05 Monitor Module
05 Monitor Module
TC841A, XLS-MM-D
Monitor Modules with FlashScan®
General
Four different monitor modules are available for Honeywell’s
intelligent control panels for a variety of applications. Monitor
modules supervise a circuit of dry-contact input devices, such
as conventional heat detectors and pull stations, or monitor
and power a circuit of two-wire smoke detectors
(TC841A1000).
TC809A is a standard-sized module (typically mounts to a 4"
6999cov.jpg
[10.16 cm] square box) that supervises either a Class A (Style
D) or Class B (Style B) circuit of dry-contact input devices.
TC809B1008 is a miniature monitor module (a mere 1.3"
(3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) that
supervises a Class B (Style B) circuit of dry-contact input TC809A1059 (Type H)
devices. Its compact design allows the TC809B1008 to often
be mounted in a single-gang box behind the device it monitors.
TC841A1000 is a standard-sized module that monitors and
supervises compatible two-wire, 24 volt, smoke detectors on a supervisory indication at the control panel. Monitored circuit
Class A (Style D) or Class B (Style B) circuit. may be wired as an NFPA Style B (Class B) or Style D (Class
XLS-MM-D is a standard-sized dual monitor module that mon- A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
itors and supervises two independent two-wire Style B (Class (provided) terminates the Style B circuit. No resistor is
B) dry-contact initiating device circuits (IDCs) at two separate, required for supervision of the Style D circuit.
consecutive addresses in intelligent, two-wire systems. TC809A OPERATION
FlashScan® (U.S. Patent 5,539,389) is a communication pro- Each TC809A1059 uses one of the available module
tocol that greatly increases the speed of communication addresses on an SLC loop. It responds to regular polls from
between analog intelligent devices. Intelligent devices commu- the control panel and reports its type and the status (open/nor-
nicate in a grouped fashion. If one of the devices within the mal/short) of its Initiating Device Circuit (IDC). A flashing LED
group has new information, the panel CPU stops the group poll indicates that the module is in communication with the control
and concentrates on single points. The net effect is response panel. The LED latches steady on alarm (subject to current
speed greater than five times that of other designs. protocols. limitations on the loop).
6720m101.wmf
control panel.
The TC841A1000 Interface Module is intended for use in intel-
ligent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being moni-
tored must be UL compatible with the module. TC841A1000
TC841A1000 APPLICATIONS
Use the TC841A1000 to monitor a zone of two-wire smoke
detectors. The monitored circuit may be wired as an NFPA
Style B (Class B) or Style D (Class A) Initiating Device Circuit.
A 3.9 K ohm End-of-Line Resistor (provided) terminates the
end of the Style B or D (class B or A) circuit (maximum IDC
loop resistance is 25 ohms). Install ELR across terminals 8
and 9 for Style D application.
The TC809B1008 Mini Monitor Module can be installed in a TC841A1000 OPERATION
single-gang junction directly behind the monitored unit. Its Each TC841A1000 uses one of the available module
small size and light weight allow it to be installed without rigid addresses on an SLC loop. It responds to regular polls from
mounting. The TC809B1008 is intended for use in intelligent, the control panel and reports its type and the status (open/nor-
two-wire systems where the individual address of each module mal/short) of its Initiating Device Circuit (IDC). A flashing LED
is selected using rotary switches. It provides a two-wire initiat- indicates that the module is in communication with the control
ing device circuit for normally-open-contact fire alarm and panel. The LED latches steady on alarm (subject to current
security devices. limitations on the loop).
TC809B1008 APPLICATIONS TC841A1000 SPECIFICATIONS
Use to monitor a single device or a zone of four-wire smoke Nominal operating voltage: 15 to 32 VDC.
detectors, manual fire alarm pull stations, waterflow devices, or
other normally-open dry-contact devices. May also be used to Maximum current draw: 5.1 mA (LED on).
monitor normally-open supervisory devices with special super- Maximum IDC wiring resistance: 25 ohms.
visory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit. Maximum operating current: 270 µA (LED flashing).
A 47K ohm End-of-Line Resistor (provided) terminates the cir- EOL resistance: 3.9K ohms.
cuit.
External supply voltage (between Terminals T3 and T4):
TC809B1008 OPERATION DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Each TC809B1008 uses one of the available module
addresses on an SLC loop. It responds to regular polls from Temperature range: 32°F to 120°F (0°C to 49°C).
the control panel and reports its type and the status (open/nor- Humidity range: 10% to 93% noncondensing.
mal/short) of its Initiating Device Circuit (IDC).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
TC809B1008 SPECIFICATIONS 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
Nominal operating voltage: 15 to 32 VDC. 2.125" (5.398 cm) deep box.