fig. 220. Latch, bearing, and prop
(closing spring discharged)
-il
-~ -il
-~
-~
-f]
Fig. 23. Adjusting trip latch and roller Fig. 24. Adjusting bearing and prop
27
Courtesy of NationalSwitchgear.com
SECTION 6-Breaker Maintenance
6.4-Electrical Mechanism 6.4.1-Control Components
The function of the electrical mechanism is to charge and Referring to Fig. 25:
discharge the closing springs either electrically or
The control relay (X) is located on the left side of the front
manually. The electrical mechanism consists of
frame channel. It may be removed by disconnecting the
a. Control components wiring, loosening the two mounting screws and lifting it
slightly to pass the top mounting screw through the
b. Charging motor
keyhole mounting. The entire relay should be replaced
c. Motor operator unit rather than changing coils and contacts.
d. Spring discharge interlock The antipump relay (W) is located on the left side of the
front channel. The connections to this relay are soldered.
Section 4.2 details the associated control circuitry for the
electrical mechanism. Relay replacement requires unsoldering of these
connections and removing the mounting hardware. When
replacing relay take care in soldering connections. Do not
use excess amount of solder on connectors as to impair
operation of contact arms.
The closing solenoid is located in the lower right hand side
of the motor operator unit. The switchette is separately
mounted in front of the solenoid.
28
Courtesy of NationalSwitchgear.com
After replacing closing solenoid or switchette check
adjustment of switchette and readjust if necessary. With
breaker in discharge position use a .010 feeler gage and
push closing solenoid to position shown in Fig. 26.
Switchette must be activated at this point. To adjust loosen
MOlor
switchette mounting screws and pivot switch until AHembly
OPERATOR
activated, then tighten screws. Recheck. Mounting
Hrmiwr.tre
~ Closing Solenoid
MOTOR
mounting
Hardware
//~
Maintenance
Handle Shall
,
W
'----='l'+.IIF:1Io-""""~Retaining Ring
Drille Link
.0'_.060,men","
required with
lever in posilion
shown Adjust
II necessary
Opening Spring
Bracket
Opt>fd!,ng leyer
Connection
"0" Points
6.4.2-Charging Motor
The charging motor is located on the right side of the
breaker. It is mounted on the motor operator as shown in
Fig. 27. A driving pawl is mounted eccentrically on the -iJ
motor shaft, see Fig. 28. As the motor turns, the driving
pawl rotates the ratchet which charges the closing springs.
The ratchet is kept from reversing its direction by the
holding pawl. To remove the motor:
a. On AKS 50 you must remove the side sheet.
b. Disconnect and identify the motor leads at the closing
solenoid and cutoff switch.
c. Remove three motor mounting screws.
1. Driving pawl
d. Remove motor.
e. When reassembling, assemble with the driving pawl Fig. 28. Motor removal
pointing toward the front of the breaker.
See Fig. 28.
29
Courtesy of NationalSwitchgear.com
SECTION 6-Breaker Maintenance
6.4.3-Motor Operator Unit The motor drives the crank roller/maintenance handle
shaft until the control circuitry stops the motor and roller is
The motor operator unit is located on the right hand side
against the prop. The crank roller drives the cam shaft,
of the breaker as shown in Fig. 29. Operator details are
charging the spring, through the cam shaft paddle,
shown in Fig. 30.
see Fig. 31.
The motor operator unit is not adjustable. To replace the
unit, refer to Fig. 27:
a. Slow close the breaker, see Section 5.1
b. Remove the motor, see Section 6.4.2. The motor
wiring doesn't have to be disconnected.
c. Disconnect the wiring to the closing solenoid and
solenoid switch.
d. Remove retaining ring from closing solenoid drive
link.
e. Remove three mounting bolts, one from the side, two
from the bottom of the charging mechanism. Note the
positions of the standoffs on the two bottom mounting
bolts and replace in the same position when reassembling.
f. Rotate motor operator shaft so its crank roller faces
the rear of the breaker. Refer to Fig. 32.
g. Slide spring charging mechanism out toward the right
of the breaker.
1. Motor operator unit h. Install new spring charging mechanism making sure
the crank roller engages cam shaft guide. Refer to
Fig. 29. Motor operator unit location Figs. 31 and 33.
1)= ===rl -
II II
- - -
Cam
Shaft Pivot I' "
~'II :I Celm Shaft
____ l'==:=:J,L---- Paddle
Crank
Roller
Maintenance Motor
Handle Shaft Operator
Crank
Roller .
Assembly Guide
r"T-t--_ era n k
Roller
30
Courtesy of NationalSwitchgear.com
i. Reassemble all components and connect all wires.
j. Remove safety pin from closing spring by placing
your maintenance handle on the shaft which extends from
the spring charging mechanism and charge the closing
spring until the charging mechanism roller engages with
tile prop. Remove safety pin. This must be done before
power is applied to motor.
k. Operate the breaker using the maintenance handle
and spring discharge mechanism a few times. Verify that
the breaker is operati ng properly.
I. Before applying control voltage to your breaker verify
that the motor cut off switches are properly adjusted.
Charge the closing spring as described in
step j. (roller resting on prop). Adjust the motor cut off
switches, shown in Fig. 35, so that they are depressed to
the point where the main stem of each switch is located
.005" to .031" from the threaded barrel, see Fig. 34.
(Continued next page)
______ .031
-4---
.005
Main Stem
Threaded Barrel
31
Courtesy of NationalSwitchgear.com
SECTION 6-Breaker Maintenance
6.4.3-Motor Operator Unit (Cont.)
m. When the control voltage is applied to your breaker,
the motor operator will be energized and charge the
closing spring. The G switch (see Fig. 36) of the motor cut
off switch unit will stop the motor operator just before the
roller engages the prop. The breaker may be closed
manually by depressing the spring discharge lever or
electrically by energizing the closing solenoid.
"F" Switch
32
Courtesy of NationalSwitchgear.com
1. Upper spring pin 21. Ratchet pawls
3. Safety pin and chain 25. Main closing crank
5. Closing springs 26. Pawl buffer stop
7. Pawl springs 27. Buffer stop shims
18. side plate shims 31. Lower spring pin
19. Side plate mounting bolts 33. Ant. rebound spring
20. Bearing side plate 34. Ant. rebound pawl
6.5.1-Mechanism Part d. Remove the closing handle (22) by removing two set
screws threaded in same hole.
Replacement
e. Remove the front escutcheon by removing four
If it is necessary to replace any of the mechanism parts, screws holding it to the front frame center support.
the following total procedure is recommended. This
procedure may be halted at the step required to replace f. Remove handle shaft extension by removing
any particular part. Referring to Figs. 37 & 38: roll pin.
a. Install the safety pin (3) as described in g. Remove the handle return spring (29) by unhooking
Section 5.1.2. either end of the spring.
b. Remove the closing spring assembly by removing the h. Disconnect the top end of each pawl spring (7).
upper and lower spring pins (1,31). i. Remove the roll pin (24), thus allowing the closing
c. Remove the right hand bearing side plate (20), and handle shaft and pawl assembly (23) to be removed.
the side plate shims (18) by removing four mounting bolts j. Remove the ratchet wheel (17) and its assembly (16)
(19), thus allowing the main closing crank (25) to be by removing self locking screw (15) and thrust bearing
removed. (12). If shims (13) are present they must also
be removed.
(Continued next page)
33
Courtesy of NationalSwitchgear.com
SECTION 6-Breaker Maintenance
MANUAL MECHANISM
- - - - - - - - - - -I---."...-~-::;;i
~. 3 4------~_+-lD\-____L
~~~~y;--ti--5-------++;~
!
I 1E--+-+-++-t+----6---------+,---';--t--'R\
!Oi£-+----7
I i i\II
! !III
I
!
I
; "
II
§D 31
-r-jH .'
(\(),
' 28
\ '
il I
!i \ !~ I
-,r~·- Ji '..
-~jJ
!
j
Partial Front View
With Handle And Escutcheon Removed
34
Courtesy of NationalSwitchgear.com
k. Remove front bearing plate (9) by removing mounting
bolts (10) accessible from the front of the breaker. The
mechanism is now completely disassembled. It is not
recommended that any of the subassemblies removed
during the above operation be further disassembled in the
field. Replacement sub-assemblies should be obtained
from the factory.
I. To reassemble the mechanism, reverse the procedure
described above and follow the adjustments given in
Section 6.5.3.
35
Courtesy of NationalSwitchgear.com
SECTION 6-Breaker Maintenance
6.6-Drawout Mechanism c. Remove racking cam assembly and replace with new
cam.
Drawout breakers are manuafactured in five different
styles depending on the type of equipment that the breaker d. Align center of worm with worm gear on racking cam
will be used in. The mounting code and description of then position collars firm against supports and tighten set
each style is found in GEI-86151 furnished with each screws in collars.
breaker. If replacement of racking cam is needed the
To replace guide support (4):
following procedure should be used. See fig. 41.
a. Remove screws (5) and support (6).
a. Remove nut (1) and screw (2).
b. Remove guide (4) and replace with new guide.
b. Loosen set screws in collar (3).
c. Reassemble.
36
Courtesy of NationalSwitchgear.com
SECTION 7........ Accessories
7.1.1-AKR 75/100 Fig. 43 shows the finger type disconnect assembly used on
AKD-6, AKD-8 switchgear and substructure type breakers.
There are two types of primary disconnects found on the
If replacement of primary finger is needed, you must
AKR 75/100 breakers.
replace complete sUbassembly set of fingers, which are
Fig. 42 shows the tubular type primary stud used on factory adjusted to proper spring tension. Reassemble as
replacement breakers for the older AKD, AKD5, AKD6 described above. See renewal parts publication GEF-4552
sWitchgear. If for any reason the primary stud must be for proper ordering data.
AKR75· AKR100
37
Courtesy of NationalSwitchgear.com
SECTION 7-Accessories
1.1.2-AKS/AKST 50 Fig. 47-The position of the spacer in the breaker stud.
The hole in the spacer must be positioned as shown so it
The AKS 50 and AKST 50 use eight primary fingers per will align with the holes in the clip.
phase as shown in Figs. 44 thru 47. Refer to these
illustrations when replacing the disconnects. Note the Fig. 46-The engagement of the fingers with the retainer.
following details. Also the location of the "bowtie" spacers in the fingers,
both upper and lower.
(Continued next page)
Fig. 44. Primary disconnect assembly Fig. 45. Partial primary disconnect ASM
Fig. 46. Partial primary disconnect ASM Fig. 47. Partial primary disconnect ASM
38
Courtesy of NationalSwitchgear.com
Fig. 44 & 45- The position of the upper and lower retainers
and, again, the 'bowtie' spacers.
1. Secondary disconnect
39
Courtesy of NationalSwitchgear.com
SECTION 7-Accessories
7.2.1-(Cont.)
e. Push wire through hollow tube of new disconnect 7.3.1-Replacement
assembly.
Referring to Fig. 51:
f. Strip insulation off end of wire to about '/, in. from the GE SB-12
end.
a. Disconnect all leads.
g. Place new contact tip on end of wire and crimp. b. Remove two mounting bolts.
h. Pull wire through hollow tube until contact tip fits c. Disengage auxiliary switch shaft (4) from triangular
snugly against end of hollow tube. link (2).
i. Crimp tab on other side of assembly to hold wire in d. Orient the shaft of the new switch so that the arrow
place. stamped on the shaft end points towards the front of the
breaker.
j. Any hollow tubes which are not used should be
pushed into the disconnect body and held in that position e. Push auxiliary switch shaft into square hole in link
by placing fiber spacers over inner ends of tubes and (breaker open).
spreading tabs. f. Replace mounting hardware and wiring.
k. When all wires have been connected, refasten the Electro Switch
body of the moveable disconnect assembly to the breaker Follow the above procedure except in step d. In step d, orient
cross-channel. the shaft of the new switch so that the horizontal line on the
end of the shaft is horizontal when the breaker is open.
7.3-Auxiliary Switch 7.3.2-Adjustment
All electrically operated breakers and manual breakers hav-
ing shunt trips are supplied with auxiliary switches. Depend- The auxiliary switch operating shaft must be positioned
ing upon the requirements of the breaker application, the such that during breaker closing, the "a" contacts make
switch may contain two to six stages. Usually each stage before or not later than the first touch of the breaker's
one "A" contact and one "B" contact. "A" contacts are open arcing contacts. If before, the open gap of the arcing
or closed as the breaker is opened or closed. "B" contacts contacts must not exceed %-inch. This can be checked by
are the reverse of this. connecting a bell set across the "a" terminals and slow-
closing the breaker with the maintenance handle. The "a"
The auxiliary switch is mounted on the upper left side of the
mechanism frame as shown in Fig. 51. As the crossbar (1) contact closing can be advanced or retarded by
moves to the open or closed position, it operates triangular lengthening or shortening operating rod (3), Fig. 51.
link (2) via operating rod (3). The triangular link rotates the The operating rod should also be aligned vertically to be
auxiliary switch operating shaft. parallel with the sides of the frame center channel and
perpendicular to crossbar (1). This is done by shifting the
position of bracket (5).
Courtesy of NationalSwitchgear.com
7.4-Shunt Trip 7.4.2-Adjustments
The shunt tripping device is mounted on a bracket With the shunt trip de-energized and the breaker
attached to the left side of the operating mechanism mechanism reset, there must be clearance between trip
(looking from the front). paddle (11) and armature arm (10) 0.03 in. min.
A remote switch or relay contacts are used to close the circuit A minimum 0.03 in. over-travel of the armature is required
of the device causing the armature (9) to engage the trip paddle when the breaker is tripped. If any adjustment is necessary
(11), thereby tripping the breaker. The spring (1) is used to to provide this amount of overtravel, the trip lever is bent in
return the armature to the neutral position after the breaker or out accordingly.
trips.
To prevent overheating, the coil (7) is cut off by contacts
of the auxiliary switch which are open when the breaker is
open.
7.4.1-Replacement
Referring to Fig. 52:
a. Disconnect coil leads.
b. Remove mounting hardware and the device.
c. I nstall new device in reverse order.
III
IIl~AA
Trip shaft of breaker shown in tripped position and
shunt trip energized.
D ------Ji:t-, 1. Spring
2. Pin
~---....
I-----IE 3. Frame
~ --=::;::::;::=~~ .::>....----'--, ./"--~
4. Weight
5. Screws
;---[D 6. Magnet
~==t:;:==~~~
7. Coil
B. Clamp
w 9. Armature
10. Armature arm
m---< 11. Trip paddle
12. Clamp
13. Mtg. bracket
14. Mtg. hardware
41
Courtesy of NationalSwitchgear.com
SECTION 7........Accessories
1. Spring
2. Bracket
3. Adjusting plate and screw
4. Shading ring
~,,---m 5. Armature
~p'----m 6. Coil
&J~ 7. Clamp
~IT:~~~h--1E 8. Magnet
~----L
9. Screws
m------.., 10.
11.
Pin
Adjusting screws
12. Locking wire*
13. Adjusting screws
14. Trip paddle and clamp
>---Q'J 15. Mtg. hardware
~-------i
* New models may use a
jam nut in place of the
f.i------l l locking wire
42
Courtesy of NationalSwitchgear.com
If the a-c control voltage is any voltage other than
208/240V ac, a control power transformer (also remotely
mounted with respect to the breaker) must be used. This
must have a minimum rating of 100 volt-amperes.
When installed, the voltage to be monitored is connected
across terminals No.1 and No.2 of the static delay box.
The coil of the tripping unit is connected across terminals
No.4 and No.5 of the static box through the secondary
disconnects of the breaker. The secondary disconnects to
be used will be shown on the breaker wiring diagram.
No more than one undervoltage tripping device should be
used in conjunction with one static time-delay unit.
The static time-delay undervoltage can also be furnished
with a thermotector control unit. Overheating of motor
windings causes the thermotector, imbedded in the motor
windings, to open. This de-energizes the undervoltage
device on the breaker and drops the motor load.
In the event the device fails to pick-up, the following
checks are recommended to determine whether the
magnetic device 01") the breaker of the static ti me delay unit
is the faulty component:
1. Stop
2. Armature 1. Check input voltages across terminals 1 and 2 on the
3. Insert wire gage static box. See Table 7 for these values.
2. Check output voltages on terminals 4 and 5 with the
Fig. 54. Positive trip check
undervoltage device connected. See Table 7 for values.
7.6-Static Time-Delay Undervoltage 3. Check resistance of the disconnected undervoltage
device. See Table 7 for values.
In addition to the instantaneous undervoltage tripping
device mourited on the breaker, the static time-delay See Instruction Sheet GEH-4545 for more detailed
undervoltage includes a separately mounted time-delay information, including schematic diagrams and circuit
unit. Table 7 lists the Cat. Nos. available. description.
43
Courtesy of NationalSwitchgear.com
SECTION 7-Accessories
7.1-Electric Lockout Device Each electric lockout device also includes a By-Pass or
"manual defeat" linkage to permit closing the breaker
The Electric Lockout Device is used in conjunction with the when the lockout is de-energized. This allows startup of
normally-closed auxiliary contacts of another breaker. This "dead" systems. A pull knob for this purpose is located
device provides a convenient method to electrically interlock beneath the breaker frame.
two or more breakers so that no two may be closed at the same
time. When Its coil Is de-energized, the electric lockout device 7.7.1 ~Adjustment
holds an open breaker trip-free. However, once the breaker is
closed, the breaker mechanism cam operates linkage which All lockout devices are factory adjusted. If adjustments are
mechanically holds the lockout device armature closed to pre- needed, referring to Fig. 55:
vent trippng the breaker in the event the lockout coil is de- a. Adjust "manual defeat" linkage adjusting nuts to
energized. obtain max travel of lockout tripping arm.
b. With breaker in open and reset position and lockout
The lockout device is mounted on the right side of the
coil de-energized, pull knob for "manual defeat". Check
mechanism frame viewed from the front as shown in Fig.
clearances between lockout trip arm and adjusting screw.
55. When the breaker opens, the breaker cam moves down,
Clearance must be .06 to .09. Release knob, lockout trip
allowing the lockout device to assume its normal, de-
arm must move trip paddle .03 to .06 beyond point of
energized position.
tripping breaker. Adjust screw accordingly.
,,
-t-
i" - - -~\
,I
I
:
'
I
I ,
I ,
: L _
_ _ _ _I
44
Courtesy of NationalSwitchgear.com
7.8-Bell Alarm Device 7.8.1-Adjustment
This device provides a means for remote indication that In Fig. 56, the components of a bell alarm with lockout are
the breaker has been tripped due to action of one of its shown in the breaker closed position. The device is
automatic trip devices (overcurrent, UV) or drawout actuated by crossbar side link pin (1) which engages
interlocks. It is not activated by the manual trip button or operating link (2). Lockout screw (3) should be adjusted so
shunt trip device. that it engages trip paddle (4) to displace trip shaft (6)
when the breaker is opened. This keeps the breaker trip
The bell alarm device can be equipped with an optional
free until the bell alarm is reset.
lockout feature which, upon activation of the bell alarm,
prevents reclosure of the breaker until the bell alarm is Operating the manual trip button must not actuate the bell
reset. A bell alarm without the lockout feature can be alarm device. With the manual trip button fully depressed,
turned off (reset) by any of three modes: the trip rod release collar (7) should be positioned on trip
rod (8) so that latch (9) and catch (10) disengage before
a. Reclosing the breaker.
the breaker opens. When the manual trip button is not
b. Depressing the manual trip button. depressed, there should be approximately a 3/16" gap
c. Energizing the shunt trip device. For this mode, a between the trip rod release collar (7) and the latch (9).
normally open contact of the bell alarm switch must be The bell alarm is bypassed also whenever the shunt trip is
connected in parallel with the auxiliary switch "A" contact energized. This is accomplished by latch release strap (1))
in the shunt trip circuit. which is engaged by shunt trip armature lever (12). Strap (11) is
For a bell alarm with lockout, only reset modes (b) and (c) part of device latch (9), and must be formed to hook around ar·
apply. mature lever (12) such that the device latch and catch
disengage before the breaker opens.
With the breaker in reset position there must be at least 1/16
clearance between shunt trip armature (12) and breaker trip
paddle (4).
td'
45
Courtesy of NationalSwitchgear.com
SECTION 7-Accessories
7.9-0pen Fuse Lockout Device rod (3) through rod guide (2). Continue lowering the
device until movement is restricted by the device wiring
The open fuse lockout device (OFLO) is an anti-single-
harness.
phasing device used on breakers employed in conjunction
with currenHimiting fuses. The device consists of an 2. Disconnect coil leads.
individual trip solenoid for each pole, connected directly
3. Remove two screws holding the trip device to the
across the fuse in that phase. Blowing of any fuse operates
device mounting plate.
its solenoid, tripping the breaker. An indicator for each
phase pinpoints the blown fuse. The breaker remains trilJ- 4. Bend lower end of brass coil clamp straight.
free until the involved phase of the OFLO device is reset. 5. Remove coil. Install new coil and replace parts in
Referring to Fig. 57, when a fuse blows, coil (6) in that reverse order.
phase is energized and closes armature (8), engaging trip
paddle (1) which trips the breaker. In the process, spring 7.9.2-Adjustments
(12) discharges and pivots arm (9) counterclockwise, From 1/32 to 1/16 inch armature overt ravel is required
latching armature (8) closed. This motion also moves reset when the breaker is tripped. A 1/8-inch minimum
button (10) forward, indicating which fuse has blown. The clearance is needed between trip paddle (1) and rod (3)
latch-held armature keeps the breaker trip-free until the with breaker in the reset position. To make these
OFLO is reset. Coil (6) is de-energized as soon as the adjustments loosen locknut (4) and turn rod (3) in or out to
breaker is tripped.
obtain the proper overt ravel and clearance. Retig hten lock
nut (4).
7.9.1-Coil Replacement
A 1/8-inch minimum clearance should be maintained at
To replace coil (6), proceed as follows:
reset button (10). To adjust, loosen lock nut ahead of
1. Remove five bolts mounting the device to the side button and turn button until proper distance is obtained.
plate and front frame. Lower the lockout device, guiding Retighten lock nut.
1. Trip paddle
2. Rod guide
3. Rod
4. Lock nut
5. Trip solenoid
6. Coil
7. Link assembly
8. Armature
9. Arm
o 0
10.
11.
Reset button
Rod, reset button
~======~-mJ 12. Springs, reset rod
13. Spring, link assembly
r-----IE 14. Mounting bracket
------ill 15. Trip shaft
~ -J
fj, -J
[D---------J
46
Courtesy of NationalSwitchgear.com
SECTION 8-Type SST Overcurrent Trip Device
The SST is a solid-state, direct-acting, self-powered trip Each target pops out when its associated trip element
device system. The SST system consists of the SST operates to trip the breaker. After a trip, the popped target
programmer unit, current sensors, and a flux shifter trip must be reset by hand. However, neglecting to reset does
device. Fig. 58 shows a block diagram of the system. not affect normal operation of any trip element or prevent
the breaker from being reclosed.
8.1-Programmer Unit The programmer unit is mounted to the left side of the breaker
Fig. 59 shows a typical SST programmer unit. The as shown in Fig. 60. The bracket attached to the top of the pro-
program mer u nit provides the comparison basis for grammer, see Fig. 59, engages with a bracket mounted to the
overcurrent detection and delivers the energy necessary to breaker's center channel.
trip the breaker. It contains the electronic circuitry for the
var'ious trip elements. Their associated pickup and time
delay adjustments (set-points) are located on the face
plate. Depending on the application, programmer units
may be equipped with various combinations of Long Time,
Short Time, Instantaneous and Ground Fault trip elements.
See Table 8 for available rc'tings, settings and trip
characteristics. Adjustments are made by removing the
clear cover over the face plate, unscrewing (counter-
clockwise) the set-point knob, moving the set-point along
the slot to the new setting, and screwing the set-point
knob in. Once all adjustments are made, install the clear
cover to the face plate.
The SST programmer units can be optionally equipped
with trip indicators (targets). These are pop-out,
mechanically-resettable plungers located across the top of
the programmer's front. Units with a ground fault element
employ three targets: from left to right, the first is for
overload, the second for short circuit (actuated by the
short time and instantaneous elements) and the third for
ground fault. The latter is omitted on units without ground
fault. Fig. 58. SST block diagram
, X = Sensor ampere rating = trip rating. 3 Time delay at lower limit of band @ 6L.
2 Pickup tolerance = :': 10%. 4 Time delay at lower limit of band.
Applicable lime-current curves: GES-6033B, 6034A, 60358
47
Courtesy of NationalSwitchgear.com
SECTION 8-Type SST Overcurrent Trip Device
48
Courtesy of NationalSwitchgear.com
AKA 75/100 AKS 50
Tap
terminal
board
49
Courtesy of NationalSwitchgear.com
SECTION 8- Type SST Overcurrent Trip Device
8.2.1-Replacement of Current
Sensors - AKS 50
Referring to Fig. 64, AKS50 phase sensors are
removed as follows:
a. Remove the connections to and the wiring harness
from the sensor tap board.
b. Remove the tap board retaining hardware.
c. Remove the lower connection strap.
d. Sensors are secured with RTV. Loosen RTV and
remove sensors.
e. If the front and back frame have not been separated,
replacement of the center pole sensor requires removal of
the mechanism prop. Refer also to Fig. 24:
1. Remove retaining rings.
2. Disconnect spring. 1. Connection strap
2. Bearing
3. Remove bearings
3. Retaining ring
4. Remove prop. 4. Prop
50
Courtesy of NationalSwitchgear.com
the underside of the front frame is coupled to the breaker's
trip shaft via a trip rod driven by the actuator arm. The
actuator is a solenoid whose armature is spring-loaded
and held in its normal (Reset) position by a permanent
magnet. In this state the spring is compressed.
So long as the actuator remains in the Reset position, the
breaker can be closed and opened normally at will.
However, when a closed breaker receives a trip signal from
the programmer unit, the actuator is energized and its
solenoid flux opposes the magnet, allowing the spring to
release the armature; this drives the trip rod against the
trip shaft paddle, tripping the breaker.
As the breaker opens, the actuator arm is returned to its
normal (Reset) position via linkage driven by a crank on
the breaker's main shaft. The permanent magnet again
holds the armature captive in readiness for the next trip
signal.
The trip device requires only one adjustment-the trip rod
length. As shown in Fig. 68, the clearance between the trip
rod end and the trip shaft paddle is gaged by a 0.109 inch
diameter rod. Adjust gap to 0.109 inch ± 0.031 inch. To
adjust, open the breaker and restore the breaker
1. Primary disconnects
mechanism to its Reset position. Loosen the jamb nut,
2. Tap board
rotate the adjuster end until the proper gap is attained,
then retighten the jamb nut.
Fig. 65. AKR 75/100 sensor replacement
While operating the breaker, insure that the actuator
bracket does not interfere with the buffer stud. Adjust by
8.2.2-Replacement of Current loosening actuator bracket mounting screws and rotating
Sensors - AKR 75/100 the bracket clockwise to take up mounting hole slack.
Retighten screws.
Referring to Fig. 65, the AKR 75/100 phase sensors are
removed as follows: The actuator is a sealed, factory-set device and requires no
maintenance or field adjustment. In case of malfunction,
a. Disconnect the wiring harness and connections from
the complete actuator unit should be replaced. When
the senser tap board.
making the electrical connection to the replacement unit, it
b. Remove the tap board hardware. is recommended that the breaker harness be cut at some
c. Remove the primary disconnect assemblies from the convenient point and the new actuator leads solder-spliced
stud. thereto. An alternate method is to untie the breaker
harness and remove the old actuator leads directly from
d. Remove the sensor and tap board. the female AMP connector on the end of the breaker
e. Reassemble in reverse order, align projections on rear harness. However, AMP extraction tool Cat. No. 305183 is
of sensor with notches in the position ring which is req uired for this method.
mounted on the stud. Refer to Section 7.1.1 for torque
requirements for the primary disconnect hardware.
CAUTION: IF THE BREAKER MUST CARRY
CURRENT WITHOUT OVERCURRENT
8.3-Flux Shift Trip Device PROTECTION, THE SST TRIP DEVICE SYSTEM
The Flux Shift Trip device is a low-energy, electromagnetic MUST BE PREVENTED FROM OPERATING.
device which, upon receipt of a trip signal from the THE RECOMMENDED METHOD IS TO SHORTEN
programmer unit, trips the breaker by actuating the trip THE TRIP ROD BY TURNING ITS ADJUSTER
shaft. END FULLY CLOCKWISE. THIS PREVENTS
ACTUATION OF THE TRI~ SHAFT PADDLE.
The mounting arrangement of this component is illustrated
in Figs. 66 and 67. An electromagnetic actuator located on
51
Courtesy of NationalSwitchgear.com
SECTION 8-Type SST Overcurrent Trip Device
1. Actuator bracket
2. Buffer stop
3. Crossbar
1. Actuator
2. Actuator arm
3. Trip rod
4. Trip rod adjuster end
5. Reset linkage
6. Actuator bracket
7. Mounting base
52
Courtesy of NationalSwitchgear.com
CROSSBAR'
(BKR. OPEN)
ACTUATOR
BRACKET - - -...........-t,..; BUFFER
STUD
POSITION
TRIP ROD
O. 109 DIA. IN "RESET"
ROD POSITION
ADJUSTER
END
Fig. 68. Flux shift trip device adjustments
Courtesy of NationalSwitchgear.com
SECTION 8-Type SST Overcurrent Trip Device
54
Courtesy of NationalSwitchgear.com
SECTION 8-Type SST Overcurrent Trip Device
8.4.2-Resistance Values
For use in troubleshooting, the Common to Tap resistance to zero and no ground signal is developed. This current
for SST current sensors is given in Tables 9 and 10. These sum will be zero only if all three sensors have the same
values apply to both phase and neutral sensors. electrical characteristics. If one sensor differs from the
others (I.e., different rating or wrong tap setting), the
Table 9-Sensor Resistance Values differential transformer can produce output sufficient to
trip the breaker. Similarly, discontinuity between any
AKS 50 sensor and the programmer unit can cause a false trip
signal.
Breaker Resistance in ohms
Frame Ampere between COMMON
Size Tap and TAP Terminals If nuisance tripping is encountered on any breaker whose SST
components have previously demonstrated satisfactory perfor-
300 5.3-6.1 mance via the TAK·TS1 Test Set, the sensors and their connec-
400 7.2-8.2 tions should be closely scrutinized after disconnecting the
600 10.8-12.4
breaker from all power sources.
800 14.6-16.9
AKS-50
600 6.4-7.6 a. Check that all phase sensors are the same type
800 8.8-10.4 (ampere range).
1200 13.5-15.8
1600 19.4-22.8 b. Ensure that the tap settings on all 3-phase sensors
are identical.
800 10.2-12.0
AKST-50 1200 15.8-18.6
1600 22.0-25.9
2000 28.5-33.6
8.5-SST Cabling Diagrams
c. Verify that the harness connections to the sensors
Table 10-Sensor Resistance Values meet the polarity constraints indicated by the cabling
AKR 75/100 diagram, I.e., white wire to COMMON, black wire to TAP.
Resistance in ohms
Tap Tap between COMMON d. On Ground Fault breakers serving 4-wire loads, check
Breaker Terminal Lead terminal (white that the neutral sensor is properly connected (see cabling
(AMP) Color lead) and TAP diagram Fig. 72. In particular,
terminal
1. Verify that the neutral sensor has the same rating and
1200 Black 13.4-15.7
tap setting as the phase sensors.
1600 Yellow 18.3-21.5
AKR-75
2000 Red 23.5-27.6 2. Check continuity between the neutral sensor and its
3200 Green 42.1-49.5 equipment-mounted secondary disconnect block. Also
1600 Black 18.3-21.6 check for continuity from the breaker-mounted neutral
2000 Yellow 23.5-27.6 secondary disconnect block through to the female harness
AKR-100
3000 Red 37.7-44.3 connector (terminals Land N.).
4000 Green 53.4-62.6
3. If the breaker's lower studs connect to the supply
The coil resistance of the SST IECS Flux shifter device is source, then the neutral sensor must have its LOAD end
approximately 16 ohms. con nected to the sou rce.
4. Ensure that the neutral conductor is carrying only
that neutral current associated with the breaker's load
8.4.3-False Tripping-Breakers current (neutral not shared with other loads).
Equipped with Ground Fault e. If the preceding steps fail to identify the problem,
then the sensor resistances should be measured. Since the
When nuisance tripping occurs on breakers equipped with
phase and neutral sensors are electrically identical, their
the Ground Fault trip element, a probable cause is the
tap-to-tap resistance should closely agree. See Table 9 or
existence of a false "ground" signal. As indicated by the
Table 10.
cabling diagram of Fig. 71 each phase sensor is connected
in a series with a primary winding on the Ground Fault
differential transformer. Under no-fault conditions on 3-
wire load circuits, the currents in these three windings add
55
Courtesy of NationalSwitchgear.com
+A +B +C
,------
PROGRAMMER
AAA
$ $ ~
FLUX SHIFT
TRIP DEVICE
UNIT
- b- b-: I
BREAKER
BACK FRAME I-~, t----'-'R=ED=---t~_<~+oB+- (48V. de)
~ r==)==-=!:' ~B~L~AC:<:.K~>+-<:H-o-+- (TO SCR
LEFT POLE I l E ANODE)
I
CURRENT WHITE
SENSOR
A
BLACK C
WHITE
HARNESS
CONNECTOR
(AMP 201298-1)
LOAD
1 .....
PROGRAMMER
CONNECTOR
(AMP 201297 -1)
+A .B tC
AAA
$ $ $
FLUX SHIFT
TRIP DEVICE
PROGRAMMER
UNIT
1------
1 1, - b- b-: I
BREAKER
BACK FRAME
~ r==)===)=1 t----'-'==-+<:o+-<: H-o-+-o (48V de)
r-=~-+<>-t-<~~-O-+-o (TO SCR
LEFT POLE I I ANODE)
CURRENT
WHITE
SENSOR
A
BLACK C
WHITE
D
BLACK F
WHITE
H
I,--_B::..:L::...A:.;::C.:..:.K_+c+-<: f-f-<K>-f--.
J
ttr LOAD
HARNESS
CONNECTOR
(AMP 201298-1)
PROGRAMMER
CONNECTOR
(AMP 201297-1)
56
Courtesy of NationalSwitchgear.com
~A ~B tC
B:~~~~~~E
AAA
r1-1-t-,
FLUX SHIFT
TRIP DEVICE
B
,-----,
PROGRAMMER
UNIT
I
I
~
J-'-'=-+O-J-< ~:....j...o4-e (48V. de)
)===)===)= (TO SCR I
LEFT POLE I E ANODE)
CURRENT
SENSOR I 'rl--+--t---t--+_...:.W~H!.!..!IT-=.E_-+-O-l-<4o-t--.
1IIIL-...}o,,--,",,","-- I ,I
A
I
BLACK c
II WHITE
I A
NEUTRAL I BLACK F
SENSOR I W D
DISCONNECT I r+o-+-_-,-,-,-H,,-,IT-=.E_+<>+<~o-+--.
/
--1I
LINE
I
I BLACK
~
~i-I----.JIII
1\';r+~C:":::O~Mtoif7)+O+--+-l-~f-+-----:!..W:!.!:H!!..!ITE.E_-+O+-<~No.L.l----,
t BLACK
liN
r r t,
I 1 -'
HARNESS
CONNECTOR PROGRAMMER
EQUIPM1NT'---M-O-UN-T-ED-
(AMP 201298-1) (AMP
CONNECTOR
201297-1)
NEUTRAL SENSOR \~---~v .
4-WIRE LOAD
BREAKER PROGRAMMER
HARNESS GROUND FAULT DEFEAT CABLE
CONNECTOR
r \., .-- f -- -,
CAT. NO. TGFD
-"A~ \
UNIT
~~~~6~~ i ~ ~--O-+---ri---..-.c..-::.+-<: ~ ~ !:
$A F~-+--i~ : i ~:. 3 I ANY SST
PROGRAMMER
$B~~---L.-i~ : i ~ i' 3 ~
UNIT WITH
GROUND FAULT
ELEMENT
$Ct I~ ~~
~ ~: 3
NEU~
I
SENSOR ~
f-t-OI
~I
DISCONNECT 0-+--< ~ I
L_J L..----r--....J 1.._______ I L_ J
MALE FEMALE L __ --.J
END END
Fig. 73. Cabling diagram with ground fault defeat cable inserted
between breaker harness and SST programmer unit-for
use during single-phase, high current-low voltage testing
57
Courtesy of NationalSwitchgear.com
SECTION 9-Type ECS Overcurrent Trip Device
1j)----
Fig. 75. ECS block diagram Fig. 76. ECS current sensor
58
Courtesy of NationalSwitchgear.com
Table 11-ECS Trip Characteristics
Table 12-
9.1-ECS Cabling Diagram Sensor Resistance Values
Resistance In Ohms
,A ,B ,C PROGRAMMER
Breaker
Type
Ampere
Rating Between Terminals
AAA FLUX SHIFT
TRIP DEVICE
UNIT
1------
BREAKER
BACK FRAME
~
r~,
~
-b- b:-:
~
)===)===)=
~
~R~ED~~-<~~B~(48V.de)
100
150
3.0 - 3.4
404 - 5.0
~B,,-,=L~AC~K4--<:>+-<~~-<>-+.... (TO SCR 225 4.8 - 5.6
LEFT POLE I 1 E ANODE) 300 6.4 - 7.2
CURRENT AKS50 6.7 - 7.8
SENSOR
WHITE 400
AKS750 600 604- 7.6
BLACK 800 8.8 - 10.4
1200 13.5-15.8
WHITE
1600 1904 - 22.8
2000 29.5 - 34.5
BLACK
WHITE
1200 13.4-15.7
BLACK 1600 18.3 - 21.5
2000 23.5 - 27.6
3000 37.7 - 44.3
\1_- --'
rrr
3200 42.1 - 49.5
HARNESS 4000 53.4 - 62.6
CONNECTOR PROGRAMMER
(AMP 201298-1) CONNECTOR
LOAD (AMP 201297-1)
59
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTri p TM Overcurrent Trip Device
I
1»-_ I
I
SHORT
,vr----.-----.- CIRCU IT
TARGET
GROUND
)}-+--ITARGET
NEUTRAL
60
Courtesy of NationalSwitchgear.com
Table 13-Trip Functions Available
Optional Features
BASIC FUNCTIONS ADD TO BASIC FUNCTIONS
STD.-or-S-or-H-or-M L T G-or-GR A 1-or-A2-or-A3-or-A Zl-or-Z2-or·Z
• Adjustable Currenl Selling X X X X I
I
• Adj Long-Time Pickup X X X X I I
LONG • Adj Long-Time Delay X X X X
TIME • Long-Time Timing Light X X X X
• Remote Long-Time Timing Light X
• Adj Short-Time Pickup X X X
SHORT • Adj Short-Time Delay X X X
TIME • Short-Time I't Switch(j) X
INSTANTA- • Adj Instantaneous Pickup X X
NEOUS • Adj High Range Instantaneous X
• Adl Ground Fault Pickup
GROUND --1 Ph. 2-W-3 PH. 3-W X I I
I
FAULT -Ground Return X
• Ad] Ground Fault Delay X X
• Tnp Indication Targets
-Overload & Short CircUit
OTHER -local only X
I IX
FUNCTIONS -local and remote
-0 L. S C and Ground Fault
I
r
-local only (2l X
-local and remote X
• Zone Selective Interlock
-Ground Faultq) X
-Short Tlme(j) IX X X
100. 150.
100,150. 225.300 .5.. 6..7. .B,9, 25.5, 1.5,2,25. 0.10. 1.5,2.2.5, .2. 25.. 3, 0.10.0.22 .
AKR-30 BOO 225,300, or .B, .B5.9, 1.0.11 10,21 3,4.5,7, 0.22. 3.4,6. B, OA 35. A, A5. 036
400.600, 300.400 .95, 1.0 (C) 9 (C) 036 10 (X) 5.. 6 (X)
BOO 600. BOO (XI
300.400.
300.400. 600. BOO
AKR-50 "
1600 600, BOO or
AKS-50 1200,1600 600. BOO
1200.1600
AKST-50 BOO, 1200. BOO. 1200
AKRT-50 2000 1600.2000 1600,2000
1 Time delay shown al 600% of ampere setting al lower limit 01 each band. c ~ current setting
2 Time delay shown at lower limit of each band. X = sensor OJrrent
All pickup lolerances are ± 10%
Ground Fault pickup not to exceed 1200 amperes
61
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTrip TM Overcurrent Trip Device
10.1.2-(Cont.)
The remote fault indication switch leads are brought out
the bottom of the MicroVersaTrip programmer as shown in
Fig. 80. This switch lead harness is plugged into the
mating connector on the breaker, see Fig. 81.
The switch leads are brought out from the breaker through
the Programmer Secondary Disconnect shown in Fig. 82.
The zone selective interlocking function wiring is also
brought out through this disconnect. See Figs. 76 and 77
for the remote fault indication and zone selective
interlocking cable diagrams.
iJ
10.2.1-AKS 50 Installation
The AKS 50 mounting bracket is shown in Fig. 83.
Installation is as follows:
a. Insert the guide pins into the holes and push on the
programmer. This will engage the connectors and release
Fig. 82. Programmer secondary connector the locking lever which will move upwards.
62
Courtesy of NationalSwitchgear.com
b. Verify that the locking lever did engage the 10.2.2.-AKR 75/100 Installalion
programmer pin.
There are two programmer mounting designs in use. The
c. Connect remote fault indication harness, if equipped, difference in the designs is in the operation of the locking
see Fig. 81. lever, see Fig. 84.
To remove the programmer:
a. Disconnect remote fault indication harness, if
equipped.
b. Move locking lever to horizontal position, releasing
programmer pin.
c. Remove programmer.
ORIGINAL LATER
DESIGN DESIGN
63
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTrip TM Overcurrent Trip Device
10.2.2-AKR 75/100 Installation (Cont.)
b. Original design-push in locking 1ever, which will The tapped or fixed phase sensors are available with an
release the programmer pin. While holding the locking additional winding. This winding is brought out to separate
lever in, remove the programmer. flag terminals rather than the screw terminals. These phase
sensors are used when the hi-level instantaneous
c. Later design-pullout locking lever, which will
MicroVersaTrip option ('H'-option) is required. Fig. 86
release the programmer pin. Remove the programmer.
shows an 'H'-option phase sensor. When the 'H'-option
phase sensor is installed, there are four leads connected to
it. There is no polarity associated with the 'H'-option
10.3-Current Sensors windings. Fig. 95 shows the connections for the additional
The current sensors supply the power and signal input 'H'-option Windings.
necessary to operate the trip system. Like the SST system,
the MicroVersaTrip uses a phase and neutral sensor.
Fig. 85 shows the phase sensors. Tapped and fixed phase
sensors are available. The tapped sensors provide field
adjustment of the trip device's continuous ampere rating.
See Section 10.5 for cabling diagrams.
The tapped and fixed phase sensors have a polarity
associated with their windings. The COMMON terminal Of
the tapped sensor and of the AKS 50 fixed sensor is the
right hand terminal as shown in Fig. 85. A white wire with a
ring terminal will be connected to this COMMON terminal.
The AKR 75/100 fixed sensor uses push-on terminals, but
the right hand terminal is still the COMMON terminal and iI
uses a white wire.
All phase sensors must be correctly wired for the
programmer summing circuitry to function properly. Refer
to the cabling diagrams in Section 10.6
1. H-option terminals
64
Courtesy of NationalSwitchgear.com
10.3.2-Replacement of Current
Sensors - AKR 75/100
The replacement of the AKR 75.100 MicroVersaTrip
current sensors follows the same procedure used for the
SST sensors, refer to Section 8.2.2
10.5-Troubleshooting
When malfunctioning is suspected, the first step in
troubleshooting is to examine the circuit breaker and its
power system for abnormal conditions such as:
Fig. 87. Typical neutral sensor a. Breaker tripping in proper response to overcurrents
or incipient ground faults.
10.3.1-Replacement of Current
b. Breaker remaining in a trip-free state due to
Sensors - AKS 50 mechanical interference along its trip shaft.
The replacement of the AKS 50 MicroVersaTrip current c. Inadvertent shunt trip activations.
sensors follows the same procedure used for the SST
sensors described in Section 8.2.1. The only difference is
that the tap board is not a separate item but is integral with WARNING: DO NOT CHANGE TAPS ON THE
the sensor. CURRENT SENSORS OR ADJUST THE
PROGRAMMER UNIT SET KNOBS WHILE
THE BREAKER IS CARRYING CURRENT.
65
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTrip rM Overcurrent Trip Device
10.5--(Cont.)
Once it has been established that the circuit breaker can Table 15-Tapped Sensor
be opened and closed normally from the test position,
attention can be directed to the trip device proper. Testing
Resistance Values
is performed by either of two methods: Breaker Resistance In ohms
1. Conduct high-current, single-phase tests on the Frame Ampere between Common
Size Vap 2nd Tap Terminals
breaker using a high current-low voltage test set.
300
400
NOTE: For these single-phase tests, special 600
800
connections must- be employed for AKS50
MicroVersaTrip breakers equipped with Ground 600
Fault. Any sing Ie-phase input to the 800
programmer circuit will generate an unwanted 1200
"ground fault" output signal which will trip the 1600
breaker. This can be nullified either by 800
1200 CONSUL T
a. Testing two poles of the breaker in series, AKST50 1600 FACTORY
or 2000
b. Using the Ground Fault Defeat Cable as AKR75 1200
shown in Fig. 94. This special test cable 1600
energizes the programmer circuit in a self- 2000
cancelling, series-parallel connection so that its 3200
output is always zero. 1600
AKR100 2000
3000
2. Test the components of the MicroVersaTrip system 4000
using portable Test Set Type TVS1 (Fig. 89). The
applicable test procedures are detailed in instruction Book
GEK-64464.
66
Courtesy of NationalSwitchgear.com
1O.5.2-False Tripping-Breakers 10.6-MicroVersaTrip Cabling
Equipped with Ground Fault Diagrams
When nuisance tripping occurs on breakers equipped with
the Ground Fault trip element, a probable cause is the
existence of a false "ground" signal. As indicated by the
cabling diagram of Fig. 91, each phase sensor is
OA oB OC PROGRAMMER
connected to summing circuitry in the programmer. Under
AAA FLUX SHIFT UNIT
no-fault conditions on 3-wire load circuits, the currents in
this circuitry add to zero and no ground signal is
developed. This current sum will be zero only if all three
B~~;~~~~E
~
11-1- t- i
r=+=:)=
TRIP DEVICE
RED
WHITE
32
1------
LEFT POLE f I 28
sensors have the same electrical characteristics. If one
sensor differs from the others (I.e., different rating or ~~%~~NRT ,'-.J':::'O::':c:+--+---+----+-<>-K.E-+<''"'8f--o
wrong tap setting), the circuitry can produce output I ~ 22
67
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTripTM Overcurrent Trip Device
+A +B 'c
,-----,
PROGRAMMER
BREAKER
AAA
r $ --$-4'- I
FLUX SHIFT
TRIP DEVICE
UNIT
rr
1
HARNESS
CONNECTOR PROGRAMMER
EQUIPMENT -MOUNTED \ '( AMP 1-350356-9 CONNECTOR
NEUTRAL SENSOR L---~v
4-WIRE LOAD
,111 '
r -__~A,- ~
,-----,
PROGRAMMER
FLUX SHIFT
UNIT
TRIP DEVICE
BREAKER r $ --$- 4'- I
BACK FRAME ~,b ~,I RED 32 I
t--'-=--t-o+<. f+<H I
~ )===)===r WHITE
LEFT POLE I 28
CURRENT
SENSOR
:t
I,
18
22
I A
I
NEUTRAL I
SENSOR I
DISCONNECT I
~-1 I
~ {t"--++=-::~
\ IN >+ot--i----t----t--+-----------t-<>-KH-C>-i
1 ......
L
HARNESS
CONNECTOR PROGRAMMER
AMP 1-350356-9 CONNECTOR
LOAD
68
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTripTMOvercurrent Trip Device
BREAKER PROGRAMMER
,
HARNESS
CONNECTOR
r ...,
GROUND FAULT DEFEAT MODULE
CAT, NO, TVTGD9
r----~A'---_ _~\
..--
1~-- ---~ ,--1
UNIT
,---,
I
0-+--< 'g ~I 1
~
0--+-< ~ I I
~ ~
o--t--<
4 4 ~ I I
0--+--<
~: i~
0-+-<
5 ~
Q 2
o---r-< 7 7 ~ I I
o-----t---< ~I
o-t-<
8 :a ~ I I
18
o---t-<
19
0
1 0 I I ANY MICROVERSATRIP
0--+--< 2'P
0 I 0 I I PROGRAMMER
~ I () UNIT WITH
0-+-<
17
0
0
I I GROUND FAULT
22
I 0 I ELEMENT
??
o.--l-<
23 23 ~I I
cr-t-< 24 24 ~ I I
o-t--<
2j 26 4-u I I
0--+-< ;!~ 28 ~+-o I I
0--+---< ~I
~ ~ 3) /
~J I I
L J ~
- - -- ~ L --l 1
L __ -l
Fig. 94. Cabling diagram with ground fault defeat module inserted between
breaker harness and MicroVersaTrip programmer unit-for use
during single-phase, high current-low voltage testing
PROGRAMMER
UNIT
1------
BREAKER
BACK FRAME r- - - -I
I
r-
'13
~ )===)===)=1
Partial
I E
LEFT POLE
CURRENT
I
I YELLOW
:t~
SENSOR
I 14
II
I A
I
I
YELLOW
YELLOW
10
-
,
t~
15
I 11
I YELLOW
:~ f-<>- ......
I
I I YELLOW
B I ......
:f-
~
f
I
I
1_ _ ___ I-.J
H
I
C
I YELLOW /
12
...... ,
rry
,,1/ '\l/
LOAD
,,1/
HARNESS
CONNECTOR PROGRAMMER
CONNECTOR
----~
69
Courtesy of NationalSwitchgear.com
SECTION 10-MicroVersaTrip TM Overcurrent Trip Device
EQUIPMENT BREAKER
------
9 9 YELLOW
I
I
OVERLOAD
{ YELLOW
I
RED
I
SHORT
CIRCUIT { RED I
GROUND J
13 13 GREEN I
14 14 GREEN
FAULT I
toE 15 15 BLUE I
OVERLOAD f 16 16 BLUE I
PICKUP
1 I
I------~
AMP AMP AMP AMP
1-350239-9 1-350246-9 1-350242-9 1-350235-9
PROGRAMMER MICROVERSATRIP
SECONDARY PROGRAMMER
DISCONNECT PROGRAMMER
HARNESS --I
EQUIPMENT BREAKER CONNECTOR
SHORT TIME { ~
INPUT - <E'----K.>-+--< <E'---_+_<J-t------t-
SHORT TIME { +
OUTPUT - <E'----f--CH--< ~_+_<)-t------H)+--<.
GROUND FAULT { +
INPUT _ <C---H.:)+--< ~+<}-f------+-
GROUND FAULT { +
OUTPUT - ~-I-Cr+--< ~+(}-+ -+-(
AMP AMP
1-350239-9 1-350246-9
--~
70
Courtesy of NationalSwitchgear.com
SECTION 11-RMS-9/Epic MicroVersaTripTM
The RMS-9/Epic MicroVersaTrip is a solid-state, direct-act-
ing, self-powered trip device system. The RMS-9 system
consists of the RMS-9 programmer, current sensors, and a
flux shifter trip device. Fig. 98 shows a block diagram of the
system.
11.1-Programmer Unit
Fig. 99 shows a typical RMS-9Epic MicroVersaTrip unit.
The RMS-9/Epic MicroVersaTrip provides the comparison
basis for overcurrent detection and delivers the energy nec-
essary to trip the breaker. It contains a programmable mi-
croelectronic processor which incorporates nine adjustable
time-current functions, three mechanical fault indicators, a
long-time pickup LED indicator and a zone selective inter-
locking function. All adjustable programmer functions are
automatic and self-contained requiring no external relaying,
power supply or accessories. See Table 17 for trip functions
available and Table 18 for trip function characteristics. A de-
tailed description of each trip function is given in publication
GEK 97367.
XFMR
N ---L}--~~~-,
AMPLIFIER
OA-{~
os----EJ
R8~ RATING PLUG ~~~;C~':STE
COMPARATOR TO
--+ ~ C~ '<2Cr,RIP 'FLUX
INST ~ SHIFTER
SWITCH FIG. 99
Fig. 98. RMS-9 Block Diagram RMS-9 & Epic MicroVersaTrip
11.1.1-Fault Trip Indicators Programmer
The optional fault trip indicators are similar to the
MicroVersaTrip indicators. They are mechanical pop-out
type for identifying overload or short circuit over-current Note Location
faults when breakers are ordered without integral ground of Pin #1
fault protection. They are also available to identify overload,
short circuit and ground fault trips for breakers supplied with
integral ground fault protection.
Each target pops out when its associated trip element
operates to trip the breaker. After a trip, the popped target
must be reset by hand. However, neglecting to reset does
not affect normal operation of any trip element or prevent
the breaker from being closed.
11.2-RMS-9 & Epic MicroVersaTrip
Installation
The programmer mounts to the lower left of the breaker
as shown in Fig. 101. It mounts to the bracket assembly
shown in Fig. 82. Referring to Fig. 82, the guide pins mate
with the holes on either side of the programmer connector.
They provide the necessary alignment for the connector
engagement. The locking lever engages with the pin which
is assembled to the programmer frame and secures the pro-
grammer to the mounting bracket
Installation using each design is as follows:
a. Insert the guide pins into the holes and push on the pro-
FIG. 100
grammer, engaging the connectors.
b. The locking lever is released, securing the programmer.
Programmer Secondary
c. Verify that the locking lever did engage the programmer ·pin. Connector Epic MicroVersaTrip
To remove the programmer: 71
a. Pull out locking lever, which will release the programmer
pin. Remove the programmer.
Courtesy of NationalSwitchgear.com
SECTION 11-RMS-9 and Epic MicroVersaTrip Trip Device ™
11.3-Current Sensors
The current sensors supply the power and signal input nec-
essary to operate the trip system. The RMS-9 and Epic
MicroVersaTrip") use a phase and neutral sensor. Fig. 102
shows the phase sensors. See Section 11.5 for cabling dia-
grams.
Fig. 101
The fixed phase sensors have a polarity associated with their
windings. Their COMMON terminal is the right hand terminal
as shown in Fig. 102. A white wire with a push on terminal
will be connected to this COMMON terminal. All phase sen-
sors must be correctly wired for the programmer summing
circuit to function properly.
The phase sensors are available with an additional winding.
This winding is brought out to separate flag terminals. These
phase sensors are used when the hi-level instantaneous
RMS-9 option ('H'-option) is required. Fig. 102 shows an
'H'-option phase sensor. When the 'H'-option phase sensor
is installed, there are four leads connected to it. There is no
polarity associated with the special winding connection. Fig.
103 shows the connections for the additional 'H'-option
Windings.
72
Courtesy of NationalSwitchgear.com
TABLE 17. TRIP FUNCTIONS AVAILABLE
Optional Features
BASIC FUNCTIONS ADD TO BASIC FUNCTIONS
STD.-or-8-or-H-or-M L T G-or-GR A1-or-A2-or-A3-or-A Z1-or-Z2-or-Z
• Adjustable Current Selting X X X X
• Adj Long-Time Pickup X X X X
LONG • Adj Long-Time Delay X X X X
TIME • Long-Time Timing Light X X X X
• Remote Long- Time nming Light X
• Adj Short-Time Pickup X X X
SHORT • Adj Short-Time Delay X X X
TIME • Short-Time 12 t Switch <D X
INSTANTA- • Adi Instantaneous Pickup X X
NEOUS • Adj High Range Instantaneous X
• Adj Ground Fault Pickup
GROUND -1 PH, 2·W-3PH, 3/4-W X
FAULT -Ground Return X
• Adj Ground Fault Delay X X
• Trip Indication Targets
-Overload & Short Circuit
OTHER -local only X
FUNCTIONS -local and remote X
-OIL, SIC and Ground Fault
-local only(2) X
-local and remote X
• Zone Selective Interlock
-Ground Fault~ X X
-Short Time<D X X
.2, .22,
.5, .6, Fixed at .24,
2 .44 at
.7, .8, 1.0 of 2.4,4.9, 1 T in: 1 1.5,2,3,5, 1.5.2,3,5, .26, .10, .21,
AKR-75 3200 3200 .4, .6, .8, 1.0 NA 200%
.9, .95, Current 9.8,20 .40 7,9,10 7.9,10,13 .28, .35
1.5,2.0. of pick
1.0,1.1 Setting .30,
2.5.3.0, up at
['T .34, .37
4.0,5.0, lower
out: 2
7.0,9.0 limit
.5, .6, Fixed al .10, .2, .22,
of
.7, .8. 1.0 of 2.4,4.9, .21,35 1.5,2,3,5, 1.5,2,3,5, .24, .10, .21,
AKR-100 4000 4000 .4, .6, .8, 1.0 NA band
.9..95, Current 9.8,20 7,9 7,9 .26, .35
1.0,1.1 Setting .28, .3
:1 Time delay shown at 600% elf Time delay shown at lower x = Rating plug amps Triple selective trip is '6; Time delay shown at lower
current setting at lower limit limit of each band. All pick S = Sensor amp rating standard when long- limit of each band.
of band. up tolerances are ± 10%. C = Current setting time/short-time only Ground fault pick up not
IS required. to exceed 1200 amps.
73
Courtesy of NationalSwitchgear.com
SECTION 11-RMS-9 and Epic MicroVersaTrip Trip Device nl
Fig. 102. RMS-9 Phase Sensors Fig. 104. Typical Neutral Sensor
Fig. 104 shows the neutral sensor. The neutral sensor is re-
quired when integral ground fault protection is used on
single phase-three wire or three phase-four wire systems. It
is inserted into the neutral conductor and therefore is sepa-
rately mounted in the cable or bus compartment.
The outputs of the phase sensors and neutral sensors are
connected to a programmer circuit which sums these values.
The total value will remain zero as long as there is no ground
current flowing. See cable diagram in Fig. 108.
The neutral sensor is an electrical duplicate of the phase
sensor. Therefore, when phase sensors are changed, the
Fig. 103. 'H' Option Phase Sensor neutral sensor must be correspondingly changed.
74
Courtesy of NationalSwitchgear.com
Since the neutral sensor is mounted separately The time-current characteristics for the RMS-9 & Epic
from the breaker, a disconnect means is required to MicroVersaTrip Trip Device are given in curves GES-6227
connect its output to the breaker. Fig. 88 shows the and GES-6228.
breaker and equipment mounted 4th wire secondary
disconnect used with the RMS-9 system.
11.3.1-Replacement of Current
Sensors
Referring to Fig. 88, replacement of RMS-9 & Epic
MicroVersaTrip® current sensors is accomplished by the
same procedure as the MicroVersaTrip® current sensors.
11.5--Troubleshooting
When malfunction ion is suspected, the first step in
troubleshooting is to examine the circuit breaker and its
power system for abnormal conditions such as:
a) Breaker tripping in proper response to overcurrents or
incipient ground faults.
b) Breaker remaining in a trip-free state due to
mechanical maintenance along its trip shaft. Fig. 105. Test Set, Cat. No. TVRMS
c) Inadvertent shunt trip activations. 11.5.1-Resistance Values
For use in troubleshooting the RMS-9 current sensors, the
WARNING: DO NOT ADJUST THE PROGRAMMER UNIT
resistance of the fixed windings is given in Table 19.
(KNOBS) WHILE THE BREAKER IS CARRYING CUR-
Once it has been established that the circuit breaker TABLE 19.
can be opened and closed normally from the test position, Ampere Resistance in Ohms
attention can be directed to the trip device proper. Testing Rating Between Terminals
is performed by either of two methods: 150 10-12
400 27-32
1. Conduct high-current, single-phase tests on the 800 58-68
breaker using a high current-low voltage test set. 1600 129-151
NOTE: For these single-phase tests, special connections 2000 207-243
must be employed for RMS-9 breakers equipped with The coil resistance of the RMS-9 & Epic MicroVersaTrip'" flux
Ground Fault. Any single-phase input to the programmer cir- shifter device is approximately 7 ohms.
cuit will generate an unwanted "ground fault" output signal
which will trip the breaker. This can be nullified either by
a) Using the Ground Fault Defeat Cable as shown in
Fig. 94 This special test cable energizes the pro-
grammer circuit in a self-cancelling, series-parallel
connection so that its output is always zero.
2. Test the components of the RMS-9 system using portable
Test Set Type. The applicable test procedures are detailed
in instruction Book 97367.
75
Courtesy of NationalSwitchgear.com
SECTION 11-RMS-9 and Epic MicroVersaTripTM Trip Device
+I..J-o--+-+-----+<::+<. ~-o~;-t-
trip the breaker. Similarly, discontinuity between any sensor
and the programmer unit can cause a false trip signal. :
I
If nuisance tripping is encountered on any breaker whose I 20
RMS-9 or Epic MicroVersaTrip components have previously I 24
demonstrated satisfactory performance via the lVRMS Test I
Set, the sensors and their connections should be closely 1- \1_- -,
rrr
scrutinized. After disconnecting the breaker from all power
sources. HARNESS PROGRAMMER
CONNECTOR CONNECTOR
a) Check that all phase sensors are the same type (am- (AMP 1-350356-9)
LOAD
pere range).
b) Verify that the harness connections to the sensors Fig. 106. Cabling diagram-RMS-9 & Epic
meet the polarity constraints indicated by the cabling MicroVersaTrip without ground fault
diagram.
c) On Ground Fault breakers serving 4-wire loads,
check that the neutral sensor is properly connected (see cj>A cj>B .v PROGRAMMER
cabling diagram Fig.108). In particular, BREAKERA A A FLUX SHIFT
TRIP DEVICE
UNIT
1------
(1) Verify that the neutral sensor has the same rating ~~;~E'f -1-t-i RED 32
as the phase sensors. "": )= ==)= ==)= WHITE
LEFT I 1 28
(2) Check continuity between the neutral sensor and its POLE
'-+---+--+--+-----+<:>-+-< ~t-<1)-8t -
equipment-mounted secondary disconnect block. Also
check for continuity from the breaker-mounted neutral
CURRENTI
SENSOR I
I
t4-<_+--I-+-----t-<>-t-<
I
22
'E-+<>+-
secondary disconnect block through to the female harness
I A
connector.
I
(3) If The breaker lower studs connect to the supply I
I
source, then the neutral sensor must have its LOAD end I
connected to the source. See Fig. 109. I
76
Courtesy of NationalSwitchgear.com
PROGRAMMER
FLUX SHIFT UNIT
TRIP DEVICE 1------
RED 32
WHITE
28
:I ~
18
~2
I I..I--_+--+--+-----~>+_<~_k>_I
I A
19
I 23
NEUTRAL I
SENSOR I
DISCONNECT I
--1 I
I LINE I I
I COM
( ~ ";-'::=1-<>+7 )-+o+--I---f---+-+----+o+<
\ L+_-kl-A .>+<>t--J--I----+~----+_O_I_<
4:..+0-1
liN
~A~
rr1
1 ......
I
HARNESS
CONNECTOR PROGRAMMER
EQUIPM1NT -MOUNTED \ AMP 1-350356-9 CONNECTOR
NEUTRAL SENSOR '---~V
4-WIRE LOAD
Fig. 108. Cabling diagram-RMS-9 & Epic MicroVersaTrip'· with ground fault on 4-wire load
4-WIRE LOAD
BREAK
BACK FR
111
~~E r1-1-t-~
FLUX SHIFT
TRIP DEVICE
RED -
~
32
PROGRAMMER
,-----
UNIT
H~
19
I 23
RAL: I
OR I I
n
I
NECT
I
B ,~
-rc;
I
:f- ~
I
~I I I
EQUIPMENT -MOUNTED I C
NEUTRAL SENSOR I ! :f- ~
~{~~+<>+' I
- I 17
\
\IN
L ~N~
" L....
-
"
/-, /--..., _J
,/
HARNESS
CONNECTOR
"
PROGRAMMER
I- - - - - ......
AMP 1-350356-9 CONNECTOR
LOAD
Fig. 109. Cabling diagram-RMS-9 & Epic MicroVersaTrip with ground fault on 4-wire
load-breaker reverse feed
77
Courtesy of NationalSwitchgear.com
SECTION 11-RMS-9 and Epic MicroVersaTripTM Trip Device
Socket
Class
No.
Note Location
5 + of Pin #1
Gnd .Fault
Zone 6 - Inputs
Selective
Interlock 7 +
Gnd. Fault
8 - Outputs
11 -
12 + Commnet
9 Spare
Epic 10 VC
MVT
1 V3
4 VA
2 24 Ret
3 + 24 VDC
78
Courtesy of NationalSwitchgear.com
SECTION 12-MicroVersaTripTM Plus and
MicroVersaTripTM PM Trip Units
The MVT-Plus/MVT-PM is a solid-state, direct-acting, self- Power Requirements
powered trip device system. The system consists of the
MVT-Plus/MVT-PM programmer current sensors and a flux A small amount of power is necessary to energize the liquid
shifter trip device. Figure 111 shows location of features on crystal display (LCD) during setup, for viewing breaker status,
programmer. See user manual GEH-5891 A. and for metering displays. MicroVersaTrip PM trip units re-
quire external 24 Vdc control power for operation. The four
12.1-Trip Unit sources of such power are the following.
MicroVersaTrip Plus Trip Unit • Flow of current - Breaker current sensors provide
MicroVersaTrip Plus trip units utilize a digital, LCD display sufficient power to energize the LCD when at least
with a four-button keypad to provide local set-up and read- 20% of the sensor's ampere rating is flowing.
out of trip settings. A 3-phase ammeter and trip indicators • 24 Vdc control power - Breakers with MicroVersaTrip
are standard, as is a clear plastic cover with provisions for PM trip units are supplied with external 24 Vdc power
sealing to allow tamper resistant installation. The trip unit that, whenever present, energizes the LCD. Some
digitally measures the current waveform in each phase to de- breaker models that are configured for
termine the true RMS value of the current, regardless of the MicroVersaTrip Plus trip units may be optionally
waveshape. MicroVersaTrip@ Plus trip units provide accu- equipped to accept an external 24 Vdc supply.
rate, predictable overload and short circuit protection for dis- • MicroVersaTrip Test Kit - The MicroVersaTrip Test
tribution systems that include ac and dc variable speed Kit, Cat. No. TVRMS, contains a 24 Vdc power sup
drives, rectifiers, induction heating, and other loads that ply. The LCD is energized whenever the test kit jack
cause high harmonic distortion as well as standard circuit. is plugged into the test receptacle on the rating plug.
They provide maximum breaker-to-breaker selectivity and
custom load protection. Short time and ground fault func- • Micro Versa Trip battery pack - The portable
tions include the flexibility of coordination with or without an MicroVersaTrip battery pack contains a 24 Vdc
12t ramp and are also available with high range instanta- power source and a jack. The LCD is energized when
neous. the jack is plugged into the rating plug test receptacle.
SELECT Key
chooses next item
for display
ENTER Key
stores options
VALUE Key
selects phase to
display or alter
setpoint values
Interchangeable
rating plug for
flexibility in matching
load requirements
LCD readout for
metered values, trip
settings, and fault trip
indication
FUNCTION Key
selects the mode
of display
79
MicroVersaTrip Plus and MicroVersaTrip PM trip units are NOTE: Trip units as received may have settings that are un-
removable. Figures 112 and 113 contain front and rear desirable for the specific application. Ensure that settings are
views of a MicroVersaTrip PM trip unit. appropriately adjusted before energizing.
Figure 113 shows the 36-pin plug that connects either trip
unit to the circuit breaker and equipment circuitry. This plug
is called the trip unit disconnect.
Fig. 112. Front view of MicroVersaTrip PM Fig. 113. Rear view of MicroVersaTrip PM
Trip Unit. Trip Unit.
80
Courtesy of NationalSwitchgear.com
12.4-Trip Unit Removal and
Replacement
The programmer mounts to the lower left of the breaker as
shown in Fig. 101. It mounts to the bracket assembly shown
in Figs. 83 and 84. Referring to Fig. 83, the guide pins mate
with the holes on either side of the programmer connector.
They provide the necessary alignment for the connector en-
gagement. The locking lever engages with the pin which is
assembled to the programmer frame and secure the pro-
grammer tot the mounting bracket. When a trip unit is re-
placed, the locking arm snaps back into place to indicate
proper engagement.
WARNING: Always de-energize Type AKR circuit breakers
before attempting to remove or replace the trip unit. Be-
cause of the exposed location of the trip unit, failure to ob-
serve this warning may result in equipment damage or per-
sonal injury, including death.
Socket
11 -
12 + Commnet
9 Spare
10 VC
MVT-PM
1 VB
4 VA
2 24 Ret
3 + 24 VDC
81
Courtesy of NationalSwitchgear.com
SECTION 12-Microversatrip Plus and ™
AKR-9D-100
Fig. 116
82
Courtesy of NationalSwitchgear.com
12.6-Neutral Current Sensors TABLE 20. Rating plug catalog numbers
CAUTION: Neutral current sensors are required for three- Sensor Plug Breaker
phase, four-wire systems. When the trip unit is connected to Cat No. Rating, Amps Rating Frames
a three-phase, three-wire system, the neutral sensor termi-
nals are left open. Do not short any neutral current sensor TR32B1200 1200
terminals in a three-phase, three-wire system, as this could TR32B1600 1600
3200 AKR75
result in damage to or malfunction of the electrical system. TR32B2400 2400
Fig. 119 shows the neutral sensor. The neutral sensor is re- TR3283200 3200
quired when integral ground fault protection is used on
single phase-three wire or three phase-four wire systems. It TR4081600 1600
is inserted into the neutral conductor and therefore is sepa- TR40B2000 2000
rately mounted in the cable or bus compartment. TR4082500 2500
4000 AKR100
TR40B3000 3000
The outputs of the phase sensors and neutral sensor are
TR4083600 3600
connected to a programmer circuit which sums these values.
TR40B4000 4000
The total value will remain zero as long as there is no ground
current flowing.
The neutral sensor is an electrical duplicate of the phase
12.8-Trip Unit Functions
sensor. Therefore, when phase sensors are changed, the MicroVersaTrip Plus and MicroVersaTrip PM trip units
neutral sensor must be correspondingly changed. have specific standard and optional functions. All trip units
share a series of interchangeable rating plugs. The standard
functions for both types of trip unit are as follows:
• Protection
- Long-time protection
- Instantaneous protection
• Status
- Trip target
• Metering display
- Phase current (selectable among phases)
The optional functions available on both types of trip unit are
as follows:
• Adjustable protection
- Switchable instantaneous and ground-fault protection
- High-range (fixed) instantaneous overcurrent
protection
- Short-time protection, with or without 12 T
Fig. 119. Typical neutral sensor - Ground-fault protection, with or without 12T
- Zone-selective interlock, with ground fault only or
12.7-Rating Plug Removal and with both ground fault and short time
Replacement Additional optional functions available only with PM style trip
CAUTION: Removal of the rating plug while the breaker is units are as follows. PM style trip units require the presence
carrying current reduces the breaker's current-carrrying ca- of external control power.
pacity to approximately 25% of the current sensor rating.
• Configurations
Interchangeable rating plugs are removed with a Rating Plug - Communication and metering
Extractor, Cat. No. TRTOOL. (Suitable equivalents are com- - Communication and protective relaying
mercially available as "integrated circuit (DIP) extractors. ") - Communicaiton, metering, and protective relaying
Grasp the rating plug tabs with the extractor and pull the
• Metering and protective-relaying functions
plug out. Be sure to grab the tabs and not the front cover of
- Voltage
the rating plug, or the plug may be damaged.
- Energy (kWh/MWh)
Rejection features are provided on all rating plugs to prevent - Real power (kW/MW)
application mismatches. Never force a rating plug into - Total power (kVAlMVA)
place. Refer to Table 20 to find the appropriate rating plugs - Frequency (Hz)
for each sensor rating and breaker frame. - Protective relays (undervoltage, overvoltage, voltage
If a replacement rating plug has a different rating than the unbalance, current unbalance, and power reversal)
plug that was removed, follow the appropriate setup proce-
dure in GEH"5891A to enter the new rating.
Do not attempt to use a rating plug from a Spectra RMS 83
breaker or a MicroVersaTrip·· RMS-9/MVT-4 function trip in a
MicroVersaTrip Plus or MicroVersaTrip PM trip unit.
Courtesy of NationalSwitchgear.com
SECTION 12- Microversatrip Plus and 1M
2. The trip unit display Can occur on Plus style trip Power the trip unit with the Test Kit or external
flashes. units when load current battery pack.
fluctuates near 20% of S.
3. The trip unit display The built-in self test has Replace the trip unit.
flashes ERR. detected an error.
4. The trip indication Trip unit is not in status Press FUNCTION until STATUS is displayed. Press
target will not clear. mode. SELECT and VALUE together to clear the target.
5. Unit does not comm- Commnet wires are shorted Locate and repair the short or the incorrect con-
municate with the or improperly connected. nection.
Monitor, POWER
LEADER Distribution FPU version is lower than 2.0 Update FPU to version 2.0 or higher.
Software, or FPU.
Trip unit address incorrect. Check that address assigned to trip unit, as in
Chapter 2, agrees with address at host.
6. Current readings are Rating plug value was Read the X value from the rating plug nameplate
incorrect. defined incorrectly. and enter this with the rating plug current
set point procedure in Chapter 2. 00 not enter
the sensor rating, S.
7. Voltage readings are Potential transformer (PD Read the PT ordinary rating from the PT name
incorrect. primary voltage was defined plate and enter this value with the PT primary
incorrectly. voltage procedure in Chapter 2.
8. kW legend is flashing. Total power metering. Indicates that the total power is metered in kVA.
9. Overload target is Test Kit-initiated trip indication. Clear target as indicated above (Symptom 4).
flashing by itself.
84
Courtesy of NationalSwitchgear.com
SECTION 13-Type EC Overcurrent Trip Device
Type EC overcurrent trip devices are magnetically The standard EC trip device for the AKS breaker frames is
operated, using a series coil or single conductor, and an the type EC-2A, see Fig. 120. An optional trip device for
associated magnetic structure to provide tripping force. these frames is the type EC-1, see Fig. 121.
There are three basic characteristics: long time delay, The EC trip device for the 4000 and 6000 amp AKA 75/100
short time delay and instantaneous, which can be used in frames is the EC-1 B shown in Fig. 122.
various combinations to suit the application.
The trip characteristics for the EC trip devices are listed in
AKA breakers with EC trips are for use on DC system Table 21.
voltages. One EC trip device is mounted per breaker pole.
This device contains its functional adjustments.
Fig. 120. EC-2A trip device Fig. 121. EC-1 trip device
85
Courtesy of NationalSwitchgear.com
SECTION 13-Type EC Overcurrent Trip Device
86
Courtesy of NationalSwitchgear.com
13.1-Direct Acting Tripping Device EC-1B 13.1.3-lnstantaneous Tripping-High Set
The type EC-1 B overcurrent tripping device is a direct- Referring to Fig. 123 adjustable instantaneous tripping is
acting device that causes the power circuit breaker with accomplished by varying the amount of tensile force on
:VVhiQh it is associated to open within a predetermined time the high-set instantaneous spring (21). When a magnetic
range which depends upon the magnitude of the current force greater than the restraining spring force is produced
overload. The EC-1 B tripping device can be constructed to by an over-current condition, the armature (22) is pUlled
supply a variety of different types of time-current charac- upward against the magnet (24), thus tripping the breaker
teristics, either alone or in combination. These are long by the movement of the connecting rod (13) against the
time delay, short time delay, and instantaneous, and they trip paddle (14).
are identified respectively by numbers 1,2 and 3. Charac-
The pickup value of the device may have one of the
teristics are further broken down within each of the first
following ranges: 4 to 9, 6 to 12, or 9 to 15 times coil rating.
two of these general classifications into maximum,
Three calibration marks will appear on the calibration
intermediate and minimum values of the time delay period.
scale (18) and the value of these calibration marks will be
These are coded respectively as AA, BB and CC. Time and
indicated by stampings on the scale as follows: (4X-6.5X-
current relationships for the various device characteristics
9X) or (6X-9X-12X) or (9X-12X-15X). depending on the
are given by the curves listed in Table 18.
desired range. To set the device at a partiCUlar pickup
TABLE 22-Time-Current Curves value, loosen the clamping nut (20) and slide the index
pointer on the calibration washer (19) to a position which
Trip lines up horizontally with the desired pickup value on the
Trip Trip Characteristic
calibration scale (18).
Device EleCD"ts (EC Devices Curve
only)
13.1.4-lnstantaneous Tripping-Low Set
EC-1 LSI (See Curves) GES-6000A
Low-set instantaneous tripping is adjustable from 80
LI 1BB-3 GES-6003 percent to 250 percent of the continuous current rating of
EC-1B LI 1CC-3 GES-6004 the device. Whenever this is used, it is the only
(See Curves) GES-600S
characteristic of the device. Instantaneous tripping used in
LSI
conjunction with any other characteristic is always
LI 1A-3 GES-6010
high-set.
EC2/2A LI 1B-3 GES-6011
If the characteristic of the device is low-set, adjustable
LI 1C-3 9ES-6012 instantaneous, a link is installed in place of spring (21) and
the instantaneous calibration spring is located where
Q L = Long Time S = Short Time I = Instantaneous
spring (15) is shown in Fig. 26. Dashpot (17) is omitted
13.1.1-Long Time Delay Tripping from assembly. See Fig. 101.
Referring to Fig. 123, the long time delay is obtained
as follows:
13.2-Replacement
The EC-1 B device is replaced as follows, referring to
The long time delay armature (22) is restrained by the long
Fig. 123:
time delay calibration spring (15). After the magnetic force
produced by the overcurrent condition overcomes this 1. Remove stud (23).
restraint, the velocity of the armature movement is
2. Remove mounting clamp.
governed by the flow of oil through an orifice in the piston
of the dashpot (17). The time required to displace the 3. Remove two screws fastening magnet (11) to lower
piston i's inversely proportional to the force tending to stud.
close the magnetic circuit. 4. Device is now free of breaker. Reassembly is
accomplished by reversing the procedure.
13.1.2-Short Time Delay Tripping
When reassembling the magnet to the lower stud, be sure
Referring to Fig. 101 the short time delay is obtained to replace any spacing washers in the same location in
ciS follows:
which they were found during disassembly. If this is not
The short time delay armature (1) is restrained by a done. misalignment and consequent malfunction may result.
calibration spring (6). If the force tending to close the
armature against the magnet (11) is great enough to
overcome the spring force, the speed of movement is
governed by the mechanical escapement mechanism
consisting of parts (2). (3), (4) and (5).
87
Courtesy of NationalSwitchgear.com
SECTION 13-Type EC Overcurrent Trip Device
The adjustment screw (7) is provided so that the short-time 3. Close the armature against the gage and magnet.
mechanism will pick up the trip link (8) at the same point at 4. If the breaker does not trip, form paddle 14 to obtain
which it is picked up by the long-time mechanism. This positive trip.
may be checked before the device is mounted by pulling
5. Check visually to make sure that the connecting rod
forward on the connecting link (10) and checking visually
does not restrict the engagement of the breaker trip latch
to see that trip link (8) contacts both the set pin in the long
when the breaker mechanism resets. It should always be
time linkage and the end of adjustment screw (7).
possible to adjust its length to a point where resetting is
After the device is mounted on the breaker, a final not interferred with and yet positive tripping by the
adjustment that must be made in the length of the overcurrent device is achieved.
+ +
+ +
+ +
--II]
IE
W
~tD
ta
~
m
Long Time & High Set
Short Time Mechanism Inst. Mechanism
1. S.T.D. armature 9. Air gap adj. 17. Dashpot
2. Pallet 10. Connecting rod 18. Calibration scale
3. Pinion 11. Magnet 19. Calibration washer
4. Escape wheel 12. Lock nut 20. Clamping nut
5. Driving segment 13. Connecting rod 21. lnst. calibration spring
6. S.T.D. calibration spring 14. Trip paddle 22. L.T.D. armature
7. S.T.D. trip adj. 15. L.T.D. calibration spring 23. Stud
8. Trip link 16. Calibration clamp nut 24. Magnet
88
Courtesy of NationalSwitchgear.com
13.4-Series Overcurrent Tripping Time values are inversely proportional to the effective
length of the dashpot arm. Therefore, the linkage setting
Device EC-2A
that gives the shortest time value is the one at which
The Type EC-2A overcurrent tripping device is available in dimension "A", Fig. 123 is greatest. The time adjustment
three forms: screw (4) may be turned by inserting a Phillips head
screwdriver through the hole in the front of the case. If it is
1. Dual overcurrent trip, with long-time delay and high-
desired to relate the linkage setting to the index marks on
set instantaneous tripping.
the linkage it will be necessary to remove the case. This
2. Low-set instantaneous tripping. may be done by removing the two mounting screws, one
on each side of the case, which may be taken off without
3. High-set instantaneous tripping.
disturbing the trip unit itself.
The dual trip has adjustable long-time and instantaneous
pick-up settings and adjustable time settings. 80th forms 13.4.2-lnstantaneous low-Set Tripping
of instantaneous trip have adjustable pick-up settings.
The low-set instantaneous pick-up point may be varied by
Adjustment Note the adjustment knob (3). The calibration in this case
usually ranges from 80 percent ot 250 percent of the series
Before attempting any checks or adjustments on breaker with coil rating, with the calibration plate indexed at values of
EC trip devices, the breaker mechanism and trip latch should 80, 100, 150, 200, and 250 percent of the rating.
be checked to assure their proper functioning so that the
breaker trip shaft is free of high friction loads. The trip latch of 13.4.3-lnstantaneous High-Set Tripping
the breaker should also be checked for proper trip latch
engagement. See Section 6.3.1.
The high-set instantaneous pick-up value may have one of the
Refer to Fig. 124 for the discussions given below. following three ranges: (4 to 9), (6 to 12), (9 to 15) times coli
rating. The pick-up setting may be varied by turning the Instan-
13.4.1-long Time-Delay and High-Set taneous pick-up adjusting screw (12).
Instantaneous Tripping
Three calibration marks (15) will appear on the operating
By means of the adjustment knob (3), which can be arm (14) and the value of these calibration marks will be
manipulated by hand, the current pick-up point can be varied indicated by stampings on the arm as follows: (4X-6.5X-9X)
from 80 to 160 percent of the series coil rating. The Indicator or (6X-9X-12X) or (9X-12X-15X).
and a calibration plate (2) on the front of the case provide a
means of indicating the pick-up point setting In terms of
percentage of coil rating. The calibration plate Is indexed at At the factory, the pick-up point has been set at the name-
percentage settings of 80, 100, 120, 140, 160. plate value of the instantaneous trip current. (Usually
expressed in times the ampere rating of1he trip coil). The
As in the case of the EC-1 over-current trip, the long-time variation in pick-up setting is accomplished by varying the
delay tripping feature can be supplied with anyone of tensile force on the instantaneous spring (5). Turning the
three time-current characteristics which correspond to the adjustment screw changes the position of the movable nut
NEMA standards maximum, intermediate and minimum (11) on the screw. The spring is anchored to this movable
long-time delay operating bands. These are identified as nut so that when the position of the nut is changed, there
1A, 18 and 1C characteristics, respectively. Approximate is a corresponding change in the spring load. As the spring
tripping time for each of these, in the same order are 30, is tightened, the pick-up point is increased.
15, and 5 seconds at 600 percent of the pick-up value of
The top edge of the movable nut (11) serves as an index
current. (See time-current characteristic curves).
pointer and should be lined up with the center of the
desired calibration mark (15) to obtain the proper
The tripping time may be varied within the limits shown on the
instantaneous trip setting.
characteristic curves by turning the time adjustment screw (4).
Turning in a clockwise direction Increases the tripping time; The trip screw (6) on the end of the armature (7) should be
counterclockwise motion decreases it. The dashpot arm (8) Is set so. that it does not contact the trip paddle on the trip
indexed at four points, MIN-1/3-2/3-MAX, as Indicated In Fig. shaft'until the air gap between armature and pole piece is
124. When the Index mark on the connecting link (9) lines up reduced to 3/32 in. or less, measured at the rivet in the
with a mark on the dashpot arm, the approximate tripping time pole piece. Also, the armature must have a minimum of
as shown by the characteristic curve Is Indicated. The 1A and 1/32 in. of travel beyond the point in its motion at which
1B characteristic devices are shipped with this setting at the the breaker is tripped.
2/3 mark and the 1C characteristic at the 1/3 mark. Standard
characteristic curves are plotted at these settings.
89
Courtesy of NationalSwitchgear.com
SECTION 13- Type EC Overcurrent Trip Device
al
tD
,. lID
ill
~ 11- ~
IE-
~
~ Ii III
m m
Left Side View Showing
Short Time Delay Mechanism o !!J
Right Side View Showing
Long Time Delay Mechanism
Front View Showing
Mounting Bracket
91
Courtesy of NationalSwitchgear.com
SECTION 13-Type EC Overcurrent Trip Device
92
Courtesy of NationalSwitchgear.com
13.7-Reverse Current Tripping Device
The device is enclosed in a molded case and is mounted which tends to rotate the armature counterclockwise. The
on the right pole base similar to the series overcurrent calibr!ition spring also tends to rotate the armature in the
tripping device. same direction. This torque causes the armature to rest
The reverse current tripping device (see Fig. 128) consists against the stop screw (12) attached to a bearing plate on
of a series coil (2) with an iron core mounted between two the right side of the device.
pole pieces (9), also a potential coil (7) connected across a If the current through the series coil (2) is reversed, the
constant source of voltage and mounted around a rotary- armature (10) tends to move in the clockwise direction
type armature (10). Calibration spring (6) determines the against the restraint of the calibration spring (6). When the
armature pick-up when a reversal of current occurs. current reversal exceeds the calibration setting, the
As long as the flow of current through the breaker is in the armature revolves clockwise causing the trip rod (3) to
normal direction, the magnetic flux of the series coil and move upward engaging the trip paddle (1), thereby
the magnetic flux of the potential coil produce a torque tripping the breaker.
'_~'l9~l! !.
II
~
IE
52
L3] sH.
-86-
!1
m
1. Trip paddle
2. Series coil
2A. Adjusting Nut
~ IE 28. Locking nut
3. Trip rod
~
lID 4. Trip crank
5. Setting sealing screw
fa 6. Calibration spring
7. Potential coil
m 8. Calibration nut
9. Pole pieces
10. Armature
mJ 11. Counter weight
12. Stop screw
9 13. Mounting screw
14. Screw
93
Courtesy of NationalSwitchgear.com
SECTION 13-Type EC Overcurrent Trip Device
13.7.1-Adjustments
The only adjustment to be made on the reverse current The switchette feature is available only in type EC-1
device is to make sure that the trip rod has a minimum devices.
overtravel of 1/32 in. beyond the point of tripping the
The switchette is used in one pole and EC-1 trips in the
breaker. This adjustment should have to be made only
other poles. For the alarm to be effective in indicating the
when an old device is being replaced by a new one.
overload before the other poles trip the breaker, the device
The new device will be factory adjusted so that the top end must have less time delay than the other two poles; this is
of the trip rod (3) will extend 1/2 in. above the top of the accomplished by using a lower characteristic on the alarm
device case, and no additional adjustments of the trip rod device than the other poles or setting the alarm devices
should be required. To obtain the proper 1/32 in. long time setting at 80%.
overtravel, close the breaker and proceed as follows:
1. Loosen the locking nut. (2B).
13.9-Trip Device Replacement
Overcurrent devices on the AKS50 breakers can be
2. Manually lift the trip rod and vary the position of the
replaced as follows:
adjusting nut (2A), this establishing the position of the
adjusting nut where the breaker is just tripped. a. Separate frames a~ described in Section 5.3
b. Referring to Fig. 126, remove bolts securing the series
NOTE: Be sure to keep clear of moving breaker
coil (1) to the lower stud.
parts when tripping the breakers.
c. Remove the clamping bracket (20).
. 3. With this position of the adjusting nut established, d. Before installing the replacement device, check the
advance the adjusting nut upward one and one-half turns. travel of trip arm as described in Section 11.5.4 and Fig.
4. Tighten the locking nut and the minimum 1/32-in. 127.
overtravel of the trip rod should be obtained. e. Replace new device in reverse order.
13.7.2-Replacement f. Adjust the new device as described in Section 11.5.4
After removing the wiring for the potential coil the reverse When replacing an EC-1 device with an EC-2 or EC-2A
current device can be removed and replaced by following device, it may be necessary to replace the trip paddles on
the procedure outlined for replacing the series overcurrent the trip shaft with slightly longer ones. If paddle
device. See Section 11.9. For wiring, see Fig. 128. replacement is required, new paddles are provided with the
replacement trip units.
13.8-Switchette Feature Pickup settings on the cover of the EC-2, EC-2A device are
The switchette is operated by the long-time delay function. calibrated for the specific device. When replacing covers,
Its purpose is to provide a set of contacts that will close replace on associated device.
before an overload occurs. This device will not trip the
breaker on overload it will trip on instantaneous only.
94
Courtesy of NationalSwitchgear.com
SECTION 14- Electrical Characteristics
Table 23 Table 27
Charging and closing operating currents Charging times
Table 24 Table 28
Bell alarm contact-rating Shunt trip and undervoltage device
Table 25 Table 29
Auxiliary switch contact sequence Coil resistance
Table 26
Auxiliary switch contact ratings
TABLE 23-Charging and Closing Operating Currents
MOTOR CD
.
~c
u >-
Current (Amps)
ANTI-PUMP
RELAY"W"
CONTROL
RELAY "X"
CLOSING
SOLENOID z:
c
fti ...
u
c ... ~
!! Rated·Amps .I!l Rated Amps .I!l Rated Amps i=
Courtesy of NationalSwitchgear.com
SECTION 14- Electrical Characteristics
TABLE 28-Shunt Trip and Undervoltage Device Operating Currents
e SHUNT TRIP UNDER VOLTAGE
C
0
U 01 0»
,.,u Current Current
-co _co c (Amps) (Amps)
0» N
c-
._ 0 ~p: Operating Inrush Sealed Inrush Sealed
E>
0 ~
LL
-- Operating
Z Voltage range Open Closed Voltage range Open Closed
24 DC 14 30 8.3 8.3 .38 .38
48 DC 28 60 4.5 4.5 .19 .19
125 DC 70 140 2.0 2.0 .08 .08
250 DC 140 280 1.0 1.0 .04 .04
OJ
70 60 59 132 - N/A N/A
-
- 0>
ro
120 60 95 127 12.3 10.8 <5 .66 .24
120 50 95 127 7.6 6.7 > .75 .25
OJ-
120 25 95 127 4.7 4.1
Ole
_ro-
c .31 .10
- 0
208 60 175 220 3.2 2.6 ~() .51 .17
208 50 175 220 3.8 3.1 (ij(ij
c c
.30 .10
208 25 175 220 2.1 1.9 'E 'E .14 .05
o 0
240 60 190 254 3.9 3.4 ZZ .37 .12
..........
240 50 190 254 4.7 4.1 o 0 .34 .11
240 40 190 254 5.8 5.1 ~PR N/A N/A
OJO
-CD
240 25 190 254 2.1 1.9 L.
o~
I
.16 .06
380 50 315 410 2.9 2.6 ;,Ro
~C')
.22 .08
480 60 380 508 3.4 3.1 co-
_ ro .23 .08
ro-
480 50 380 508 7.5 7.3 :J
0.0
.17 ..06
_-
480 25 380 508 3.5 3.3 :Jo.
.11 .05
ti
._ 0
L.
575 60 475 625 2.8 2.5 0.0 .16 .06
575 50 475 625 5.1 4.7 .14 .06
[ 575 25 475 625 3.1 3.0 See Table 30 .10 .05
48VDC 41 14-29
97
Courtesy of NationalSwitchgear.com
Courtesy of NationalSwitchgear.com
Courtesy of NationalSwitchgear.com
These instructions do not purport to cover all details or variations in equipment nor to provide for every possihle
contingency to he met in connection with installation operation or maintenance. Should further information he
desired or should particular prohlems arise which are nOl covered sutnciently for the purchaser's purposes, the
matter should be referred to the GE Company.
Courtesy of NationalSwitchgear.com