1 Transformer Protection
1 Transformer Protection
Transformer Protection
BY
PROF. DR MOUSA ABD-ALLAH
1
4/19/2022
Transformer Faults
Sustained
Winding On-load tap Abnormal and
Tank and
and changer operating uncleared
Core faults accessory
terminal faults conditions external
faults
faults faults
2
4/19/2022
External Conditions
Through Reduced
Overload system Overvoltage system
faults frequency
Differential protection
Overcurrent protection
Overfluxing protection
Thermal protection
Tank-earth protection
3
4/19/2022
4
4/19/2022
Typical range of taps would be +15 to –5% giving an overall range of 20%.
5
4/19/2022
At q = 0 𝜑 = ±𝜑𝑟 + 𝜑𝑚 − 𝜑𝑚 cos(𝜔𝑡)
6
4/19/2022
Most %age differential relay have a bias slope setting of 20%, 30% and 40%
Desired setting is dictated by operating range of OLTC, which is responsible for biggest
voltage unbalance under healthy conditions;
e.g. if OLTC range is +15 to –5% = 20% then 20% bias setting is selected.
7
4/19/2022
8
4/19/2022
Problems encountered in
Differential protection
Type of
Residual flux
Transformer Power system magnetic
before
size size material
energizing
(core)
EX: A 3-phase power transformer having a line voltage ratio of 400V/33kV is connected in Y-Δ.
The CTs on 400V side have current ratio as 1000/5. What must be the CT ratio on 33kV side.
Solution 33kV
1000/5 12.12A
Assume Ip=1000A 1000A 400V
400
𝐼𝑠 = 1000𝑥 = 12.12𝐴
33𝑥103
𝑝𝑟𝑖𝑚𝑎𝑟𝑦 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜 =
𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
12.12
= = 1.4: 1
5 3
9
4/19/2022
10
4/19/2022
EX: Consider 3-, 3-winding transformer. The three windings are rated at: 34.5 kV, ∆, 500MVA;
500 kV, Y, 300MVA; and 138 kV, Y, 200MVA.
500 kV,
500𝑥103 34.5 kV,
Solution 𝐼34.5𝑘𝑉 = = 8367.39 𝐴 500MVA
300MVA
3𝑥34.5
Take CT ratio on primary side = 9000:5 9000/5
Isecondary=5/√3=2.886A, CT ratio=577.35:2.886
Tne nearest standard CTs ratio is 1000:5
2. For 138 kV side, with 500 kV side open, and transformer loaded to 500MVA
500𝑥106
𝐼138𝑘𝑉 = = 2091.85 𝐴 & secondary CT current=5/√3=2.886 A
3𝑥138𝑥103
CT ratio = 2091.85 : 2.886 The nearest standard CT ratio = 3600:5
500𝑥103
3. When transformer is normally loaded, 𝐼34.5𝑘𝑉 = = 8367.39 𝐴
3𝑥34.5
300𝑥103 200𝑥103
𝐼500𝑘𝑉 = = 346.41 𝐴 𝐼138𝑘𝑉 = = 836.74 𝐴
3𝑥500 3𝑥138
11
4/19/2022
Overcurrent relays
12
4/19/2022
If an earth fault occurs just near neutral point, voltage driving fault current will be very
low, result in a low current in primary side of transformer.
Thus differential protection may not operate.
Therefore restricted earth fault protection need more sensitive protection scheme.
Normally the setting of REF protection is kept as low as 5%.
13
4/19/2022
Auto-Transformer Protection
Overfluxing Protection
Transformer overfluxing can be a result of:
1. High system voltage
2. Low system frequency
Magnetic flux in the core increases with either increasing voltage or decreasing frequency
During start up or shutdown of generator-connected transformers, or following a load
rejection, the transformer may subjected to excessive ratio v/f, that is become over excited.
The transformer may operate in a non-linear magnetic region, and creates harmonics in
exciting current.
14
4/19/2022
Transformer Overheating
Transformer operating temperature versus oil life
15
4/19/2022
sudden pressure
frangible disc type
relief valve
16
4/19/2022
RTDs are used for measuring oil temp. and ambient temp.,
but cannot used for measuring Winding temperature
Adjustable compression fitting
RTDs are preferred over thermocouple for measuring temp.
Platinum RTD most common
Older transformers may have copper RTDs
4-wire connections are preferred
3-wire connections are most common and are acceptable if
the resistance of all three wires is identical
17
4/19/2022
Three-winding transformer
18
4/19/2022
19