Marvair ComPac 01.18 Rev.20
Marvair ComPac 01.18 Rev.20
Marvair ComPac 01.18 Rev.20
General Description
Used primarily to cool electronic and communication equipment shelters, Marvair®
ComPac® I and ComPac® II air conditioners are problem solvers for a wide range
of conditions and applications. Due to the high internal heat load, these shelters
require cooling even when outside temperatures drop below 60°F (15°C).
The ComPac I and ComPac II air conditioners have the necessary controls and
components for operation during these (less than 60°F [15°C]) temperatures. All
models use the non-ozone depleting R-410A refrigerant.
The primary difference between the ComPac I and the ComPac II units is that
the ComPac® II air conditioner has a factory installed economizer. When ambient AVPA36ACA-100C
conditions are cool and dry, the economizer uses outside air to cool the shelter.
The economizer provides temperature control, energy cost savings, and increased
reliability by decreasing the operating hours of the compressor and the condenser
fan. To insure proper operation and optimum performance, all economizers are
non-removable, factory installed and tested. In addition, factory and field installed
accessories can be used to meet specific requirements. Features and Benefits
Built-In Energy Savings
➤ Standard Efficiency Models • Optional Factory Installed Economizer
AVPA: Marvair’s most popular model with an Energy Efficiency Ratio (EER) of 9.0 • Four Model Lines to Meet Any Budget and
to 10.0. The ComPac AVPA is available in cooling capacities of 1, 1.5, 2, 2.5, 3, 3.5, Efficiency Requirements
4, 5 and 6 tons (12,000 BTUH to 72,000 BTUH). • Available EER of up to 11.75
• Available 2-Stage Compressor on HVESA Models
➤ High Efficiency Models
HVEA: Marvair’s most efficient wall mount air conditioners. Electronically commu- R-410A Refrigerant
tated indoor fan motors combined with highly efficient scroll compressors result • Efficient Heat Release
• Non-Ozone Depleting Refrigerant
in Energy Efficiency Ratios (EER’s) of up to 11.75.
• Synthetic Lubricant
AVHA: ComPac models with an EER of 10.0. The AVPA72 is also rated 10 EER. • Reduced Compressor Wear
Standard Features
➤ Designed for Operation in Low ➤ Remote Alarm Capability ➤ Rugged Construction
Ambient Conditions • Dry contacts can be used for • Copper tube, aluminum fin
• Low ambient control cycles remote alarm or notification evaporator & condenser coils.
condenser fan to maintain proper upon air conditioner lockout. • Field or factory installed heaters
refrigerant pressures. Allows ➤ Ease of Service on discharge side of evaporator
operation in mechanical cooling • Service access valves are coil (optional)
(compressor) of our standard standard. • Baked on neutral beige finish
air conditioners down to 20°F
• Standard 2” (50 mm) pleated over galvanneal steel for
(-7°C). With the Extreme Duty
filter with a MERV rating of 8 maximum cabinet life. (Other
option, the units will operate
changeable from outside. finishes are available.)
down to 0°F (-18°C). Note: low
temperature operation is affected • All major components are readily ➤ Ease of Installation
by ambient conditions, e.g. wind accessible. • Sloped top with flashing
and humidity. • Front Control Panel allows easy eliminates need of rainhood.
• Three minute by-pass of the access and complies with NEC • Built-in mounting flanges
low pressure switch for start-up clearance codes on redundant facilitate installation and
of compressor when outdoor side-by-side systems. minimize chance of water leaks.
temperatures are below 55°F • LEDs indicate operational status • Supply and return openings
(13°C). and fault conditions. exactly match previous models.
• Optional economizer. • Foil backed insulation on the • Factory installed disconnect on
➤ High Efficiency indoor air path. all units.
• High efficiency compressor. • A minimum position • Single Point Power Entry
• Lanced fins standard on all potentiometer that can be complies with latest edition of
evaporator and condenser coils. adjusted to prevent the U.L. Standard 1995.
➤ Built-in Reliability economizer damper from closing • Side access panels on
completely. This control ensures economizer models for easy
• High pressure switch and low
that whenever the evaporator
pressure switch with lockout access to electrical connections.
fan is operating, fresh air is being
protects refrigerant circuit.
introduced into the building.
• Adjustable .03 to ten minute
delay on make for short cycle
protection.
Hours of Operation Los Angeles, CA Miami, FL Phoenix, AZ Pittsburgh, PA Seattle, WA St. Louis, MO
Annual Compressor & Condenser Motor Run Time without Economizer (Hrs.) 6,467 6,779 6,765 6,386 6,465 6,472
Annual Compressor & Condenser Motor Run Time with Economizer (Hrs.) 3,862 6,391 3,106 1,929 1,654 2,716
Run Time Savings with the Economizer (Hrs.) 2,605 388 3,659 4,457 4,811 3,756
Annual Costs Saving ($) of 9.0 EER unit with an Economizer (ComPac II)
Annual Operating Cost 9.0 EER Unit without Economizer ($) $4,060.00 $4,255.00 $4,247.00 $4,009.00 $3,653.00 $4,063.00
Annual Operating Cost 9.0 EER with Economizer $2,686.00 $4,051.00 $2,315.00 $1,667.00 $1,368.00 $2,090.00
Annual Savings using 9.0 EER Unit with Economizer $1,374.00 $204.00 $1,932.00 $2,342.00 $2,285.00 $1,973.00
Shelter Metrics: Air Conditioner Metrics:
•10’ x 20’ x 9’ building •ComPac II Economizer setting: 57ºF (dry bulb or enthalpy sensor)
•Internal heat gain (electronics load): 12,000 watts. •A/C unit capacity: 60,000 BTUH (5 tons) with 1-stage compressor
•Building surface area (excluding floor area): 740 ft² •Nominal EER (unit efficiency): 9.0 (models AVPA)
•R-Value of walls and ceiling: R-12 •Cost of power: $.10 per KWH
•Internal shelter temperature (Thermostat set point): 75ºF
in a variety of outside conditions. For existing shelters with window Wall Sleeve Thru
Wall Opening
to the exterior of the building. The single piece supply and return
M
PA
CO
the Marvair One Ton Air Conditioner thus eliminating baseboard heat
and a second power source.
Options
The ComPac® I and ComPac® II air conditioners were designed and are built to stringent requirements of the
communications/electronic shelter. Applications occur that have special requirements. Numerous options are available
for the ComPac I and ComPac II air conditioners that meet these special needs.
➤ Hard Start Kit
Used on single phase equipment to give the compressor higher starting torque under low voltage conditions. (Field
installed only) (Note: Not recommended for use on scroll compressors.)
➤ Dehumidification
ComPac® I and ComPac® II A/C – Allows the electric heat to operate simultaneously with cooling. See
Dehumidification Application Bulletin for details. Note: The electrical characteristics and requirements of air
conditioners with the dehumidification option are different from standard air conditioners. Refer to the appropriate
Summary Rating Charts for the electrical characteristics of units with Electric Reheat. Available on all units except the
AVPA12. Units with reheat require a thermostat and a dehumidistat for proper operation.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 01/2018 Rev.20 6
➤ Protective Coating Packages
Typically, only the ComPac I is used in corrosive environments, but the ComPac II air conditioner is also available
with corrosion protection. Two corrosion protection packages are offered - one for the condenser section (Coastal
Environmental Package) and the other for the entire unit (Coat-All Package).
The Coastal Environmental Package includes:
• Corrosion resistant fasteners
• Sealed or partially sealed condenser fan motor
• Protective coating applied to all exposed internal copper and metal in the condenser section
• Protective coating on the condenser coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment)
technology.
The Coat all Package includes all of the above, plus:
• Protective coating on the evaporator coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment)
technology
• Protective coating on exterior and interior components and sheet metal. (Note: the internal sheet metal which is
insulated, bottom outside panel, and the internal control box are not coated)
Note: The AVPA12 is available with the protective coatings and corrosion resistant fasteners, but does not have a
sealed condenser fan motor.
➤ Protective Coil Coatings
The Condenser Coil or the Evaporator Coil or Both can be coated. Coating the Evaporator Coil in not common. For
harsh conditions, e.g., power plants, paper mills or sites where the unit will be exposed to salt water, the coils should
be protected by a protective coating.
Note: Cooling capacity may be reduced by up to 5% on units with coated coils.
➤ External Low Noise Blower (ELNB)
ComPac® I and ComPac® II A/C – A field installed kit that consists of a condenser air hood, centrifugal blowers,
controls and a compressor jacket to reduce the sound level by up to 6 dbA of Marvair ComPac air conditioners.
Available for models AVPA30-60. See External Low Noise Blower Product Data Sheet for details.
➤ ComPac® II Air Conditioner Transition Curb
ComPac II A/C only – A sheet metal curb that enables AVPA42/48/60 ComPac II air conditioner to replace an
AVPA30/36 ComPac II unit. Curb transitions supply and return openings of the 3-1/2, 4 and 5 ton units to the smaller
openings.
➤ Hot Gas By-Pass (Non-Economizer Models)
ComPac® I A/C Only – Used in specialty applications; i.e., Magnetic Resonance Imaging (MRI) buildings, to prevent
magnetic voltage disturbance caused by compressor cycling. Hot gas by-pass option packages are available to
allow operation to 20°F (-7°C). Please refer to Hot Gas By-pass Application Bulletin for details. Not available on the
AVPA12, 20 & 24.
➤ High Filtration
Selected units are built with larger blowers/motors for use with higher efficiency filters with MERV ratings of 11, 13
and 14 when tested to ASHRAE 52.2. Units with economizers have a prefilter on the outside air. Not available on the
AVPA12. Contact your Marvair representative for specific models.
➤ Color
ComPac® air conditioners are available in five different cabinet colors -the standard Marvair® beige, white,
gray, brown and dark bronze. The standard cabinet’s sides, top and front panels are constructed of 20
gauge painted steel. As an option, these panels can be built of 16 gauge steel in beige & gray or .050
stucco aluminum. When the 16 gauge painted steel or the aluminum is used, only the side, top and front
panels are 16 gauge or aluminum. Contact your Marvair representative for color chips. The cabinet can
also be constructed of type 316 stainless steel. Two stainless steel cabinet constructions are available-
the complete cabinet, including most internal sheet metal or only the exterior sheet metal. Custom colors
are also available; contact Marvair for details.
Custom colors available
➤ Extended Warranty
A first-year labor (Silver), and a two-year labor (Gold) are available. See www.marvair.com for optional warranty details.
➤ Dirty Filter Indicator
A factory installed option that measures the difference in pressure across the internal filter and
illuminates a LED when the pressure exceeds the desired difference. Not available on the AVPA12.
When the K/04317 back panel adapter is used, a return filter grille, p/n 80671, must be used. When the K/04315 back
panel adapter is used, a return filter grille, p/n 80672, must be used.
Control Box
The internal control board in the ComPac® air conditioners simplifies wiring, consolidates several of the
electrical functions onto one device and improves the reliability of the air conditioner. In addition, the control board has
LED’s that indicate operational status and fault conditions.
➤ LED Indicator Lights
COLOR TYPE STATUS DESCRIPTION
Green Power Constant On 24 VAC power has been applied
Constant On Normal operation
1 Blink High pressure switch has opened twice
Red Status
2 Blinks Low pressure switch has opened twice
3 Blinks Freeze stat (optional) - indoor coil temperature is below 35°F (1°C)
➤ Modes of Operation
Normal Start-up: On a call for cooling, and the with the high pressure switch closed, the cooling system (compressor,
indoor blower motor and outdoor fan motor) will be energized. (Note: See the Delay on Make feature). The cooling
system will remain energized during the three minute low pressure switch bypass cycle. If the low pressure is closed,
the cooling system will continue to operate after the three-minute bypass. If the low pressure switch is open after the
three-minute bypass, the cooling system will be de-energized.
Lockout Mode: If either the high or low pressure switch opens twice on the same call for cooling, the control board
enters into and indicates the lockout mode. In the lockout mode, the compressor is turned off, the alarm output is
energized and the status LED’s will blink to indicate which fault has occurred. If there is a call for air flow, the indoor
blower will remain energized. When the lockout condition has cleared, the unit will reset if the demand of the ther-
mostat is removed or when power is reset. The lockout circuit is factory wired for normally open contacts. The user
can select either normally closed or normally open remote alarm dry contacts.
Delay on Make: On initial power up or on resumption of power, the air conditioner will wait .03 to 10 minutes from a
call for cooling before allowing the contactor to energize.
Refrigerant System Type Electric Heat – kW Special Option Code Brand Designation
A = R410A Air Conditioner 000 = No Heat 080 = 8 kW R = Electric Reheat Unused = Marvair
Nominal Cooling 022 = 2.2 kW 090 = 9 kW U = Scroll Compressor ComPac
12 = 11,000 BTUH 036 = 3.6 kW 100 = 10 kW X = Hot Gas Bypass EUB = Eubank Cabinet Color
2-Stage
040 = 4 kW 120 = 12 kW O = Opposite side
WalPac 100 = Beige
20 = 20,000 BTUH
Compressor 200 = Gray
24 = 24,000 BTUH 050 = 5 kW 150 = 15 kW compressor
30 = 30,000 BTUH 060 = 6 kW E = Extreme Duty 400 = White
36 = 36,000 BTUH D = Desert Duty 500 = Stainless Steel
42 = 42,000 BTUH G = Hot Gas Reheat (Exterior Only)
AVP 48/49 = 48,000 BTUH Power Supply
SS-500 = Stainless Steel
AVH 60 = 60,000 BTUH A = 208/230V,1ø,60Hz
700 = Aluminum
HVE 72 = 72,000 BTUH C = 208/230V,3ø,60Hz
Stucco
D = 460V,3ø,60Hz (3 wire) Configuration
Z = 575V,3ø,60Hz A5 = Built in
N = Non-Economizer
compliance with
C = Economizer-Equipped
UL 1995, 4th edition
Standard Unit (C) -40ºF - 120ºF (-40ºC - 48.9ºC) -40ºF - 120ºF (-29ºC - 48.9ºC)
ComPac II
Desert Duty (CD) -40ºF - 130ºF (-40ºF - 54ºC) -40ºF - 130ºF (-29ºC - 54ºC)
(Economizer-Equipped)
Extreme Duty Kit (CE) -40ºF - 130ºF (-40ºF - 54ºC) -40ºF - 130ºF (-29ºC - 54ºC)
Cooling BTUH1 10,800 19,600 24,000 29,000 35,000 42,000 46,000 54,500 62,000 70,000
EER2 9.00 9.00 9.25 9.25 9.25 9.25 9.50 9.25 10.00 10.00
Rated Air Flow (CFM3) 400 755 840 1,000 1,100 1,575 1,725 1,850 1,925 1,925
Cooling BTUH1 10,800 19,600 24,000 29,000 33,000 42,000 46,000 54,000
EER2 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00
Rated Air Flow (CFM3) 400 755 840 1,000 1,100 1,575 1,725 1,850
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air. 2EER=Energy Efficiency Ratio 3CFM=Cubic Feet per Minute
1
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
AVPA/AVHA Air Conditioners
AVPA12 AVPA20 AVPA24 AVPA30 AVPA36 AVPA42 AVPA48 AVPA60 AVPA72
Model Number
ACA ACA ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ ACA ACC ACD ACZ
Total Capacity 10,800 19,600 24,000 29,000 35,000 42,000 46,000 54,500 62,000 70,000
Sensible Heat Ratio 0.74 0.76 0.75 0.75 0.69 0.76 0.76 0.73 0.71 0.67
Sensible Capacity 8,000 14,800 18,000 21,740 24,155 31,900 34,940 39,800 43,815 46,800
Rated Air Flow (CFM1) 400 755 840 1,000 1,100 1,575 1,725 1,850 1,925 1,925
Total Capacity 10,800 19,600 24,000 29,000 33,000 42,000 46,000 54,000
Sensible Heat Ratio 0.74 0.76 0.75 0.75 0.74 0.74 0.76 0.72
Sensible Capacity 8,000 14,800 18,000 21,700 24,500 31,000 35,000 39,000
Rated Air Flow (CFM1) 400 755 840 1,000 1,100 1,575 1,725 1,850
1
CFM=Cubic Feet per Minute. Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
AVPA12AC 12,525 12,095 11,660 11,230 10,800 10,365 9,9935 9,500 9,285 8,640 8,205 7,775
AVPA20AC 22,735 21,950 21,165 20,380 19,600 18,815 18,030 17,245 16,855 15,680 14,895 14,110
AVPA24AC 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640 19,200 18,240 17,280
AVPA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 23,200 22,040 20,880
AVPA36AC 40,600 39,200 37,800 36,400 35,000 33,600 32,200 30,800 30,100 28,000 26,600 25,200
AVPA42AC 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120 33,600 31,920 30,240
AVPA48AC 53,360 51,520 49,680 47,840 46,000 44,160 42,320 40,480 39,560 36,800 34,960 33,120
AVPA60AC 63,220 61,040 58,860 56,680 54,500 52,320 50,140 47,960 46,870 43,600 41,420 39,240
AVPA72ACA 71,920 69,440 66,960 64,480 62,000 59,520 57,040 54,560 53,320 49,600 47,120 44,640
AVPA72ACC, ACD, ACZ 81,200 78,400 75,600 72,800 70,000 67,200 64,400 61,600 60,200 56,000 53,200 50,400
AVHA12AC 12,525 12,095 11,660 11,230 10,800 10,365 9,9935 9,500 9,285 8,640 8,205 7,775
AVHA20AC 22,735 21,950 21,165 20,380 19,600 18,815 18,030 17,245 16,855 15,680 14,895 14,110
AVHA24AC 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640 19,200 18,240 17,280
AVHA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 23,200 22,040 20,880
AVHA36AC 38,280 36,960 35,640 34,320 33,000 31,680 30,360 29,040 28,380 26,400 25,080 23,760
AVHA42AC 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120 33,600 31,920 30,240
AVHA48AC 53,360 51,520 49,680 47,840 46,000 44,160 42,320 40,480 39,560 36,800 34,960 33,120
AVHA60AC 63,220 61,040 58,860 56,680 54,500 52,320 50,140 47,960 46,870 43,600 41,420 39,240
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Note: Operation of units above 120°F (48.9°C) requires the Desert Duty package.
AVPA/AVHA20ACA 208/230-60-1 8.3 43.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5
AVPA/AVHA24ACA 208/230-60-1 10.6 54.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5
AVPA30ACA 208/230-60-1 13.1 74.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA36ACA RECIPROCATING 208/230-60-1 14.7 84.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA42ACA 208/230-60-1 15.7 84.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA48ACA 208/230-60-1 18.6 102.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA60ACA 208/230-60-1 23.0 130.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4
AVPA/AVHA24ACA 208/230-60-1 12.8 64.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5
AVPA/AVHA30ACA 208/230-60-1 14.1 77.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA/AVHA36ACA 208/230-60-1 17.9 112.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA/AVHA42ACA SCROLL 208/230-60-1 19.8 109.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA/AVHA48ACA 208/230-60-1 21.8 117.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA/AVHA60ACA 208/230-60-1 26.2 134.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4
AVPA72ACA 208/230-60-1 30.1 158.0 208/230-60-1 825 2.9 1/2 1075 5.2 3/4
AVPA/AVHA24ACC 208/230-60-3 8.3 61.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5
AVPA/AVHA30ACC 208/230-60-3 9.0 71.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA/AVHA36ACC 208/230-60-3 13.2 88.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA/AVHA42ACC SCROLL 208/230-60-3 13.6 83.1 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA/AVHA48ACC 208/230-60-3 13.7 83.1 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA/AVHA60ACC 208/230-60-3 15.6 111.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4
AVPA72ACC 208/230-60-3 22.4 149.0 208/230-60-1 825 2.9 1/2 1075 5.2 3/4
AVPA/AVHA24ACD 460-60-3 5.1 28.0 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5
AVPA/AVHA30ACD 460-60-3 5.6 38.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA/AVHA36ACD 460-60-3 6.0 44.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA/AVHA42ACD SCROLL 460-60-3 6.1 41.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA/AVHA48ACD 460-60-3 6.2 41.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA/AVHA60ACD 460-60-3 7.7 52.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4
AVPA72ACD 460-60-3 10.6 75.0 208/230-60-1 825 2.9 1/2 1075 5.2 3/4
AVPA24ACZ 575-60-3 3.3 23.7 208/230-60-1 1075 1.5 1/5 1075 1.5 1/5
AVPA30ACZ 575-60-3 3.8 36.5 208/230-60-1 1075 1.5 1/5 1075 1.5 1/4
AVPA36ACZ 575-60-3 4.2 30.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/4
AVPA42ACZ SCROLL 575-60-3 4.2 33.0 208/230-60-1 1075 1.8 1/4 1075 2.5 1/2
AVPA48ACZ 575-60-3 4.8 33.0 208/230-60-1 825 2.8 1/3 1075 3.1 1/2
AVPA60ACZ 575-60-3 5.8 38.9 208/230-60-1 825 2.8 1/3 1075 3.1 3/4
AVPA72ACZ 575-60-3 7.7 54.0 208/230-60-1 825 2.8 1/3 1075 5.2 3/4
1
RLA = Rated Load Amps 2
LRA = Locked Rotor Amps 3
RPM = Revolutions per Minute 4
FLA = Full Load Amps 5
HP = Horsepower
The 460 volt (ACD) units will have a step down transformer for the 230 volt motors.
MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
AVPA/AVHA30ACA 208/230-1-60 21.9 35 23.4 35 28.5 35 33.8 35 44.1 45 54.6 60 65.0 70 80.6 90
AVPA/AVHA36ACA 208/230-1-60 26.7 40 26.7 40 28.5 40 33.8 40 44.1 45 54.6 60 65.0 70 80.6 90
BASIC VOLTAGE SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3
MODEL PHASE / HZ MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS
2
MCA 1
MFS 2
MCA 1
MFS 2
MCA 1
MFS 2
MCA1 MFS2
AVPA/AVHA60ACA 208/230-1-60 40.8 60 66.8 70 92.9 100 103.3 110 118.9 120
AVPA72ACA 208/230-1-60 45.6 60 71.6 80 97.7 100 108.1 110 123.7 130
AVPA/AVHA12ACA 208/230-1-60 6.1 0.85 9.2 15.0 20.8 10.1 15.0 21.7
AVPA/AVHA20ACA 208/230-1-60 11.3 1.5 16.7 20.8 25.0 33.3 41.7 18.2 22.3 26.5 34.8 43.2
AVPA/AVHA24ACA 208/230-1-60 15.8 1.5 16.7 20.8 25.0 33.3 41.7 18.2 22.3 26.5 34.8 43.2
AVPA/AVHA30ACA 208/230-1-60 18.4 2.5 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.2 23.3 27.5 35.8 44.2 52.5 65.0
AVPA/AVHA36ACA 208/230-1-60 22.2 2.5 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.2 23.3 27.5 35.8 44.2 52.5 65.0
AVPA/AVHA42ACA 208/230-1-60 25.7 3.1 20.8 41.7 50.0 62.5 23.9 44.8 53.1 65.6
AVPA/AVHA48ACA 208/230-1-60 27.7 3.1 20.8 41.7 50.0 62.5 23.9 44.8 53.1 65.6
AVPA/AVHA60ACA 208/230-1-60 34.2 5.2 20.8 41.7 50.0 62.5 26.0 46.9 55.2 67.7
AVPA72ACA 208/230-1-60 38.2 5.2 20.8 41.7 50.0 62.5 26.0 46.9 55.2 67.7
AVPA/AVHA24ACC 208/230-3-60 11.2 1.5 14.4 21.7 28.9 36.1 15.9 23.2 30.4 37.6
AVPA/AVHA30ACC 208/230-3-60 13.3 2.5 14.4 21.7 28.9 36.1 16.9 24.2 31.4 38.6
AVPA/AVHA36ACC 208/230-3-60 17.5 2.5 14.4 21.7 28.9 36.1 16.9 24.2 31.4 38.6
AVPA/AVHA42ACC 208/230-3-60 19.5 3.1 14.4 21.7 28.9 36.1 17.5 24.8 32.0 39.2
AVPA/AVHA48ACC 208/230-3-60 19.6 3.1 14.4 21.7 28.9 36.1 17.5 24.8 32.0 39.2
AVPA/AVHA60ACC 208/230-3-60 23.6 5.2 14.4 21.7 28.9 36.1 19.6 26.9 34.1 41.3
AVPA72ACC 208/230-3-60 30.5 5.2 14.4 21.7 28.9 36.1 19.6 26.9 34.1 41.3
AVPA/AVHA24ACD 460-3-60 6.6 0.8 7.2 10.8 14.4 18.0 8.0 11.6 15.2 18.8
AVPA/AVHA30ACD 460-3-60 7.8 1.3 7.2 10.8 14.4 18.0 8.5 12.1 15.7 19.3
AVPA/AVHA36ACD 460-3-60 8.2 1.3 7.2 10.8 14.4 18.0 8.5 12.1 15.7 19.3
AVPA/AVHA42ACD 460-3-60 9.1 1.6 7.2 10.8 14.4 18.0 8.8 12.4 16.0 19.6
AVPA/AVHA48ACD 460-3-60 9.2 1.6 7.2 10.8 14.4 18.0 8.8 12.4 16.0 19.6
AVPA/AVHA60ACD 460-3-60 11.7 2.6 7.2 10.8 14.4 18.0 9.8 13.4 17.0 20.6
AVPA72ACD 460-3-60 14.7 2.6 7.2 10.8 14.4 18.0 9.8 13.4 17.0 20.6
AVPA24ACZ 575-3-60 4.5 0.6 5.8 8.7 11.5 6.4 9.3 12.1
AVPA30ACZ 575-3-60 5.5 1.0 5.8 8.7 11.5 14.4 6.8 9.7 12.5 15.4
AVPA36ACZ 575-3-60 5.9 1.0 5.8 8.7 11.5 14.4 6.8 9.7 12.5 15.4
AVPA42ACZ 575-3-60 6.6 1.2 5.8 8.7 11.5 14.4 7.0 9.9 12.7 15.6
AVPA48ACZ 575-3-60 7.2 1.2 5.8 8.7 11.5 14.4 7.0 9.9 12.7 15.6
AVPA60ACZ 575-3-60 9.0 2.1 5.8 8.7 11.5 14.4 7.9 10.8 13.6 16.5
AVPA72ACZ 575-3-60 10.9 2.1 5.8 8.7 11.5 14.4 7.9 10.8 13.6 16.5
1
AC = Air Conditioner Unit Amps 2
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models. Total heating and
cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are maximum phase loads.
Rated Air Flow (CFM3) 800 1,000 1,300 1,400 1,750 1,900
1
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air EER=Energy Efficiency Ratio
2
CFM=Cubic Feet per Minute
3
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
HVEA Air Conditioners with Single Stage Compressor
HVEA24 HVEA30 HVEA36 HVEA42 HVEA49 HVEA60
Model Number
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
Rated Air Flow (CFM1) 800 1,000 1,300 1,400 1,750 1,900
Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
HVEA24AC 27,375 26,430 25,490 24,545 23,600 22,655 21,710 20,770 20,295 19,870 19,445 19,020
HVEA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 24,420 23,895 23,375
HVEA36AC 41,295 39,870 38,450 37,025 35,600 34,175 32,750 31,320 30,615 29,975 29,335 28,695
HVEA42AC 46,400 44,800 43,200 41,600 40,000 38,400 36,800 35,200 34,400 33,680 32,960 32,240
HVEA49AC 56,840 54,880 52,920 50,960 49,000 47,040 45,080 43,120 42,140 41,260 40,375 39,495
HVEA60AC 67,280 64,960 62,640 60,320 58,000 55,680 53,360 51,040 49,880 48,835 47,790 46,745
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
BASIC VOLTAGE SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3
MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
HVEA24ACA 208/230-1-60 20.6 30 23.1 30 28.8 30 34.1 35 44.4 45 54.9 60
HVEA30ACA 208/230-1-60 21.6 30 23.1 30 28.8 30 34.1 35 44.4 45 54.9 60 65.3 70 80.9 90
HVEA36ACA 208/230-1-60 26.4 40 26.4 40 28.8 40 34.1 35 44.4 45 54.9 60 65.3 70 80.9 90
HVEA42ACA 208/230-1-60 30.4 50 30.4 50 54.9 60 65.3 70 80.9 90
HVEA49ACA 208/230-1-60 34.4 50 34.4 50 56.4 60 66.8 70 82.4 90
HVEA60ACA 208/230-1-60 40.1 60 40.1 60 56.4 60 66.8 70 82.4 90
HVEA24ACC 208/230-3-60 14.2 20 20.8 25 29.9 30 38.9 40
HVEA30ACC 208/230-3-60 16.0 20 20.8 25 29.9 30 38.9 40 47.9 50
HVEA36ACC 208/230-3-60 18.6 25 20.8 25 29.9 30 38.9 40 47.9 50
HVEA42ACC 208/230-3-60 22.6 35 22.6 35 29.9 35 38.9 40 47.9 50
HVEA49ACC 208/230-3-60 24.2 35 24.2 35 31.4 35 40.4 50 49.4 50
HVEA60ACC 208/230-3-60 27.0 40 27.0 40 31.4 40 40.4 50 49.4 50
HVEA24ACD 460-3-60 7.3 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA30ACD 460-3-60 9.2 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA36ACD 460-3-60 10.1 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA42ACD 460-3-60 10.4 15 10.4 15 14.9 15 19.4 20 23.9 25
HVEA49ACD 460-3-60 11.3 15 11.3 15 15.7 20 20.2 25 24.7 25
HVEA60ACD 460-3-60 13.2 20 13.2 20 15.7 20 20.2 25 24.7 25
1
MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2
MFS = Maximum Fuse or HACR Breaker Size 3
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. he 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
1 2
EER=Energy Efficiency Ratio
Integrated Part Load Value is an integrated efficiency measure from 1st and 2nd stage capacity modulation.
3 4
CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect perfor-
mance and air flow.
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
HVESA Air Conditioners with 2-Stage Compressors
HVESA36 HVESA42 HVESA49 HVESA60
Model Number
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
HVESA36ACA 208/230-60-1 16.6 82.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA42ACA 208/230-60-1 16.6 96.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVESA49ACA 208/230-60-1 21.1 96.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA60ACA 208/230-60-1 25.6 118.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA36ACC 208/230-60-3 11.1 58.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA42ACC 208/230-60-3 13.4 88.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVESA49ACC 208/230-60-3 13.4 88.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA60ACC 208/230-60-3 17.6 123.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA36ACD 460-60-3 4.5 29.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA42ACD 460-60-3 6.1 44.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
SCROLL
HVESA49ACD 460-60-3 6.4 41.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA60ACD 460-60-3 9.0 62.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
1
RLA = Rated Load Amps 2LRA = Locked Rotor Amps 3RPM = Revolutions per Minute 4
FLA = Full Load Amps 5
HP = Horsepower 6
ECM = Electronically Commutated Motor
The 460 volt units have a step down transformer for the 230 volt motors.
HVESA36AC1A 208/230-1-60 24.6 35 24.6 35 28.8 35 34.1 35 44.4 45 54.9 60 65.3 70 80.9 90
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
BASIC VOLTAGE SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3 SPPE3
MODEL PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
HVESA36ACA 208/230-1-60 24.6 35 45.5 50 50.6 60 55.9 60 76.7 80 87.1 90 102.7 110
HVESA60ACA 208/230-1-60 41.0 60 67.0 70 93.1 100 103.5 110 119.1 120
HVESA36ACA 208/230-1-60 20.8 2.8 16.7 20.8 25.0 33.3 41.7 50.0 62.5 19.5 23.6 27.8 36.1 44.5 52.8 65.3
HVESA42ACA 208/230-1-60 23.5 2.8 20.8 41.7 50.0 62.5 23.6 44.5 52.8 65.3
HVESA49ACA 208/230-1-60 28.2 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8
HVESA60ACA 208/230-1-60 34.2 4.3 20.8 41.7 50.0 62.5 25.1 46.0 54.3 66.8
HVESA36ACC 208/230-3-60 17.2 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVESA42ACC 208/230-3-60 19.7 2.8 14.4 21.7 28.9 36.1 17.2 24.5 31.7 38.9
HVESA49ACC 208/230-3-60 21.1 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4
HVESA60ACC 208/230-3-60 23.6 4.3 14.4 21.7 28.9 36.1 18.7 26.0 33.2 40.4
HVESA36ACD 460-3-60 8.5 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVESA42ACD 460-3-60 9.0 1.4 7.2 10.8 14.4 18.0 8.6 12.2 15.8 19.4
HVESA49ACD 460-3-60 9.2 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
HVESA60ACD 460-3-60 10.0 2.2 7.2 10.8 14.4 18.0 9.4 13.0 16.6 20.2
1
AC = Air Conditioner Unit Amps 2
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models.
Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are
maximum phase loads.
Filter Size
AVPA12 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 10” x 20” x 2” 254 x 508 x 52 91974 1 7
Filter Size
AVPA12 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 6¼” x 22¼” x 2” 159 x 565 x 52 80172 1 7
Filter Size
AVHA12 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 10” x 20” x 2” 254 x 508 x 52 91974 1 7
COMPAC II 375/170.5
Filter Size
AVPA/AVHA20/24 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 25” x 16” x 2” 635 x 406 x 51 80137 1 7
COMPAC II 445/202.5
Filter Size
AVPA/AVHA30/36 & HVEA24 INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
RETURN AIR FILTER 30 x 16 x 2 762 x 406 x 51 80138 1 7
COMPAC II 565/257
Filter Size
AVPA/AVHA42/48/60,
HVEA30/36/42, & INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
HVESA30/36/42
RETURN AIR FILTER 36½ x 22 x 2 927 x 559 x 51 80162 1 8
COMPAC II 705/320.5
Filter Size
AVPA/AVHA72, HVEA49/60
INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
& HVESA49/60
RETURN AIR FILTER 18 x 24 x 2 457 x 610 x 51 81257 2 7
NOTES:
UNIT IS SHIPPED FROM THE FACTORY WITH SUPPLY AND RETURN LINES CENTERED LEFT TO RIGHT
ON BACK PANEL. RETURN AND SUPPLY OPENINGS MAY BE SHIFTED 2-9/16” LEFT OR RIGHT TO
ALLOW FOR A BETTER FIT. A SLOTTED HOLE PATTERN IS PROVIDED TO ASSIST WITH CUT OUT OF
OPENINGS AND COVER PLATES ARE ALSO PROVIDED TO COVER EXCESSIVE HOLES LEFT IN BACK
PANEL AFTER MAKING CUT OUTS.
Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data is available upon
request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website or by contacting
Marvair at 229-273-3636. As part of the Marvair continuous improvement program, specifications are subject to change without notice.