M Thermal Mono Series
M Thermal Mono Series
Service
Manual
M thermal Mono Series
CONTENTS
CONTENTS
202004 1
Midea CAC Confidential
M thermal Mono
Midea M thermal Mono Service Manual
2 202004
Midea CAC Confidential
M thermal Mono
CONTENTS
202004 3
Midea CAC Confidential
M thermal Mono
Part 1
General Information
1 Unit Capacities and External Appearance .............................................. 4
202004 3
Midea CAC Confidential
M thermal Mono
1 Unit Capacities and External Appearance
1.1 Unit Capacities
Table 1-1.1: Capacity range
Capacity 4kW 6kW 8kW 10kW 12kW 14kW 16kW
1
Model
V4W V6W V8W V10W V12W V14W V16W
(MHC-*/D2N82)
4 202004
Midea CAC Confidential
M thermal Mono
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components .............................................................. 6
202004 5
Midea CAC Confidential
M thermal Mono
1 Layout of Functional Components
MHC-V4W/D2N8-B / MHC-V6W/D2N8-B
Figure 2-1.1: MHC-V4(6)W/D2N8-B top view
Midea M thermal Mono Service Manual
6 202004
Midea CAC Confidential
M thermal Mono
Figure 2-1.3: MHC-V4(6)W/D2N8-B
202004 7
Midea CAC Confidential
M thermal Mono
MHC-V8W/D2N8-B / MHC-V10W/D2N8-B
Figure 2-1.1: MHC-V8(10)W/D2N8-B top view
Midea M thermal Mono Service Manual
8 202004
Midea CAC Confidential
M thermal Mono
MHC-V12W/D2N8-B / MHC-V14W/D2N8-B / MHC-V16W/D2N8-B
Figure 2-1.4: MHC-V12(14, 16)W/D2N8-B top view
10 202004
Midea CAC Confidential
M thermal Mono
2 Piping Diagrams
Figure 2-2.1: MHC-V4 (6) W/D2N8-B / MHC-V12( 14, 16) W/D2N8-B / MHC-V12 (14, 16) W/D2RN8-B piping diagram
Safety valve Air purge valve Pump
T2b F
Twout
Flow switch
Evaporator
Manometer
Expansion vessel
T2
Twin
Filter
Pressure sensor
EXV Filter
c
High-pressure switch
Low-pressure switch T4
Figure 2-2.2: MHC-V8(10) W/D2N8-B / MHC-V12( 14, 16) W/D2N8-B / MHC-V12 (14, 16) W/D2RN8-B piping diagram
Safety valve Air purge valve Pump
T2b F
Twout
Flow switch
Evaporator
Manometer
Expansion vessel
T2
Twin
Filter
Pressure sensor
EXV Filter
e
DC motor
d s
c
High-pressure switch
Low-pressure switch T4
202004 11
Midea CAC Confidential
M thermal Mono
Key components:
1. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
2. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
3. Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the air side heat
exchanger functions as a condenser and water side heat exchanger functions as an evaporator; when open, the air
side heat exchanger functions as an evaporator and water side heat exchanger function as a condenser.
4. High and low pressure switches:
Regulate refrigerant system pressure. When refrigerant system pressure rises above the upper limit or falls below the
lower limit, the high or low pressure switches turn off, stopping the compressor.
5. Air purge valve:
Automatically removes air from the water circuit.
6. Safety valve:
Prevents excessive water pressure by opening at 43.5 psi (3 bar) and discharging water from the water circuit.
Midea M thermal Mono Service Manual
7. Expansion vessel:
Balances water system pressure. (Expansion vessel volume: 8L)
8. Water flow switch:
Detects water flow rate to protect compressor and water pump in the event of insufficient water flow.
9. Backup heater:
Provides additional heating capacity when the heating capacity of the heat pump is insufficient due to very low
outdoor temperature. Also protects the external water piping from freezing.
10. Water pump:
Circulates water in the water circuit.
12 202004
Midea CAC Confidential
M thermal Mono
3 Refrigerant Flow Diagrams
Heating and domestic hot water operation(4,6KW for example)
Figure 2-3.1: Refrigerant flow during heating or domestic hot water operation
202004 13
Midea CAC Confidential
M thermal Mono
Midea M thermal Mono Service Manual
14 202004
Midea CAC Confidential
M thermal Mono
Part 3
Control
1 Stop Operation ........................................................................................ 16
Part 3 - Control
7 Role of Temperature Sensors in Control Functions ................................... 28
202004 15
Midea CAC Confidential
M thermal Mono
1 Stop Operation
The stop operation occurs for one of the following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off’ operation and an error code is displayed on the outdoor unit PCB digital displays and on the user
interface.
2. The system stops when the set temperature has been reached.
2 Standby Control
2.1 Crankcase Heater Control
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped.
The crankcase heater is controlled according to outdoor ambient temperature and the compressor on/off state. When the
outdoor ambient temperature is above 8°C or the compressor is running, the crankcase heater is off; when the outdoor
ambient temperature is at or below 8°C and either the compressor has been stopped for more than 3 hours or the unit has
just been powered-on (either manually or when the power has returned following a power outage), the crankcase heater
Midea M thermal Mono Service Manual
turns on.
16 202004
Midea CAC Confidential
M thermal Mono
3 Startup Control
3.1 Compressor Startup Delay Control
In initial startup control and in restart control (except in oil return operation and defrosting operation), compressor startup
is delayed such that a minimum of the set re-start delay time has elapsed since the compressor stopped, in order to
prevent frequent compressor on/off and to equalize the pressure within the refrigerant system. The compressor re-start
delays for cooling and heating modes are set on the user interface. Refer to the M thermal Mono Engineering Data Book
Part 3, 7.5 “COOL MODE SETTING Menu” and Part 3, 7.6 “HEAT MODE SETTING Menu”.
Figure 3-3.1: 4-6kW to 12-16kW Compressor startup program1,2 when ambient temperature is above 3°C
Hz TARGET FREQUENCY
目标频率
90
82Hz
80 120S
70Hz
70 66Hz
120S
60 40S
56Hz
50 40S
42Hz
40 38Hz 40S
40S 32Hz
Part 3 - Control
30 60S
20
10 TIME
时间
Figure 3-3.2: 8-10kW Compressor startup program1,2 when ambient temperature is above 11°C
Hz TARGET FREQUENCY
目标频率
82Hz
70Hz 120S
40S
66Hz
40S
56Hz
40S
42Hz 42Hz
90S 40S
36Hz TIME
60S 时间
202004 17
Midea CAC Confidential
M thermal Mono
Figure 3-3.3: 4-10KW compressor startup program1 when ambient temperature is at or below
3°C(4-6KW)/11°C(8-10KW)
TARGET FREQUENCY
TIME
Figure 3-3.4: 12-16KW compressor startup program1 when ambient temperature is at or below 3°C
TARGET FREQUENCY
Midea M thermal Mono Service Manual
TIME
Notes:
1. Once the first, 40-second stage of the program is complete, the program proceeds to the subsequent stages in a
step-by-step fashion and exits when the target rotation speed has been reached.
3.3 Startup Control for Heating and Domestic Hot Water Operation
Table 3-3.1: Component control during startup in heating and domestic hot water modes
Wiring diagram 8/10/12/
Component 4/6kW Control functions and states
label 14/16kW
Compressor startup program selected according to
Inverter compressor COMP ● ●
ambient temperature1
DC fan motor FAN ● ● Fan runs at maximum speed2
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to outdoor ambient
Electronic expansion valve EXV ● ●
temperature, discharge temperature and suction
superheat
Four-way valve ST ● ● On
18 202004
Midea CAC Confidential
M thermal Mono
4 Normal Operation Control
4.1 Component Control during Normal Operation
Table 3-4.1: Component control during heating and domestic hot water operations
Wiring diagram
Component 4/6kW 8/10/12/14/16kW Control functions and states
label
Controlled according to load requirement from
Inverter compressor COMP ● ●
hydronic system
Controlled according to outdoor heat exchanger
DC fan motor FAN ● ●
pipe temperature
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge
Electronic expansion valve EXV ● ●
temperature, suction superheat and compressor
speed
Four-way valve ST ● ● On
Part 3 - Control
Controlled according to outdoor heat exchanger
DC fan motor FAN ● ●
pipe temperature
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge
Electronic expansion valve EXV ● ●
temperature, suction superheat and compressor
speed
Four-way valve ST ● ● Off
During operation the compressor speed is controlled according to the rate of change in water temperature, the refrigerant
system pressure and the refrigerant temperature.
202004 19
Midea CAC Confidential
M thermal Mono
4.4 Four-way Valve Control
The four-way valve is used to change the direction of refrigerant flow through the water side heat exchanger in order to
switch between cooling and heating/DHW operations.
During heating and DHW operations, the four-way valve is on; during cooling and defrosting operations, the four-way
valve is off.
20 202004
Midea CAC Confidential
M thermal Mono
4.7 Spray liquid cooling control
When the discharge temperature of compressor exceeds 105℃, the solenoid valve opens and the frequency of
compressor drops in order to reduce the discharge temperature. When the discharge temperature is below 100℃, the
solenoid valve closes.
If the discharge temperature exceeds 108℃ while the spray liquid cooling control is in progress, which is judged every 20s,
the frequency of compressor drops 4Hz until the minimum frequency which differs from every model. When the discharge
temperature is below 101℃, the compressor runs at the current frequency.
5 Protection Control
5.1 High Pressure Protection Control
This control protects the refrigerant system from abnormally high pressure and protects the compressor from transient
spikes in pressure.
Figure 3-5.1: High pressure protection control
Normal operation
Part 3 - Control
Notes:
1. Pc: Discharge pressure
When the discharge pressure rises above 4.3MPa the system displays P1 protection and the unit stops running. When the
discharge pressure drops below 3.6MPa, the compressor enters re-start control.
Normal operation
Notes:
1. Pe: Suction pressure
When the suction pressure drops below 0.14MPa the system displays P0 protection and the unit stops running. When the
suction pressure rises above 0.3MPa, the compressor enters re-start control.
202004 21
Midea CAC Confidential
M thermal Mono
5.3 Discharge Temperature Protection Control
This control protects the compressor from abnormally high temperatures and transient spikes in temperature.
Normal operation
When the discharge temperature rises above 115°C the system displays P4 protection and the unit stops running. When
the discharge temperature drops below 95°C, the compressor enters re-start control.
Normal operation
When the discharge temperature is lower than suction temperature for more than 5 minutes, the system displays EA
protection and the unit stops running. When the discharge temperature is higher than suction temperature, the
compressor enters re-start control.
Normal operation
When the compressor current rises above Currentmax the system displays P3 protection and the unit stops running. When
the compressor current drops below Currentmax, the compressor enters re-start control.
22 202004
Midea CAC Confidential
M thermal Mono
5.5 Voltage Protection Control
This control protects the M thermal Mono from abnormally high or abnormally low voltages.
Normal operation
Voltage ≥ 265V
254V < Voltage < 187V
or Voltage ≤ 172V
When the phase voltage of AC power supply is at or above 265V for more than 30 seconds, the system displays H7
protection and the unit stops running. When the phase voltage drops below 265V for more than 30 seconds, the
refrigerant system restarts once the compressor re-start delay has elapsed. When the phase voltage is at or below 172V,
the system displays H7 protection and the unit stops running. When the AC voltage rises to at or more than 187V, the
refrigerant system restarts once the compressor re-start delay has elapsed.
Part 3 - Control
Outdoor ambient temperature is at or above 4°C and actual fan speed differs from target fan speed by more than
200rpm for more than 3 minutes.
Outdoor ambient temperature is below 4°C and actual fan speed differs from target fan speed by more than 300rpm
for more than 3 minutes.
Actual fan speed is less than 150rpm for more than 90 seconds.
When DC fan motor protection control occurs the system displays the H6 error code and the unit stops running. After 3
minutes, the unit restarts automatically. When H6 protection occurs 10 times in 120 minutes, the HH error is displayed.
When an HH error occurs, a manual system restart is required before the system can resume operation.
In heating mode, if the outdoor temperature falls below 3°C and either the water side heat exchanger water inlet
temperature or water side heat exchanger water outlet temperature are below 25°C, the water side heat exchanger
electric heater turns on. When the outdoor ambient temperature rises above 5°C and either the water side heat exchanger
water inlet temperature or water side heat exchanger water outlet temperature are above 30°C, the water side heat
exchanger turns off.
When water side heat exchanger anti-freeze protection occurs the system displays error code Pb and the unit stops
running.
202004 23
Midea CAC Confidential
M thermal Mono
5.8 Module Temperature Protection Control
This control protects the module from abnormally high temperatures.
Normal operation
When the module temperature rises at or above Tf2 the system displays C7 protection and the unit stops running. When
the module temperature drops at or below Tf0-1, the compressor enters re-start control.
Tf2 75 81 100 84
Tf0 69 75 94 78
24 202004
Midea CAC Confidential
M thermal Mono
6 Special Control
6.1 Oil Return Operation
In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor and into the refrigerant piping. When the oil return operation is being conducted, the
outdoor unit refrigerant system main PCB displays code d0.
The oil return operation ceases when any one of the following three conditions occurs:
Oil return operation duration reaches 5 minutes.
Compressor stops.
Mode change command is received.
Tables 3-6.1 show component control during oil return operation in cooling mode.
Table 3-6.1: Outdoor unit component control during oil return operation in cooling mode
Wiring diagram 8/10/12/
Component 4/6kW Control functions and states
label 14/16kW
Inverter compressor COMP ● ● Runs at oil return operation rotation speed
Controlled according to outdoor heat exchanger pipe
DC fan motor FAN ● ●
temperature
Part 3 - Control
Electronic expansion valve EXV ● ● 304 (steps)
Four-way valve ST ● ● Off
Tables 3-6.2 show component control during oil return operation in heating and DHW modes.
Table 3-6.2: Outdoor unit component control during oil return operation in heating and DHW modes
Wiring diagram 8/10/12/
Component 4/6kW Control functions and states
label 14/16kW
Inverter compressor COMP ● ● Runs at oil return operation rotation speed
Controlled according to outdoor heat exchanger pipe
DC fan motor FAN ● ●
temperature
Electronic expansion valve EXV ● ● 304 (steps)
Four-way valve ST ● ● On
Domestic hot water demand priority can be ended by changing the switch on controller from "on" to "off".
Two zones control function is used to control temperature of each zone separately, thus different type radiator will operate
at its optimal temperature and water pump cycle time will be reduced to save energy.
In two zones control for cooling mode, when the setting temperature of a certain zones is reached, the zone and water
pump of this zone will turn off.
In two zones control for heating mode, the on/off control of zone and water pump is same with cooling mode, but in
addition, the mixing valve (3-way valve SV3) control function will be activated to adjust the water temperature of the low
temperature zone by control the opening time and closing time of the valve. The mixing valve will only turn on when two
zones control for heating is activated. On other conditions, the mixing valve will keep off.
When the valve initially turns on, the opening time and closing time is same and then the time is controlled according to
the difference between water pipe temperature and setting water temperature of the controlling zone.
26 202004
Midea CAC Confidential
M thermal Mono
6.5 Smart grid control
Unit adjusts the operation according to different electrical signals to realize energy saving.
Free electric energy signal: DHW mode turn on, the setting temperature will be changed to 70℃ automatically, and the
TBH operate as below:T5<69. the TBH is on, T5 ≥ 70, the TBH is off. The unit operate in cooling/heating mode as the
normal logic.
Expensive electric energy signal: only available for cooling or heating mode and user can set the maximum operating time.
6.6 Balance tank temperature control
Balance tank temperature sensor is used to control on/off of heat pump.
Once the heat pump stops, internal pump stops to save energy and then balance tank provides hot water for space heating.
In addition, balance tank temperature control can meet both space heating and domestic hot water needs at the same
time. Balance tank can store energy to provide hot water whilst heat pump runs heat mode/cooling, which can reduce the
host selection and the initial investment.
Part 3 - Control
Parameter setting transmission between wired controllers
Installer can quickly copy the setting from one controller to another via USB, which save the time of on-site installation.
202004 27
Midea CAC Confidential
M thermal Mono
7 Role of Temperature Sensors in Control Functions
Figure 3-7.1: Location of the temperature sensors on 4~16KW unit systems
Solenoid valve
capillary
Midea M thermal Mono Service Manual
Notes:
1. The names and functions of the temperature sensors labelled 1 to 12 in this figure are detailed in
Table 3-6.1.
28 202004
Midea CAC Confidential
M thermal Mono
Table 3-7.1: Names and functions of the temperature sensors
Sensor
Number Sensor name1 Mode Control functions
code
Electronic expansion valve control2
Heating
Discharge superheat control
Discharge pipe temperature
1 Tp Electronic expansion valve control2
sensor
Cooling Outdoor fan control3
Discharge superheat control
Compressor startup control4
Compressor output control5
Electronic expansion valve control2
Heating
Defrosting operation control7
Low pressure protection control7
Outdoor ambient temperature
2 T4 Crankcase heater control9
sensor
Compressor startup control4
Compressor output control5
Cooling Electronic expansion valve control2
Outdoor fan control3
Crankcase heater control9
Electronic expansion valve control2
Air side heat exchanger Heating Defrosting operation control7
3 refrigerant outlet temperature T3 Outdoor fan control3
sensor Compressor output control5
Cooling
Outdoor fan control3
Water side heat exchanger Heating
4 refrigerant inlet (liquid pipe) T2 Compressor output control5
temperature sensor DHW
Water side heat exchanger
5 refrigerant outlet (gas pipe) T2B Heating Freeze prevention control10
Part 3 - Control
temperature sensor
Suction pipe temperature Heating
6 Th Electronic expansion valve control2
sensor Cooling
Water side heat exchanger Heating
7 water inlet temperature Tw_in Freeze prevention control10
sensor Cooling
Water side heat exchanger Heating
Compressor output5 and on/off control6
8 water outlet temperature Tw_out Cooling
Freeze prevention control10
sensor DHW
Compressor output control5
Backup electric heater control
Heating
DHW priority control11
Auto mode control
Backup electric heater water
9 T1 Compressor output5 and on/off control6
outlet temperature sensor Cooling
Auto mode control
Compressor output control5
DHW Backup electric heater control
DHW priority control11
Circuit 2 water outlet
10 T1B Heating Mixing valve control
temperature sensor
Heating Auto mode control
Room temperature sensor
11 Ta Climate related curve
Built in wire controller Cooling Compressor output control5
Disinfection operation control
DHW tank immersion heater control
Backup electric heater control
Domestic hot water tank
12 T5 DHW Auxiliary heat source control
temperature sensor
Solar energy kit control
Compressor output control5
DHW priority control11
Notes:
1. Sensor names in this service manual referring to refrigerant flow is 6. Refer to Part 3, 1 “Stop Operation”.
named according refrigerant flow during cooling operation refer to 7. Refer to Part 3, 6.2 “Defrosting Operation”.
Part 2, 3 “Refrigerant Flow Diagrams”. 8. Refer to Part 3, 5.2 “Low Pressure Protection Control”.
2. Refer to Part 3, 4.5 “Electronic Expansion Valve Control”. 9. Refer to Part 3, 2.1 “Crankcase Heater Control”.
3. Refer to Part 3, 4.6 “Outdoor Fan Control”. 10. Refer to Part 3, 2.2 “Freeze Prevention Control”.
4. Refer to Part 3, 3 “Startup Control”. 11. Refer to Part 3, 6.4 “Fast DHW Operation”.
5. Refer to Part 3, 4.2 “Compressor Output Control”.
202004 29
Midea CAC Confidential
M thermal Mono
Midea M thermal Mono Service Manual
30 202004
Midea CAC Confidential
M thermal Mono
Part 4
Diagnosis and
Troubleshooting
1 Outdoor Unit Electric Control Box Layout ................................................. 32
4 Troubleshooting ....................................................................................... 52
202004 31
Midea CAC Confidential
M thermal Mono
1 Outdoor Unit Electric Control Box Layout
MHC-V4W/D2N8-B / MHC-V6W/D2N8-B
Figure 4-1.1: Electric control box front view
Main PCB for refrigerant system Main PCB for hydronic system
Midea M thermal Mono Service Manual
32 200204
Midea CAC Confidential
M thermal Mono
MHC-V8W/D2N8-B / MHC-V10W/D2N8-B
Figure 4-1.2: Electric control box front view
Main PCB for refrigerant system Main PCB fort hydronic system
Inverter module Outdoor unit power supply terminals Communication terminal blocks
Inverter module
202004 33
Midea CAC Confidential
M thermal Mono
MHC-V12W/W/D2RN8-B / MHC-V14W/W/D2RN8-B / MHC-V16W/W/D2RN8-B
Figure 4-1.4: Electric control box front view
Main PCB for refrigerant system Main PCB for hydronic system
Midea M thermal Mono Service Manual
34 200204
Midea CAC Confidential
M thermal Mono
2 Outdoor Unit PCBs
2.1 Types
M thermal Mono outdoor units have two main PCBs – one for the hydronic system and one for the refrigerant system. The
hydronic system main PCB is the same on all M thermal Mono models.
The locations of each PCB in the outdoor unit electric control boxes are shown in Figures 4-1.1 to 4-1.4 in Part 4, 1
“Outdoor Unit Electric Control Box Layout”.
11
1 12
13
14
15
30
29
16
28
17
27
18
26 19
25 22 20
21
24 31 23 22
202004 35
Midea CAC Confidential
M thermal Mono
Table 4-2.1: Main PCB for hydronic system
Label in Figure
Code Content
4-2.1
1 CN21 Port for power supply
2 S3 Rotary dip switch
3 DIS1 Digital display
4 CN5 Port for ground
5 CN28 Port for internal pump
6 CN25 Port for IC programming
7 S1,S2,S4 Dip switch
8 CN4 Port for USB
9 CN8 Flow switch
10 CN6 Port for temp. sensors (T2,T2B,TW_out,TW_in, T1,)
11 CN24 Port for temp. sensor(Tbt1, The balanced water tank of up temp. sensor)
12 CN16 Port for temp. sensor(Tbt2, The balanced water tank of up temp. sensor)
13 CN13 Port for temp. sensor(T5, domestic hot water tank temp. sensor)
Midea M thermal Mono Service Manual
14 CN15 Port for temp. sensor(Tw2, The outlet water for zone 2 temp. sensor)
15 CN18 Port for temp. sensor(Tsolar, Solar panel temp. sensor)
16 CN17 Port for internal pump
Control port for room thermostat (heating mode)(HT)/Control port for room thermostat (cooling
17 CN31
mode)(CL)/Power port for room thermostat(COM)
18 CN35 Port for smart grid (grid signal, photovoltaic signal)
19 CN36 Port for remote switch, temperature board
20 CN19 Communicate port between indoor unit and outdoor unit
21 CN14 Port for communication with the wired controller
Communicate port between indoor unit and outdoor unit, port for communication with the wired
22 CN30
controller, internal machine parallel
23 CN7 Port for antifreeze E-heating tape(external), additional heat source, compressor run/defrost run
Control port for tank booster heater, internal backup heater 1, input port for solar energy, Port for room
24 CN11 thermostat, SV1(3-way valve), SV2(3-way valve), SV3(3-way valve), zone 2 pump, outside circulation
pump, solar energy pump, DHW pipe pump,
25 CN2 Feedback port for external temp. switch(shorted in default)
26 CN1 Feedback port for temperature switch
27 CN22 Control port for backup heater/booster heater
28 CN41 Port for anti-freeze electric heating tape
29 CN42 Port for anti-freeze electric heating tape
30 CN29 Port for anti-freeze electric heating tape
31 IC39 EEPROM
36 200204
Midea CAC Confidential
M thermal Mono
2.3 Main PCBs for Refrigerant System, Inverter Modules and filter board
MHC-V4W/D2N8-B / MHC-V6W/D2N8-B / MHC-V8W/D2N8-B / MHC-V10W/D2N8-B
Figure 4-2.2: MHC-V4(6,8,10)W/D2N8-B outdoor unit main PCB for refrigerant system
4 5 6 7 8 9 10
11
2 12
13
1 14
15
16
17
18
19
27 26 25 24 23 22 21 20
202004 37
Midea CAC Confidential
M thermal Mono
Table 4-2.2: MHC-V4(6,8,10)W/D2N8-B outdoor unit main PCB for refrigerant system
Label in Figure
Code Content
4-2.2
1 CN28 Output port L to MAIN CONTROL BOARD FOR REFRIGERANT SYSTEM
2 CN22 Reserved
3 CN27 Output port N to MAIN CONTROL BOARD FOR REFRIGERANT SYSTEM
4 CN3 Reserved
5 PE2 Port for ground wire
6 DSP1 Digital display
7 CN17 Port for communication with MAIN CONTROL BOARD FOR REFRIGERANT SYSTEM
8 PE1 Port for ground wire
9 CN26 Port for IC programming
10 CN10 Input port for neutral wire
11 CN11 Input port for live wire
12 CN9 Port for outdoor ambient temp. sensor and condenser temp. sensor
13 CN24 Input port for +12V/9V
Midea M thermal Mono Service Manual
38 200204
Midea CAC Confidential
M thermal Mono
Figure 4-2.3: MHC-V4(6)W/D2N8-B outdoor unit inverter module
1 2 3
6 9
202004 39
Midea CAC Confidential
M thermal Mono
Figure 4-2.3: MHC-V8(10)W/D2N8-B outdoor unit inverter module
1 2 3
8
Midea M thermal Mono Service Manual
6 9
40 200204
Midea CAC Confidential
M thermal Mono
MHC-V12W/D2N8-B / MHC-V14W/D2N8-B / MHC-V16W/D2N8-B
Figure 4-2.4: MHC-V12( 14, 16)W/D2N8-B outdoor unit main PCB for refrigerant system1
4 5 6 7 8 9 10
11
2 12
13
1 14
15
16
17
18
19
27 26 25 24 23 22 21 20
202004 41
Midea CAC Confidential
M thermal Mono
Table 4-2.4: MHC-V12(14, 16)W/D2N8-B outdoor unit main PCB for refrigerant system
Label in Figure
Code Content
4-2.3
1 CN28 Output port L to MAIN CONTROL BOARD FOR REFRIGERANT SYSTEM
2 CN22 Reserved
3 CN27 Output port N to MAIN CONTROL BOARD FOR REFRIGERANT SYSTEM
4 CN3 Reserved
5 PE2 Port for ground wire
6 DSP1 Digital display
7 CN17 Port for communication with MAIN CONTROL BOARD FOR REFRIGERANT SYSTEM
8 PE1 Port for ground wire
9 CN26 Port for IC programming
10 CN10 Input port for neutral wire
11 CN11 Input port for live wire
12 CN9 Port for outdoor ambient temp. sensor and condenser temp. sensor
13 CN24 Input port for +12V/9V
Midea M thermal Mono Service Manual
42 200204
Midea CAC Confidential
M thermal Mono
Figure 4-2.5: MHC-V12( 14, 16)W/D2N8-B outdoor unit inverter module
1 2 3 4
10 9 11 8
202004 43
Midea CAC Confidential
M thermal Mono
MHC-V12W/W/D2RN8-B / MHC-V14W/W/D2RN8-B / MHC-V16W/W/D2RN8-B
Figure 4-2.6: MHC-V12(14, 16)W/W/D2RN8-B outdoor unit main PCB for refrigerant system 1
1 2 3 4 5 6 7 8
3 9
10
1
11
12
Midea M thermal Mono Service Manual
13
28 27 26 25 24 23 22 21 20 19 18 17 16 15 14
44 200204
Midea CAC Confidential
M thermal Mono
Table 4-2.6: MHC-V12(14, 16)W/W/D2RN8-B outdoor unit main PCB for refrigerant system
Label in Figure
Code Content
4-2.4
1 CN38 Port for GND
2 CN27 Port for 2-way valve 5
3 CN20 Port for 2-way valve 6
4 CN10 Port for electric heating tape1
5 CN7 Port for electric heating tape2
6 CN11 Port for IC programming
7 CN18 Port for 4-way value
8 CN21 Power supply port for hydro-box control board
9 CN41 Power supply port for FILTER BOARD
10 CN26 Port for communication with Power Meter
11 CN24 Port for communication with hydro-box control board
12 CN4 Port for communication with INVERT MODULE BOARD
13 CN6 Port for pressure sensor
CN36 Port for communication with MAIN CONTROL BOARD FOR REFRIGERANT
14
SYSTEM(CN36)
15 CN4 Port for temp.sensor Tp(CN4)
16 CN8 Port for temp.sensor Th(CN8)
17 CN9 Port for outdoor ambient temp. sensor and condenser temp.sensor(CN9)
18 DSP1 Digital display(DSP1)
19 S5,S6 DIP switch(S5,S6)
20 CN31 Port for high pressure switch(CN31)
21 CN29 Port for low pressure switch and quick check(CN29)
22 S3 Rotary dip switch(S3)
23 CN35 Port for temp.sensors(TW_out, TW_in, T1, T2,T2B )
24 CN28 Port for communication XYE
25 S5, S6 DIP switch
26 CN37 Port for communication D1D2E
27 CN22 Port for electrical expansion value
28 CN30 Port for fan 15VDC power supply
29 CN53 Port for fan 310VDC power supply
30 CN107 Port for fan
202004 45
Midea CAC Confidential
M thermal Mono
Figure 4-2.7: MHC-V12(14, 16)W/W/D2RN8-B outdoor unit inverter module
2 3 4 5 6 7 8
9
Midea M thermal Mono Service Manual
14
13 12 11 10
46 200204
Midea CAC Confidential
M thermal Mono
Figure 4-2.8: MHC-V12(14, 16)W/W/D2RN8-B outdoor unit filter board
5 67 8 9 10
11
2
12
13
16 15 14 13
202004 47
Midea CAC Confidential
M thermal Mono
2.4 Digital Display Output
Table 4-2.9: Digital display output in different operating states
Parameters displayed on hydronic Parameters displayed on refrigerant
Outdoor unit state
system DSP1 system DSP1
On standby 0 0
Running speed of the compressor in
Normal operation Leaving water temperature (°C)
rotations per second
Error or protection Error or protection code Error or protection code
48 200204
Midea CAC Confidential
M thermal Mono
3 Error Code Table
Table 4-3.1: Error code table
Error Serial
Content1 Displayed on Remarks
code number
Transducer module temperature too high User interface and refrigerant system
C7 65 Contact your local dealer
protect main PCB
E0 1 User interface and hydronic system
Water flow failure
E8 9 main PCB
User interface and refrigerant system Only applies to 3-phase
E1 2 Phase sequence error
main PCB models
Communication error between outdoor unit User interface and hydronic system
E2 3
and user interface main PCB
Backup electric heater exchanger water User interface and hydronic system
E3 4 Sensor T1
outlet temperature sensor error main PCB
Domestic hot water tank temperature sensor User interface and hydronic system
E4 5 Sensor T5
error main PCB
Air side heat exchanger refrigerant outlet User interface and refrigerant system
E5 6 Sensor T3
temperature sensor error main PCB
User interface and refrigerant system
E6 7 Outdoor ambient temperature sensor error Sensor T4
main PCB
User interface and refrigerant system
E9 10 Suction pipe temperature sensor error Sensor Th
main PCB
User interface and refrigerant system
EA 11 Discharge pipe temperature sensor error Sensor Tp
main PCB
Water side heat exchanger water inlet User interface and hydronic system
Ed 14 Sensor Tw_in
temperature sensor error main PCB
User interface and hydronic system
EE 15 Hydronic system EEPROM error
main PCB
User interface and refrigerant system
F1 116 DC bus voltage is too low
main PCB
Communication error between refrigerant User interface, refrigerant system
H0 39 system main control chip and hydronic main control board for refrigerant
system main control chip system and hydronic system main PCB
Communication error between refrigerant
User interface and refrigerant system
H1 40 system main control chip and inverter driver
main PCB
chip
Water side heat exchanger refrigerant inlet User interface and hydronic system
H2 41 Sensor T2
(liquid pipe) temperature sensor error main PCB
Water side heat exchanger refrigerant outlet User interface and hydronic system
H3 42 Sensor T2B
(gas pipe) temperature sensor error main PCB
User interface and hydronic system
H5 44 Room temperature sensor error Sensor Ta
main PCB
H6 45 User interface and refrigerant system
DC fan error
HH 55 main PCB
User interface and refrigerant system
H7 46 Abnormal main circuit voltage
main PCB
202004 49
Midea CAC Confidential
M thermal Mono
Table continued on next page …
Table 4-3.1: Error code table (continued)
User interface and refrigerant system
H8 47 Pressure sensor error
main PCB
Zone 2 water outlet temperature sensor User interface and hydronic system
H9 48 Sensor T1B
error main PCB
Water side heat exchanger water outlet User interface and hydronic system
HA 49 Sensor Tw_out
temperature sensor error main PCB
User interface and refrigerant system
HF 54 Refrigerant system EEPROM error
main PCB
P0 20 User interface and refrigerant system
Low pressure protection
HP 57 main PCB
User interface and refrigerant system
P1 21 High pressure protection
main PCB
User interface and refrigerant system
P3 23 Compressor current protection
main PCB
Midea M thermal Mono Service Manual
50 200204
Midea CAC Confidential
M thermal Mono
202004 51
Midea CAC Confidential
M thermal Mono
4 Troubleshooting
4.1 Warning
Warning
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
Midea M thermal Mono Service Manual
52 200204
Midea CAC Confidential
M thermal Mono
4.2 E0, E8 Troubleshooting
Digital display output
Description
Water flow failure.
E0 indicates E8 has displayed 3 times. When an E0 error occurs, a manual system restart is required before the system
can resume operation.
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
The wire circuit is short connected or open.
Water flow rate is too low.
Water flow switch damaged.
202004 53
Midea CAC Confidential
M thermal Mono
Procedure
E0 / E8
Water flow switch connection on Yes Ensure the switch is connected properly
hydronic system main PCB is loose1
No
No
Water flow switch is damaged Yes Replace the water flow switch
No
Notes:
1. Water flow switch connection is port CN8 on the main PCB for hydronic system (labeled 5 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”).
2. Check water pressure on the manometer. If the water pressure is not > 1 bar, water flow is insufficient. Refer to Figure 2-1.2 and 2-1.6 in Part 2, 1 “Layout
of Functional Components”.
3. The fuse is labeled 25 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”.
54 200204
Midea CAC Confidential
M thermal Mono
4.3 E1 Troubleshooting
Digital display output
Description
Phase sequence error.
Only applies to 3-phase models.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Power supply phases not connected in correct sequence.
Power supply terminals loose.
Power supply abnormal.
Main PCB damaged.
202004 55
Midea CAC Confidential
M thermal Mono
Procedure
E1
The phase sequence of the 3-phase Yes Exchange any two of the 3 phase wires
power supply is incrorrect1
No
The power supply is abnormal Yes Check the power supply equipment
No
Midea M thermal Mono Service Manual
Notes:
1. The A, B, C terminals of 3-phase power supply should match compressor phase sequence requirements. If the phase sequence is inverted, the compressor
will operate inversely. If the wiring connection of each outdoor unit is in A, B, C phase sequence, and multiple units are connected, the current difference
between C phase and A, B phases will be very large as the power supply load of each outdoor unit will be on C phase. This can easily lead to tripped
circuits and terminal wiring burnout. Therefore if multiple units are to be used, the phase sequence should be staggered, so that the current is distributed
among the three phases equally.
2. Loose power supply terminals can cause the compressors to operate abnormally and compressor current to be very large.
56 200204
Midea CAC Confidential
M thermal Mono
4.4 E2 Troubleshooting
Digital display output
Description
Communication error between outdoor unit and user interface.
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
Communication wires between outdoor unit and user interface not connected properly.
Communication wiring X Y E terminals misconnected.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Damaged main PCB or electric control box communication terminals block.
202004 57
Midea CAC Confidential
M thermal Mono
Procedure
E2
Interference from high voltage (220V or Yes Ensure the communication wires and
higher) wires high voltage wires are separated
No
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.
Communication wiring has polarity. Ensure that the P wire is connected to P terminals and the Q wire is connected to Q terminals.
58 200204
Midea CAC Confidential
M thermal Mono
4.5 E3, E4, H2, H3, Ed, HA, H5, H9 Troubleshooting
Digital display output
Description
E3 indicates a backup electric heater water outlet temperature sensor error.
E4 indicates a domestic hot water tank temperature sensor error.
H2 indicates a water side heat exchanger refrigerant outlet (liquid pipe) temperature sensor error.
H3 indicates a water side heat exchanger refrigerant inlet (gas pipe) temperature sensor error.
Ed indicates a water side heat exchanger water inlet temperature sensor error.
HA indicates a water side heat exchanger water outlet temperature sensor error.
H5 indicates a room temperature sensor error.
H9 indicates a zone 2 water outlet temperature sensor error.
Eb indicates solar panel temperature sensor error
E7 indicates balance tank upper temperature sensor error
EC indicates balance tank nether temperature sensor error
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Damaged hydronic system main PCB.
202004 59
Midea CAC Confidential
M thermal Mono
Procedure
E3 / E4 / H2 / H3 / Ed / HA / H5 / H9/ Eb
/ E7 / EC
Notes:
1. Backup electric heater water outlet temperature sensor, water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor, water side heat
exchanger refrigerant outlet (gas pipe) temperature sensor, water side heat exchanger water inlet temperature sensor and water side heat exchanger
water outlet temperature sensor connections are port CN6 on the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for
Hydronic System”). Domestic hot water tank temperature sensor connection is port CN13 on the hydronic system main PCB (labeled 9 in Figure 4-2.1 in
Part 4, 2.2 “Main PCB for Hydronic System”). Circuit 2 water outlet temperature sensor connection is port CN15 on the hydronic system main PCB (labeled
10 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”). Room thermostat connection is port CN3 on the hydronic system main PCB (labeled 28 in
Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 4-5.1 or 4-5.3 in Part 4, 5.1 “Temperature Sensor Resistance Characteristics”.
60 200204
Midea CAC Confidential
M thermal Mono
4.6 E5, E6, E9, EA Troubleshooting
Digital display output
Description
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Damaged refrigerant system main PCB.
202004 61
Midea CAC Confidential
M thermal Mono
Procedure
E5 / E6 / E9 / EA
Notes:
1. Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connections are port CN9 on the
MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 12 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN9 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 12 in Figure 4-2.3 in Part 4, 2.1 “Main PCBs for
Refrigerant System, Inverter Module”), port CN9 on the MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 17 in Figure 4-2.4
in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter Module”). Discharge pipe temperature sensor connection are port CN8 on the
MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN8 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.3 in Part 4, 2.1 “Main PCBs for
Refrigerant System, Inverter Module”), port CN4 on the MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.4
in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter Module”). Suction pipe temperature sensor connection are port CN1 on the
MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 14 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN1 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 14 in Figure 4-2.3 in Part 4, 2.1 “Main PCBs for
Refrigerant System, Inverter Module”), port CN8 on the MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 16 in Figure 4-2.4
in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter Module”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 4-5.1, and Table 4-5.2 in Part 4, 5.1 “Temperature Sensor Resistance Characteristics”
62 200204
Midea CAC Confidential
M thermal Mono
4.7 EE Troubleshooting
Digital display output
Description
Hydronic system EEPROM error.
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
Hydronic system main PCB EEPROM is not connected properly.
Hydronic system main PCB damaged.
Procedure
EE
Notes:
1. Hydronic system main PCB EEPROM is designated IC18 on the hydronic system main PCB (labeled 29 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic
System”).
202004 63
Midea CAC Confidential
M thermal Mono
4.8 F1 Troubleshooting
Digital display output
Description
Low DC bus voltage.
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
The DC bus voltage is too low.
Procedure
Midea M thermal Mono Service Manual
F1
No
LED light is OK Yes Voltage of PN is 380V. Yes Check the main board.
No
64 200204
Midea CAC Confidential
M thermal Mono
4.9 HF Troubleshooting
Digital display output
Description
Refrigerant system EEPROM error.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Refrigerant system main PCB EEPROM is not connected properly.
Refrigerant system main PCB damaged.
Procedure
HF
Notes:
1. Refrigerant system main PCB EEPROM is designated IC23 on the refrigerant system main PCBs (labeled 29 in Figure 4-2.2 in Part 4, 2.3 “Main PCBs for
Refrigerant System, Inverter Modules and Filter Boards”), designed IC13 on the refrigerant system main PCBs (labeled 19 in Figure 4-2.4 in Part 4, 2.2
“Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”), designed IC23 on the refrigerant system main PCBs (labeled 26 in Figure 4-2.6 in
Part 4, 2.2 “Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”).
202004 65
Midea CAC Confidential
M thermal Mono
4.10 H0 Troubleshooting
Digital display output
Description
Communication error between refrigerant system main control chip and hydronic system main control chip.
M thermal Mono stops running.
Error code is displayed on hydronic system main PCB, refrigerant system main control board for refrigerant system and
user interface.
Possible causes
Power supply abnormal.
Transformer malfunction.
Midea M thermal Mono Service Manual
Procedure
H0
Power supply for main PCBs and Yes Provide normal power supply
transformer(s) is abnormal1
No
No
Notes:
1. Measure the voltages of transformer(s) input port and on the main PCB. The normal voltage between transformer input port terminals is 220V, between
GND and 18V is 18V. If one or more of the voltages are not normal, the power supply for main control board for refrigerant system and transformer is
abnormal.
2. Measure the voltages of transformer(s) output ports. If the voltages are not normal, the transformer has malfunctioned.
4.11 H1 Troubleshooting
Digital display output
66 200204
Midea CAC Confidential
M thermal Mono
Description
Communication error between refrigerant system main control chip and the inverter driver chip.
M thermal Mono stops running.
Error code H1 is displayed on refrigerant system main control board and user interface.
Possible causes
Power supply abnormal.
Transformer malfunction.
Interference from a source of electromagnetic radiation.
Refrigerant system main PCB or inverter driven module damaged.
Procedure
H1
No
Notes:
1. Measure the voltages of transformer input port and on the main PCB. The normal voltage between transformer input port terminals is 220V, output two
sets of voltages 11V and 17V. If one or more of the voltages are not normal, the power supply for main control board for refrigerant system and
transformer is abnormal.
2. Measure the voltages of transformer output ports. If the voltages are not normal, the transformer has malfunctioned.
202004 67
Midea CAC Confidential
M thermal Mono
4.12 H6, HH Troubleshooting
Digital display output
Description
H6 indicates a DC fan error.
HH indicates that H6 protection has occurred 10 times in 2 hours. When an HH error occurs, a manual system restart
is required before the system can resume operation. The cause of an HH error should be addressed promptly in order
to avoid system damage.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Midea M thermal Mono Service Manual
68 200204
Midea CAC Confidential
M thermal Mono
Procedure
H6 / HH
Strong wind is blowing towards the Changer the outdoor unit’s installation
fan, making the fan running in the wrong Yes direction or build a shelter to protect the
direction fan from strong wind
No
Some power wires or communication Yes Ensure power and communication wires
wires of fan are not connected properly1 are connected properly
No
The power supply is abnormal Yes Check the power supply equipment
No
No
No
Notes:
1. Refer to Figures 4-1.1 to 4-1.7 in Part 4, 1 “Outdoor Unit Electric Control Box Layout” and to the M thermal Mono Engineering Data Book, Part 2, 5 “Wiring
Diagrams”.
2. Only applies to single-phase power supply models. Check the voltage between “+” and “-” terminals on the PFC module on the inverter module. The
normal range is 277V to 354V. If the voltage is outside this range, the PFC module is damaged.
3. Measure the voltage between the DC fan motor power supply’s white and black wires. The normal voltage is 15V when the unit is in standby. If the voltage
is significantly different from 15V, the IPM module on the inverter module is damaged. The fan connections on each type of refrigerant system main
control board for refrigerant systemre labelled in Figures 4-2.2, 4-2.4 and 4-2.6 in Part 4, 2.3 “Main PCBs for Refrigerant System, Inverter Modules and
Filter Boards”.
202004 69
Midea CAC Confidential
M thermal Mono
4.13 H7 Troubleshooting
Digital display output
Description
Abnormal main circuit voltage.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Power supply voltage not within ±10% of rated voltage or a phase is missing.
Outdoor unit powered on immediately after being powered off.
Loosened wiring within electric control box.
Midea M thermal Mono Service Manual
70 200204
Midea CAC Confidential
M thermal Mono
Procedure
H7
Outdoor unit powered on immediately Power-off the unit and wait for at least 3
Yes
after being powered off minutes before powering-on
No
202004 71
Midea CAC Confidential
M thermal Mono
4.14 H8 Troubleshooting
Digital display output
Description
Pressure sensor error.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Pressure sensor not connected properly or has malfunctioned.
Refrigerant system main PCB damaged.
Midea M thermal Mono Service Manual
Procedure
H8
No
High pressure sensor connection on Yes Ensure the sensor is connected properly
refrigerant system main PCB is loose
No
Notes:
1. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed. The pressure sensor connection on each type of refrigerant system main PCB is labelled in Figures 4-2.2, 4-2.4 and 4-2.6 in Part 4, 2.3 “Main
PCBs for Refrigerant System, Inverter Modules and Filter Boards”. Refer also to Part 2, 1 “Layout of Functional Components”.
72 200204
Midea CAC Confidential
M thermal Mono
4.15 P0, HP Troubleshooting
Digital display output
Description
P0 indicates suction pipe low pressure protection. When the suction pressure falls below 0.14MPa, the system
displays P0 protection and M thermal Mono stops running. When the pressure rises above 0.30MPa, P0 is removed
and normal operation resumes.
HP indicates P0 protection has occurred 3 times in 60 minutes. When an HP error occurs, a manual system restart is
required before the system can resume operation.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Low pressure switch not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange in heating mode or DHW mode.
Insufficient water flow in cooling mode.
Main PCB damaged.
202004 73
Midea CAC Confidential
M thermal Mono
Procedure
P0 / HP
Insufficient refrigerant caused by Yes Add refrigerant or inspect the system for
refrigerant leakage1 leaks
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, blocked EXV, or Yes filter is blocked by ice, the piping should
dirty filter2 be cleaned
No
error
mode3
No
The water flow rate is not sufficient in Yes Inspect the water system and fix the
cooling mode4 error
No
Notes:
1. To check for insufficient refrigerant:
An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once
sufficient refrigerant has been charged into the system.
2. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters.
3. Check air side heat exchanger, fan(s) and air outlets for dirt/blockages.
4. Check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages.
74 200204
Midea CAC Confidential
M thermal Mono
4.16 P1 Troubleshooting
Digital display output
Description
Discharge pipe high pressure protection. When the discharge pressure rises above 4.2MPa, the system displays P1
protection and M thermal Mono stops running. When the discharge pressure falls below 3.2MPa, P1 is removed and
normal operation resumes.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Pressure sensor/switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.
202004 75
Midea CAC Confidential
M thermal Mono
Procedure
P1
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV3
Midea M thermal Mono Service Manual
No
The heat exchange is poor4 Yes Inspect the system and fix the error
No
The water flow rate is not sufficient in Yes Inspect the water system and fix the
cooling mode5 error
No
Notes:
1. High pressure switch connection is port CN13 on the MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 16 in Figure 4-2.2 in
Part4, 2.3 "Main PCB for Refrigerant System, Inverter Module"). port CN13 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB
(labeled 16 in Figure 4-2.3 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter Module"), port CN31 on the MHA-V12(14,16)W/D2RN8-B outdoor unit
refrigerant system main PCB (labeled 20 in Figure 4-2.4 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter Module").
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
3. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal.
4. In heating mode check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages. In cooling mode check air side
heat exchanger, fan(s) and air outlets for dirt/blockages.
5. Check water pressure on the manometer. If the water pressure is not > 1 bar, water flow is insufficient. Refer to Figure 2-1.2 and 2-1.6 in Part 2, 1 “Layout
of Functional Components”.
76 200204
Midea CAC Confidential
M thermal Mono
4.17 P3 Troubleshooting
Digital display output
Description
Compressor current protection.
When the compressor current rises above the protection value (4/6kW models 18A, 8/10kW model 19A, 12/14/16kW
single phase model 30A, 12/14/16kW three phase model 14A), the system displays P3 protection and M thermal
Mono stops running. When the current returns to the normal range, P3 is removed and normal operation resumes.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Power supply abnormal.
Poor condenser heat exchange.
High pressure side blockage.
Inverter module damaged.
Compressor damaged.
Main PCB damaged.
202004 77
Midea CAC Confidential
M thermal Mono
Procedure
P3
The power supply is abnormal Yes Check the power supply equipment
No
The condenser heat exchange is poor1 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV2
No
Midea M thermal Mono Service Manual
No
No
Notes:
1. In heating mode check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages. In cooling mode check air side
heat exchanger, fan(s) and air outlets for dirt/blockages.
2. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal.
3. Set a multi-meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
4. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
78 200204
Midea CAC Confidential
M thermal Mono
4.18 P4 Troubleshooting
Digital display output
Description
Discharge temperature protection.
When the compressor the discharge temperature rises above 115°C, the system displays P4 protection and M thermal
Mono stops running. When the discharge temperature falls below 95°C, P4 is removed and normal operation
resumes.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Temperature sensor error
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.
202004 79
Midea CAC Confidential
M thermal Mono
Procedure
P4
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV4
No
The condenser heat exchange is poor in Yes Inspect the system and fix the error
heating mode5
No
The water flow rate is not sufficient in Yes Inspect the water system and fix the
cooling mode6 error
No
80 200204
Midea CAC Confidential
M thermal Mono
Notes:
1. Discharge pipe temperature sensor connection is port CN8 on the MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 15 in
Figure 4-2.2 in Part4, 2.3 "Main PCB for Refrigerant System, Inverter Module"). port CN8 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant
system main PCB (labeled 15 in Figure 4-2.3 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter Module"), port CN4 on the
MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.4 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter
Module").
2. Final outlet water temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on the hydronic box main
PCB (labeled 10 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System"). Domestic hot water tank temperature sensor connection is port CN13 on
hydronic box main PCB (labeled 13 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System").
3. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.1 or 5-5.2 in Part 5, 5.1 “Temperature
Sensor Resistance Characteristics”.
4. High pressure switch connection is port CN13 on the MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 16 in Figure 4-2.2 in
Part4, 2.3 "Main PCB for Refrigerant System, Inverter Module"). port CN13 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB
(labeled 16 in Figure 4-2.3 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter Module"), port CN31 on the MHA-V12(14,16)W/D2RN8-B outdoor unit
refrigerant system main PCB (labeled 20 in Figure 4-2.4 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter Module").
5. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
6. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal.
7. Check air side heat exchanger, fan and air outlets for dirt/blockages.
8. Check the water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages.
202004 81
Midea CAC Confidential
M thermal Mono
4.19 P5 Troubleshooting
Digital display output
Description
High temperature difference between water side heat exchanger water inlet and water outlet temperatures
protection.
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Water piping contains air.
Midea M thermal Mono Service Manual
82 200204
Midea CAC Confidential
M thermal Mono
Procedure
P5
Water side heat exchanger water inlet / Yes Ensure the temperature sensor is
outlet temperature sensor is loose1 connected properly
No
Water piping contains air Yes Purge air from the water system
No
Notes:
1. Water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on
the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.3 in Part 5, 5.1 “Temperature Sensor
Resistance Characteristics”.
202004 83
Midea CAC Confidential
M thermal Mono
4.20 Inverter module Troubleshooting for single-phase models
Digital display output
Description
Inverter module protection.
M thermal Split stops running.
Specific error code L0, L1, L2, L4, L5, L8, L9 is displayed on the user interface and the main control board of refrigerant
system.
Midea M thermal Mono Service Manual
Possible causes
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
PED board self checking fail.
84 200204
Midea CAC Confidential
M thermal Mono
The specific error codes can also be obtained from the LED indicators on the inverter module.
Table 4-4.2: Errors indicated on LED, single-phase 4~10kW
LED301 flashing pattern (GREEN)
Corresponding error
LED302 is always on (RED)
Flashes 8 times and stops for 1 second, then repeats L0 - Inverter module protection
Flashes 9 times and stops for 1 second, then repeats L1 - DC bus low voltage protection
Flashes 10 times and stops for 1 second, then repeats L2 - DC bus high voltage protection
Flashes 12 times and stops for 1 second, then repeats L4 - MCE error
Flashes 13 times and stops for 1 second, then repeats L5 - Zero speed protection
Flashes 16 times and stops for 1 second, then repeats L8 - Compressor frequency variation greater than 15Hz within one second protection
L9 - Actual compressor frequency differs from target frequency by more than 15Hz
Flashes 17 times and stops for 1 second, then repeats
protection
202004 85
Midea CAC Confidential
M thermal Mono
Principle of DC inverter
L PTC P
Inductor U
Power
Bridge Inverter V Comp
supply Contactor PFC Capacitor
N rectifier module W ressor
(220V)
N
○
1 ○
2 ○
3
①Contactor is open, the current across the PTC to charge capacitor. After 5 seconds, the contactor closed.
②220-240V AC power supply change to DC power supply after bridge rectifier.
③The capacitor output steady power supply for inverter module P N terminals. In standby the voltage between P and N
terminal on inverter module is 1.4 time of AC power supply. When the fan motor is running, the voltage is 377V DC.
L0/L4 troubleshooting
Situation 1: L0 or L4 error appears immediately after the outdoor unit is powered-on
Midea M thermal Mono Service Manual
L0 / L4
IPM
IGBT
diode
IGBT
diode
brigde rectifier
86 200204
Midea CAC Confidential
M thermal Mono
Situation 2: L0 or L4 error appears immediately after the compressor starts up
L0 / L4
U V W wire between inverter module and Yes Ensure U V W wire is connected properly
compressor is not connected properly1
No
No
Yes
Compressor has malfunctioned 4 Replace the compressor
No
202004 87
Midea CAC Confidential
M thermal Mono
Situation 3: L0 or L4 error appears after the compressor has been running for a period of time and the compressor
speed is over 60rps
L0 / L4
No
Midea M thermal Mono Service Manual
L0
Yes
The outdoor unit ventilation is not good Ensure enough space for unit ventilation
88 200204
Midea CAC Confidential
M thermal Mono
L1/L2 troubleshooting
The normal DC voltage between terminals P and N on inverter module is 1.4 time of AC power supply in standby , the DC
voltage is 377V when the fan motor is running. If the voltage is lower than 160V, the unit displays L1. If the voltage is
higher than 500V, the unit display L2.
Figure 4-4.3: Inverter module terminals
Inverter module terminals (4-10KW) Inverter module terminals (12-16KW)
U V W N P U V W N P
L1 / L2
Notes:
1. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module, IGBT, diode, brigde rectifer (on the
reverse side of the inverter module PCB). Refer to Figure 4-4.2.
Situation 2: L1 or L2 error appears after the compressor has been running for a period of time and the compressor
speed is over 20rps
L1 /L2
Relay on outdoor unit main PCB is open Yes Replace the outdoor unit main PCB
No
202004 89
Midea CAC Confidential
M thermal Mono
Notes:
1. If the fan motor is running and the DC voltage between terminals P and N on inverter module declined, Relay on the main control board of outdoor unit is
open.
2. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on IPM module (on the reverse side of the inverter module
PCB). Refer to Figure 4-4.2.
L5/L8/L9 troubleshooting
L5/L8/L9
NO
The wire is not connected properly Ensure wire is connected properly
Yes
Yes
Inverter module PCB has malfunctioned Replace inverter module PCB1
No
90 200204
Midea CAC Confidential
M thermal Mono
4.21 Inverter module Troubleshooting for three-phase models
Digital display output
Description
Inverter module protection or high pressure protection.
M thermal Mono stops running.
Specific error code L0, L1, L2, L4, L5, L8 , L9 is displayed on the user interface and the refrigerant system main PCB.
Possible causes
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
Contactor stuck or 908 self checking fail.
202004 91
Midea CAC Confidential
M thermal Mono
The specific error codes can also be obtained from the LED indicators LED1/LED2 on the inverter module.
Figure 4-4.5: LED location of inveter module for three-phase 12~16kW unit
Principle of DC inverter
PTC
A P U
Inductor
Power
Bridge Contactor Inverter module
B V
supply Capacitor Compressor
rectifier (VP-N: 540V DC)
(380V AC) C W
N
○
1 ○
2 ○
3
92 200204
Midea CAC Confidential
M thermal Mono
L0 troubleshooting
Situation 1: L0 error appears immediately after the outdoor unit is powered-on
L0
Yes
Inverter module is damaged2
No
Notes:
1. For MHC-V12(14,16)W/D2RN8-B, the communication port between refrigerant system main control board for refrigerant system inverter module is port
CN36 on refrigerant system main control board for refrigerant system port CN8 on inverter module.
2. Measure the resistance between each of U, V and W and each of P and N on the inverter module. All the resistances should be infinite. If any of them are
not infinite, the inverter module is damaged and should be replaced.
3. The normal voltage between F0 and GND is 5V. Refer to Figure 4-4.6.
4. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module (on the reverse side of the inverter
module PCB). Refer to Figure 4-4.2.
IC28-1(F0) IC28-4(GND)
202004 93
Midea CAC Confidential
M thermal Mono
Situation 2: L0 error appears immediately after the compressor starts up
L0
Yes
DC bus wire is not connected properly1 Ensure DC bus wire is connected properly
No
Yes
Compressor has malfunctioned2 Replace the compressor
No
Notes:
Midea M thermal Mono Service Manual
1. The DC bus wire should run from the N terminal on the inverter module, through the current sensor (in the direction indicated by the arrow on the current
sensor), and end at the N terminal of capacitor. Refer to Figure 4-4.7.
2. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
94 200204
Midea CAC Confidential
M thermal Mono
Situation 3: L0 error appears within 2 seconds of compressor start-up
L0
U V W wire between inverter module and Yes Ensure U V W wire is connected properly
compressor is not connected properly1
No
Notes:
1. Connect the U V W wire from the inverter module to the correct compressor terminals, as indicated by the labels on the compressor.
2. Measure the voltage between each of W-, W+, V-, V+, U-, U+ and GND when the unit is in standby. The normal voltage should be 2.5V-4V and the six
voltages should be same, otherwise the communication terminal has failed. Refer to Figure4-4.8.
3. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module (on the reverse side of the inverter
module PCB). Refer to Figure 4-4.2.
202004 95
Midea CAC Confidential
M thermal Mono
Condition 4: L0 error appears after the compressor has been running for a period of time and the compressor speed is
over 60rps
L0
No
Notes:
1. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module (on the reverse side of the inverter
module PCB).
2. Use clip-on ammeter to measure the compressor current, if the current is normal indicates the inverter module is failed, if the current is abnormal
indicates the compressor has failed.
L0
Yes
The outdoor unit ventilation is not good Ensure enough space for unit ventilation
96 200204
Midea CAC Confidential
M thermal Mono
L1/L2 troubleshooting
The normal DC voltage between terminals P and N on inverter module is 540V. If the voltage is lower than 300V, the unit
displays an L1 error; if the voltage is higher than 830V, the unit displays an L2 error. Refer to Figure4-4.9.
Vnormal = 540V DC
L1 / L2
P N +15V wire on refrigerant system main Yes Ensure P N +15V wire is connected
PCB is not connected properly1 properly
No
No
DC voltage between terminal P and N is Yes Check power supply, three phase bridge
abnormal rectifier4
No
202004 97
Midea CAC Confidential
M thermal Mono
Figure 4-4.10: P N +15V terminal-+15V(IC4/5/6PIN12)
;N-(IC/4/5、6)PIN13
+15V
N
Midea M thermal Mono Service Manual
3. Check the +15V circuit according to corresponding wiring diagram. If IC4/5/6PIN12 on inverter module output voltage is not +15V means the inverter
module is failed. If voltage output of inverter module is +15V means main PCB is failed.
4. Check the bridge rectifier using one of the following two methods (refer to Figure 4-4.11):
Method 1: measure the resistance between any two of the 5 bridge rectifier terminals. If any of the resistances is close to zero, the bridge rectifier
has failed.
Method 2: dial a multimeter to the diode setting:
- Put the red probe on the DC power output negative terminal (terminal 5) and put the black probe onto each of the AC power input terminals
(terminals 1, 2 and 3) in turn. The voltage between terminal 5 and each of terminals 1, 2 and 3 should be around 0.378V. If the voltage is 0, the
bridge rectifier has failed.
- Put the red probe on the DC power output positive terminal (terminal 4), then put black probe onto each of the AC power input terminals
(terminals 1, 2 and 3) in turn. The voltage between terminal 4 and each of terminals 1, 2 and 3 should be infinite. If the voltage is 0, the bridge
rectifier has failed.
Figure 4-4.11: Bridge rectifier
DC power output
Schematic diagram
98 200204
Midea CAC Confidential
M thermal Mono
L4 troubleshooting(the same as L1/L2)
Situation 1: L4 error appears immediately after the outdoor unit is powered-on
L4
Condition 2: L4 error appears after the compressor has been running for a period of time and the compressor speed is
over 60rps
L4
No
L5/L8/L9 troubleshooting
L5/L8/L9
NO
The wire is not connected properly Ensure wire is connected properly
Yes
Yes
Inverter module PCB has malfunctioned Replace inverter module PCB
No
202004 99
Midea CAC Confidential
M thermal Mono
4.22 bH Troubleshooting
Digital display output
Description
PED PCB failure
M thermal Split stops running.
Error code is displayed on hydronic box main PCB and user interface.
Possible causes
Power supply problem.
PED board broken.
Midea M thermal Mono Service Manual
100 200204
Midea CAC Confidential
M thermal Mono
Procedure
bH
PED1 board broken. Yes Replace PED PCB and power on again.
No
IPM module broken. Yes Replace IPM module and power on again.
Notes:
1. PED is port CN22 on the hydronic box main PCB (labeled 11 in Figure 4-2.7: MHA-V12(14,16)W/D2RN8-B outdoor unit inverter module ).
202004 101
Midea CAC Confidential
M thermal Mono
4.23 Pb Troubleshooting
Digital display output
Description
Water side heat exchanger anti-freeze protection.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and ANTI.FREEZE icon is
displayed on user interface.
Possible causes
Normal system protection.
Temperature sensor not connected properly or has malfunctioned.
Hydronic system main PCB damaged.
Midea M thermal Mono Service Manual
Procedure
Pb
Outdoor ambient temperature is lower Yes Normal system protection. The system
than 4°C will resume automatically1
No
Notes:
1. Refer to Part 3, 5.7 “Water Side Heat Exchanger Anti-freeze Protection Control”.
2. Backup electric heater water outlet temperature sensor, water side heat exchanger water inlet temperature sensor and water side heat exchanger water
outlet temperature sensor connections are port CN6 on the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic
System”).
3. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 4-5.3 in Part 4, 5.1 “Temperature Sensor
Resistance Characteristics”.
102 200204
Midea CAC Confidential
M thermal Mono
4.24 Pd Troubleshooting
Digital display output
Description
High temperature protection of air side heat exchanger refrigerant outlet in cooling mode. When the air side heat
exchanger refrigerant outlet temperature is higher than 61°C for more than 3 seconds, the system displays Pd
protection and M thermal Mono stops running. When the air side heat exchanger refrigerant outlet temperature
returns drops below 55°C, Pd is removed and normal operation resumes.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Poor condenser heat exchange.
Fan motor damaged.
Hydronic system main PCB damaged.
202004 103
Midea CAC Confidential
M thermal Mono
Procedure
Pd
Air side heat exchanger refrigerant outlet Yes Ensure the temperature sensor is
temperature sensor is loose1 connected properly
No
The air side heat exchanger heat Yes Inspect the system and fix the error
exchange is poor3
Midea M thermal Mono Service Manual
No
The fan or fan motor is blocked or Yes Inspect the system and fix the error
damaged
No
Notes:
1. Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connections are port CN9 on the refrigerant
system main PCB (labeled 12 in Figure 4-2.2 in Part 4, 2.3 “Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”, (labeled 5 in Figure 4-2.4
in Part 4, 2.3 “Main PCBs for Refrigerant System, Inverter Modules and Filter Boards” and labeled 6 in Figure 4-2.6 in Part 4, 2.3 “Main PCBs for Refrigerant
System, Inverter Modules and Filter Boards”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 4-5.1 in Part 4, 5.1 “Temperature Sensor
Resistance Characteristics”.
3. Check air side heat exchanger, fan(s) and air outlets for dirt/blockages.
104 200204
Midea CAC Confidential
M thermal Mono
4.25 PP Troubleshooting
Digital display output
Description
Water side heat exchanger inlet temperature is higher than outlet temperature in heating mode.
M thermal Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
If PP error occurs 3 times then Hb will appear.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
4-way valve is blocked or damaged.
Hydronic system main PCB damaged.
202004 105
Midea CAC Confidential
M thermal Mono
Procedure
PP/Hb
Water side heat exchanger water inlet / Yes Ensure the temperature sensor is
outlet temperature sensor is loose1 connected properly
No
The 4-way valve is blocked or damaged3 Yes Replace the 4-way valve
Midea M thermal Mono Service Manual
No
Notes:
1. Water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on
the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Min PCB for Hydronic System”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 4-5.1 to 4-5.2 in Part 4, 5.1 “Temperature
Sensor Resistance Characteristics”.
3. Restart the unit in cooling mode to change the refrigerant flow direction. If the unit does not operate normally, the 4-way valve is blocked or damaged.
106 200204
Midea CAC Confidential
M thermal Mono
4.26 HE Troubleshooting
Digital display output
Description
Communication error between main control board of hydronic module and Ta/room thermostat transfer PCB
M thermal Mono stops running.
Error code is displayed on hydronic system main PCB, outdoor unit main PCB and user interface.
Possible causes
Temperature collecting plate(Optional) connection wire is not connected.
Temperature collecting plate(Optional) is damaged.
Procedure
HE
Temperature collecting plate Yes Check the connection line and joint.
connection wire is not connected.
No
202004 107
Midea CAC Confidential
M thermal Mono
5 Appendix to Part 4
5.1 Temperature Sensor Resistance Characteristics
Table 4-5.1: Outdoor ambient temperature sensor, water side heat exchanger refrigerant inlet / outlet (liquid / gas pipe) temperature sensor,
air side heat exchanger refrigerant out temperature sensor and suction pipe temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
-25 144.266 15 16.079 55 2.841 95 0.708
-24 135.601 16 15.313 56 2.734 96 0.686
-23 127.507 17 14.588 57 2.632 97 0.666
-22 119.941 18 13.902 58 2.534 98 0.646
-21 112.867 19 13.251 59 2.44 99 0.627
-20 106.732 20 12.635 60 2.35 100 0.609
-19 100.552 21 12.05 61 2.264 101 0.591
-18 94.769 22 11.496 62 2.181 102 0.574
-17 89.353 23 10.971 63 2.102 103 0.558
Midea M thermal Mono Service Manual
202004 109
Midea CAC Confidential
M thermal Mono
Table 4-5.3: Water side heat exchanger water inlet / outlet temperature sensor, final outlet water temperature sensor and DHW temperature
sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
110 200204
Midea CAC Confidential
Ver. 2020-04