Va 26 22 00
Va 26 22 00
Va 26 22 00
SECTION 26 22 00
LOW-VOLTAGE TRANSFORMERS
26 22 00 - 1
11-01-22
rise, wiring and connection diagrams, plan, front, side, and rear
elevations, accessories, and device nameplate data.
SPEC WRITER NOTE: Include the following
paragraph for projects in seismic areas
of moderate-high, high and very high
seismicities as listed in Table 4 of VA
Handbook H-18-8, Seismic Design
Requirements. Coordinate with the
structural engineer.
26 22 00 - 2
11-01-22
PART 2 - PRODUCTS
2.1 TRANSFORMERS
A. Unless otherwise specified, transformers shall be in accordance with
NEMA, NFPA, UL and as shown on the drawings.
B. Transformers shall have the following features:
1. Self-cooled by natural convection, isolating windings, //indoor//and
outdoor// dry-type. Autotransformers will not be accepted, except as
specifically allowed for buck-boost applications.
2. Rating and winding connections shall be as shown on the drawings.
3. Ratings shown on the drawings are for continuous duty without the use
of cooling fans.
4. Copper windings.
5. Insulation systems:
a. Transformers 30 kVA and larger: UL rated 220 °C (428 °F) system
with an average maximum rise by resistance of 150 °C (302 °F) in a
maximum ambient of 40 °C (104 °F).
b. Transformers below 30 kVA: Same as for 30 kVA and larger or UL
rated 185 °C (365 °F) system with an average maximum rise by
resistance of 115 °C (239 °F) in a maximum ambient of 40 °C (104
°F).
26 22 00 - 3
11-01-22
26 22 00 - 4
11-01-22
26 22 00 - 5
11-01-22
PART 3 - EXECUTION
3.1 INSTALLATION
A. Installation of transformers shall be in accordance with the NEC, as
recommended by the equipment manufacturer and as shown on the drawings.
B. Anchor transformers with rustproof bolts, nuts, and washers, in
accordance with manufacturer’s instructions, and as shown on drawings.
//C. In seismic areas, transformers shall be adequately anchored and braced
per details on structural contract drawings to withstand the seismic
forces at the location where installed.//
SPEC WRITER NOTE: Mounting slab
connections may have to be given in detail
depending on the requirements for the
seismic zone in which the equipment is
located. Include construction
requirements for concrete slab only if
slab is not detailed in drawings.
26 22 00 - 6
11-01-22
26 22 00 - 7