PRODUCT DATA SHEET

1 to 6 Ton Vertical Wall Mount Air Conditioners


Models AVPA12-20-24-30-36-42-48-60-72 (Single Stage Compressor) Models HVEA24-30-36-42-49-60 (Single Stage Compressor)
Models AVHA12-20-24-30-36-42-48-60 (Single Stage Compressor) Models HVESA36-42-49-60 (2-Stage Compressor)

General Description
Used primarily to cool electronic and communication equipment shelters, Marvair®
ComPac® I and ComPac® II air conditioners are problem solvers for a wide range
of conditions and applications. Due to the high internal heat load, these shelters
require cooling even when outside temperatures drop below 60°F (15°C).
The ComPac I and ComPac II air conditioners have the necessary controls and
components for operation during these (less than 60°F [15°C]) temperatures. All
models use the non-ozone depleting R-410A refrigerant.
The primary difference between the ComPac I and the ComPac II units is that
the ComPac® II air conditioner has a factory installed economizer. When ambient AVPA36ACA-100C
conditions are cool and dry, the economizer uses outside air to cool the shelter.
The economizer provides temperature control, energy cost savings, and increased
reliability by decreasing the operating hours of the compressor and the condenser
fan. To insure proper operation and optimum performance, all economizers are
non-removable, factory installed and tested. In addition, factory and field installed
accessories can be used to meet specific requirements. Features and Benefits
Built-In Energy Savings
➤ Standard Efficiency Models • Optional Factory Installed Economizer
AVPA: Marvair’s most popular model with an Energy Efficiency Ratio (EER) of 9.0 • Four Model Lines to Meet Any Budget and
to 10.0. The ComPac AVPA is available in cooling capacities of 1, 1.5, 2, 2.5, 3, 3.5, Efficiency Requirements
4, 5 and 6 tons (12,000 BTUH to 72,000 BTUH). • Available EER of up to 11.75
• Available 2-Stage Compressor on HVESA Models
➤ High Efficiency Models
HVEA: Marvair’s most efficient wall mount air conditioners. Electronically commu- R-410A Refrigerant
tated indoor fan motors combined with highly efficient scroll compressors result • Efficient Heat Release
• Non-Ozone Depleting Refrigerant
in Energy Efficiency Ratios (EER’s) of up to 11.75.
• Synthetic Lubricant
AVHA: ComPac models with an EER of 10.0. The AVPA72 is also rated 10 EER. • Reduced Compressor Wear

➤ 2-Stage Compressor Models High Efficiency and Reliability


HVESA: ComPac models 36-42-49-60 have a 2-stage compressor with first stage • High Efficiency Compressor and Lanced Coil Fins
• High/Low Pressure Switches with Lockout & Short
cooling approximately 65% of the total cooling capacity. The 2-stage compressor
Cycle Protection
provides lower start-up amps which can be critical when operating with a
generator. The two stage compressor can also reduce energy costs and is able to Ease of Installation and Service
more precisely match the cooling capacity of the air conditioner with the heat • Side Access Panels for Power Connections
load in the shelter. Both non-economizer and economizer-equipped ComPac units are • Built-In Mounting Flanges and Internal Disconnect
• Standard Access Valves and Filters, Status LEDs
available with 2 stage compressors. 1 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20
Safety Listed and Energy Certified
All ComPac air conditioners are built to UL standard 1995, 4th edition and CAN/CSA C22.2, No. 236-11. For energy
efficiency and performance, the units are tested and rated in accordance to the ANSI/ARI (Air-Conditioning and
Refrigeration Institute) Standard 390- 2003 (Single Package Vertical Units). All units meet or exceed the efficiency
requirements of ANSI/ASHRAE/IESNA 90.1.2010. Marvair ComPac air conditioners are commercial units and are not
intended for use in residential applications.

Standard Features
➤ Designed for Operation in Low ➤ Remote Alarm Capability ➤ Rugged Construction
Ambient Conditions • Dry contacts can be used for • Copper tube, aluminum fin
• Low ambient control cycles remote alarm or notification evaporator & condenser coils.
condenser fan to maintain proper upon air conditioner lockout. • Field or factory installed heaters
refrigerant pressures. Allows ➤ Ease of Service on discharge side of evaporator
operation in mechanical cooling • Service access valves are coil (optional)
(compressor) of our standard standard. • Baked on neutral beige finish
air conditioners down to 20°F
• Standard 2” (50 mm) pleated over galvanneal steel for
(-7°C). With the Extreme Duty
filter with a MERV rating of 8 maximum cabinet life. (Other
option, the units will operate
changeable from outside. finishes are available.)
down to 0°F (-18°C). Note: low
temperature operation is affected • All major components are readily ➤ Ease of Installation
by ambient conditions, e.g. wind accessible. • Sloped top with flashing
and humidity. • Front Control Panel allows easy eliminates need of rainhood.
• Three minute by-pass of the access and complies with NEC • Built-in mounting flanges
low pressure switch for start-up clearance codes on redundant facilitate installation and
of compressor when outdoor side-by-side systems. minimize chance of water leaks.
temperatures are below 55°F • LEDs indicate operational status • Supply and return openings
(13°C). and fault conditions. exactly match previous models.
• Optional economizer. • Foil backed insulation on the • Factory installed disconnect on
➤ High Efficiency indoor air path. all units.
• High efficiency compressor. • A minimum position • Single Point Power Entry
• Lanced fins standard on all potentiometer that can be complies with latest edition of
evaporator and condenser coils. adjusted to prevent the U.L. Standard 1995.
➤ Built-in Reliability economizer damper from closing • Side access panels on
completely. This control ensures economizer models for easy
• High pressure switch and low
that whenever the evaporator
pressure switch with lockout access to electrical connections.
fan is operating, fresh air is being
protects refrigerant circuit.
introduced into the building.
• Adjustable .03 to ten minute
delay on make for short cycle
protection.

A Marvair® First – Factory Installed Economizer


Marvair’s ComPac® II air conditioner has been the industry standard since its introduction in 1986. Tens of thousands of
ComPac II air conditioners are in operation from the metropolitan areas of North America to the deserts of the Mid-East
to the Siberian tundra. Here’s how the economizer works:
On a signal from the wall mounted indoor thermostat that cooling is required, either mechanical cooling with the
compressor or free cooling with the economizer is provided. A factory installed enthalpy controller determines whether
the outside air is sufficiently cool and dry to be used for cooling. If suitable, the compressor is locked out and the
economizer damper opens to bring in outside air. Integral pressure relief allows the interior air to exit the shelter,
permitting outside air to enter the shelter. The temperature at which the economizer opens is adjustable from 63°F
(17°C) at 50% Relative Humidity to 73°F (23°C) at 50% Relative Humidity.
After the enthalpy control has activated and outside air is being brought into the building, the mixed air sensor measures
the temperature of the air entering the indoor blower and then modulates the economizer damper to mix the right
proportion of cool outside air with warm indoor air to maintain 50-63°F (10 - 17°C) air being delivered to the building.
This prevents shocking the electronic components with cold outside air. The compressor is not permitted to operate
when the economizer is functioning.
If the outside air becomes too hot or humid, the economizer damper closes completely, or to a field selectable minimum
open position, and mechanical cooling is activated.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 2
In all ComPac II air conditioners, the supply air flow in the economizer mode is the same or greater than the rated air
flow. (The rated air flow is the AHRI certified air flow when the unit is in mechanical cooling.) The “full flow” economizer
reduces electrical costs by maximizing the use of outside air for cooling.

100% Mechanical Cooling 100% Economizer Cooling

Savings with an Economizer


The following table shows the annual electrical cost of cooling a 10 ft. x 20 ft. x 9 ft. (3m x 6m x 2.7m) shelter in twelve
cities in the US. Costs are shown for an air conditioner without an economizer (ComPac I units), for an air conditioner
with an economizer (ComPac II units) and the savings. The savings do not include any demand charges. The savings are
based on the electrical usage of a five ton air conditioner and an electric rate of $.10 per kilowatt-hour, the approximate
average commercial rate in the US.
Hours of Operation Atlanta, GA Boston, MA Chicago, IL Dallas, TX Denver, CO Houston, TX
Annual Compressor & Condenser Motor Run Time without Economizer (Hrs.) 6,531 6,348 6,361 6,628 6,472 6,655
Annual Compressor & Condenser Motor Run Time with Economizer (Hrs.) 3,841 2,153 2,424 3,798 750 4,970
Run Time Savings with the Economizer (Hrs.) 2,690 4,195 3,937 2,830 5,722 1,685
Annual Costs Saving ($) of 9.0 EER unit with an Economizer (ComPac II)
Annual Operating Cost 9.0 EER Unit without Economizer ($) $4,100.00 $3,985.00 $4,792.00 $4,161.00 $3,657.00 $4,178.00
Annual Operating Cost 9.0 EER with Economizer $2,685.00 $1,784.00 $2,315.00 $2,671.00 $940.00 $3,291.00
Annual Savings using 9.0 EER Unit with Economizer $1,415.00 $2,201.00 $2,477.00 $1,490.00 $2,717.00 $887.00

Hours of Operation Los Angeles, CA Miami, FL Phoenix, AZ Pittsburgh, PA Seattle, WA St. Louis, MO
Annual Compressor & Condenser Motor Run Time without Economizer (Hrs.) 6,467 6,779 6,765 6,386 6,465 6,472
Annual Compressor & Condenser Motor Run Time with Economizer (Hrs.) 3,862 6,391 3,106 1,929 1,654 2,716
Run Time Savings with the Economizer (Hrs.) 2,605 388 3,659 4,457 4,811 3,756
Annual Costs Saving ($) of 9.0 EER unit with an Economizer (ComPac II)
Annual Operating Cost 9.0 EER Unit without Economizer ($) $4,060.00 $4,255.00 $4,247.00 $4,009.00 $3,653.00 $4,063.00
Annual Operating Cost 9.0 EER with Economizer $2,686.00 $4,051.00 $2,315.00 $1,667.00 $1,368.00 $2,090.00
Annual Savings using 9.0 EER Unit with Economizer $1,374.00 $204.00 $1,932.00 $2,342.00 $2,285.00 $1,973.00
Shelter Metrics: Air Conditioner Metrics:
•10’ x 20’ x 9’ building •ComPac II Economizer setting: 57ºF (dry bulb or enthalpy sensor)
•Internal heat gain (electronics load): 12,000 watts. •A/C unit capacity: 60,000 BTUH (5 tons) with 1-stage compressor
•Building surface area (excluding floor area): 740 ft² •Nominal EER (unit efficiency): 9.0 (models AVPA)
•R-Value of walls and ceiling: R-12 •Cost of power: $.10 per KWH
•Internal shelter temperature (Thermostat set point): 75ºF

3 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Controllers and Thermostats
➤ Controllers
CommStat 6 2/4 Telecom HVAC Controller........................................................................................................................................P/N 70705
CommStat 6 4/8 Telecom HVAC Controller............................................................................................................................. P/N S/12087-04
CommStat 6 6/12 Telecom HVAC Controller.......................................................................................................................... P/N S/12087-06
The CommStat 6 is an HVAC controller, is available in three configurations, and is designed
specifically for controlling up to six redundant air conditioners with two stage compressors
in a telecommunications shelter or enclosure. The CommStat 6 2/4 controls up to two
single or 2-stage air conditioners (4 Stages max.), the CommStat 6 4/8 controls up to four
single or 2-stage air conditioners (8 Stages max.) and the CommStat 6 6/12 controls up to
six single or 2-stage air conditioners (12 Stages max.)
In addition to the control of the air conditioners, the CommStat 6 has multiple configurable
outputs for remote alarms or notification. The CommStat 6 is factory programmed with standard industry set points,
but can be configured on site. Settings are retained indefinitely in the event of a power loss.
CommStat Touch HVAC Controller NEW!........................................................................................................................................P/N K/10439
The CommStat Touch telecom controller with a touch screen interface is designed to allow
remote control and monitoring of Marvair air conditioners and heat pumps with single or
2-stage compressors in a shelter or enclosure and is certified by ETL for HVAC UL60950-1 and
FCC47CFR compliance. In addition to the control of HVAC equipment, CommStat Touch includes
the Marvair RemoteLink IPv4/IPv6 communication module to provide status information, alarm
notifications, set point adjustment, and remote HVAC configuration. See the CommStat Touch
PDS for more details.
CommStat 4 Telecom HVAC Controller...............................................................................................................................................P/N S/7846
The CommStat 4 HVAC controller is designed specifically for controlling two redundant air
conditioners, heat pumps or air conditioners with 2-stage compressors. The CommStat 4 has seven
outputs for remote alarms or notification. Status LED’s indicate HEAT, COOL, POWER and the LEAD
unit. When a fault is detected, an alarm LED flashes and the LCD screen displays the fault.
The CommStat can be daisy chained with a second CommStat 4 controllers for controlling up to four
air conditioners in one shelter. See the CommStat 4 PDS for more details.
CommStat3™ Lead/Lag Microprocessor Controller.................................................................................................................. P/N S/04581
Solid state controller designed to operate a fully or partially redundant air conditioning system. Ensures
equal wear on both air conditioners while allowing the lag unit to assist upon demand. Lead/ lag
changeover is factory set at 7 days, but is field programmable in 1/2 day increments from 1/2 to 7 days.
The CommStat 3™ Controller has LED’s to indicate status & function, digital display of temperature, a
comfort override button for energy savings, five alarm relays, a built in temperature sensor and is fully
programmable. See the CommStat 3 PDS for more details.

➤ Thermostats & Thermostat Guards


Note: All air conditioners with 2-stage compressors (models HVESA) require a 2-stage cooling thermostat.
Thermostat ....................................................................................................................................................................................................P/N 50123
Digital thermostat. 1-stage heat, 1-stage cooling. 7 day programmable. Fan switch: Auto & On. Auto-change over.
Keypad lockout. Non-volatile program memory.
Thermostat ....................................................................................................................................................................................................P/N 50107
Digital thermostat. 2-stage heat, 2-stage cooling. 7 day programmable. Fan switch: Auto & On. Auto-change over.
Status LED’s. Backlit display. Programmable fan. Non-volatile program memory.
Thermostat Guard..........................................................................................................................................................................................P/N 50092
Thermostat guard for use with the 50123 and 50107 thermostats.
Thermostat.......................................................................................................................................................................................................P/N 50218
Digital, non-programmable thermostat. 1-stage cooling and 1-stage heat. Auto-changeover.
Digital Humidistat.........................................................................................................................................................................................P/N 50254
To be used with units with hot gas or electric reheat. Programmable dehumidistat and ventilation controller.
Permanent memory retention of set points.Humidity sensor can be field calibrated. High & low dehumidification set
points. Outdoor temperature and humidity sensor included. °F or °C selectable.
Thermostat.......................................................................................................................................................................................................P/N 50252
Non-programmable digital thermostat with backlit display. 2 stage heat and 2-stage cooling. Auto changeover.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 4
Operation of 2-Stage Compressor Air Conditioners with a CommStat Touch,
CommStat 4™ or CommStat 6 Lead/Lag Thermostat Controller
Marvair’s HVESA air conditioners have 2-stage compressors. These units can provide substantial energy savings and
better control of temperature and humidity by matching the cooling requirement with the performance of the air
conditioner. First stage is typically 65% of the total (2-stage) capacity of the air conditioner. When operated from power
supplied by a generator, starting the air conditioner in the first stage means lower start-up amps.
• CommStat Touch or CommStat™ 4 Controller: When two, 2-stage air conditioners are controlled by a CommStat 4 lead/
lag controller in a redundant application, one of the air conditioners is the lead unit and the second is the lag unit.
On a call for cooling, the lead unit starts operation in the first stage (low capacity). If the temperature in the building
continues to rise above the set point temperature, the first stage (low capacity) of the lag unit will be initiated. When
the temperature in the building drops to the set point, the air conditioners will turn off. On a subsequent call for
cooling the process will repeat.
If the set point temperature is not reached with the first stage capacity operation of both air conditioners, the lead
air conditioner will commence operation in second stage (full capacity). If the temperature in the building continues
to rise past the setpoint, the lag unit will switch to second stage cooling operation. At that time, both air conditioners
are operating in maximum capacity.
• CommStat™ 6 Controller: When two, 2-stage air conditioners are controlled by a CommStat 6 lead/lag controller
in a redundant application, one of the air conditioners is the lead unit and the second is the lag unit. On a call for
cooling, the lead unit starts operation in the first stage (LOW capacity). If the temperature in the building continues
to rise above the set point temperature, the second stage (FULL capacity) of the LEAD unit will be initiated. When the
temperature in the building drops to the set point, the unit will turn off. On a subsequent call for cooling the process
will repeat.
If the set point temperature is not reached with second stage capacity operation of the LEAD air conditioner, the LAG
air conditioner will commence operation in first stage (LOW capacity). If the temperature in the building continues to
rise past the setpoint, the lag unit will switch to second stage cooling operation. At that time, both air conditioners
are operating in maximum capacity
When the temperature in the building is satisfied with either controller, both units will turn off.
If the units have economizers (ComPac II air conditioners), the enthalpy sensor determines whether to use outside air or
use mechanical cooling. When the economizer is used, the compressors do not operate.

Marvair’s AVPA12 One Ton Air Conditioner


Ideal Replacement for Old Window Air Conditioners or New Construction
The electronic/communication shelter requires cooling virtually year-round because of the heat load generated by the
internal electronic equipment (i.e., switching and transmission gear). Residential window room air conditioners are not
designed to operate when outside air temperatures are moderate to cold, i.e., below 65°F (18°C). Typical problems are
freezing of the coil, diminished capacity and compressor damage which all contribute to high maintenance and short
operating life.
The Marvair® One Ton ComPac® I and ComPac® II air conditioners are designed for the electronic/ communication shelter
to provide a commercial grade air conditioner for years of operation.
The Marvair One Ton is built to operate continuously and efficiently Combination Supply & Return Grille

in a variety of outside conditions. For existing shelters with window Wall Sleeve Thru
Wall Opening

air conditioners, upgrading to the commercial grade Marvair air


conditioners is made easy by the design of the One Ton ComPac
II unit with the factory installed economizer. The back panel is
designed for either a 19” x 19” (483 mm x 483 mm) or 28” x 19” (711 Built-In Sloped
Top Rain Hood
mm x 483 mm) opening, standard opening sizes for many window
units. The unit is shipped from the factory for mounting on a 19” x
19” (483 mm x 483 mm) opening, but can be easily changed at site
to fit in a 28” x 19” (711 mm x 483 mm) opening. With the built-in
mounting flanges, the air conditioner mounts quickly and simply C
II

to the exterior of the building. The single piece supply and return
M
PA
CO

grille attaches easily to the wall sleeve to complete the installation.


The ComPac I (non-economizer) unit has separate supply and return
grilles. (See the Accessories section for the part numbers of the
grilles and wall sleeves). Factory installed electric heat is available in Built-In Mounting
Flanges

the Marvair One Ton Air Conditioner thus eliminating baseboard heat
and a second power source.

5 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Accessories
➤ Supply Grilles
For AVPA20/24...............................................................................................................................................................................................P/N 80674
20” x 8” (508 mm x 203 mm)
For AVPA/AVHA30,36 and HVEA24..........................................................................................................................................................P/N 80675
28” x 8” (711 mm x 203 mm)
For AVPA/AVHA42,48,60, AVPA72 and HVEA30, 36, 42, 49, 60.....................................................................................................P/N 80676
30” x 10” (762 mm x 254 mm)
➤ Return Grilles
For AVPA20/24...............................................................................................................................................................................................P/N 80677
20” x 12” (508 mm x 305 mm)
For AVPA/AVHA30,36 and HVEA24..........................................................................................................................................................P/N 80678
28” x 14” (711 mm x 356 mm)
For AVPA/AVHA42,48,60, AVPA72 and HVEA30, 36, 42, 49, 60.....................................................................................................P/N 80679
30” x 16” (762 mm x 406 mm)
➤ Return Filter Grilles
Used when filter must be changed from the interior. Not recommended for ComPac II air conditioners.
Note: Filter used in Return Filter Grille is 1” (25 mm) thick.
For AVPA20/24...............................................................................................................................................................................................P/N 80671
20” x 12” (508 mm x 305 mm)
For AVPA/AVHA30,36 and HVEA24..........................................................................................................................................................P/N 80672
28” x 14” (711 mm x 356 mm)
For AVPA/AVHA42,48,60, AVPA72 and HVEA30, 36, 42, 49, 60.....................................................................................................P/N 80673
30” x 16” (762 mm x 406 mm)
➤ AVPA12 Grilles and Wall Sleeves
For AVPA12 ComPac (non-economizer)..................................................................................................................................................P/N 80682
Supply Grille 17” x 5” ( 432 mm x 127 mm)
Return Air Grilles For AVPA12 (non-economizer unit).......................................................................................................................P/N 92352
17” x 10” (432 mm x 25)
For AVPA12 ComPac (non-economizer) unit Return Air Filter Grille.............................................................................................P/N 80683
17” x 10” (432 mm x 25)
➤ For AVPA12 ComPac II with Factory Installed Economizer
Combination Supply and Return Air Grille and Wall Sleeve for 19” x 19” Opening
Wall Sleeve for 19” x 19” (483 mm x 483 mm) opening (standard)........................................................................................P/N S/09392
Combination Supply and Return Air Grille for 19” x 19” (483 mm x 483 mm) opening (standard)...................................P/N 92379
Note: Grille is 17” x 17” (432 mm x 432 mm)
Combination Supply and Return Air Grille and Wall Sleeve for 28” x 19” Opening
Wall Sleeve for 28” x 19” (711 mm x 483 mm) opening............................................................................................................ P/N S/01784
Combination Supply and Return Air Grille for 28” x 19” (711 mm x 483 mm) opening....................................................... P/N 80681
Note: Grille is 26” x 17” (660 mm x 432 mm)

Options
The ComPac® I and ComPac® II air conditioners were designed and are built to stringent requirements of the
communications/electronic shelter. Applications occur that have special requirements. Numerous options are available
for the ComPac I and ComPac II air conditioners that meet these special needs.
➤ Hard Start Kit
Used on single phase equipment to give the compressor higher starting torque under low voltage conditions. (Field
installed only) (Note: Not recommended for use on scroll compressors.)
➤ Dehumidification
ComPac® I and ComPac® II A/C – Allows the electric heat to operate simultaneously with cooling. See
Dehumidification Application Bulletin for details. Note: The electrical characteristics and requirements of air
conditioners with the dehumidification option are different from standard air conditioners. Refer to the appropriate
Summary Rating Charts for the electrical characteristics of units with Electric Reheat. Available on all units except the
AVPA12. Units with reheat require a thermostat and a dehumidistat for proper operation.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 6
➤ Protective Coating Packages
Typically, only the ComPac I is used in corrosive environments, but the ComPac II air conditioner is also available
with corrosion protection. Two corrosion protection packages are offered - one for the condenser section (Coastal
Environmental Package) and the other for the entire unit (Coat-All Package).
The Coastal Environmental Package includes:
• Corrosion resistant fasteners
• Sealed or partially sealed condenser fan motor
• Protective coating applied to all exposed internal copper and metal in the condenser section
• Protective coating on the condenser coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment)
technology.
The Coat all Package includes all of the above, plus:
• Protective coating on the evaporator coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment)
technology
• Protective coating on exterior and interior components and sheet metal. (Note: the internal sheet metal which is
insulated, bottom outside panel, and the internal control box are not coated)
Note: The AVPA12 is available with the protective coatings and corrosion resistant fasteners, but does not have a
sealed condenser fan motor.
➤ Protective Coil Coatings
The Condenser Coil or the Evaporator Coil or Both can be coated. Coating the Evaporator Coil in not common. For
harsh conditions, e.g., power plants, paper mills or sites where the unit will be exposed to salt water, the coils should
be protected by a protective coating.
Note: Cooling capacity may be reduced by up to 5% on units with coated coils.
➤ External Low Noise Blower (ELNB)
ComPac® I and ComPac® II A/C – A field installed kit that consists of a condenser air hood, centrifugal blowers,
controls and a compressor jacket to reduce the sound level by up to 6 dbA of Marvair ComPac air conditioners.
Available for models AVPA30-60. See External Low Noise Blower Product Data Sheet for details.
➤ ComPac® II Air Conditioner Transition Curb
ComPac II A/C only – A sheet metal curb that enables AVPA42/48/60 ComPac II air conditioner to replace an
AVPA30/36 ComPac II unit. Curb transitions supply and return openings of the 3-1/2, 4 and 5 ton units to the smaller
openings.
➤ Hot Gas By-Pass (Non-Economizer Models)
ComPac® I A/C Only – Used in specialty applications; i.e., Magnetic Resonance Imaging (MRI) buildings, to prevent
magnetic voltage disturbance caused by compressor cycling. Hot gas by-pass option packages are available to
allow operation to 20°F (-7°C). Please refer to Hot Gas By-pass Application Bulletin for details. Not available on the
AVPA12, 20 & 24.
➤ High Filtration
Selected units are built with larger blowers/motors for use with higher efficiency filters with MERV ratings of 11, 13
and 14 when tested to ASHRAE 52.2. Units with economizers have a prefilter on the outside air. Not available on the
AVPA12. Contact your Marvair representative for specific models.
➤ Color
ComPac® air conditioners are available in five different cabinet colors -the standard Marvair® beige, white,
gray, brown and dark bronze. The standard cabinet’s sides, top and front panels are constructed of 20
gauge painted steel. As an option, these panels can be built of 16 gauge steel in beige & gray or .050
stucco aluminum. When the 16 gauge painted steel or the aluminum is used, only the side, top and front
panels are 16 gauge or aluminum. Contact your Marvair representative for color chips. The cabinet can
also be constructed of type 316 stainless steel. Two stainless steel cabinet constructions are available-
the complete cabinet, including most internal sheet metal or only the exterior sheet metal. Custom colors
are also available; contact Marvair for details.
Custom colors available
➤ Extended Warranty
A first-year labor (Silver), and a two-year labor (Gold) are available. See www.marvair.com for optional warranty details.
➤ Dirty Filter Indicator
A factory installed option that measures the difference in pressure across the internal filter and
illuminates a LED when the pressure exceeds the desired difference. Not available on the AVPA12.

7 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


➤ Phase Monitor
Continuously measures the voltage of each of the three phases. The monitor separately senses low and high voltage,
voltage unbalance including phase loss and phase reversal. A red LED glows to indicate a fault. When all voltages are
acceptable, a green LED glows. Automatically resets when voltages and phases are within operating tolerances.
Note: Not required on 1ø units.
➤ Thermal Expansion Valve
Available on all ComPac air conditioners. Improves performance in hot ambient temperatures.
➤ Sealed Condenser Fan Motors
Recommended on units to be installed in corrosive sites, e.g., near the ocean and in deserts with blowing sand.
Available on all units except the AVPA12.
➤ Compressor Sound Jacket
To reduce sound of compressor. Available on all units except the AVPA12
➤ Extreme Duty Package (Not Available on AVPA12)
Allows Marvair® air conditioners to operate in extremely cold and hot
ambient conditions. The Extreme Duty Kit is always factory installed and
is available on all air conditioners. ComPac I units without an economizer
will operate from 0°F to 130°F (-18°C to 54°C). ComPac II units with an
economizer will operate from -40°F to 130°F (-40°C to 54°C).
The Extreme Duty Package includes a suction line accumulator, thermal
expansion valve (TXV), crankcase heater, hard start kit, an auto reset high
pressure switch and an outdoor thermostat and fan cycle switch. The fan
cycle control is standard on all ComPac air conditioners and operates
based upon the liquid line pressure. The outside thermostat opens
whenever the outside temperature is below 50°F (10°C) and closes when
the outside temperature is 50°F (10°C) or higher. When the temperature
is below 50°F (10°C), the fan cycle switch is in the circuit; when
temperatures are 50°F (10°C) or higher, the fan cycle switch is not in the
circuit. The outdoor thermostat is used with a TXV to prevent excessive
cycling or “hunting” of the TXV.
➤ Lockable Disconnect Access Cover Plate
The access plate to the service disconnect switch can be equipped with a lockable cover.
➤ Desert Duty Package (Not available on the AVPA12)
Our standard air conditioners will operate in outside ambient temperatures up to 120°F (48.9°C) The Desert Duty
package is a factory installed package of components and cabinet modifications to allow operation in ambient
temperatures up 130°F (54°C). Standard features of the Desert Duty package include a thermal expansion valve and
a sealed condenser fan motor. Cabinet modifications include a slotted panel in the base pan that improves condenser
air flow and also provides access to the compressor and condenser fan motor. To prevent sand and dust infiltration,
the electrical control box is sealed. A closed loop design on non-economizer ComPac units insures that no outside
air is introduced into the shelter. Note: the ComPac II unit with the economizer may be ordered with the Desert Duty
Package. If the ComPac II air conditioner is required with the Desert Duty Package, sand intrusion into the shelter
should be considered.
➤ Washable Filter
Spun aluminum construction allows cleaning of filters with water.
➤ Hot Gas Reheat (HGR)
A Hot Gas Reheat coil and controls allow the indoor humidity of the controlled environment to be maintained at or
below a certain humidity set point. These units do not have the ability to add humidity to the room. Dehumidification
is achieved by operating mechanical cooling in conjunction with a hot gas reheat coil.
➤ Right & Left Side Compressor Location
The air conditioners can be built with the compressor on the opposite side to facilitate service access when two units
are installed side by side. In the AVPA20-24-30-36 & AVHA30/36, the standard location for the compressor is on the
right hand side. In the AVPA12 and the AVPA42-48-60 & AVHA42-48-60, the standard location for the compressor is
on the left hand side. In the 72, the compressor is accessed from the front of the unit and an opposing configuration
is not required.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 8


➤ Marvair Coil Cop® Theft Deterrent System
The Marvair Coil Cop® is a factory installed, multi-layered theft deterrent system designed for use in
Marvair wall mounted air conditioners and heat pumps. It provides visual and audio warnings and remote
notification in the event of an attempted theft or vandalism of the unit. It is especially useful for air
conditioners located in remote or unsupervised locations, e.g., many cell sites, and can eliminate bulky and
expensive cages. For a complete description of the components and operation of the Coil Cop system, please
see the Coil Cop brochure (available for download at www.marvair.com).
Two variations of the Coil Cop theft deterrent system are available:
• Coil Cop Variation T1 is the complete Coil Cop Package. Includes stainless steel channels to secure both
the condenser and evaporator coils, warning labels, a speaker, tamper resistant fasteners, loss of charge
switch, tri-axis accelerometer and operator panel with status lights.
• Coil Cop Variation T2 includes stainless steel channels to secure the condenser coil, warning labels, a
speaker, tamper resistant fasteners, loss of charge switch, tri-axis accelerometer and operator panel with
status lights. Variation T2 does not include stainless steel channel on the evaporator coil.

Remote Access Data Points


Through the Ethernet connection, the network operations • Dew point - Current
center can monitor and change various data points in the • Inside Temperature - Average Last Hour
HVAC system and the shelter.
• Outside Temperature - Average Last Hour
Data Points which can be monitored and changed:
• First Stage Cooling Set Point Temperature • Outside Humidity - Average Last Hour
• Second Stage Cooling Set Point Differential • Dew point - Average Last Hour
Temperature • Unit 1 & Unit 2 Mechanical Cooling Time - Last Hour
• First Stage Heating Set Point Temperature • Unit 1 & Unit 2 Mechanical Cooling Requests - Last
• Second Stage Heating Set Point Differential Hour
Temperature • Unit 1 & Unit 2 Free Air Cooling Time - Last Hour
Data points which can only be monitored: • Unit 1 & Unit 2 Free Air Cooling Requests - Last
• Inside Temperature - Current Hour
• Outside Temperature - Current • Unit 1 & Unit 2 Heating Time - Last Hour
• Outside Humidity - Current • Unit 1 & Unit 2 Heating Requests - Last Hour

Dry Contacts Alarm Outputs


A dry contact is provided for each HVAC unit to indicate HVAC unit failure to the shelter alarm block. Unit failure
is defined as 1) a high pressure lockout or 2) a low pressure lockout or 3) a loss of landline power. This dry
contact is a normally open contact.

9 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Back Panel Adapters for AVPA60 & AVHA60 Air Conditioners
These back panel adapters are factory installed on the non-economizer AVPA60 & AVHA60 ComPac air conditioners and
to match the supply and return air openings on Marvair 2 and 3 ton air conditioners. This allows the AVPA60 & AVHA60
to be quickly and easily installed. No cutting or sawing of the shelter is required. The back panel, K/04317 has supply and
return openings that match the openings of AVP24 & AVPA24 wall mounted air conditioners. The back panel, K/04315,
has supply and return openings that match the openings of Marvair’s AVP36 & AVPA36 air conditioners. In addition to
matching the openings of Marvair units, the back panels will also match the openings of other brands.

When the K/04317 back panel adapter is used, a return filter grille, p/n 80671, must be used. When the K/04315 back
panel adapter is used, a return filter grille, p/n 80672, must be used.

Control Box
The internal control board in the ComPac® air conditioners simplifies wiring, consolidates several of the
electrical functions onto one device and improves the reliability of the air conditioner. In addition, the control board has
LED’s that indicate operational status and fault conditions.
➤ LED Indicator Lights
COLOR TYPE STATUS DESCRIPTION
Green Power Constant On 24 VAC power has been applied
Constant On Normal operation
1 Blink High pressure switch has opened twice
Red Status
2 Blinks Low pressure switch has opened twice
3 Blinks Freeze stat (optional) - indoor coil temperature is below 35°F (1°C)

➤ Modes of Operation
Normal Start-up: On a call for cooling, and the with the high pressure switch closed, the cooling system (compressor,
indoor blower motor and outdoor fan motor) will be energized. (Note: See the Delay on Make feature). The cooling
system will remain energized during the three minute low pressure switch bypass cycle. If the low pressure is closed,
the cooling system will continue to operate after the three-minute bypass. If the low pressure switch is open after the
three-minute bypass, the cooling system will be de-energized.
Lockout Mode: If either the high or low pressure switch opens twice on the same call for cooling, the control board
enters into and indicates the lockout mode. In the lockout mode, the compressor is turned off, the alarm output is
energized and the status LED’s will blink to indicate which fault has occurred. If there is a call for air flow, the indoor
blower will remain energized. When the lockout condition has cleared, the unit will reset if the demand of the ther-
mostat is removed or when power is reset. The lockout circuit is factory wired for normally open contacts. The user
can select either normally closed or normally open remote alarm dry contacts.
Delay on Make: On initial power up or on resumption of power, the air conditioner will wait .03 to 10 minutes from a
call for cooling before allowing the contactor to energize.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 10


Model Identification
••• S A •• AC • ••• • • A5 ••• •••

Refrigerant System Type Electric Heat – kW Special Option Code Brand Designation
A = R410A Air Conditioner 000 = No Heat 080 = 8 kW R = Electric Reheat Unused = Marvair
Nominal Cooling 022 = 2.2 kW 090 = 9 kW U = Scroll Compressor ComPac
12 = 11,000 BTUH 036 = 3.6 kW 100 = 10 kW X = Hot Gas Bypass EUB = Eubank Cabinet Color
2-Stage
040 = 4 kW 120 = 12 kW O = Opposite side
WalPac 100 = Beige
20 = 20,000 BTUH
Compressor 200 = Gray
24 = 24,000 BTUH 050 = 5 kW 150 = 15 kW compressor
30 = 30,000 BTUH 060 = 6 kW E = Extreme Duty 400 = White
36 = 36,000 BTUH D = Desert Duty 500 = Stainless Steel
42 = 42,000 BTUH G = Hot Gas Reheat (Exterior Only)
AVP 48/49 = 48,000 BTUH Power Supply
SS-500 = Stainless Steel
AVH 60 = 60,000 BTUH A = 208/230V,1ø,60Hz
700 = Aluminum
HVE 72 = 72,000 BTUH C = 208/230V,3ø,60Hz
Stucco
D = 460V,3ø,60Hz (3 wire) Configuration
Z = 575V,3ø,60Hz A5 = Built in
N = Non-Economizer
compliance with
C = Economizer-Equipped
UL 1995, 4th edition

ComPac I & ComPac II Ambient Temperature Operating Ranges


Basic Model Special Option AVPA AVHA/HVEA/HVESA
Standard Unit (N) 20ºF - 120ºF (-7ºC - 48.9ºC) 20ºF - 120ºF (-7ºC - 48.9ºC)
ComPac I
Desert Duty (ND) 20ºF - 130ºF (-7ºC - 54ºC) 20ºF - 130ºF (-7ºC - 54ºC)
(Non-Economizer)
Extreme Duty Kit (NE) 0ºF - 130ºF (-18ºC - 54ºC) 0ºF - 130ºF (-18ºC - 54ºC)

Standard Unit (C) -40ºF - 120ºF (-40ºC - 48.9ºC) -40ºF - 120ºF (-29ºC - 48.9ºC)
ComPac II
Desert Duty (CD) -40ºF - 130ºF (-40ºF - 54ºC) -40ºF - 130ºF (-29ºC - 54ºC)
(Economizer-Equipped)
Extreme Duty Kit (CE) -40ºF - 130ºF (-40ºF - 54ºC) -40ºF - 130ºF (-29ºC - 54ºC)

EER Comparison by Model


Nominal Cooling Capacity (BTUH) Basic Model EER Nominal Cooling Capacity (BTUH) Basic Model EER
AVPA12 9.00 AVPA42 9.25
12,000
AVHA12 10.00 AVHA42 10.00
42,000
AVPA20 9.00 HVEA42 10.50
20,000
AVHA20 10.00 HVESA42 10.50
AVPA24 9.25 AVPA48 9.50
24,000 AVHA24 10.00 AVHA48 10.00
48,000
HVEA24 10.75 HVEA49 11.50
AVPA30 9.25 HVESA49 11.50
30,000 AVHA30 10.00 AVPA60 9.25
HVEA30 11.75 AVHA60 10.00
60,000
AVPA36 9.25 HVEA60 10.50
AVHA36 10.00 HVESA60 11.00
36,000
HVEA36 11.25 72,000 AVPA72 10.00
HVESA36 11.25
Note: HVESA models have 2-stage compressors.

11 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


ComPac®AVPA Standard Efficiency Air Conditioners
Certified Efficiency and Capacity Ratings at
ANSI/AHRI Standard 390 - AVPA/AVHA Air Conditioners
AVPA12 AVPA20 AVPA24 AVPA30 AVPA36 AVPA42 AVPA48 AVPA60 AVPA72
Model Number
ACA ACA ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ

Cooling BTUH1 10,800 19,600 24,000 29,000 35,000 42,000 46,000 54,500 62,000 70,000
EER2 9.00 9.00 9.25 9.25 9.25 9.25 9.50 9.25 10.00 10.00
Rated Air Flow (CFM3) 400 755 840 1,000 1,100 1,575 1,725 1,850 1,925 1,925

AVHA12 AVHA20 AVHA24 AVHA30 AVHA36 AVHA42 AVHA48 AVHA60


Model Number
ACA ACA ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ

Cooling BTUH1 10,800 19,600 24,000 29,000 33,000 42,000 46,000 54,000
EER2 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00
Rated Air Flow (CFM3) 400 755 840 1,000 1,100 1,575 1,725 1,850
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air. 2EER=Energy Efficiency Ratio 3CFM=Cubic Feet per Minute
1

Ratings are with no outside air. Performance will be affected by altitude.


Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect perfor-
mance and air flow.

Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
AVPA/AVHA Air Conditioners
AVPA12 AVPA20 AVPA24 AVPA30 AVPA36 AVPA42 AVPA48 AVPA60 AVPA72
Model Number
ACA ACA ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ

Total Capacity 10,800 19,600 24,000 29,000 35,000 42,000 46,000 54,500 62,000 70,000
Sensible Heat Ratio 0.74 0.76 0.75 0.75 0.69 0.76 0.76 0.73 0.71 0.67
Sensible Capacity 8,000 14,800 18,000 21,740 24,155 31,900 34,940 39,800 43,815 46,800
Rated Air Flow (CFM1) 400 755 840 1,000 1,100 1,575 1,725 1,850 1,925 1,925

AVHA12 AVHA20 AVHA24 AVHA30 AVHA36 AVHA42 AVHA48 AVHA60


Model Number
ACA ACA ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ

Total Capacity 10,800 19,600 24,000 29,000 33,000 42,000 46,000 54,000
Sensible Heat Ratio 0.74 0.76 0.75 0.75 0.74 0.74 0.76 0.72
Sensible Capacity 8,000 14,800 18,000 21,700 24,500 31,000 35,000 39,000
Rated Air Flow (CFM1) 400 755 840 1,000 1,100 1,575 1,725 1,850
1
CFM=Cubic Feet per Minute. Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.

Cooling Performance (BTUH) at Various Outdoor Temperatures -


AVPA/AVHA Air Conditioners
Outdoor Temperature
Model Number
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC 100ºF / 38ºC 105ºF / 40.5ºC 110ºF / 43.3ºC 115ºF / 46ºC 120ºF / 48.9ºC 125ºF / 51.7ºC 130ºF / 54.4ºC

AVPA12AC 12,525 12,095 11,660 11,230 10,800 10,365 9,9935 9,500 9,285 8,640 8,205 7,775
AVPA20AC 22,735 21,950 21,165 20,380 19,600 18,815 18,030 17,245 16,855 15,680 14,895 14,110
AVPA24AC 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640 19,200 18,240 17,280
AVPA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 23,200 22,040 20,880
AVPA36AC 40,600 39,200 37,800 36,400 35,000 33,600 32,200 30,800 30,100 28,000 26,600 25,200
AVPA42AC 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120 33,600 31,920 30,240
AVPA48AC 53,360 51,520 49,680 47,840 46,000 44,160 42,320 40,480 39,560 36,800 34,960 33,120
AVPA60AC 63,220 61,040 58,860 56,680 54,500 52,320 50,140 47,960 46,870 43,600 41,420 39,240
AVPA72ACA 71,920 69,440 66,960 64,480 62,000 59,520 57,040 54,560 53,320 49,600 47,120 44,640
AVPA72ACC, ACD, ACZ 81,200 78,400 75,600 72,800 70,000 67,200 64,400 61,600 60,200 56,000 53,200 50,400

AVHA12AC 12,525 12,095 11,660 11,230 10,800 10,365 9,9935 9,500 9,285 8,640 8,205 7,775
AVHA20AC 22,735 21,950 21,165 20,380 19,600 18,815 18,030 17,245 16,855 15,680 14,895 14,110
AVHA24AC 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640 19,200 18,240 17,280
AVHA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 23,200 22,040 20,880
AVHA36AC 38,280 36,960 35,640 34,320 33,000 31,680 30,360 29,040 28,380 26,400 25,080 23,760
AVHA42AC 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120 33,600 31,920 30,240
AVHA48AC 53,360 51,520 49,680 47,840 46,000 44,160 42,320 40,480 39,560 36,800 34,960 33,120
AVHA60AC 63,220 61,040 58,860 56,680 54,500 52,320 50,140 47,960 46,870 43,600 41,420 39,240
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Note: Operation of units above 120°F (48.9°C) requires the Desert Duty package.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 12


Electrical Characteristics - Compressor, Fan & Blower Motors -
AVPA/AVHA Air Conditioner
OUTDOOR FAN & OUTDOOR INDOOR
COMPRESSOR
BASIC INDOOR BLOWER MOTORS FAN MOTOR BLOWER MOTOR
MODEL VOLTS / HZ
TYPE RLA1 LRA2 VOLTS / HZ / PH RPM3 FLA4 HP5 RPM3 FLA4 HP5
/ PH
AVPA/AVHA12ACA ROTARY 208/230-60-1 4.7 25.0 208/230-60-1 1630 0.65 1/6 1650 0.85 1/5

AVPA/AVHA20ACA 208/230-60-1 8.3 43.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5

AVPA/AVHA24ACA 208/230-60-1 10.6 54.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5

AVPA30ACA 208/230-60-1 13.1 74.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA36ACA RECIPROCATING 208/230-60-1 14.7 84.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA42ACA 208/230-60-1 15.7 84.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA48ACA 208/230-60-1 18.6 102.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA60ACA 208/230-60-1 23.0 130.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4

AVPA/AVHA24ACA 208/230-60-1 12.8 64.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5

AVPA/AVHA30ACA 208/230-60-1 14.1 77.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA/AVHA36ACA 208/230-60-1 17.9 112.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA/AVHA42ACA SCROLL 208/230-60-1 19.8 109.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA/AVHA48ACA 208/230-60-1 21.8 117.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA/AVHA60ACA 208/230-60-1 26.2 134.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4

AVPA72ACA 208/230-60-1 30.1 158.0 208/230-60-1 825 2.9 1/2 1075 5.2 3/4

AVPA/AVHA24ACC 208/230-60-3 8.3 61.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5

AVPA/AVHA30ACC 208/230-60-3 9.0 71.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA/AVHA36ACC 208/230-60-3 13.2 88.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA/AVHA42ACC SCROLL 208/230-60-3 13.6 83.1 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA/AVHA48ACC 208/230-60-3 13.7 83.1 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA/AVHA60ACC 208/230-60-3 15.6 111.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4

AVPA72ACC 208/230-60-3 22.4 149.0 208/230-60-1 825 2.9 1/2 1075 5.2 3/4

AVPA/AVHA24ACD 460-60-3 5.1 28.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5

AVPA/AVHA30ACD 460-60-3 5.6 38.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA/AVHA36ACD 460-60-3 6.0 44.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA/AVHA42ACD SCROLL 460-60-3 6.1 41.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA/AVHA48ACD 460-60-3 6.2 41.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA/AVHA60ACD 460-60-3 7.7 52.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4

AVPA72ACD 460-60-3 10.6 75.0 208/230-60-1 825 2.9 1/2 1075 5.2 3/4

AVPA24ACZ 575-60-3 3.3 23.7 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5

AVPA30ACZ 575-60-3 3.8 36.5 208/230-60-1 1075 1.5 1/5 1075 1.5 1/4

AVPA36ACZ 575-60-3 4.2 30.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4

AVPA42ACZ SCROLL 575-60-3 4.2 33.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/2

AVPA48ACZ 575-60-3 4.8 33.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2

AVPA60ACZ 575-60-3 5.8 38.9 208/230-60-1 825 2.8 1/3 1075 3.1 3/4

AVPA72ACZ 575-60-3 7.7 54.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4
1
RLA = Rated Load Amps 2
LRA = Locked Rotor Amps 3
RPM = Revolutions per Minute 4
FLA = Full Load Amps 5
HP = Horsepower
The 460 volt (ACD) units will have a step down transformer for the 230 volt motors.

13 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Summary Electrical Ratings (Wire and Circuit Breaker Sizing) -
AVPA/AVHA Air Conditioners with Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”),
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT 000 = None 022 = 2.2 kw036 = 3.6 kw 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw

BASIC VOLTAGE SPPE SPPE


3
SPPE3
SPPE 3
SPPE 3
SPPE SPPE
3
SPPE 3
SPPE 3
SPPE SPPE
3 3 3 3

MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2

AVPA/AVHA12ACA 208/230-1-60 7.4 15 12.4 15 19.7 20 26.9 30

AVPA/AVHA20ACA 208/230-1-60 13.4 20 22.4 25 27.5 30 32.8 35 43.1 45 53.6 60

AVPA/AVHA24ACA 208/230-1-60 19.0 30 22.4 30 27.5 30 32.8 35 43.1 45 53.6 60

AVPA/AVHA30ACA 208/230-1-60 21.9 35 23.4 35 28.5 35 33.8 35 44.1 45 54.6 60 65.0 70 80.6 90

AVPA/AVHA36ACA 208/230-1-60 26.7 40 26.7 40 28.5 40 33.8 40 44.1 45 54.6 60 65.0 70 80.6 90

AVPA/AVHA42ACA 208/230-1-60 30.7 50 30.7 50 55.2 60 65.6 70 81.2 90

AVPA/AVHA48ACA 208/230-1-60 33.2 50 33.2 50 55.2 60 65.6 70 81.2 90

AVPA/AVHA60ACA 208/230-1-60 40.8 60 40.8 60 57.3 60 67.7 70 83.3 90

AVPA72ACA 208/230-1-60 45.6 60 45.6 60 57.3 60 67.7 70 83.3 90

AVPA/AVHA24ACC 208/230-3-60 13.4 20 19.5 20 28.6 30 37.6 40

AVPA/AVHA30ACC 208/230-3-60 15.6 20 20.5 25 29.6 30 38.6 40 47.6 50

AVPA/AVHA36ACC 208/230-3-60 20.8 30 20.8 30 29.6 30 38.6 40 47.6 50

AVPA/AVHA42ACC 208/230-3-60 22.9 35 22.9 35 30.2 35 39.1 40 48.1 50

AVPA/AVHA48ACC 208/230-3-60 23.0 35 23.0 35 30.2 35 39.1 40 48.1 50

AVPA/AVHA60ACC 208/230-3-60 27.5 40 27.5 40 32.3 40 41.3 45 50.2 60

AVPA72ACC 208/230-3-60 36.1 50 36.1 50 36.1 50 41.3 50 50.2 60

AVPA/AVHA24ACD 460-3-60 7.9 15 9.8 15 14.3 15 18.8 20 23.3 25

AVPA/AVHA30ACD 460-3-60 9.2 15 10.3 15 14.8 15 19.3 20 23.8 25

AVPA/AVHA36ACD 460-3-60 9.7 15 10.3 15 14.8 15 19.3 20 23.8 25

AVPA/AVHA42ACD 460-3-60 10.6 15 10.9 15 15.1 20 19.6 20 24.1 25

AVPA/AVHA48ACD 460-3-60 10.7 15 10.9 15 15.1 20 19.6 20 24.1 25

AVPA/AVHA60ACD 460-3-60 13.6 20 13.6 20 16.1 20 20.6 25 25.1 30

AVPA72ACD 460-3-60 17.3 25 17.3 25 17.3 25 20.6 25 25.1 30

AVPA24ACZ 575-3-60 5.3 15 7.9 15 11.5 15 15.0 16

AVPA30ACZ 575-3-60 6.5 15 8.3 15 11.9 15 15.4 20 19.0 20

AVPA36ACZ 575-3-60 7.0 15 8.3 15 11.9 15 15.4 20 19.0 20

AVPA42ACZ 575-3-60 7.6 15 8.5 15 12.1 15 16.6 20 19.2 20

AVPA48ACZ 575-3-60 8.4 15 8.5 15 12.1 15 16.6 20 19.2 20

AVPA60ACZ 575-3-60 10.5 15 10.5 15 13.0 15 16.5 20 20.1 25

AVPA72ACZ 575-3-60 12.8 20 12.8 20 13.0 20 16.5 20 20.1 25


1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2
MFS = Maximum Fuse or HACR Breaker Size 3
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 14


Summary Electrical Ratings (Wire and Circuit Breaker Sizing) -
AVPA/AVHA Air Conditioners with Elec. Reheat (“R”) and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”),
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT 000 = None 022 = 2.2 kw 036 = 3.6 kw 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw

BASIC VOLTAGE SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3
MODEL PHASE / HZ MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS
2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA1 MFS2

AVPA/AVHA12ACA 208/230-1-60 7.4 15 18.9 20 26.2 30 33.4 35

AVPA/AVHA20ACA 208/230-1-60 13.4 20 34.3 35 39.4 40 44.7 45 65.5 70

AVPA/AVHA24ACA 208/230-1-60 19.0 30 39.9 40 45 45 50.3 60 71.1 80

AVPA/AVHA30ACA 208/230-1-60 21.9 35 42.8 45 47.9 50 53.2 60 74 80 84.8 90 100 100

AVPA/AVHA36ACA 208/230-1-60 26.7 40 47.6 50 52.7 60 58 60 78.8 80 89.2 90 104.8 110

AVPA/AVHA42ACA 208/230-1-60 30.7 50 56.7 60 82.8 90 93.2 100 108.8 110

AVPA/AVHA48ACA 208/230-1-60 33.2 50 59.2 60 85.3 90 95.7 100 111.3 120

AVPA/AVHA60ACA 208/230-1-60 40.8 60 66.8 70 92.9 100 103.3 110 118.9 120

AVPA72ACA 208/230-1-60 45.6 60 71.6 80 97.7 100 108.1 110 123.7 130

AVPA/AVHA24ACC 208/230-3-60 13.4 20 31.4 35 40.5 45 49.5 50 58.5 60

AVPA/AVHA30ACC 208/230-3-60 15.6 20 33.6 35 42.7 45 51.7 60 60.7 70

AVPA/AVHA36ACC 208/230-3-60 20.8 30 38.8 40 47.9 50 56.9 60 65.9 70

AVPA/AVHA42ACC 208/230-3-60 22.9 35 40.9 45 50.0 50 59.0 60 68.0 70

AVPA/AVHA48ACC 208/230-3-60 23.0 35 41.0 45 50.1 60 59.1 60 68.1 70

AVPA/AVHA60ACC 208/230-3-60 27.5 40 45.5 50 54.6 60 63.6 70 72.6 80

AVPA72ACC 208/230-3-60 36.1 50 54.1 60 63.2 70 72.2 80 81.2 90

AVPA/AVHA24ACD 460-3-60 7.9 15 16.9 20 21.4 25 25.9 30 30.4 35

AVPA/AVHA30ACD 460-3-60 9.2 15 18.2 20 22.7 25 27.2 30 31.7 35

AVPA/AVHA36ACD 460-3-60 9.7 15 18.7 20 23.2 25 27.7 30 32.2 35

AVPA/AVHA42ACD 460-3-60 10.6 15 19.6 20 24.1 25 28.6 30 33.1 35

AVPA/AVHA48ACD 460-3-60 10.7 15 19.7 20 24.2 25 28.7 30 33.2 35

AVPA/AVHA60ACD 460-3-60 13.6 20 22.6 25 27.1 30 31.6 35 36.1 40

AVPA72ACD 460-3-60 17.3 25 26.3 30 30.8 35 35.3 40 39.8 40

AVPA24ACZ 575-3-60 5.3 15 12.6 15 16.2 20 19.7 20

AVPA30ACZ 575-3-60 6.5 15 13.7 15 17.3 20 20.8 25 24.5 25

AVPA36ACZ 575-3-60 7.0 15 14.2 15 17.8 20 21.3 25 25.0 25

AVPA42ACZ 575-3-60 7.6 15 14.9 16 18.5 20 22.0 25 25.6 30

AVPA48ACZ 575-3-60 8.4 15 15.6 20 19.2 20 22.7 25 26.4 30

AVPA60ACZ 575-3-60 10.5 15 17.7 20 21.3 25 24.8 25 28.5 30

AVPA72ACZ 575-3-60 12.8 20 20.1 25 23.7 25 27.2 30 30.8 35


1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2
2MFS = Maximum Fuse or HACR Breaker Size 3
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.

15 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Unit Load Amps - AVPA/AVHA Air Conditioners with Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS) TOTAL MAXIMUM HEATING AMPS
CUR-
BASIC VOLTAGE (1) ALL HEATING ELEMENTS ARE ON A SEPARATE INCLUDES AMPS FROM MOTOR(S) THAT ARE
RENT
MODEL PHASE CIRCUIT LOCATED ON AN ELECTRICAL CIRCUIT THAT
AMPS
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS DOES NOT HAVE HEATERS
NUMBER / HZ
AC1 IBM2 2.2 kW 3.6 kW 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 2.2 kW 3.6 kW 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW

AVPA/AVHA12ACA 208/230-1-60 6.1 0.85 9.2 15.0 20.8 10.1 15.0 21.7

AVPA/AVHA20ACA 208/230-1-60 11.3 1.5 16.7 20.8 25.0 33.3 41.7 18.2 22.3 26.5 34.8 43.2

AVPA/AVHA24ACA 208/230-1-60 15.8 1.5 16.7 20.8 25.0 33.3 41.7 18.2 22.3 26.5 34.8 43.2

AVPA/AVHA30ACA 208/230-1-60 18.4 2.5 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.2 23.3 27.5 35.8 44.2 52.5 65.0

AVPA/AVHA36ACA 208/230-1-60 22.2 2.5 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.2 23.3 27.5 35.8 44.2 52.5 65.0

AVPA/AVHA42ACA 208/230-1-60 25.7 3.1 20.8 41.7 50.0 62.5 23.9 44.8 53.1 65.6

AVPA/AVHA48ACA 208/230-1-60 27.7 3.1 20.8 41.7 50.0 62.5 23.9 44.8 53.1 65.6

AVPA/AVHA60ACA 208/230-1-60 34.2 5.2 20.8 41.7 50.0 62.5 26.0 46.9 55.2 67.7

AVPA72ACA 208/230-1-60 38.2 5.2 20.8 41.7 50.0 62.5 26.0 46.9 55.2 67.7

AVPA/AVHA24ACC 208/230-3-60 11.2 1.5 14.4 21.7 28.9 36.1 15.9 23.2 30.4 37.6

AVPA/AVHA30ACC 208/230-3-60 13.3 2.5 14.4 21.7 28.9 36.1 16.9 24.2 31.4 38.6

AVPA/AVHA36ACC 208/230-3-60 17.5 2.5 14.4 21.7 28.9 36.1 16.9 24.2 31.4 38.6

AVPA/AVHA42ACC 208/230-3-60 19.5 3.1 14.4 21.7 28.9 36.1 17.5 24.8 32.0 39.2

AVPA/AVHA48ACC 208/230-3-60 19.6 3.1 14.4 21.7 28.9 36.1 17.5 24.8 32.0 39.2

AVPA/AVHA60ACC 208/230-3-60 23.6 5.2 14.4 21.7 28.9 36.1 19.6 26.9 34.1 41.3

AVPA72ACC 208/230-3-60 30.5 5.2 14.4 21.7 28.9 36.1 19.6 26.9 34.1 41.3

AVPA/AVHA24ACD 460-3-60 6.6 0.8 7.2 10.8 14.4 18.0 8.0 11.6 15.2 18.8

AVPA/AVHA30ACD 460-3-60 7.8 1.3 7.2 10.8 14.4 18.0 8.5 12.1 15.7 19.3

AVPA/AVHA36ACD 460-3-60 8.2 1.3 7.2 10.8 14.4 18.0 8.5 12.1 15.7 19.3

AVPA/AVHA42ACD 460-3-60 9.1 1.6 7.2 10.8 14.4 18.0 8.8 12.4 16.0 19.6

AVPA/AVHA48ACD 460-3-60 9.2 1.6 7.2 10.8 14.4 18.0 8.8 12.4 16.0 19.6

AVPA/AVHA60ACD 460-3-60 11.7 2.6 7.2 10.8 14.4 18.0 9.8 13.4 17.0 20.6

AVPA72ACD 460-3-60 14.7 2.6 7.2 10.8 14.4 18.0 9.8 13.4 17.0 20.6

AVPA24ACZ 575-3-60 4.5 0.6 5.8 8.7 11.5 6.4 9.3 12.1

AVPA30ACZ 575-3-60 5.5 1.0 5.8 8.7 11.5 14.4 6.8 9.7 12.5 15.4

AVPA36ACZ 575-3-60 5.9 1.0 5.8 8.7 11.5 14.4 6.8 9.7 12.5 15.4

AVPA42ACZ 575-3-60 6.6 1.2 5.8 8.7 11.5 14.4 7.0 9.9 12.7 15.6

AVPA48ACZ 575-3-60 7.2 1.2 5.8 8.7 11.5 14.4 7.0 9.9 12.7 15.6

AVPA60ACZ 575-3-60 9.0 2.1 5.8 8.7 11.5 14.4 7.9 10.8 13.6 16.5

AVPA72ACZ 575-3-60 10.9 2.1 5.8 8.7 11.5 14.4 7.9 10.8 13.6 16.5
1
AC = Air Conditioner Unit Amps 2
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models. Total heating and
cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are maximum phase loads.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 16


ComPac®HVEA High Efficiency Air Conditioners

Certified Efficiency and Capacity Ratings at ANSI/AHRI Standard 390


for HVEA Air Conditioners with Single Stage Compressor
HVEA24 HVEA30 HVEA36 HVEA42 HVEA49 HVEA60
Model Number
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD

Cooling BTUH1 23,600 29,000 35,600 40,000 49,000 58,000

EER2 10.75 11.75 11.25 10.50 11.50 10.50

Rated Air Flow (CFM3) 800 1,000 1,300 1,400 1,750 1,900
1
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air EER=Energy Efficiency Ratio
2
CFM=Cubic Feet per Minute
3

Ratings are with no outside air. Performance will be affected by altitude.


Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect
performance and air flow.

Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
HVEA Air Conditioners with Single Stage Compressor
HVEA24 HVEA30 HVEA36 HVEA42 HVEA49 HVEA60
Model Number
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD

Total Capacity 23,600 29,000 35,600 40,000 49,000 58,000

Sensible Heat Ratio 0.74 0.76 0.76 0.73 0.74 0.73

Sensible Capacity 17,435 22,020 26,945 29,270 36,175 42,505

Rated Air Flow (CFM1) 800 1,000 1,300 1,400 1,750 1,900

CFM=Cubic Feet per Minute


1

Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.

Cooling Performance (BTUH) at Various Outdoor Temperatures


for HVEA Air Conditioners with Single Stage Compressor
Model Outdoor Temperature
Number 75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC 100ºF / 38ºC 105ºF / 40.5ºC 110ºF / 43.3ºC 115ºF / 46.1ºC 120ºF / 48.9ºC 125ºF / 51.7ºC 130ºF / 54.4ºC

HVEA24AC 27,375 26,430 25,490 24,545 23,600 22,655 21,710 20,770 20,295 19,870 19,445 19,020

HVEA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 24,420 23,895 23,375

HVEA36AC 41,295 39,870 38,450 37,025 35,600 34,175 32,750 31,320 30,615 29,975 29,335 28,695

HVEA42AC 46,400 44,800 43,200 41,600 40,000 38,400 36,800 35,200 34,400 33,680 32,960 32,240

HVEA49AC 56,840 54,880 52,920 50,960 49,000 47,040 45,080 43,120 42,140 41,260 40,375 39,495

HVEA60AC 67,280 64,960 62,640 60,320 58,000 55,680 53,360 51,040 49,880 48,835 47,790 46,745

Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.

17 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Electrical Characteristics - Compressor, Fan & Blower Motors -
HVEA Air Conditioner with Single Stage Compressor
BASIC COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR (ECM)
MODEL Type VOLTS-HZ-PH RLA1 LRA2 VOLTS-HZ-PH RPM3 FLA4 HP5 VOLTS-HZ-PH RPM3 FLA4 HP5
HVEA24ACA 208/230-60-1 12.8 58.3 208/230-60-1 1075 1.8 1/4 208/230-60-1 1500 2.8 1/3
HVEA30ACA 208/230-60-1 12.8 64.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVEA36ACA 208/230-60-1 16.6 79.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVEA42ACA 208/230-60-1 19.8 109.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVEA49ACA 208/230-60-1 21.8 117.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVEA60ACA 208/230-60-1 26.4 134.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVEA24ACC 208/230-60-3 7.7 55.4 208/230-60-1 1075 1.8 1/4 208/230-60-1 1500 2.8 1/3
HVEA30ACC 208/230-60-3 8.3 61.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVEA36ACC 208/230-60-3 10.4 88.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVEA42ACC 208/230-60-3 13.6 83.1 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVEA49ACC 208/230-60-3 13.7 83.1 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVEA60ACC 208/230-60-3 15.9 111.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVEA24ACD 460-60-3 4.0 28.0 208/230-60-1 1075 1.8 1/4 208/230-60-1 1500 2.8 1/3
HVEA30ACD 460-60-3 5.1 28.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVEA36ACD 460-60-3 5.8 38.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVEA42ACD 460-60-3 6.1 41.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVEA49ACD 460-60-3 6.2 41.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVEA60ACD 460-60-3 7.7 52.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
1
RLA = Rated Load Amps 2
LRA = Locked Rotor Amps 3
RPM = Revolutions per Minute 4
FLA = Full Load Amps 5
HP = Horsepower
The 460 volt units will have a step down transformer for the 230 volt motors.

Summary Electrical Ratings (Wire and Circuit Breaker Sizing) -


HVEA Air Conditioners with Single stage Compressors & Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT 000 = None 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw

BASIC VOLTAGE SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3
MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
HVEA24ACA 208/230-1-60 20.6 30 23.1 30 28.8 30 34.1 35 44.4 45 54.9 60
HVEA30ACA 208/230-1-60 21.6 30 23.1 30 28.8 30 34.1 35 44.4 45 54.9 60 65.3 70 80.9 90
HVEA36ACA 208/230-1-60 26.4 40 26.4 40 28.8 40 34.1 35 44.4 45 54.9 60 65.3 70 80.9 90
HVEA42ACA 208/230-1-60 30.4 50 30.4 50 54.9 60 65.3 70 80.9 90
HVEA49ACA 208/230-1-60 34.4 50 34.4 50 56.4 60 66.8 70 82.4 90
HVEA60ACA 208/230-1-60 40.1 60 40.1 60 56.4 60 66.8 70 82.4 90
HVEA24ACC 208/230-3-60 14.2 20 20.8 25 29.9 30 38.9 40
HVEA30ACC 208/230-3-60 16.0 20 20.8 25 29.9 30 38.9 40 47.9 50
HVEA36ACC 208/230-3-60 18.6 25 20.8 25 29.9 30 38.9 40 47.9 50
HVEA42ACC 208/230-3-60 22.6 35 22.6 35 29.9 35 38.9 40 47.9 50
HVEA49ACC 208/230-3-60 24.2 35 24.2 35 31.4 35 40.4 50 49.4 50
HVEA60ACC 208/230-3-60 27.0 40 27.0 40 31.4 40 40.4 50 49.4 50
HVEA24ACD 460-3-60 7.3 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA30ACD 460-3-60 9.2 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA36ACD 460-3-60 10.1 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA42ACD 460-3-60 10.4 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA49ACD 460-3-60 11.3 15 11.3 15 15.7 20 20.2 25 24.7 25
HVEA60ACD 460-3-60 13.2 20 13.2 20 15.7 20 20.2 25 24.7 25
1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2
MFS = Maximum Fuse or HACR Breaker Size 3
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. he 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 18


Summary Electrical Ratings (Wire and Circuit Breaker Sizing) -
HVEA Air Conditioners with Electric Reheat (“R”) with Single stage Compressors and
Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT 000 = None 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw
3 3 3 3 3 3 3 3
BASIC VOLTAGE SPPE SPPE SPPE SPPE SPPE SPPE SPPE SPPE SPPE3
MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
HVEA24ACA 208/230-1-60 20.6 30 41.5 45 46.6 50 51.9 60 72.7 80
HVEA30ACA 208/230-1-60 21.6 30 42.5 45 47.6 50 52.9 60 73.7 80 84.1 90 99.7 100
HVEA36ACA 208/230-1-60 26.4 40 47.3 50 52.4 60 57.7 60 78.5 80 88.9 90 104.5 110
HVEA42ACA 208/230-1-60 30.4 50 56.4 60 82.5 90 92.9 100 108.5 110
HVEA49ACA 208/230-1-60 34.4 50 60.4 70 86.5 90 96.9 100 112.5 120
HVEA60ACA 208/230-1-60 40.1 60 66.1 70 92.2 100 102.6 110 118.2 120
HVEA24ACC 208/230-3-60 14.2 20 32.2 35 41.3 45 50.3 60 59.3 60
HVEA30ACC 208/230-3-60 16.0 20 34.0 35 43.1 45 52.1 60 61.1 70
HVEA36ACC 208/230-3-60 18.6 25 36.6 40 45.7 50 54.7 60 63.7 70
HVEA42ACC 208/230-3-60 22.6 35 40.6 45 49.7 50 58.7 60 67.7 70
HVEA49ACC 208/230-3-60 24.2 35 42.2 45 51.3 60 60.3 70 69.3 70
HVEA60ACC 208/230-3-60 27.0 40 45.0 45 54.1 60 63.1 70 72.1 80
HVEA24ACD 460-3-60 7.3 15 16.3 20 20.8 25 25.3 30 29.8 30
HVEA30ACD 460-3-60 9.2 15 18.2 20 22.7 25 27.2 30 31.7 35
HVEA36ACD 460-3-60 10.1 15 19.1 20 23.6 25 28.1 30 32.6 35
HVEA42ACD 460-3-60 10.4 15 19.4 20 23.9 25 28.4 30 32.9 35
HVEA49ACD 460-3-60 11.3 15 20.3 25 24.8 25 29.3 30 33.8 35
HVEA60ACD 460-3-60 13.2 20 22.2 25 26.7 30 31.2 35 35.7 40
1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2
2MFS = Maximum Fuse or HACR Breaker Size 3
3SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.

Unit Load Amps -


HVEA Air Conditioners with with Single stage Compressors and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
CURRENT LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS) TOTAL MAXIMUM HEATING AMPS
BASIC (1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON
VOLTAGE AMPS
MODEL (2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS AN ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
PHASE / HZ
NUMBER
AC1 IBM2 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
HVEA24ACA 208/230-1-60 17.4 2.8 16.7 20.8 25.0 33.3 41.7 19.5 23.6 27.8 36.1 44.5
HVEA30ACA 208/230-1-60 18.4 2.8 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.5 23.6 27.8 36.1 44.5 52.8 65.3
HVEA36ACA 208/230-1-60 22.2 2.8 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.5 23.6 27.8 36.1 44.5 52.8 65.3
HVEA42ACA 208/230-1-60 25.4 2.8 20.8 41.7 50.0 62.5 23.6 44.5 52.8 65.3
HVEA49ACA 208/230-1-60 28.9 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8
HVEA60ACA 208/230-1-60 33.5 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8
HVEA24ACC 208/230-3-60 12.3 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA30ACC 208/230-3-60 13.9 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA36ACC 208/230-3-60 16.0 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA42ACC 208/230-3-60 19.2 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVEA49ACC 208/230-3-60 20.8 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4
HVEA60ACC 208/230-3-60 23.0 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4
HVEA24ACD 460-3-60 6.3 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA30ACD 460-3-60 7.9 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA36ACD 460-3-60 8.6 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA42ACD 460-3-60 8.9 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVEA49ACD 460-3-60 9.8 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
HVEA60ACD 460-3-60 11.3 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
1
AC = Air Conditioner Unit Amps 2
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models.
Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are
maximum phase loads.

19 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


ComPac®HVESA Air Conditioners with 2-Stage Compressor
Certified Efficiency and Capacity Ratings at ANSI/AHRI Standard 390
for HVESA Air Conditioners with 2-Stage Compressors
HVESA36 HVESA42 HVESA49 HVESA60
Model Number
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD

Cooling BTUH1 - 2nd Stage 35,000 39,000 47,000 56,000


EER2 - 2nd Stage 11.00 10.50 11.75 11.00
Integrated Part Load Value3 16.0 14.1 16.0 14.8
Rated Air Flow (CFM4) 1,300 1,400 1,750 1,900

Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
1 2
EER=Energy Efficiency Ratio
Integrated Part Load Value is an integrated efficiency measure from 1st and 2nd stage capacity modulation.
3 4
CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect perfor-
mance and air flow.

Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
HVESA Air Conditioners with 2-Stage Compressors
HVESA36 HVESA42 HVESA49 HVESA60
Model Number
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD

Total Capacity 35,000 39,000 47,000 56,000


Sensible Heat Ratio 0.70 0.71 0.79 0.77
Sensible Capacity 24,445 27,590 36,920 43,235
Rated Air Flow (CFM1) 1,300 1,400 1,750 1,900

CFM=Cubic Feet per Minute


1

Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.

Stage 2 Cooling Performance (BTUH) at Various Outdoor Temperatures


Outdoor Temperature
Model Number
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC

HVESA36AC 40,600 39,200 37,800 36,400 35,000


HVESA42AC 45,240 43,680 42,120 40,560 39,000
HVESA49AC 54,520 52,640 50,760 48,880 47,000
HVESA60AC 64,960 62,720 60,480 58,240 56,000

Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.

Stage 1 Cooling Performance (BTUH) at Various Outdoor Temperatures


Outdoor Temperature
Model Number
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC

HVESA36AC 30,856 29,792 28,728 27,664 26,600


HVESA42AC 34,336 33,152 31,968 30,784 29,600
HVESA49AC 44,080 42,560 41,040 39,520 38,000
HVESA60AC 51,040 49,280 47,520 45,760 44,000

Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 20


Electrical Characteristics - Compressor, Fan & Blower Motors -
HVESA Air Conditioner with 2-Stage Compressor
BASIC COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR (ECM6)
Type
MODEL VOLTS-HZ-PH RLA1 LRA2 VOLTS-HZ-PH RPM3 FLA4 HP5 VOLTS-HZ-PH RPM3 FLA4 HP5

HVESA36ACA 208/230-60-1 16.6 82.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2

HVESA42ACA 208/230-60-1 16.6 96.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVESA49ACA 208/230-60-1 21.1 96.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4

HVESA60ACA 208/230-60-1 25.6 118.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4

HVESA36ACC 208/230-60-3 11.1 58.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2

HVESA42ACC 208/230-60-3 13.4 88.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVESA49ACC 208/230-60-3 13.4 88.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4

HVESA60ACC 208/230-60-3 17.6 123.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4

HVESA36ACD 460-60-3 4.5 29.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2

HVESA42ACD 460-60-3 6.1 44.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVESA49ACD 460-60-3 6.4 41.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4

HVESA60ACD 460-60-3 9.0 62.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
1
RLA = Rated Load Amps 2LRA = Locked Rotor Amps 3RPM = Revolutions per Minute 4
FLA = Full Load Amps 5
HP = Horsepower 6
ECM = Electronically Commutated Motor
The 460 volt units have a step down transformer for the 230 volt motors.

Summary Electrical Ratings (Wire and Circuit Breaker Sizing) -


HVESA Air Conditioners with Two Stage Compressor and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT 000 = None 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw
3 3 3 3 3 3 3 3
BASIC VOLTAGE SPPE SPPE SPPE SPPE SPPE SPPE SPPE SPPE SPPE3
MODEL PHASE / HZ MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA1 MFS2

HVESA36AC1A 208/230-1-60 24.6 35 24.6 35 28.8 35 34.1 35 44.4 45 54.9 60 65.3 70 80.9 90

HVESA42AC1A 208/230-1-60 28.0 45 28.8 45 54.9 60 65.3 70 80.9 90

HVESA49AC1A 208/230-1-60 33.5 50 33.5 50 56.4 60 66.8 70 82.4 90

HVESA60AC1A 208/230-1-60 41.0 60 41.0 60 56.4 60 66.8 70 82.4 90

HVESA36AC1C 208/230-3-60 20.1 30 20.8 25 29.9 30 38.9 40 47.9 50

HVESA42AC1C 208/230-3-60 23.2 35 23.2 35 29.9 35 38.9 40 47.9 50

HVESA49AC1C 208/230-3-60 24.6 35 24.6 35 31.4 35 40.4 50 49.4 50

HVESA60AC1C 208/230-3-60 27.7 40 27.7 40 31.4 40 40.4 50 49.4 50

HVESA36AC1D 460-3-60 9.9 15 10.4 15 14.9 15 19.4 20 23.9 25

HVESA42AC1D 460-3-60 10.6 15 10.6 15 14.9 15 19.4 20 23.9 25

HVESA49AC1D 460-3-60 11.6 15 11.6 15 15.7 20 20.2 25 24.7 25

HVESA60AC1D 460-3-60 14.7 20 14.7 20 15.7 20 20.2 25 24.7 25


1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2MFS = Maximum Fuse or HACR Breaker Size
2
3SPPE = Single Point Power Entry
3

MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.

21 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Summary Electrical Ratings (Wire and Circuit Breaker Sizing) -
HVESA Air Conditioners with Two Stage Compressor,
Electric Reheat (“R”) and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT 000 = None 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw

BASIC VOLTAGE SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3
MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2

HVESA36ACA 208/230-1-60 24.6 35 45.5 50 50.6 60 55.9 60 76.7 80 87.1 90 102.7 110

HVESA42ACA 208/230-1-60 28.0 45 54.0 60 80.1 90 90.5 100 106.1 110

HVESA49ACA 208/230-1-60 33.5 50 59.5 60 85.6 90 96.0 100 111.6 120

HVESA60ACA 208/230-1-60 41.0 60 67.0 70 93.1 100 103.5 110 119.1 120

HVESA36ACC 208/230-3-60 20.1 30 38.1 40 47.2 50 56.2 60 65.2 70

HVESA42ACC 208/230-3-60 23.2 35 41.2 45 50.3 60 59.3 60 68.3 70

HVESA49ACC 208/230-3-60 24.6 35 42.6 45 51.7 60 60.7 70 69.7 70

HVESA60ACC 208/230-3-60 27.7 40 45.7 50 54.8 60 63.8 70 72.8 80

HVESA36ACD 460-3-60 9.9 15 18.9 20 23.4 25 27.9 30 32.4 35

HVESA42ACD 460-3-60 10.6 15 19.6 20 24.1 25 28.6 30 33.1 35

HVESA49ACD 460-3-60 11.6 15 20.6 25 25.1 30 29.6 30 34.1 35

HVESA60ACD 460-3-60 12.6 15 21.6 25 26.1 30 30.6 35 35.1 40


1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2
2MFS = Maximum Fuse or HACR Breaker Size 3
3SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.

Unit Load Amps -


HVESA Air Conditioners with Two Stage Compressor and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer,Outside Air with Pressure Relief (“C”)
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY
CURRENT TOTAL MAXIMUM HEATING AMPS
BASIC (AMPS) INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON
VOLTAGE AMPS (1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
MODEL AN ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
PHASE / HZ (2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
NUMBER
AC1 IBM2 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw

HVESA36ACA 208/230-1-60 20.8 2.8 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.5 23.6 27.8 36.1 44.5 52.8 65.3

HVESA42ACA 208/230-1-60 23.5 2.8 20.8 41.7 50.0 62.5 23.6 44.5 52.8 65.3

HVESA49ACA 208/230-1-60 28.2 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8

HVESA60ACA 208/230-1-60 34.2 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8

HVESA36ACC 208/230-3-60 17.2 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9

HVESA42ACC 208/230-3-60 19.7 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9

HVESA49ACC 208/230-3-60 21.1 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4

HVESA60ACC 208/230-3-60 23.6 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4

HVESA36ACD 460-3-60 8.5 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4

HVESA42ACD 460-3-60 9.0 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4

HVESA49ACD 460-3-60 9.2 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2

HVESA60ACD 460-3-60 10.0 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
1
AC = Air Conditioner Unit Amps 2
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models.
Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are
maximum phase loads.

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 22


ComPac Model & Cabinet Designation
CABINET DESIGNATION
MODEL
A B C D E F G H I
AVPA12 ComPac I ✓
AVPA12 ComPac II ✓
AVHA12 ComPac I ✓
AVPA20/24 ComPac I & II ✓
AVHA20/24 ComPac I & II ✓
AVPA30/36 ComPac I & II ✓
AVHA30/36 ComPac I & II ✓
HVEA24 ComPac I & II ✓
AVPA42/48/60 ComPac I & II ✓
AVHA42/48/60 ComPac I & II ✓
HVEA30/36/42 ComPac I & II ✓
HVESA30/36/42 ComPac I & II ✓
AVPA72 ComPac I & II ✓
HVEA49/60 ComPac I & II ✓
HVESA49/60 ComPac I & II ✓
AVPA42/48/60 with K/04315 Back Panel, ComPac I Only ✓
AVHA42/48/60 with K/04315 Back Panel, ComPac I Only ✓
AVPA42/48/60 with K/04317 Back Panel, ComPac I Only ✓
AVHA42/48/60 with K/04317 Back Panel, ComPac I Only ✓

23 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Dimensional Data - Cabinet A

Shipping Weight (pounds/kilograms)


AVPA12 LBS/KGS
COMPAC I 185/84

Filter Size
AVPA12 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 10” x 20” x 2” 254 x 508 x 52 91974 1 7

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 24


Dimensional Data - Cabinet B

Shipping Weight (pounds/kilograms)


AVPA12 LBS/KGS
COMPAC II 194/88

Filter Size
AVPA12 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 6¼” x 22¼” x 2” 159 x 565 x 52 80172 1 7

25 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Dimensional Data - Cabinet C

Shipping Weight (pounds/kilograms)


AVHA12 LBS/KGS
COMPAC I 185/84

Filter Size
AVHA12 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 10” x 20” x 2” 254 x 508 x 52 91974 1 7

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 26


Dimensional Data - Cabinet D

Shipping Weight (pounds/kilograms)


AVPA/AVHA20/24 LBS/KGS
COMPAC I 350/159

COMPAC II 375/170.5

Filter Size
AVPA/AVHA20/24 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 25” x 16” x 2” 635 x 406 x 51 80137 1 7

27 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Dimensional Data - Cabinet E

Shipping Weight (pounds/kilograms)


AVPA/AVHA30/36 & HVEA24 LBS/KGS
COMPAC I 420/191

COMPAC II 445/202.5

Filter Size
AVPA/AVHA30/36 & HVEA24 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 30 x 16 x 2 762 x 406 x 51 80138 1 7

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 28


Dimensional Data -Cabinet F

Shipping Weight (pounds/kilograms)


AVPA/AVHA42/48/60 and HVEA30/36/42, HVESA30/36/42 LBS/KGS
COMPAC I 540/245.5

COMPAC II 565/257

Filter Size
AVPA/AVHA42/48/60,
HVEA30/36/42, & INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
HVESA30/36/42
RETURN AIR FILTER 36½ x 22 x 2 927 x 559 x 51 80162 1 8

29 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Dimensional Data - Cabinet G

Shipping Weight (pounds/kilograms)


AVPA/AVHA72, and HVEA49/60, HVESA49/60 LBS/KGS
COMPAC I 680/309

COMPAC II 705/320.5

Filter Size
AVPA/AVHA72, HVEA49/60
INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
& HVESA49/60
RETURN AIR FILTER 18 x 24 x 2 457 x 610 x 51 81257 2 7

Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 30


Dimensional Data - Cabinet H
For matching existing AVP36 wall opening with new AVPA42/48/60 & AVHA42/48/60
For Non-Economizer models Only. For Economizer-Equipped models, use transition curb in Options section.
A B C D E F G H I J K L M N O P Q
Inches 45 225/8 86 8 18 14 421/2 28 15/16 409/16 389/16 11/8 431/8 423/16 401/2 21/4 835/16
mm 1,143 575 2,184 203 457 356 1,080 711 33 1,030 980 29 1,095 1,072 1,029 57 2,116
Note: Dimensional tolerance +/- 1/16” (2mm)

31 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20


Dimensional Data - Cabinet I
For matching existing AVP24 wall opening with new AVPA42/48/60 & AVHA42/48/60
For Non-Economizer models Only. For Economizer-Equipped models, use transition curb in Options section.

NOTES:
UNIT IS SHIPPED FROM THE FACTORY WITH SUPPLY AND RETURN LINES CENTERED LEFT TO RIGHT
ON BACK PANEL. RETURN AND SUPPLY OPENINGS MAY BE SHIFTED 2-9/16” LEFT OR RIGHT TO
ALLOW FOR A BETTER FIT. A SLOTTED HOLE PATTERN IS PROVIDED TO ASSIST WITH CUT OUT OF
OPENINGS AND COVER PLATES ARE ALSO PROVIDED TO COVER EXCESSIVE HOLES LEFT IN BACK
PANEL AFTER MAKING CUT OUTS.

Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data is available upon
request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website or by contacting
Marvair at 229-273-3636. As part of the Marvair continuous improvement program, specifications are subject to change without notice.

P.O. Box 400 • Cordele, GA 31010


156 Seedling Drive • Cordele, GA 31015
Ph: 229-273-3636 • Fax: 229-273-5154
Email: [email protected] • Internet: www.marvair.com