Quick Quide For CT Saturation Demo
Quick Quide For CT Saturation Demo
CTsaturationDemo.exe
ABB Oy,
Medium Voltage Products
Contents:
1 Starting the tool ................................................................................................... 2
2 Using the tool........................................................................................................ 3
2.1 CT data - parameters..................................................................................... 4
2.2 Fault data + remanence – parameters ........................................................... 5
2.3 Plotting parameters ....................................................................................... 6
2.3.1 Plotting to external window(s) .......................................................... 6
2.4 Saving simulated CT secondary current ....................................................... 8
2.5 Loading disturbance files.............................................................................. 9
3 Case study........................................................................................................... 11
4 Notes .................................................................................................................... 14
5 Testing with real relay – some ideas/hints ....................................................... 15
Copyright 2015 ABB Oy, Medium Voltage Products, Vaasa, FINLAND 1 (15)
Quick guide for CTsaturationDemo.exe
When you run the tool: CTsaturationDemo.exe it will first load the Matlab RunTime
dynamic libraries which can take a long time, with a slow computer even more than half of a
minute.
Please read the text! Then press Enter or click OK and the tool is ready for use.
When simplified CT is selected, the CT rated primary and secondary currents can be given
together with the CT actual accuracy limit factor (ALF, also known as Fa)
In real world, depending on at which point of the sinus-wave the fault occurs there can be
DC component. This can be given with the DC component slider. Worst case situation is
100%. The DC decays with time-constant of fault circuit L/R which can also be set.
When a fault current is broke with the Circuit Breaker, the current tends to break at sinus-
wave zero-crossing. But at this point CT magnetic flux has highest value. Because of this some
flux will remain in the CT after CB opening. This flux is known as remanence. This can be set
in the tool as per cent of the maximum (saturation point) flux. Often remanence is not
considered (=0%). In practice, it is assumed to be 40% or less.
Note: if the primary current has been loaded from the Comtrade file, only the CT remanence
can be set and the Fault current shows “Comtrade file” with green background. Entering a
number for the fault current puts simulation back to normal (i.e. ends using comtrade data).
Sample frequency is recommended to be at least 2000 Hz (i.e. 2000 samples per second), but
especially when studying CT heavy saturation, higher value like 30 000 Hz give more accurate
output.
Tool can also show the CT magnetic flux (but without any numeric value) this is handy when
studying effect of DC component.
Measuring modes
- DFT = calculated fundamental frequency component value
- TrueRMS = RMS value (includes DC-component)
- Peak-to-Peak = current value using peak-to-peak measuring principle
External window has some nice tools in the toolbar, for example
- zoom
- data cursors
o Select Data Cursors from the toolbar, then point with mouse to any point in the
curve(s) and mouse left-click. This adds datatip with values from X and Y axis
o right mouse-click to create more data cursors, or removing them
The current injection device (like Omicron) might not be able to give out high current values,
but with the “Max current” parameter can be used to limit max current values. In practice it
means cutting the current.
When “Create COMTRADE files” is pressed the program asks for filename. The tool will then
create .DAT and .CFG files.
Clicking the “Load Comtrade” button opens new window which can be used to load data
from the disturbance file to be used as primary current for the CT simulation.
You can now load data to the CT simuation with the “Load and simulate” button.
It is also possible to select only part of the data by clicking the “Set X-range” button. Next
you must show starting point and click mouse, then show the end point and click mouse
again. The tool will then take data from that part only
Note: when the primary current has been loaded from the Comtrade file, only the CT
remanence can be set and the Fault current shows “Comtrade file” with green background.
Entering a number for the fault current puts simulation back to normal (i.e. ends using
comtrade data).
3 Case study
Motor feeder is protected against short-circuit with a non-directional overcurrent protection
function set for 5.0kA 0.050 sec. CT is 400/5A having actual ALF = 26. The incoming feeder
has non-directional overcurrent relay set for 7.3kA 0.25 sec. Assume 2-phase fault, DC time-
constant 0.06 sec, 50Hz network, no CT remanence.
- Will CT saturate at 5kA fault current, will it delay relay operation?
- Will CT saturate at 7.3kA fault current, will it delay relay operation and how much?
- Assume maximum fault current 40kA, will relay operate correctly?
The actual ALF tells that CT will saturate at 26 x 400A = 10.4kA in case there is no DC
component. But DC component will cause CT to saturate at much lower fault current level.
At 5kA fault level, we can see that the CT saturates before the positive side peak values is
reached, which means that relay will not see current value correctly. Only after about 0.1
sec, as the DC component decays, the CT recovers enough and we can expect relay to pick-
up. Expected relay operation time at 5kA is therefore 0.1 + 0.05 = 0.15 sec
At 7.3kA we can see from the peak-to-peak estimation, that at begin of the fault, relay (set
for 5kA) will pick-up, but at about 0.025 sec it will reset because of the CT saturation. Relay
will pick-up again at about 0.045 sec. We can expect relay to operate at 0.045 + 0.05 = 0.09
sec.
Assuming the CT in the incoming do not saturate, its relay will operate at 0.25 sec. We have
0.25 sec - 0.09 sec = 0.16 sec in between, which must cover: relay operation time tolerances,
breaker opening time, retardation time in the relay of incoming feeder and some safety
margin.
At 40kA, the peak-to-peak estimation indicates that relay will see current correctly, but we
must also check protection relay performance of detecting short peaks of the saturated CT
secondary current. In this case the width of the peak seems to be about 3 ms or more, which
generally is enough for a non-directional overcurrent relay.
4 Notes
This tool is not accurate.
- Using the predefined CTs give more accurate results. The simulation is based on the
CT data received ABB CT manufacturing (before CT manufacturing was transferred
from Vaasa)
- Peak-to-peak calculation is simplified and has no filtering. It also assumes that relay
can see the peak values. In reality if the width of the peak is too narrow, relay might
not see peak value correctly
- Peak-to-peak, RMS and DFT are calculated over 1 fundamental cycle without any
further smoothing/filtering. Actual IED can use for wider calculation window and/or
smoothing/filtering.
- The tool gives out (in Comtrade format) only 1 phase. Thus only 1 and 2-phase short-
circuits can be simulated with a real relay (In a 2-phase short-circuit, the two phases
are equal but have opposite direction).
- The simulation is not accurate, which means that if this tool is used for testing the
relay performance, some errors must be accepted. When testing the CT + relay
performance for example with 12.5kA fault current, it is therefore advisable to higher
value, like 15kA instead. This gives some safety margin.
- Especially when testing relay performance with saturated CT waveforms, the “Sample
rate” parameter in the tool is important. Also it must be noted that it is not enough
to test something only once. Tests should be repeated at least about 50 times for
ensuring that operation is correct every time.
- It is also advisable to use relay disturbance recording for capturing the actual
waveform used in tests. This can reveal possible mistakes in scaling or weak
performance of the current injection device.