Mechatronics UNIT-1
Mechatronics UNIT-1
Introduction
The word mechatronics was first used in Japan in the late 1960s, spread through Europe and
is now commonly used in all other parts of the world. In the 1980s, there was a veritable explosion
in microprocessor- based products. This is self-evident in the ever-increasing performance and
reduction of costs of electronic products. The microprocessor has been incorporated into every
aspect of traditional mechanical systems. The utility of the microcomputer and other similar
microprocessor-based devices have been employed in countless applications — for system
monitoring, data handling, data presentation and control. The modern mechanical engineer must,
therefore, be competent in the application of microprocessor-based systems. Mechatronics is a
rapidly developing inter-disciplinary field of engineering. The field of mechatronics deals with the
synergistic integration of mechanical engineering, electronic engineering, computer technology
and control engineering in the development of electromechanical products, through an integrated
design approach. Therefore, a mechatronics system requires a multi-disciplinary approach for the
design, development and implementation of its product and the entire mechatronics system is
treated concurrently in an integrated manner.
1. information systems;
2. mechanical systems;
3. electrical systems;
4. computer systems;
5. sensors and actuators;
6. real-time interfacing.
Figure 1.3 shows all the elements in a typical mechatronics system. The actuators and sensors
form a mechanical system. The actuators produce motion or cause some action whereas the sensors
detect the state of the system parameters, inputs and outputs. The input signal conditioning and
interfacing systems provide connections between the control circuits and input/output (I/O) devices.
The overall control of the system is carried out by digital controls. The graphical display of devices
provides visual feedback to the users.
System
A "System" is a group of physical components combined to perform a specific function. All
mechatronics devices consist of systems. A system can be considered as a box that has an input and
an output. We are mainly concerned with the relationship between the input and the output rather
than what is going on inside the box. For example, an electric generator may be thought of as a
system which has mechanical rotation as its input and electric power as its output (Figure 1.7).
Fig.1.7 System.
A measurement system can be considered as a system that is used to measure the required
parameter. The quantity being measured is given as the input and the value of that quantity is obtained
as the output. For example, a rotational speed measurement system, that is a digital tachometer, has
the rotation of shaft as its input and gives an output of a number on the LED display. Figure 1.8
shows such a system for measuring the rotational speed.
Measurement Systems
A fundamental part of many mechatronics systems is a measurement system used for making measure-
ments. This system comprises four basic parts as shown in Figure 1.10. The transducer or sensor
is a sensing device that is used to convert a physical input into an output, usually a voltage. The
signal processor performs functions such as filtering, amplification or other signal conditioning on
the output of the transducer. The growth of micromachining that has led to low-cost high-
performing sensors with built-in intelligence has enabled sensor level of signal processing and
the ability to communicate with other sensors and sub systems.
As an example of a measurement system, consider a filled thermal system used for process
temperature measurement as shown in Figure 1.1.3. The liquid- or gas-filled temperature bulb acts
as a primary sensing element and a variable conversion element. It senses the input quantity
(i.e., temperature) and converts it into a pressure built up within the bulb. This pressure is
transmitted through the capillary tube (which acts as a data transmission element) to a spiral
Bourdon-type pressure gauge. The gauge acts as a variable conversion element that converts
pressure into displacement. The displacement is manipulated by the linkage and gearing
arrangement to give a larger pointer deflection. This arrangement acts as a variable manipulation
element. Gearing elements act also as a data processing element by converting linear motion
into rotary motion. The pointer and scale indicate the temperature, thus serving as data
presentation elements.
Fig.1.13 Measurement System of a filled thermal system.
Control Systems
In a control system there is an interconnection between the constituent components.
These individual components may be electrical, mechanical, hydraulic, pneumatic, thermal
or chemical in nature. A well-designed control system will provide the best response for the
complete system to external, time-dependent disturbances operating on the system. The basic
functions of the control systems are:
1. to minimize the error between the actual and the desired output;
2. to minimize the time response to load changes in the system.
A simple example of a control system is a water-level control system in a tank (Figure 1.14).
In this pump is switched ON for an interval that would allow enough discharge of liquid into the
tank to fill it. Once the tank is filled to the required level, the pump will switch OFF.
The system has an input from the water-level sensor that notifies it what the liquid level is,
then compares this data with what the level should have been and provides the appropriate
response in order to obtain the required water level in the tank. This is an example of feedback
control in which the sensor signals are given feedback from the output in order to modify the
reaction of the pump to switch ON or OFF. Feedback control is exercised by the control
system, which compares the actual output of the system with what is required and adjusts the
output accordingly.
Modern washing machine design uses a microcontroller. All the control functionalities of the
system are built around this. Single-phase motors or brushless DC motors are used in the design
of washing machines. Controlling the motor is a very crucial part of the design. The pulse width
modulation (PWM) feature of the microcontroller controls the motor speed. PWM output is fed
to the driver circuit and then to the motor: To rotate the motor in two different directions,
"forward" and "reverse" direction control blocks are used. A motor speed sensor is interfaced to
a microcontroller. The microcontroller reads the speed of the motor and appropriately controls
the speed of the motor in different phases of washing using PWM output. Door sensor, pressure
sensor, keypad are also interfaced to the microcontroller
A potentiometer consists of a resistance element with a sliding contact that can be moved from
one end to the other. This sliding contact is called a wiper. The motion of the sliding contact may
be linear or angular. Figure 1.32(a) shows the linear potentiometer and Figure 1.32(b) shows the
rotary potentiometer. A linear wire-wound potentiometer consists of resistance elements with a
number of turns of wire wound around a non-conducting mandrel together with a sliding contact
that travels over the bare wires. The rotary potentiometer consists of a circular wire-wound track
over which a rotatable sliding contact can be rotated. The rotary potentiometer consists of a
circular wire-wound track over which a rotatable sliding contact can be rotated. The linear or
angular displacement of the wiper contact is directly converted into proportional output voltage.
The exciting voltage may be either AC or DC and the output voltage is proportional to the input
motion, provided that the measuring device has a resistance that is greater than the potentiometer
resistance. The wire-wound track may be single turn or helical turn.
V O R 23
=
V 1 R 13
Fig. 1.33 Circuit: a) for linear potentiometer and b) for rotary potentiometer
With a wire-wound track, the slider moves from one turn to other changing output
voltage in steps. The outputs proportional to the angle through which the slider has rotated. So
the angular displacement can be converted into a potential difference. The important effect to be
considered with a potentiometer is the effect of a load R L connected across the output as shown
in Figure 1.33(b). The VL is only directly proportional to Vo if the RL is infinite. For finite RL the
effect of load is to transform into a non-linear relationship. The R L is in parallel with fraction x of
the potentiometer resistance Rp. This combined resistance is given by (xR LRP)/(RL+ xRp). Thus,
the total resistance across the source voltage is
xR L RP
Total resistance = R P (1−x )+
R L + xR P
where RP is the potentiometer resistance; x is a fraction and RL is the load resistance. This circuit
acts as a potential divider, since the divider or wiper divides the resistance into two parts.
Therefore, the voltage across the load is
xR L RP
V L Cobined Resistance R L + xR P x
= = =
V1 Total Resistance xR L R P RP
R P ( 1−x )+ x (1−x )+ 1
R L + xR P R L
If the load is of infinite resistance then
VL = x V1
Thus the error introduced by the load having a finite resistance is
xV 1
RP 2
Error = x V1 - VL = x V1 - R P = V1 (x – x3)
x ( 1−x ) +1 RL
RL
Advantages of Resistance Potentiometers
1. They are simple and inexpensive.
2. They are useful for measurement of large amplitudes of displacement.
3. Their electrical efficiency is high.
4. They are simple in operation.
Resistance Strain Gauge
The ratio of change in length to the original length is called strain. Resistance strain gauge is a
transducer that exhibits the change in electrical resistance when it is stretched or strained. When
the strain gauge is subject to strain, the resistance "R" changes and the change in resistance ∆ R /
R is proportional to the strain s. They may be of the bonded or unbonded type, consisting of a
length of resistance wire formed into a zigzag pattern mounted onto a flexible backing sheet. If a
metal conductor is stretched or compressed; its resistance changes on account of the fact that the
resistance of the wire per unit length is inversely proportional to the cross-sectional area. The
resistance of metal sample is given by:
lo
Ro =ρ
Ao
where ρ , lo and Ao are density, length and cross-sectional area, respectively. When the sample is
stressed by the application of a force F, the material elongates by some amount ∆ l and the
change in resistance is given by
∆l
∆ R=2 R o
lo
V ∆ Rg
V o= ×
4 Rg
But
∆ Rg ∆l
=GF ×
Rg l
Therefore,
V ∆l ∆l
V o= GF × ∨V o=a constant ×
4 l l
The output voltage is proportional to mechanical strain for small changes of gauge resistance.
Here GF is the gauge factor.
In typical applications, the change in resistance is very small and hence it may be affected
with the temperature variations. Therefore, it is a common method to provide a "dummy" gauge
into the bridge circuit as shown in. Figure1.35. The dummy gauge is at all times subjected to the
same ambient temperature as the strained element, but it is attached to a separate unstrained
piece of the same material.
Strain gauges are used in two forms, wire and foil. The basic characteristics of each type are
the same in terms of resistance change for a given strain. The length of the strain gauge is very
long in order to give enough nominal resistance. Normally, strain gauges are bonded or
cemented directly onto the surface of the body, or the structure that is being examined (Figure
1.36). In metal wire strain gauges, a wire is stretched between two points in an insulating
medium such as air. The wires may be made of copper nickel, chrome nickel or nickel iron
alloys. They are about 0.003 mm in diameter and have a gauge factor of 2. The length of wire
is 25 mm or less. In a bonded fill strain gauge the foil is usually made up of constantan, and it
is etched in a grid pattern onto a thin plastic backing material, usually polyamide. The foil is
terminated at both ends with large metallic pads. The size of the entire gauge is very small and
has a length of 5-15 mm.
Fig. 1.36 a)Bonded flat grid b) bonded helical wound gauge c) bonded metal foil gauge
Bonded foil and metal wire strain gauges are rigidly attached to the strained members. Figure
1.37 illustrates the cases where the strain gauge is attached to flexible elements in the form of
cantilevers, rings and U shape. When the flexible element is bent due to force applied by a
contact point, the electrical resistance will change. The change in electrical resistance is the
measure of displacement
Fig. 1.41 a) Reflective type photo electric sensor b) Transmissive type photo electric
sensor
Hall Effect Sensors
When a beam of charged particles passes through a magnetic field, the beam is deflected from its
straight line path due to the forces acting on the particles. A current flowing in a conductor, such
as a beam, is deflected by a magnetic field. This effect is called Hall effect.
Fig. 1.42 Hall-effect sensor
The working principle of a Hall effect sensor is that if a strip of conducting material carries a
current in the presence of a transverse magnetic field as shown in Figure 1.42, the difference of
potential is produced between the opposite edges of the conductor. The magnitude of the voltage
depends upon the current and the magnetic field. The current is paised through leads 1 and 2 of
the strip and the output leads 3 and 4 are connected with a Hall strip. When a transverse
magnetic field passes through the strip, the voltage difference occurs in the output leads. The
Hall effect sensor has the advantage of being able to operate as a switch and it can operate upto
100 kHz.
Applications of Hall Effect Sensor
1.It is used as a magnetic switch for electric transducer.
2.It is used for the measurement of the position, displacement and proximity.
3.It is used for measurement of current.
4.It is used for measurement of power.
Optical Encoder
An encoder is a device that provides a digital output in response to a linear or angular
displacement. An optical encoder is a suitable transducer for the measurement of angular
position and has the added advantage of having a digital output. An optical encoder has four
main parts: a light source, a code disk, a light detector and a signal conditioner. Most rotary
encoders are composed of a glass or plastic code disk with a photographically deposited radial
pattern organized in tracks. A digital optical encoder is a device that converts motion into a
sequence of digital pulses. By counting or decoding these bits, the pulses can be converted into
relative or absolute position measurements. Optical encoders are in rotary or linear
configurations. The rotary encoders are of two forms: absolute encoder and incremental encoder.
Absolute Encoder
The absolute encoder is designed to produce a unique digital word corresponding to each
rotational position of the shaft that distinguishes "N" distinct positions of the shaft.
Fig. 1.43 Components of an optical encoder
Figure 1.43 shows the basic form of an absolute encoder. The rotating disk has four
concentric circular slots and four sensors to detect the light pulses. The slots are arranged in such
a way that the output is made in the binary code. The number of bits in the binary number will be
equal to the number of tracks.
The most common types of numerical encoding used in the absolute encoder are gray and
natural binary codes. To illustrate the action of an absolute encoder, gray code and natural binary
code disk track patterns for a simple 4 track (4-bit) encoder are shown in Figures 1.44 and 1.45,
respectively.
Incremental Encoder
An incremental encoder produces equally spaced pulses from one or more concentric tracks on
the code disk. Each track has its own light beam. Thus, an encoder with 3 tracks will have three
light sources and three light sensors.
Fig. 1.44 4 bit gray code absolute encoder disk track patterns
Fig. 1.45 4 bit natural binary absolute encoder disk track patterns a) Schematic and signals
b) actual disk
Fig. 1.50 Various methods used with photo electric sensors: a) Direct scan b) retro-
reflective scan c) diffuse scan d) convergent beam scan e) specular scan
Velocity Sensors
Velocity is the rate of change of displacement. It is measured in length per unit time (m/s).
Angular velocity is the rate of change of angular displacement. It is measured in terms of
revolutions per minute.
Velocity sensors or tachogenerators are devices that give an output proportional to angular
velocity. These sensors find wide application in motor speed control systems. The following are
the various velocity sensors.
Electromagnetic Transducers
The most commonly used transducer for measurement of linear velocities is an electromagnetic
transducer. These transducers use the voltage produced in a coil due to the change in flux
linkages resulting from a change in reluctance. The electromagnetic transducers are classified
into the following two categories.
1.Moving magnet type velocity transducer: In this, the sensing element is a rod that is
rigidly coupled to the device whose velocity is being measured. This rod is a permanent
magnet. This permanent magnet is surrounded by a coil. The motion of the magnet induces
a voltage in the coil and the amplitude of the voltage is directly proportional to the
velocity.
The voltage generated when a coil is placed in a magnetic field is given by
Vo = BANv
= Kv
where K = BAN is a constant; B is the flux density (Wb/m 2); A is the area of coil (m 2); N is
the number of turns of coil and v is the relative velocity of magnet with respect to coil. The
polarity of the output voltage determines the direction of motion.
2.Moving coil type velocity transducer: This is operated through the action of a coil moving
in a magnetic field. The voltage generated in the coil is proportional to the velocity of the
coil (Figure 1.52). This is a more satisfactory arrangement due to it forming a closed
magnetic circuit with a constant air gap. The device is contained in an anti-magnetic case
which reduces the effects of a stray magnetic field.
Advantages of DC Tachogenerator
1.Direction of rotation is directly indicated.
2.Conventional-type DC voltmeters are sufficient to use.
Motion Sensors
Stroboscope
The stroboscope consists of a source of variable frequency flashing light that can be controlled
by the operator. A distinctive mark is made on the shaft or on the disk attached to the shaft as
shown in Figure 1.57. The stroboscope is made to flash light directly on the mask. The flashing
frequency is adjusted till the mark appears stationary. The stroboscope dial may be directly
calibrated to the given speed.
The deflection of the spring when a force F is applied at the free end is given by the equation
3
8FD n
x= 4
Gd
where F is the applied force; d is the diameter of the spring wire; D is the mean coil diameter of
the spring; n is the number of coils of the spring and G is the modulus of rigidity of the spring
material. From this equation, it is clear that the deflection is a linear function of force and can be
directly used as a measure of force.
Proving Rings
Proving rings are steel rings used for the calibration of material-testing machines in situations
where, due to their bulkness, dead weight standards cannot be used. Proving ring is a circular ring
of rectangular section and may support tensile or compressive force across its diameter as shown
in Figure 1.60. Let δ be the change in radius in the direction of force (F); it is given by
( )
3
k π 4 Fd
δ= −
16 2 π EI
where d is the outer diameter of the ring; E is the modulus of elasticity of the ring material; I is the
second moment of inertia of the cross-section and k is the stiffness.
The deflection of the ring is measured using a precision micrometer. To get precise
measurements, one edge of the micrometer is mounted on a vibrating reed which is plugged to
obtain a vibratory motion. The micrometer contact is then moved forward until a noticeable
damping of the vibration is observed.
The maximum deflection is typically of the order of 1% of the outside diameter of the ring.
Proving rings are normally used for force measurement within the range of 2 kN to 2 MN
where R1, R2, R3 and R4 are the resistances of strain gauges 1, 2, 3 and 4, respectively; V 1 is the
input voltage and Vo is the output voltage.
Fig. 1.63 Load cells: a) Load cell arrangement in rectangular bar; b) Section X-X of
rectangular bar; c) bridge circuit
The output voltage of bridge using two strain gauges mounted at 90° to each other can be
expressed in terms of strain as follows:
εV1
V o =( 1+ ϑ ) ×GF ×
4
where ϑ is the Poisson's ratio; GF is the gauge or gain factor and ε is the strain.
Shear-type Load Cell It is a special method to measure the load in terms of loads and bending
moments. In this type of load cell, the free ends of the two cantilever beam are butted together.
The strain gauge is placed at 45° in each of the cantilever beam. The strain gauge "T" on the
left-hand side cantilever beam measures the tensile force but the compressive force is measured
by the strain gauge "C" attached on the right-hand side cantilever beam. These strain gauges
measure both tensile and compressive forces corresponding to the load applied at the junction
point of the cantilever beam. At the same time, the amount of both tensile and compressive
forces is equal. The resultant output is measured by a bridge network which linearly varies with
the applied load. This type of load cell is mainly used to measure shock loads (Figure 1.64).
This configuration is also best suited for a torque cell. The main advantage of this load cell is
its capability to withstand high loads, bending moments, impact loads and thermal gradient
error.
Shear load cell is more suitable for tank-bin weighing systems, portable scales, hopper scales
and motion weighing systems.
Electromagnetic Balance
An electromagnetic balance is shown in Figure 1.65. The main parts of the electromagnetic
balance are photoelectric transducer, an amplifier and a coil suspended in a magnetic field. The
coil carries a current while producing "an electromagnetic torque". The servo system is used
with the coil to balance the difference between the unknown force and the gravitational force
acting on a standard mass. The photoelectric transducer is used to check the balance of the
unknown force and the standard mass produces the electrical voltage in a resistor. It is taken as
output and the circuit connected to the resistor is used to measure the unknown force. The
output signal can be recorded or used for automatic control applications.
Fig. 1.66 Pressductor: a) Flux contour under no load b) flux contour under load and c)
transducer assembly
Applications
Platform weighing, mobile scales and batch-weighing systems.
Acceleration Sensors
Acceleration can be measured by using accelerometer. Accelerometers are widely used for
measurement of acceleration, velocity and displacement. They are also used to measure
vibrations and shocks.
Basic Principle of Accelerometer
This operation is based on Newton's second law of motion and Hooke's law of elasticity. The
basic structure is shown in Figure 1.67. According to Newton's second law, if mass "m" is
undergoing acceleration " a" , it will exert a force "F" on a mass. Mathematically,
Fa= ma
This force is opposed by the restraining effect of a spring. Let k be the stiffness of spring and δx
the displacement of mass from original position. Then, according to Hooke's law,
F s=kδx
In a steady state, when the acceleration of mass and accelerometer assembly are the same,
then we can write
Fa = F s
ma=kδx
kδx
a=
m
The above equation represents a second-order system. Without damping such systems undergo
non-decaying sustained oscillation. Therefore, it is necessary to provide damper in these system.
The damper will provide damping force Fd proportional to the velocity of mass. The damping
force is given by
Fd = cv
where c is the damping coefficient and v is the velocity of mass.
ω c
where r = and ξ = Damping ratio ¿
ωn 2m ω n
The steady-state amplitude Z of seismic mass with respect to the frame is the measure of
acceleration, when the natural frequency of the instrument is high compared to that of the
vibration to be measured. This implies
Z 2
=r if r <¿ 1
y
2
2 ω y
Z=r y= 2
ωn
A slip ring arrangement results in noise due to change in contact resistance. Also slip rings
and brushes wear out and hence need to be renewed. A non-contacting type of arrangement as
shown in Figure 1.77 is preferred. Here, the bridge supply and output signals are transmitted
between the rotating and stationary member through transformers. Through AC supply of the
bridge, an amplitude modulated AC voltage proportional to the torque is obtained as the output
of the bridge.
Fig. 1.77 Non-contacting type strain gauge torque transducer
where G is the shear modulus; θ is the angular twist; d is the diameter of shaft and L is the
length of the shaft. The various methods used to measure angular twist of torsion bar are
discussed next.
Optical Method
Figure 1.78 shows a typical torsion-bar system using an optical method for deflection
measurement. Owing to the transmission of torque, the two disks 1 and 2 are mounted at a
distance L on the shaft move relative to each other through an angle θ . The angle θ is recorded
by the observer.
Capacitive Method
A torsion-bar system using capacitive torque sensing is shown in Figure 1.79. A shaft is fitted
with a concentric sleeve of dielectric material. The sleeve is fixed to the shaft at one end, and
rests on a rubbing bearing at the other end. When torque is applied to the shaft it causes relative
motion between the surface of the shaft and the free end of the concentric tube. This motion is
used to vary the capacitance applied on two opposing patterns of conducting strips, one of
which is applied to the shaft and the other one to the tube.
The capacitive torque sensor is connected to an inductor coil (L1) wound around the shaft.
The resulting passive circuit thus has a resonance frequency which depends on the applied
torque. The passive resonant circuit rotates with the drive shaft, and is excited from an adjacent
stationary location by inductive coupling using a second inductor coil (L2) driven by an
oscillator as shown in Figure 1.80. Torque measurement can be done by measuring the
resonance frequency.
When the oscillator frequency is the same as that at which resonance occurs in the passive
circuit, an increased current is drawn. If the frequency at which occurs is measured, it can be
used to indicate the torque. The advantage of this arrangement is that no physical connection
between the rotating shaft and the frame is required.
Fig. 1.79 Capacitive method torsion bar: a) Cross section through shaft and sensor and b)
longitudinal section
Stroboscope Method
Figure 1.83 shows an arrangement of two flanges A and B placed at a distance on the shaft.
Flange A carries a scale while flange B carries a pointer. When a torque is applied on the shaft,
it causes angular displacement of pointer relative to the scale due to the angular twist. The
deflection of the shaft may be read off directly when the shaft is stationary. However, this is not
possible if the shaft is rotating. In such cases stroboscope is used. The flashing light of the
stroboscope is applied onto the scale and the flashing frequency is adjusted till a stationary
image is obtained. The scale reading can now be taken for measuring the angular twist. This
method is simple and inexpensive. However, the accuracy of measurement is poor.
Fig. 1.90 a) Measurement of pressure with bellows and LVDT and b) Pressure
measurement with bourdon tube and LVDT
Potentiometric Transducer
This is a type of pressure sensor where a potentiometer is attached to bellows or a diaphragm
(see Figure 1.91). The bellows acts as primary sensor. As pressure increases, bellows expand.
This moves the wiper upward and initiates an increase in the meter reading. Therefore, pressure
can be read from the readings of the meter.
Advantages
1. high range;
2. simplicity;
3. ruggedness.
Limitations
1.poor resolution;
2.large size;
3.poor frequency response.
Fig. 1.97 Simple U-tube manometer: a) For gauge pressure and b) for vacuum pressure
Equating these two pressures, we get
h+h1S1 = h2S2
h = h 2S 2 - h 1S 1
Case (B): For measuring vacuum pressure: Pressure above X-X in the left column=
h + h 1S 1 + h 2S 2
Pressure above X-X in the right column -= 0
Equating these two pressures, we get
h + h 1S 1 + h 2S 2 = 0
h = -( h1S1 + h2S2)
Differential U-tube Manometer
Case (A): When two pipes are at different levels: Figure 1.98 shows the arrangement of U-tube
manometer for the fore-mentioned case. Two pipes are containing liquids of different specific
gravities.
Let h be the difference of mercury level in the U-tube; h 1 the distance of the center of A
from the mercury level in the left limb; h 2 the distance of the center of B from the mercury
level in the right limb; S 1 the specific gravity of liquid in pipe A; S 2 the specific gravity of
liquid in pipe B; h A the pressure head at A; h B the pressure head at B. Taking datum line as
X-X
Pressure head in the left limb = h A+ (h1 + h) S1
Pressure head in the right limb = h B + h2 x S2 + h x S
Equating the above pressure heads, we get
hA+ (h1 + h) S1= hB + h2 x S2 + h x S
hA - hB = h2 x S2+ h x S (h1 + h)S1
= h2 X S2 +h x S – h1S1 — hS1
Difference of pressure heads at A and B
hA - hB =h(S - S1)+h2S2 - h1S1
Fig. 1.98 Differential U-tube manometer when pipes are at different levels
Case (B): When two pipes are at same level: The arrangement of U-tube differential
manometer connected between two pipes A and B are at same level and containing the liquid of
same specific gravity is illustrated in Figure 1.99.
Pressure head above X-X in left limb = h A +(h1 + h)S1
Pressure head above X-X in right limb = h B + h1S1+hxS
Equating the above two pressure, we get
hA +(h1 + h)S1 = hB + h1S1+hxS
hA - hB = h1S1+hxS - (h1 + h)S1
= h1S1+hxS - h1S1- hS1
Difference of pressure heads at A and B
hA - hB = h (S — S1)
Fig. 1.99 Differential U-tube manometer when pipes are at the same level
Orifice Meter
The orifice meter is the most common type of head flow measuring device for medium
and large pipe sizes. When the orifice plate is placed in pipe flow, the flow rate increases but
the pressure drop decreases. The point at which the velocity is maximum and , the pressure
is minimum is known as vena contracta. So, the flow rate is maximum at vena contracta. The
orifice plate, placed in the pipe flow is generally a thin metal plate which has a circular
opening. Depending on the hole (circular opening) placement, the orifice plates are configured
into three types such as concentric, eccentric and segmented (Figure 1.100). But concentric
types of orifice plates are mainly used to measure the flow rate.
Orifice meter is fitted in the pipe, the flow through which is to be measured (Figure 1.101).
Let a1 be the area at section 1-1; ao be the area of orifice; Cd be the discharge coefficient.
Then flow rate,
C . a .a √ 2 gh
Q= d 1 2 o 2
√a 1−a o
( )
2
v
F= ρ Cd A
2g
where v is the velocity; ρ is the fluid density; C d is the disk friction coefficient and A is the disk
area.
Q=
√)
Cd ( A r− A f )
2g (
v f ρf −ρ
)
√
Af ρ
1−
( A r− A f 2
Ar
where Ar is the area of the rotor; A f is the area of the float and v f the velocity of flow.
Magnetic flowmeter
Magnetic flowmeters cause no head loss and they can easily measure liquids with solids in
suspension. By their design, they produce an electrical signal ideal for plant submission. In a
magnetic flowmeter, the pipe is lined with a non-conducting material and at least two electrodes
are mounted with the non-conducting wall. Electromagnetic coils surround the flow path with a
uniform magnetic field. Figure 1.106 exhibits the principle of a magnetic flowmeter.
Faraday's law dictates that the voltage produced by a conducting fluid flowing through a
magnetic field is directly proportional to the velocity of the fluid.
The major disadvantage of a magnetic flowmeter is that it cannot be used for hydrocarbons
due to their low conductivities and is limited to measuring the volume flow rate of
electronically conductive fluids.
Fig. 1.112 Hot wire anemometers: a) Circuit for constant current type b) Circuit for
constant temperature type c) construction
Liquid-Level Sensors
Industrial processes often require the measurement of liquid or fluid in a tank or a container.
Measurement of liquid level can be made directly by following the liquid surface using floats or
indirectly by measuring some variables related to the liquid level. The direct methods include
sight glasses attached with the container and various floats attached with external indicators.
Indirect methods of measuring liquid level employ some means of measuring the static pressure at
some points in the liquid. Various indirect methods for measuring liquid level are explained next.
Float Level Sensor
In this method the level of liquid is measured by movement of a float. The movement of a float
due to a rise in the liquid level turns the lever about the pivot. Thus, the lever applies a
downward force on the bonded strain gauge load cell. The load cell converts the change in load
into proportional change of resistance. The Wheatstone bridge attached to the output of the load
cell converts the change of resistance into a measurable electrical signal. The output result is
related to the height of the liquid (Figure 1.113).
r=
6 ( α 2−α 1 ) ( T −T o ( 1+m ) )
2
where t is the combined thickness of the bonded strip in mm; α 1 is the lower coefficient of
expansion per °C; α 2 is the higher coefficient of expansion per °C; m is the ratio of thickness of
low to high expansion materials; n is the ratio of modulus of elasticity of low to high expansion
materials; T is the temperature in °C and T o is the initial bonding temperature in °C.
The bimetallic strip materials should have high coefficient of expansion, high ductility,
high modulus of elasticity and high electrical conductivity. These properties are very important
for selection of bimetallic strip.
In almost all industrial applications, the equation is inconvenient for measurement purpose
as it is nonlinear. The equation becomes linear by neglecting higher order terms; that is
R=R o ( 1+α 1 T ) will suffice for temperature from 0 oC to 150 oC.
The constant α 1 is called temperature coefficient of resistance. For copper the typical value
is 0.0043 and for platinum it is 0.0039.
The materials used for RTDs are nickel, iron, platinum, copper, lead, tungsten, mercury,
manganin, silver, etc. Platinum is one such metal where the resistance temperature relationship
is linear within 0.4% over the temperature range between - 200°C and 40°C. This can be
effectively used as an RTD and a typical construction is exhibited in Figure 1.118. Thin film
platinum elements are often made by depositing the metal on a suitable substrate wire-wound
elements involving a platinum wire held by a high temperature glass adhesive inside a ceramic
tube.
Applications
1. It is used for.varying temperatures.
2. It is used in time-delay circuits.
3. Thermistors are used for temperature compensation.
4. It is used to measure pressure and flow of liquids.
5. It is used to measure thermal conductivity.
6. It is used to measure gas composition.
Advantages
1.It has very high accuracy.
2.It can be manufactured for very small sizes.
3.It is used to measure very high temperature.
4.It has the ability to withstand mechanical and electrical stresses.
Limitations
1.In it self-heating may occur.
2.It has a highly non-linear behavior over its range of operation.
3.It is possible for the thermistor to have an increase of resistance when time lapses.
Thermocouples
The most common method of temperature measurement uses the thermocouples. It is based on the
Seebeck effect. The thermocouple temperature measurement is based on the creation of an emf.
Basic Principle
The basic principle of thermocouple is: when two dissimilar metals are joined together an emf
will exist between the two points A and B, which is primarily a function of the junction
temperature. This principle is known as the Seebeck effect. Figure 1.124 illustrates Seebeck
effect, where two metals A and B are used to close the loop connecting junctions at temperature
T1 and T2. The emf produced is found to be almost linear-in temperature and very repetitive for
constant materials.
The emf produced by the thermocouple loop is approximately given by
emf = α (T2 – T1)
where α is the constant in V/K; T1 and T2 are junction temperatures.
Construction
The thermocouple consists of one hot junction and one cold junction. The hot junction will be
introduced into the place where temperature is measured. The other cold junction is maintained:at
a constant reference temperature. Also one voltage-measuring instrument is connected to the free
end of the thermocouple.
Operation
In a thermocouple, the known temperature is called the reference temperature. The temperature
which is to be measured is introduced in the thermocouple's hot junction. A common arrangement
for establishing the reference temperature is an ice bath. The reference temperature is held
constant at 0 °C.
Fig. 1.134 Field view of the pyrometer: a) Equal brightness; b) more brightness of filament
and c) more darkness of filament
Advantages
1.It is relatively inexpensive.
2.It does not depend on the surface properties of the material.
3.It is a quite accurate method for the measurement of radiant energy from a surface.
4.If surface emissive properties are accurately known, the temperature measurement will be
very accurate.
Limitations
1.It is not suitable for measurement of low temperature.
2.Since adjustment of standard lamp temperature is done manually. Therefore, there would be
some error in the measurement.
Thermodiodes and Thermotransistors
Thermodiodes
Thermodiode is a widely used temperature-measuring instrument. When the temperature of doped
semiconductors changes, the mobility of their charge carrier's changes and this affects the rate at
which electrons and holes can diffuse across a PN junction.
The difference in voltage and current through the junction is a function of the temperature.
Current, I, can be found out using
I =I o ( e eV / KT −1 )
where T is the temperature on the Kelvin scale; e is the charge on electron; I o is a constant and K
is a constant.
From the above equation the voltage "V" is proportional to the temperature on Kelvin scale
and the potential difference measurement across a diode at constant current is used to measure the
temperature.
Thermotransistor
In a thermotransistor the voltage across the junction between the base and the emitter depends on
the temperature. A common method is the use of two transistors with different collector currents
to find the difference in the base—emitter voltages between them. This difference is the measure
of temperature.
The thermotransistors can be combined with circuit components on a single chip to give a
temperature sensor as shown in Figure 1.135.