A Virtual Impedance Optimization Method For Reactive Power Sharing in Networked Microgrid
A Virtual Impedance Optimization Method For Reactive Power Sharing in Networked Microgrid
A Virtual Impedance Optimization Method For Reactive Power Sharing in Networked Microgrid
4, APRIL 2016
Abstract—Unlike the typical microgrid with a common ac bus, mode or grid-connected mode. Microgrid can not only solve the
networked microgrid always suffers more serious reactive power problem of large scale DG coupling but also play full advantages
sharing issues due to its complex inner structure. In such case, of DG units, improve power supply reliability and bring more
the system reactive power sharing error cannot be easily evalu-
ated and eliminated. So, this paper proposes a wireless control benefits to its users. However, microgrid also faces some chal-
strategy that employs optimized virtual impedance controllers and lenging problems, such as control stability and power sharing
local load measurements for the reactive power sharing in net- issues.
worked microgrid. First, from the modeling of microgrid network, In an islanded microgrid, loads must be properly shared by
an estimation method for network reactive power sharing error multiple DG units. Conventionally, the frequency and voltage
is derived. Through the estimation method-based network fea-
ture analyses, corresponding design for virtual impedance con- magnitude droop control method is adopted, which mimics the
troller is presented. Then, by introducing genetic algorithm, virtual behavior of synchronous machines in power systems [4]–[9].
impedance controller parameters of each distributed generation The droop control technique provides a decentralized control
unit are optimized, which aims to minimize the microgrid global capability, which makes the microgrid operation independent
reactive power sharing error. The parameter optimization process of communication links. This wireless control manner enables
is performed offline in microgrid configuration stage. By using
these optimized virtual impedance controllers, the reactive power the “plug and play” interfacing of DG units and also enhances
sharing performance of a networked microgird can be greatly im- the reliability of system. Although the frequency droop control
proved. Finally, the accuracy of the estimation method is validated always achieves accurate real power sharing, the voltage droop
by MATLAB simulation results, and the feasibility of the proposed control typically results in poor reactive power sharing due to
virtual impedance optimization method is verified through real the mismatch in feeder impedances, and also to the different
power experiments.
offsets of local loads. Moreover, when the microgrid structure
Index Terms—Estimation method, genetic algorithm (GA), net- is networked, the reactive power sharing issue will be further
worked microgrid, reactive power sharing, virtual impedance. aggravated due to the irregular distribution of DG units.
I. INTRODUCTION To improve the reactive power sharing performance of droop
control, many solutions have been developed [10]–[18]. In [10],
ITH the increased concerns on environment and clean
W energy, more and more renewable energy sources such
as photovoltaic cells, wind turbines, and microturbines are in-
reactive power sharing errors are reduced through the injection
of a small ac voltage signal in the system. However, this ap-
proach may reduce the quality of DG output voltages and line
tegrated into the power grid in the form of distributed genera- currents. As an important tool for droop control method, the
tion (DG) units. These DG units are normally interfaced to the well-known virtual impedance method can enhance the system
grid through power electronic converters. To effectively man- stability and reactive power sharing accuracy at the same time.
age these DG units, the microgrid concept is proposed, which In [11] and [12], predominant virtual inductors are placed at
is considered to pave the way to the future smart grid [1]–[3]. DG unit outputs, which mainly aimed to prevent the power con-
Microgrid usually connects to the power grid through the point trol instability. In [13]–[16], a comprehensive treatment about
of common coupling (PCC); it can operate in either islanded virtual impedance concept is presented. The focus has been on
the mismatched output impedances of closed-loop controlled
Manuscript received December 6, 2014; revised May 4, 2015 and Febru- DG units, while the mismatch in feeder impedances has not
ary 21, 2015; accepted June 12, 2015. Date of publication June 26, 2015; been considered. Thus, reactive power sharing issues cannot
date of current version November 30, 2015. This work was supported by Na-
tional High-tech Research and Development Program (863 program) under be solved completely. In [17], reactive power sharing errors
Grant 2015AA050606 and Natural Science Foundation of China under Grant are reduced through the modification of droop control slopes.
51177130. Recommended for publication by Associate Editor J. M. Guerrero. With the preset virtual inductor and estimated feeder impedance
Y. Zhu, F. Zhuo, F. Wang, and B. Liu are with the State Key Laboratory
of Electrical Insulation and Power Equipment, School of Electrical Engineer- value, the slope of Q–V droop control is modified to compensate
ing Xi’an Jiaotong University, Xi’an 710049, China (e-mail: zhuyixin1987@ the mismatch in feeder voltage drops. In [18], communication
163.com; [email protected]; [email protected]; comeliu is introduced to facilitate the estimation of feeder impedance
[email protected]).
R. Gou and Y. Zhao are with the Xian High Voltage Apparatus Research value, making the system reactive power sharing more accurate.
Institute, XiDian Group, Xi’an 710049, China (e-mail: [email protected]; Aforementioned reactive power sharing strategies have consid-
[email protected]). ered the impacts of DG output impedances, feeders, and local
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. loads. However, in a networked (multi-bus) microgrid, besides
Digital Object Identifier 10.1109/TPEL.2015.2450360 aforementioned mismatched factors, the networked structure is
0885-8993 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
ZHU et al.: VIRTUAL IMPEDANCE OPTIMIZATION METHOD FOR REACTIVE POWER SHARING IN NETWORKED MICROGRID 2891
nodes j to k)
Vn D j Vn D k Vn D i
− = Af i (4)
Vn Q j Vn Q k Vn Q i
where
Rf i −ωcom Lf i
Af i = .
ωcom Lf i Rf i
In (4), Vn D j and Vn Q j are the DQ axis voltages of node j;
Vn D k and Vn Q k are the DQ axis voltages of node k; If D i and
If Q i are the DQ axis currents of feeder i; Rf i and Lf i are the
resistance and reactance of feeder i. It is to be noted that line i
can be either a DG feeder or a network feeder, and node j can
be either a DVS node or a network node. By combining all the
feeder voltages together, the whole feeder model can be derived
as
Fig. 2. Sketch of the networked microgrid model.
BF Vn D Q = AF If D Q (5)
where
⎡ ⎤
to evaluate the system reactive power sharing performance due Af 1 0 ... 0
⎢ ⎥
to its complex structure. To address this problem, more detailed ⎢ 0 Af 2 ... 0 ⎥
⎢ ⎥
power sharing analyses are needed. Fig. 2 depicts a conceptual Af = ⎢ ⎥
⎢ ... ... ... ... ⎥
networked microgrid model, and the dashed part indicates the ⎣ ⎦
research object in this paper: equivalent network, containing 0 0 ... Af (n +s)
physical network and DG feeders. For the sake of analysis, only
T
linear load condition is considered, and all the DG units are set Vn D Q = Vn D 1 Vn Q 1 ... Vn D (m +s) Vn Q (m +s)
to the same power rating. T
As can be seen from Fig. 2, the whole microgrid system is If D Q = If D 1 If Q 1 ... If D (n +s) If Q (n +s) .
composed of a physical network and several DG units. Each In (5), the mapping matrix BF is size of 2(n+s) × 2(n+s),
DG unit can be equivalent to a droop controlled voltage source which reflects the connecting relationship between nodes and
(DVS) in series with a DG feeder. The DG feeder can be either feeders. For example, if line i connects between nodes j and k,
a coupling inductor or a virtual feeder if virtual impedance the element BF (i,j) and BF (i,k) will be +1 or –1 (depending on
method is applied. By separating DVS units from the system, the current direction), and all the other elements in that row will
the equivalent network of microgrid is obtained. The detailed be 0. In the equivalent network, some nodes are DVS nodes,
network model will be explained in the following part of this and the voltages of these nodes are treated as the inputs of this
section. It is worth noting that in the modeling process, the network model. By extracting them from vector Vn D Q , equation
three-phase voltages and currents are all represented as vectors (5) can be revised as
in d–q rotating reference frame. In this paper, the reference
frame of DVS 1 is regarded as the common reference frame, BF 1 VdvsD Q + BF 2 Vpn D Q = AF If D Q (6)
whose rotating frequency is ωcom , while the system variables where
in other individual reference frames are all translated to this T
common reference frame using the following equations: EdvsD Q = EdvsD 1 EdvsQ 1 ... EdvsD s EdvsQ s
Vpn D Q = Vpn D 1 Vpn Q 1 ... Vpn D m Epn Q m
T
.
FD cos δi − sin δi Fdi
= (3)
FQ sin δi cos δi Fq i In (6), EdvsD i and EdvsQ i are the DQ axis voltages of DVS
i; the mapping matrixes BF 1 and BF 2 are separated from BF ,
where FD and FQ are the DQ axis components of variable F and they are size of 2(n+s) × 2s and 2(n+s) × 2m, respectively.
in the common reference frame; Fdi and Fq i are the dq axis 2) Load Model: The voltage of the RL load connected to
components of variable F in the reference frame of DVS i; and network node j can be expressed as
δi is the angle difference between the two reference frames.
Vpn D j IlD j
Back to the microgrid model shown in Fig. 2, the equivalent = Alj (7)
network totally contains s DG feeders, n network feeders, s DVS Vpn Q j IlQ j
nodes and m network nodes, where s is the number of DG units. where
The detailed modeling process is shown as follows:
Rlj −ωcom Llj
1) Feeder Model: The voltage of feeder line i between nodes Alj = .
j and k can be expressed as (assuming that currents flow from ωcom Llj Rlj
ZHU et al.: VIRTUAL IMPEDANCE OPTIMIZATION METHOD FOR REACTIVE POWER SHARING IN NETWORKED MICROGRID 2893
In (7), IlD j and IlQ j are the DQ axis currents of load j; In (12), YNET is presented as a partition matrix. Its diagonal
Rlj and Llj are the resistance and reactance values of load j, submatrix Yli is the input admittance of DVS i, which reflects
respectively. If there is no load connected to node j, a sufficiently the network port characteristics. Its off-diagonal submatrix Yij
large ground resistance can be introduced to mimic the no load and Yj i reflect the interconnection between DVS i and j, and
characteristic. Hence, the whole model of m loads can be given they are always equal. Thus, the network matrix is a partition
by symmetric matrix. By observing the diagonal elements in YNET ,
the mismatch in network can be basically obtained. When the
Vpn D Q = AL IlD Q (8) input admittances of DVS units are equal, the corresponding
where network will have an ideal reactive power sharing performance.
⎡ ⎤ However, this is not a necessary condition for accurate reactive
Al1 0 ... 0 power sharing, as will be discussed in the following.
⎢ ⎥
⎢ 0 Al2 ... 0 ⎥
⎢ ⎥
AL = ⎢ ⎥ C. Estimation of Reactive Power Sharing Errors
⎢... ··· ... ... ⎥
⎣ ⎦
As mentioned before, DG units are all set to the same power
0 0 ... Alm rating for a convenient comparison. That means each DG unit
IlD Q = IlD 1 IlQ 1 ... IlD m IlQ m
T
. should output the same real and reactive powers in microgrid.
According to (11) and (12), the DVS DQ axis currents can be
3) Complete Model of Equivalent Network: According to the calculated as
network connection, the relationship between feeder currents
and load currents can be expressed as IdvsD = GNET EdvsD − BNET EdvsQ (13)
IdvsQ = BNET EdvsD + GNET EdvsQ (14)
IlD Q = AF 2L If D Q . (9)
where
In (9), matrix AF 2L is size of 2m × 2n maps the connection
between loads and feeders. For example, when lines i and j EdvsD = [EdvsD 1 EdvsD 2 ... EdvsD s ]T
are connected to the network node k, the element AF 2L (k,i)
and AF 2L (k,j) will be +1 or –1 (depending on whether the EdvsQ = [EdvsQ 1 EdvsQ 2 ... EdvsQ s ]T
line current is entering or leaving the node), and all the other IdvsD = [IdvsD 1 IdvsD 2 ... IdvsD s ]T
elements in that row will be 0. By transforming (6), (8), and (9),
the complete equivalent network model can be derived as IdvsQ = [IdvsQ 1 IdvsQ 2 ... IdvsQ s ]T .
If D Q = ANET EdvsD Q (10) In (13) and (14), IdvsD i and IdvsQ i are the DQ axis currents
of DVS i; EdvsD i and EdvsQ i are the DQ axis voltages of DVS
where i; GNET and BNET are the system conductance and susceptance
ANET = (AF − BF 2 AL AF 2L )−1 BF 1 . matrixes obtained from matrix YNET . According to the common
reference frame setting, the Q axis voltage of DVS 1 should be
By extracting DVS currents from vector If D Q , following 0. Then, equation (13) can be rewritten as
equation can be derived:
IdvsD = GNET EdvsD − BNET EdvsQ (15)
IdvsD Q = CNET If D Q = YNET EdvsD Q (11)
where matrix BNET is size of s×(s–1), which is obtained from
where BNET by eliminating the first column; Similarly, vector EdvsQ
is obtained from EdvsQ by eliminating the first element EdvsQ 1 .
YNET = CNET ANET .
As the real power sharing of the system using the droop control
In (11), CNET is of size 2s × 2n, which is used to pick method is always accurate, the elements in IdvsD should be
out DVS currents from feeder currents. YNET is the admittance equal. Thus, equation (13) can be transformed as
matrix of equivalent network, and its detailed form is shown
Tr e IdvsD = Tr e GNET EdvsD − Tr e BNET EdvsQ =0 (16)
next
⎡ ⎤ where
Y11 Y12 . . . Y1s
⎢ ⎥ ⎡ ⎤
⎢ Y21 Y22 . . . Y2s ⎥ 1 −1 0 ... 0
⎢ ⎥ ⎢ ⎥
YNET = ⎢ ⎥ (12) ⎢ 1 −1 ⎥
⎢... ... ... ... ⎥ ⎢ 0 ... 0 ⎥
⎣ ⎦ Tr e =⎢ ⎥ .
⎢ ... ... ... ... ... ⎥
Ys1 Ys2 . . . Yss ⎣ ⎦
where 1 0 0 ... −1 s×s
Glj −Blj Then, the relationship between EdvsD and EdvsQ is derived
Ylj = .
Blj Glj EdvsQ = Ted 2eq EdvsD (17)
2894 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 4, APRIL 2016
where
−1
Ted 2eq = Tin (Tr e BNET ) Tr e GNET
and
⎡ ⎤
0 0 ... 0
⎢ ⎥
⎢ 1 0 ... 0 ⎥
⎢ ⎥
⎢ ⎥
Tr e =⎢
⎢ 0 1 ... 0 ⎥
⎥ . Fig. 3. Structure of the target networked system in this paper.
⎢ ⎥
⎢... ... ... ...⎥
⎣ ⎦ TABLE I
0 0 ... 0 s×(s−1) RELATED PARAMETERS OF THE TARGET MICROGRID SYSTEM
np
Qer global % = Qer n etj % (29)
j =1
At the beginning, each load is set with three real power opera-
tion points (1.5, 3 and 4.5 kW), and two reactive power operation
points (2 and 4 kVar). So, each load has six operation points, and
the system has total 6m (m is the load number) operation points
accordingly. This number is too large for Qer global % calcula-
tion, and in practice, the number may be even larger. However,
some operation points are not so valuable for the optimization.
To make the optimization more effective, the focus should be
on those operation points associated with local load change,
while the other load changes can be neglected properly. Finally,
there are five operation points for each local load and two for
each public load. Thus, total 500 operation points are selected
as the preset operation points for Qer global % calculation. The
calculation function FQ (x) based on the global reactive power
sharing error is established in MATLAB as illustrated in Fig. 9.
The output of function FQ (x) is the optimization objective
Qer global %, and the decision factors in each virtual resistance Fig. 10. Illustration of GA in MATLAB.
controller, which need to be optimized, are set as the inputs. In
a microgrid, different operation points correspond to different
networks. As the figure shows, by accumulating reactive power in this paper can be solved. Related configuration parameters
sharing errors of different networks, the global reactive power used in GA toolbox are listed in Table III.
sharing error value is obtained. When optimization algorithm Some other parameters keep their default values in MATLAB.
is utilized, the best values for these decision factors, which can The virtual impedance controller optimizations for simulation
minimize the output value Qer global %, will be obtained. and experiment systems are separate, and their optimization re-
sults are listed in Tables IV and VIII, respectively. With the opti-
B. Optimization Algorithm and Configuration mized virtual impedance controllers, the reactive power sharing
performance of the target system can be improved, and this will
To deal with such a nonlinear optimization problem, GA
be verified by simulation and experimental results.
is a good choice [32], [33]. GA is a search technique used
in computer, which mimics Darwinian natural selection. The
V. SIMULATION VERIFICATION
operation process of GA in MATLAB is described in Fig. 10.
When the network structure and feeder impedance values are To verify the effectiveness of the proposed control strategy,
known, corresponding FQ (x) can be established. By calling the as well as the reactive power sharing evaluation method, the
optimization toolbox in MATLAB, choosing GA as the solver microgrid system depicted in Fig. 3 is established in MATLAB
and FQ (x) as the objective function, the optimization problem simulation. The DG unit configurations and initial microgrid
2898 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 4, APRIL 2016
TABLE III
CORRESPONDING SETTING IN GA OPTIMIZATION
TABLE IV
DG UNIT AND MICROGRID PARAMETERS USED IN MATLAB SIMULATION
DG unit parameters
operation point are listed in Table IV. With the same power
rating, the three DG units shall share the load equally. Fig. 12. Simulated currents of DG units with the conventional method under
the initial operation point.
Fig. 13. Simulated DG voltage magnitudes with the conventional method. Fig. 15. Simulated currents of DG units with the optimized virtual impedance
method under the initial operation point.
TABLE VI
COMPARISON BETWEEN ESTIMATION AND SIMULATION RESULTS
TABLE VII
FEEDER IMPEDANCE CHANGES IN “VARIANT” MICROGRID SYSTEMS
From the change in GNET and BNET , it can be seen that,
at the beginning, the input admittance of each DG unit is large
Feeder 1 Feeder 2 Feeder 3 Feeder 4
and significantly different. And these mismatched character-
istics lead to the poor reactive power sharing performance of MG 0 0.1 Ω 0.4 Ω 0.2 Ω 0.1 Ω
MG 1 +15% +15% +15% +15%
system. When fixed virtual impedance method is applied, DVS
MG 2 −15% −15% −15% −15%
input admittances are decreased, and the match degree of net- MG 3 +10% −15% −10% +15%
work is improved relatively. But these fixed virtual impedances
cannot compensate the mismatch in network specifically. On
the other hand, the input admittance magnitude of each DVS
unit can be calculated from GNET and BNET . It will be found
that the DVS unit with larger input admittance value always
outputs more reactive power, and this phenomenon obeys the
laws of physics. With the system matrixes obtained from the
equivalent network, reactive power sharing can be analyzed
qualitatively. And with the further deduced evaluation array,
the reactive power sharing can even be estimated quantitatively.
The reactive power sharing error estimation results derived from
network matrixes are listed in Table VI.
In the table, Qav e is the averaged value of DG unit reactive Fig. 19.
power outputs, and Qi /Qav e is calculated for a better com- Performances of the optimized virtual impedance method while applied in mis-
∗
parison with CAPSN . As the aforementioned table shows, the matched systems.
proposed estimation method can well reflect the reactive power
sharing state of a microgrid network, and its accuracy is favor- is limited fewer than 20%, when optimized virtual impedance
able. Compared with simulation results, the estimation results controllers are utilized.
can be obtained much faster. As the estimation method has a
good accuracy, it is feasible to use the estimation results in the
E. Performance in Mismatched Systems
calculation of Qer global %, which serves the parameter opti-
mization of virtual impedance controller. To test the fault-tolerant capability of the proposed method,
the optimized virtual impedance controllers designed for the
original target system will be applied to several “variant” mi-
D. Performance Comparison With Different Operation Points crogrid systems, which are created from the original system by
To further compare the reactive power sharing performance changing feeder impedance values. The changed feeder param-
between the conventional method and proposed method, the eters of each “variant” system are listed in Table VII.
target microgrid will operate under more different operation In the table, MG 0 represents the original microgrid system,
points, and the corresponding comparison results are shown in and MG 1–3 represent the “variant” microgrid systems. In MG
Fig. 18. 1 and 2, feeder impedance values are enlarged and reduced
In the comparison, according to the load range, 30 opera- uniformly. While in MG 3, feeder impedance values are changed
tion points are randomly generated. As Fig. 18 shows, the net- irregularly. The performances of the original virtual impedance
work reactive power sharing error Qer n etj % is always high with controllers in different “variant” systems are shown in Fig. 19.
fixed virtual impedances, while the system using optimized vir- As can be seen from the figure, these virtual impedance
tual impedances has a much better performance. It also can be controllers, which are designed for the original target system,
seen that the microgrid network reactive power sharing error are also suitable for “variant” systems. The maximal network
ZHU et al.: VIRTUAL IMPEDANCE OPTIMIZATION METHOD FOR REACTIVE POWER SHARING IN NETWORKED MICROGRID 2901
Fig. 20. DG currents of each phase under the proposed method in unbalanced TABLE VIII
load condition. DG UNIT AND MICROGRID PARAMETERS USED IN EXPERIMENT
DG unit parameters
TABLE IX
SYSTEM MATRIXES OF DIFFERENT EQUIVALENT NETWORK IN EXPERIMENTS
GN E T BN E T
1.93 −1.61 0.23 0.04
Physical network without virtual impedances
−1.61 1.77 0.04 0.06
0.28 −0.12 0.66 −0.45
Network with fixed virtual impedances
−0.12 0.32 −0.45 0.60
0.34 −0.17 0.57 −0.40
Network with optimized virtual impedances
−0.17 0.35 −0.04 0.58
Fig. 24. Experimental DG voltage and current waveforms with the conven-
tional control method. (a) Original figure. (b) Enlarge figure.
Fig. 23. Power sharing performance with the conventional control method in
experiment. (Before the load change, P1 , P2 are each 1800 W, and Q1 , Q2 are
2000 and 1300 Var, respectively; then, P1 , P2 drop to 1500 W, and Q1 , Q2 drop
to 1500 and 1000 Var, respectively.)
[25] Y. X. Zhu, F. Zhuo, and H. T. Shi, “Accurate power sharing strategy for Feng Wang (S’08–M’13) received the B.S., M.S.,
complex microgrid based on droop control method,” in Proc. IEEE Conf. and Ph.D. degrees in electrical engineering from
ECCE Asia, Downunder, 2013, pp. 344–350. Xi’an Jiaotong University, Xi’an, China, in 2005,
[26] T. L. Vandoorn, J. D. M. De Kooning, B. Meersman, and L. Vandevelde, 2009 and 2013, respectively.
“Communication-based secondary control in microgrids with voltage- Between 2010 and 2012, he was an exchang-
based droop control,” in Proc. IEEE Transmiss. Distrib. Conf. Expo., ing Ph.D. student in the Center for Power Elec-
2012, pp. 1–6. tronics Systems at Virginia Polytechnic Institute and
[27] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. De Vicuna, and M. State University (Virginia Tech), Blacksburg, USA.
Castilla, “Hierarchical control of droop-controlled ac and dc microgrids— In November 2013, he joined Xi’an Jiaotong Univer-
A general approach toward standardization,” IEEE Trans. Ind. Electron., sity as a Postdoctoral Fellow, where he is currently
vol. 58, no. 1, pp. 158–172, Jan. 2011. with the State Key Laboratory of Electrical Insulation
[28] M. Savaghebi, A. Jalilian, J. C. Vasquez, and J. M. Guerrero, “Secondary and Power Equipment, School of Electrical Engineering. His research interests
control scheme for voltage unbalanced compensation in an islanded droop include dc/dc conversion, digital control of switched converters, especially in
controlled microgrid,” IEEE Trans. Smart Grid, vol. 3, no. 2, pp. 797–807, renewable energy generation fields.
Jun. 2012.
[29] H. Mahmood, D. Michaelson, and J. Jiang, “Accurate reactive power
sharing in an islanded microgrid using adaptive virtual impedances,” IEEE
Trans. Power Electron., vol. 30, no. 3, pp. 1605–1617, Mar. 2015.
[30] Y. Zhang and H. Ma, “Analysis of networked control schemes and data-
processing method for parallel inverters,” IEEE Trans. Ind. Electron.,
vol. 61, no. 4, pp. 1834–1844, Apr. 2014.
[31] Y. Zhang and H. Ma, “Theoretical and experimental investigation of net-
worked control for parallel operation of inverters,” IEEE Trans. Ind. Elec- Baoquan Liu (S’13) received the B.S. degree in elec-
tron., vol. 59, no. 4, pp. 1961–1970, Apr. 2012. trical engineering from the Harbin Institute of Tech-
[32] M. B. Shadmand and R. S. Balog, “Multi-objective optimization and nology, Harbin, China, in 2009, and the M.S. de-
design of photovoltaic-wind hybrid system for community smart dc gree from Xi’an Jiaotong University, Xi’an, China, in
microgrid,” IEEE Trans. Smart Grid, vol. 5, no. 5, pp. 2635–2643, 2012, where he is currently working toward the Ph.D.
Sep. 2014. degree in the State Key Laboratory of Electrical In-
[33] S. Jazebi, M. M. Haji, and R. A. Naghizadeh, “Distribution network re- sulation and Power Equipment, School of Electrical
configuration in the presence of harmonic loads: optimization techniques Engineering.
and analysis,” IEEE Trans. Smart Grid, vol. 5, no. 4, pp. 1929–1937, His research interests include system operation
Apr. 2012. and energy management of microgrids, especially hy-
[34] J. W. He, Y. W. Li, and F. Blaabjerg, “An enhanced islanding microgrid brid energy storage systems in microgrids.
reactive power, imbalance power, and harmonic power sharing scheme,”
IEEE Trans. Power Electron., vol. 30, no. 6, pp. 3389–3401, Jun. 2015.