Energy Meter
Type EM340
• Three phase energy meter
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Accuracy ±0.5% RDG (current/voltage)
• Direct current measurement up to 65AAC
• Backlit LCD display (3x 8-digit) with integrated touch
key-pad
• Energy readout on display: 8 digit
• Variable readout on display: 4 digit
• Energy measurement: kWh and kvarh (imported/
exported); kWh+ by 2 tariffs; kWh per phase
• System variables: kW, kvar, kVA, VLL, VLN, PF, Hz,
kWdmd, kWdmd peak
• Phase variables: kW, kvar, kVA, VLL, VLN, A, PF
• Digital input (for tariff management) • Self power supply
• Easy connection or wrong current direction detection • Dimensions: 3-DIN module
• Certified according to MID Directive (option PF only): • Protection degree (front): IP51
see “how to order” below • Pulse output (optional, by open collector NPN)
• Other versions available (not certified, option X): see • RS485 Modbus port (optional)
“how to order” on the next page • M-bus port (optional)
Product description
Three-phase energy meter applications up to 65 A (direct the imported one. Housing for measured, RS485 Modbus
with backlit LCD display with connection), with dual tariff DIN-rail mounting, with IP51 port or M-bus port. Available
integrated touch keypad. management availability. front degree protection. The for legal metrology (PF option,
Particularly indicated for It can measure imported meter is optionally provided only for imported energy).
active energy metering and exported energy or be with pulse output proportional
and for cost allocation in programmed to consider only to the active energy being
AV2: 208 to 400 VLL AC - 3: 3-phase, 3 or 4 wire; X: Self power supply O1: pulse output
5(65)A 2-phase 3 wire -20% +20% of the S1: RS485 Modbus port
(Direct connection) rated measuring input
M1: M-bus port
voltage, 45 to 65Hz
Option Measurement
PF: Certified according to A: The power is always integrated (both in case of positive imported and negative
MID Directive. Can exported power) and the total energy meter is certified according to MID. Operating
be used for fiscal temperature: from –25 to +55°C/from –13 to +131°F.
(legal) metrology. B: Only the total positive energy meter is certified according to MID. Operating
temperature: from –25 to +55°C/from –13 to +131°F.
A70: The power is always integrated (both in case of positive imported and negative
exported power) and the total energy meter is certified according to MID. Operating
temperature: from –25 to +70°C/from –13 to +158°F.
B70: Only the total positive energy meter is certified according to MID. Operating
temperature: from –25 to +70°C/from –13 to +158°F.
Type Selection
AV2: 208 to 400 VLL AC - 3: 3-phase, 3- or 4-wire; X: self power supply O1: pulse output
5(65)A 2-phase 3-wire -20% +20% of the S1: RS485 Modbus port
(Direct connection) rated measuring input
M1: M-bus port
voltage, 45 to 65Hz
Option
X: none
Input specifications
Rated Inputs Energy additional errors
Current type 3-phase loads, direct Influence quantities According to EN62053-21
connection Temperature drift ≤200ppm/°C
Current range 5(65)A Sampling rate 4096 samples/s @ 50Hz
Nominal voltage 208 to 400 VLL AC 4096 samples/s @ 60Hz
Accuracy
Display and touch key-pad
(@25°C ±5°C, R.H. ≤60%,
Type Backlit LCD, 3 rows by
45 to 65 Hz) Imin=0.25A; Ib: 5A, Imax:
8-digit each, h 7 mm
65A; Un: 113 to 265VLN
Read-out Energy: 8 digit. Variables: 4
(196 to 460VLL)
digit
Imin=0.25A; Ib: 5A, Imax:
Touch key 3 (DOWN, Enter and UP).
65A; from 208 to 400 VLL AC
Max. and Min. indication
Current From 0.04Ib to 0.2Ib:
Energies Max. 99 999 999
±(0.5%RDG+1DGT)
Min. 0.01
From 0.2Ib to Imax:
Variables Max. 9999
±(0.5%RDG)
Min. 0.01
Phase-neutral voltage In the range Un: ±(0.5% RDG)
Memory
Phase-phase voltage In the range Un: ±(1% RDG)
Energy 10^12 cycles. Energy value
Frequency Range: 45 to 65Hz.
is saved every time the less
Active power From 0.05 In to Imax,
significant digit increases.
within Un range, PF=1:
Programming parameters 10^12 cycles. When a
±(1% RDG)
parameter is modified, only
From 0.1 In to Imax, within
the relevant memory cell is
Un range, PF=0.5L or 0.8C:
overwritten
±(1% RDG)
LEDs Flashing red light pulses
Power factor ±[0.001+1%(1.000 - “PF RDG”)]
according to EN50470-3,
Reactive power From 0.05 In to Imax,
EN62052-11, 1000 imp./
within Un range, sinphì=1:
kWh (min. period: 90ms)
±(2% RDG)
Fix orange light: wrong
From 0.1 In to Imax, within
current direction (only with
Un range, sinphì=0.5L or
PFB option or with “B”
0.8C: ±(2% RDG)
measurement selection in
Energies
case of X option)
Active energy Class 1 according to
EN62053-21 Class B Current overloads
(Class B (kWh) according Continuous 65A, @ 50Hz
to EN50470-3) For 10ms 1950 A
Reactive energy Class 2 according to Short circuit withstand 4.5kA 10 ms according to
EN62053-23 IEC62052-31:2015
Start-up current: 20mA Voltage Overloads
Self-consumption is not Continuous 1.2 Un
measured. For 500ms 2 Un
Start-up voltage 90VLN Input impedance
Resolution Display 230VL-N 1.2Mohm
Current 0.1 A 120VL-N 1.2Mohm
Voltage 0.1 V 5(65) A < 1.5 VA per channel
Power 0.01 kW or kVar Wrong connection detection Installation guide to
Frequency 0.1 Hz indicate if connections are
PF 0.01 correctly carried out. Can
Energies (positive) 0.01 kWh or kvarh be disabled.
Energies (negative) 0.01 kWh or kvarh Phase sequence Indicates if the phase
Serial communication sequence is not the correct
Current 0.001 A one (L1-L2-L3)
Voltage 0.1 V Correct current direction Indicates if the current
Power 0.1 W or var direction is not the right one
Frequency 0.1Hz (only with PFB option or
PF 0.001 with type “B” measurement
Energies (positive) 0.001 kWh or kvarh selection in case of X
Energies (negative) 0.001 kWh or kvarh
Output specifications
RS485 serial port RS485 by screw Protocol M-bus according to
connection. EN13757-1
Function For communication Baud rate 0.3, 2.4, 9.6 kbaud
of measured data, Meters in the M-bus network 250
programming parameters Primary address Selectable
Protocol ModBus RTU (slave Secondary address Univocally defined in each
function) unit
Baud rate 9.6, 19.2, 38.4, 57.6, 115.2 Identification number range from 9000 0000 to 9999
kbaud, 9999
Data format even or no parity, Other Available functions: wild
Address 1 to 247 (default: 01) card, header, initialisation
Driver input capability 1/8 unit load. Maximum 247 SND_NKE, and req_udr
devices on the management. Management
same bus. of primary address
Data refresh time 1sec modification via M-bus and
Read command 50 words available in 1 reset of partial energy via
read command M-bus available.
Rx/Tx indication Rx segment on display VIF, VIFE, DIF and DIFE:
is shown when a valid see protocoll
Modbus command is sent Static output
to that specific meter Purpose For pulse output
Tx segment on display proportional to the active
is shown when a valid energy (kWh)
Modbus reply is sent back Pulse rate Selectable in multiple of
to the master 100
M-bus port M-bus by screw Max 500 or 1500 kWh
connection. according to pulse ON
Function For communication of duration
measured data
General specifications
Operating temperature Standard compliance
PF option (standard or with Safety EN62052-11
suffixes from 01 to 60) From –25 to +55°C/from Metrology EN62053-21, EN50470-3
–13 to +131°F Approvals CE, MID (PF option only)
PF option Connections
(with suffixes from 61 to 99) From –25 to +70°C/from Cable cross-section area Measuring inputs: max.
–13 to +158°F 16 mm2, min. 2.5 mm2
with/without metallic
X option From –25 to +65°C/from
cable ferrule; Max. screw
–13 to +149°F indoor,
tightening torque: 2.8 Nm
(R.H. from 0 to 90% non-
Other terminals 1.5 mm², Min./Max. screws
condensing @ 40°C)
tightening torque: 0.4 Nm
Storage temperature From –30 to +80°C/from
Housing
–22 to +176°F (R.H. < 90%
Dimensions (WxHxD) 54 x 90 x 63 mm
non-condensing @ 40°C)
Material Noryl, self-extinguishing:
Overvoltage category Cat. III UL 94 V-0
Utilisation category UC2 Sealing covers Included
Insulation (for 1 minute) 4000 VAC RMS between Mounting DIN-rail
measuring inputs and
Protection degree
digital/serial output (see
Front IP51
table) 4000 VAC RMS
Screw terminals IP20
Dielectric strength 4000 VAC RMS for 1
Weight Approx. 240 g (packing
minute
included)
EMC According to EN62052-11
Electrostatic discharges 15kV air discharge;
Immunity to irradiated
electromagnetic fields Test with current: 10V/m
from 80 to 2000MHz;
Electromagnetic fields Test without any current:
30V/m from 80 to
2000MHz;
Burst On current and voltage
measuring inputs circuit:
4kV
Immunity to conducted
disturbances 10V/m from 150KHz to
80MHz
Surge On current and voltage
measuring inputs circuit:
4kV;
Radio frequency According to CISPR 22
kWh, accuracy (RDG) depending on the current kvarh, accuracy (RDG) depending on the current
+1.5% +2.5%
+1% +2%
0% 0%
-1% -2%
-1.5% -2.5%
PF=1 0.25A(Imin) 0.5A(Itr) 5A(In) 65A(Imax) sinj =1 0.25A 0.5A 5A(Ib) 65A(Imax)
(0.05Iref) (0,1Iref) (0.05Ib) (0.1Ib)
PF=L0.5 0.5A(Itr) 5A(In) 65A(Imax) sinj=0.5 0.5A 1A 5A(Ib) 65A(Imax)
or C0.8 (0,1Iref) (0.1Ib) (0.25Ib)
Class 1 accuracy limits (Active energy) Class 2 accuracy limits (Reactive energy)
5(65)A Start-up current: 20mA 5(65)A Start-up current: 20mA
Display pages
X= available
Wiring diagrams
+
9 +
9
- 10 - 10
Rc Rc
4
1. Display
Backlit LCD display with touch key-pad.
2. LED
1 LED proportional to kWh reading
3. Serial number
3 2 Area reserved to serial number and MID-relevant data in
PF versions
Dimensions
54 43
91
45
63