Figure 5 - Orion Modbus IED Port Configuration Screen

This document provides instructions for configuring communication between a Conitel C300 or C2020 and ABB protective relays using Modbus. It describes setting parameters for the Modbus communication port and Conitel configuration. Screenshots show the configuration screens and parameters to match the Conitel and relay settings.

Uploaded by

malik.ai.tech100
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views1 page

Figure 5 - Orion Modbus IED Port Configuration Screen

This document provides instructions for configuring communication between a Conitel C300 or C2020 and ABB protective relays using Modbus. It describes setting parameters for the Modbus communication port and Conitel configuration. Screenshots show the configuration screens and parameters to match the Conitel and relay settings.

Uploaded by

malik.ai.tech100
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ORION Quick Start Guide For The Conitel C300 Or C2020 To ABB Protective Relays Using Modbus AN-78A-00

“CONTROL and ENTER” key on the configuration terminal’s keyboard.

+--------------¦ NovaTech Conitel-Modbus Configuration Program ¦---------------+


¦ PRINTER: READY FILE NAME: TEST.CTL ¦
¦ File Setup Memory Map Transfer About 10:37:10 ¦
¦¦¦¦¦¦¦¦¦+------------------------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ PC-P+-------¦ Modbus Communication Setup ¦--------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ Prot¦ ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ Prot¦ Baud Rate Parity Data Bits Stop Bits ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦+------¦ ( )300 ( )NONE ( )6 (¦)1 ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦ ( )600 ( )ODD ( )7 ( )2 ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦+--------------¦ ( )1200 (¦)EVEN (¦)8 ¦---------------+¦
¦¦Current Video ¦ ( )2400 ¦ ¦¦
¦¦ ¦ ( )4800 WarmUp Time [ms]: 10 ¦ ¦¦
¦¦ ¦ (¦)9600 WarmDown Time [ms]: 10 ¦ ¦¦
¦¦ ¦ ( )19200 Response Timeout [ms]: 1000 ¦ ¦¦
¦¦ ¦ Intercommand Delay [ms]: 100 ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ +---------------------------------------------+ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦+-----------------------------¦ Message Window ¦-----------------------------+¦
+------------------------------------------------------------------------------+
<Tab>: Next Field <Esc>: Abort <Ctrl>+<Enter>: Accept

Figure 5 - Orion Modbus IED Port Configuration Screen.

12. With the “SETUP” parameter highlighted, select the ProtConv Conitel Setup submenu selection, until
the following screen is displayed. The parameters listed in Figure 6 match those in the Conitel Host.
After selection of all parameters, simultaneously depress the “CONTROL and ENTER” key on the
configuration terminal’s keyboard.

+--------------¦ NovaTech Conitel-Modbus Configuration Program ¦---------------+


¦ PRINTER: READY FILE NAME: TEST.CTL ¦
¦ File Setup Memory Map Transfer About 10:37:15 ¦
¦¦¦¦¦¦¦¦¦+------------------------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ PC-+¦ Edit Conitel Comm Parameters ¦----------------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ Pro¦ ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ Pro¦ Station Address: 1 ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦+-----¦ Baud Rate: 1200 ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦ Warmup Time [ms]: 40 ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦+-------------¦ Warmdown Time [ms]: 0 ¦-------------+¦
¦¦Current Video¦ Timeout [ms]: 800 ¦ ¦¦
¦¦ ¦ PLC with Reset Coil: 1 ¦ ¦¦
¦¦ ¦ Reset Coil: 9999 ¦ ¦¦
¦¦ ¦ Check Back Before Operate Time [ms]: 1000 ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ +------------------------------------------------+ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦+-----------------------------¦ Message Window ¦-----------------------------+¦
+------------------------------------------------------------------------------+
<Esc>: Abort <Ctrl>+<Enter>: Accept New Parameters

Figure 6 – Conitel Configuration Screen For The Orion Scada Port

13. The configuration of each of the hardware communication ports is now completed. The next steps
illustrate the configuration of a single point map from the Conitel unit to the Modbus nodes attached.
Within the Configuration Program, select the MEMORY MAP item in the configuration selection, a
display with several choices is displayed. Select the ADD INPUTS selection.