TECHNICAL SPECIFICATIONS
winding design, the transformer needs to operate reliable with only one
Inverter supplying power to only one LV winding.
a. The Transformer tank and cover shall be fabricated from high grade low
carbon plate steel of tested quality. The tank and the cover shall be of
welded construction and there should be provision for lifting by crane.
b. A double float type Buchholz relay conforming to IS: 3637 shall be
provided.
c. Suitable Inspection hole(s) with welded flange(s) and bolted cover(s) shall
be provided on the tank cover. The inspection hole(s) shall be of sufficient
size to afford easy access to the lower ends of the bushings, terminals etc.
d. All bolted connections to the tank shall be fitted with suitable oil-tight
gaskets which shall give satisfactory service under the operating
2.2 Windings
a) The Bidder shall ensure that windings of all transformers are made in dust
proof & conditioned atmosphere.
b) The conductors shall be of electrolytic grade copper/electrolytic grade
Aluminum free from scales & burrs.
c) All windings of the transformers shall have uniform insulation.
d) Tapping shall be so arranged as to preserve the magnetic balance of the
transformer at all voltage ratio.
2.3 Core
a) The core shall be constructed from non-ageing, cold rolled, super grain
oriented silicon steel laminations equivalent to M4 grade steels or better.
b) Core isolation level shall be 2 kV (rms.) for 1 minute in air.
c) Adequate lifting lugs will be provided to enable the core & windings to be
lifted.
No inhibitors shall be used in the transformer oil. The oil supplied with
transformers shall be new and previously unused and must conform to
following while tested at supplier's premises and shall have following
parameters.
2.5 Bushings
ii. LV Bushing below 3.6 kV used within transformer cable box, epoxy type
bushing confirming to IS 2099/IEC 60137 also allowed as alternate to
porcelain type
iii. No arcing horns to be provided on the bushings.
iv. Inverter Transformer LV bushing palms shall be silver/tin plated.
2.7 Valves
2.8 Gaskets
a) Gasket shall be fitted with weather proof, hot oil resistant, nitrile rubber
based gasket.
c) The gaskets shall not deteriorate during the life of transformer if not opened
for maintenance at site. All joints flanged or welded associated with oil shall
be such that no oil leakage or sweating occurs during the life of transformer.
The quality of these joints is considered established, only if the joints do not
exhibit any oil leakage or sweating for a continuous period of at least 3
months during the guarantee period. In case any sweating / leakage is
observed, contractor shall rectify the same & establish for a further period of
3 months of the same. If it is not established during the guaranteed period,
the guaranteed period shall be extended until the performance is
established.
2.9 PAINTING
Neutral earthing shall be done as per system requirement and SLD. In case of
solidly earthed neutral of Transformers, it shall be brought through insulated
support from tank to the ground level at a convenient point with 2 nos. copper
flat, for connection to ground network (as applicable).Neutral of Transformer if
not used should be taken out through bushing and covered by insulating cap.
(a) HV Cable boxes shall be of phase segregated air insulated type & shall be
nation. Phase
segregation shall be achieved by insulating barriers (for 3.3 kV and above
side)
(b) Cable boxes shall have bus bars / suitable terminal connectors of adequate
size & bolt holes to receive cable lugs. The degree of protection of cable
boxes shall be IP 55.
(c) A suitable removable gland plate of non-magnetic material drilled as per the
(d) The support from base for the cable box (for 3.3 kV and above side) shall be
of galvanized iron
(e) The contractor shall provide earthing terminals on the cable box, to suit
(f) The minimum length provided for terminating 33 kV, 11KV & 3.3 KV XLPE
cable shall be 1000 mm (for 33 kV) 650 mm (for 3.3 kV and 11 kV) from
cable gland plate to the cable lug) for the cable boxes, for 433V side
suitable length shall be provided (shall be discussed during detail
engineering). The final cable size, number & length of terminating XLPE
cable shall be furnished during detailed engineering.
(g) Cable boxes shall be designed such that it shall be possible to move away
the transformer without disturbing the cable terminations, leaving the cable
box on external supports (as applicable).
(h) Cable boxes shall have removable top cover (for transformer above 100
KVA) & ample clearance shall be provided to enable either transformer or
each cable to be subjected separately to high voltage test.
2.12 FITTINGS
Following fittings shall be provided with Transformers covered under this sub
section.
a) -Conservator for main tank shall be provided with MOG with low oil level alarm
contact, drain valve & indicating type free Cobalt free breather with transparent
enclosure (maximum height 1400 mm above ground level) etc.
b) - Buchholz relay, double float type with alarm and trip contacts, along with
suitable gas collecting arrangement.
c) - It shall be provided with minimum two numbers of spring operated PRD (with
trip contacts) with suitable discharge arrangement for oil shall be provided.
d) OTI & WTI shall be 150 mm dial type with alarm and trip contacts with max.
reading pointer & resetting device (maximum height 1500 mm above ground
level).
For Inverter Transformers, WTI shall be provided at least for all LV windings.
e) Top & bottom filter valves with threaded male adapters, bottom sampling valve,
drain valve/sludge removal valve at the bottom most point of the tank.
f) Air release plug, bushing with metal parts & gaskets, terminal connectors on
bushings (as applicable).
g) Prismatic/toughened glass oil gauge for transformers.
k) Rain hoods to be provided on Buchholz, MOG & PRD. Entry points of wires
shall be suitably sealed.
The fittings listed above are only indicative and other fittings, which generally are
required for satisfactory operation of the transformers are deemed to be included.
AN
Transformer shall be provided with suitable
x) Type of cooling ventilation system to ensure the temperature rise
limits under most severe condition while in service
however all tests and performance guarantee
shall correspond to air natural (AN) cooling.
Bushing rating, As per relevant IS/IEC
Insulation class (However Inverter Transformer LV side winding &
xi)
(Winding & bushing insulation class shall be of at least 3.6
bushing) kV)
Maximum 90 deg.C. ( class F)
Temperature rise of 115 deg.C. ( class H)
winding over 50
deg. C ambient.
xii)
(by resistance
method) with Air
Natural (AN)
cooling.
SC withstand time
xiii) 2 sec
(thermal)
xiv) Noise Level Not to exceed values specified in NEMA TR-1.
PD Level (max.
xv) Allowable) 10 pc
Continuous operation at rated KVA on any tap
with voltage variation of +/-10% corresponding to
xvi) Loading Capability
the voltage of the tap as well as in accordance
with IEC60076-12/IS: 6600.
Not to exceed 1.9 Wb/sq.m. at any tap position
with +/-10% voltage variation from voltage
corresponding to the tap. Transformer shall also
xvii) Flux Density withstand following over fluxing conditions due
combined voltage and frequency fluctuations:
a) 110% for continuous rating.
b) 125% for at least one minute.
3.2.1 The core shall be constructed from high grade non-ageing cold rolled grain
oriented silicon steel laminations of M4 grade or better quality. The insulation of
core to clamp-plates shall be able to withstand a power frequency voltage of 2 kV
(rms) for one (1) minute.
3.2.2 The transformers shall be housed in a metal protective housing, having a degree
of protection of IP-23.In case it is placed outdoor, IP for enclosure shall be
minimum IP-42 or higher. Enclosure shall be of a tested quality sheet steel of
minimum thickness 2mm & shall also accommodate cable terminations. The
housing door shall be interlocked such that it should be possible to open the door
only when transformer is off. The enclosure shall be provided with lifting lugs and
other hardware for floor mounting. Suitable bi-directional skids with pre-drilled
holes shall be provided integral with the enclosure or bi-directional rollers shall be
provided with suitable locking arrangement.
3.2.3 Winding conductor shall be electrolytic grade Copper/ Aluminum. Windings shall
be of class F insulation or better. All windings are to be uniformly insulated.
3.2.4 Transformer HV bushings and LV bushings can be either solid porcelain or epoxy
type. Bushing shall be suitable for satisfactory operation in the high ambient
temperature inside Bus Duct enclosure (if applicable). LV flange area shall be of
non-magnetic material.
3.2.5 Bushing CTs shall be provided in the LV neutral side of adequate rating for REF
protection, WTI, etc (as applicable).
3.2.6 For Marshalling Box the sheet steel used shall be at least 1.6 mm thick cold
rolled. The box shall be tank mounted type. The degree of protection shall be IP-
54 in accordance with IS-13947. Wiring Scheme shall be engraved in a stainless
steel plate with viewable font size and the same shall be fixed inside the
Marshalling Box door.
3.2.7 Transformer shall be provided with suitable ventilation system to ensure the
temperature rise limits under most severe condition while in service however all
tests and performance shall correspond to air natural cooling.
3.3 PAINTING
3.3.1 The inside of enclosure and accessories (except M. Box) shall be painted with
two coats of fully glossy white colour with total DFT of 25 to 60 microns. The
external paint colour of transformer & accessories shall be blue corresponding to
RAL 5012. The external surface of transformer & accessories shall have two
coats of chemical resistant epoxy zinc phosphate primer and two coats of
polyurethane finish paint with total DFT of 80 to 150 microns. The internal surface
of M.Box shall have two coats of chemical resistant epoxy zinc phosphate primer
and two coats of chemical & thermal resistant epoxy enamel white paint with total
DFT of 80 to 150 microns.
3.4 FITTING
In case the bidder/contractor has conducted type test(s) within last ten years, he
may submit the type test reports to the owner for waiver of conductance of such
type test(s). These reports should be for the tests conducted on the equipment
similar to those proposed to be supplied under this contract and test(s) should
have been either conducted at an independent laboratory or should have been
witnessed by a client.
In case the Bidder is not able to submit report of the type test(s) conducted within
last ten years from the date LOA by GVREL, or in case the type test report(s) are
not found to be meeting the specification requirements, the Bidder shall conduct
all such tests under this contract at no additional cost to the Employer and submit
the reports for approval
In case short circuit test has not been conducted or the test report not meeting
the specification requirement for the offered transformer manufacturer, Bidder
/Sub-
offered transformer as per latest IEC 60076-5.The ability to
withstand the dynamic effects of short circuit can be established either by
performing actual short circuit test or by method of calculation with reference to
short circuit tested reference transformer as per IEC-60076-5/Annexure-A&B.
Bidder shall choose any one the two options mentioned below;
Option-1:- Performing actual short circuit test as Type Test. In order to meet
project schedule, Bidder/Sub vendor shall take suitable steps quite in advance to
ensure successful conduction of short circuit test within three months time from
date of LOA failing which the offered make of the transformer shall not be
considered.
In this regard the guidelines given in Annexure-A with applicable tables of the IEC
60076-5 is to be followed. The reference transformer chosen shall be of same
application, winding configuration, conductor current density and as per
Annexure-B of latest IEC-60076-5. Necessary Design document and reference
test reports related to theoretical comparative evaluation must be submitted by
Manufacturer/Bidder as required by Employer in this case.
S.N. ROUTINE TESTS
1. All routine test shall be carried out in accordance with IEC 60076.
2. Measurement of Voltage Ratio & phase displacement (as per IEC
60076-1)
3. Measurement of winding resistance on all the taps (as per IEC
60076-1)
4. Vector group and Polarity Check (as per IEC 60076-1)
5. Magnetic Balance and Magnetising Current Test
6. Measurement of no load current with 415 V, 50 Hz AC supply
7. Measurement of no load losses and current at 90%, 100% & 110%
of rated voltage (as per IEC 60076-1)
8. Load Loss & Short Circuit Impedance Measurement on principal &
Extreme Taps
9. IR measurement (As per IEC 60076-1)
10. Measurement of capacitance & tan delta to determine capacitance
between winding & earth.
11. Separate Source Voltage Withstand Test /Applied voltage test (as
per IEC 60076-3)
12. Induced overvoltage test/Induced voltage withstand(IVW) test as
per IEC60076 part 3
13. Repeat no load current/loss & IR after completion of all electrical
test
14. Oil leakage test on completely assembled transformer along with
radiators (as per relevant clause of this sub section)
15. Jacking test followed by D.P. test
(#) NOTE:-
i) All the type and special tests shall be conducted after performing Short
Circuit Test. If Tank Vacuum & Pressure Test is to be carried out then it
shall be conducted before SC test.
iii)
All tank & oil filled compartment shall be tested for oil tightness by being
completely filled with oil of viscosity not greater than that of specified oil at the
ambient temperature & applying pressure equal to the normal pressure plus 35
KN/sq. m measured at the base of the tank. The pressure shall be maintained
for a period of not less than 6 hours during which time no sweating shall occur.
Bidder can perform this test at site depending upon urgency subject to GVREL
approval.
Suitable Fire Fighting arrangements for Oil filled Transformers shall be provided
if applicable as per Tariff Advisory Committee (TAC)/statutory requirements. In
case Nitrogen based fire protection system is used, CBIP manual shall be
followed for compliance. Firewall & soak pit as applicable (as per statuary
requirement/TAC/IS 10028 / IS 1646) shall be provided of minimum 230 mm
thickness of RCC wall or 355 mm thick fire resisting brick wall subject to GVREL
approval. However for all oil filled outdoor a pit shall be provided all around at a
distance of 1.0 meter (min.) from transformer outer edge, a sump pit shall be
provided for each pit. Transformer efficiency shall be as per Central Electricity
Authority (Technical Standards for Construction of Electrical Plants and
Electrical Lines) regulation, 2010.
Transformer shall be short circuit tested after conducting the routine tests.
Rest of the type tests shall be conducted after successful short circuit testing.
All routine tests in accordance with IS: 11171 / IEC 60076-11 shall be carried out
on each transformer.